More Related Content
Similar to Sample Power Audit Results (20)
Sample Power Audit Results
- 1. Results from Power Audit of xxx Facility,
Hyderabad
Presentation to
Mr. XXX
Version 1
18 August, 2008
- 2. © 2008-09 Choice Solutions2
About This Report
Choice Solutions is submitting this report of findings and
insights based on our power audit of xxx facility at Hyderabad.
We estimate significant opex and capex savings through
capacity optimization, PF correction, CMD correction and
implementation of wastage control measures. Our strong
recommendation is to replace the existing common electrical
distribution system with a separate panel to avoid unnecessary
break downs in facility. Our important suggestion: existing DG
sets are very old and cannot be used forever.
As a next step, we recommend implementing the suggested
changes followed by maintenance of electrical infrastructures.
- 3. Agenda
Audit Scope of Work
Contract Demand Diversity Factor
Capacity vs. Utilization (Infrastructure Optimization)
MD
DG
UPS
Consumption (End Loads)
UPS
LDB
AHU
Spilt A/C’s
Potential Power Savings (Infrastructure Optimization)
MD
DG
UPS
Power Quality
Facility Observations
Conclusions and Next Steps
- 4. © 2008-09 Choice Solutions4
Audit Scope of Work
DG Backup
Energy Meter
750 kVA
Facility End to End Power Distribution System
Floor Panels and
Intermediate Loads
1800 kVA
HT 11 KV
OCB 1 1 1 1 1 Transformer
Gnd Floor A/C
Gnd Floor UPS
Gnd Floor Lighting n
raw power
First Floor UPS
First Floor A/C
First Floor PAC
Second Floor UPS
Second Floor A/C
Second Floor Lighting
Raw Power
First Floor Lighting
Terrace and Cafeteria
Elevator
Sub DB
(West Wing)
DG-1 DG-2 DG-3 DG-4
500kVA500kVA 500kVA 500kVA
4X500 kVA Synchronization panel APFC
AMF Panel Common
Bus Bar
Main LT Panel
Sub DB
(East Wing)
Second Floor
Sub DB
(West Wing)
Sub DB
(East Wing)
Sub DB
(West Wing)
First Floor
Ground Floor
Sub DB
(East Block)
- 5. © 2008-09 Choice Solutions5
APSEB (CMD) Power
Audit Activities
Check CMD allotted, utilization and cable size
Check cable temperature, % loss across the cable
from starting to end point
Measure PF
Check for loads connected
Measure phases and neutral current
Contd…
- 6. © 2008-09 Choice Solutions6
APSEB (CMD) Power
Audit Activities
Check for load balancing
Check for body and neutral earthing
Check for PCC
Check for PCC panel bus bar conductor size
- 7. © 2008-09 Choice Solutions7
DG
Audit Activities
Measure phase and neutral current
Check for load balancing and % of load
Measure load PF
Ascertain same cable and lug material as per standards
Copper or aluminum
Contd...
- 8. © 2008-09 Choice Solutions8
DG
Audit Activities
Check for gland and gland plates
Check for cable routing, bunching and termination
Check for generator capacity, utilization, and age
Engine and alternator
Check for loads connected
Contd...
- 9. © 2008-09 Choice Solutions9
DG
Audit Activities
Check for MCO/AMF panel
Check generator battery’s age and condition
Check for body and neutral earthing
Check for earth resistance
Measure current rating of ACB/MCBs and sockets
Check for MCB enclosure
Check for emergency lighting in critical and common areas
- 10. © 2008-09 Choice Solutions10
Load Balancing on EB and DG
Audit Activities
Loads on EB
Check load on R-phase current
Check load on Y-phase current
Check load on B-phase current
Loads on DG
Check load on R-phase current
Check load on Y-phase current
Check load on B-phase current
- 11. © 2008-09 Choice Solutions11
MCO Panel / AMF Panel
Audit Activities
Check terminations of changeover
Check for inter locking system between EB and DG
Check for connection status of APFC while on DG
Check for glands and gland plates
Check for switchgear neutral contact rating
Check for cable size and bus bar capacity
Check for body earthing
- 12. © 2008-09 Choice Solutions12
APFC
Audit Activities
Check for automatic/manual connection
Check for faulty capacitors/contactors
Check for sufficient number of capacitors
Check for capacitor bank fuses
Check for PF close to unity
Contd…
- 13. © 2008-09 Choice Solutions13
APFC
Audit Activities
Check cable size
Check if capacitors designed as per PF correction
Check capacitors working conditions
Check for body earthing
Check for PF which causes incentive / penalty
- 14. © 2008-09 Choice Solutions14
Main LT Panel
Audit Activities
Ensure combined load or other facility load billing
shouldn’t reflect in xxxmonthly billing
Assess power in LT panel
Check routing, bunching and termination of cables
Check MCCB/ACB ratings and function
Check for interlocking system function
Contd…
- 15. © 2008-09 Choice Solutions15
Main LT Panel
Audit Activities
Check for bus bar size
Check for neutral size
Check earth cable size
Check for body earthing
Check for emergency lighting in critical and common areas
- 16. © 2008-09 Choice Solutions16
UPS
Audit Activities
Check UPS input PF
Check UPS input and output harmonics (VTHD and ITHD)
Check input filter inside UPS
Check efficiency and backup
Check loads connected
Measure phases and neutral current
- 17. © 2008-09 Choice Solutions17
UPS
Audit Activities
Check routing, bunching and termination of cables
Check body and neutral earthing
Check efficiency and heat dissipation of UPS
Check ventilation for air circulation in the UPS room
Check for emergency lighting in critical and common areas
Check if, UPS are having parallel redundancy
- 18. © 2008-09 Choice Solutions18
Other Loads
Audit Activities
Check lighting load
Check AC and chiller plant load
Check elevator load
Check routing, bunching and termination of cables
Check body and neutral earthing
Check load protections
- 19. Agenda
Audit Scope of Work
Contract Demand Diversity Factor
Capacity vs. Utilization (Infrastructure Optimization)
MD
DG
UPS
Consumption (End Loads)
UPS
LDB
AHU
Spilt A/C’s
Potential Power Savings (Infrastructure Optimization)
MD
DG
UPS
Power Quality
Facility Observations
Conclusions and Next Steps
- 20. © 2008-09 Choice Solutions20
Loads and Maximum Consumption
APSEB Power 750 kVA CMD with 11 kV HT
1800 kVA Transformer
Total: 1054 kVA Max
Electricity
Bill
Unit = 1 kW
3x160 kVA UPS
(For facility)
2X120 KVAUPS
(For server and HUB room)
Air conditioners (AHU)
LDB
(For lighting and raw power)
Current: 105 kVA
Current: 250 kVA Current: 75 kVA
Current: 470 kVA Current: 100 kVA
Other Loads
(Water, elevator, terrace and cafeteria)
- 21. © 2008-09 Choice Solutions21
Capacity vs. Utilization
MD (Peak Load)
• Peak load consumption is 1054 kVA
• Avoid maximum demand cross penalty by increasing MD to 2000 kVA from current 750 kVA
• Hence results in opex savings
• Includes cushion of ~35%
• Peak load consumption is 1054 kVA
• Avoid maximum demand cross penalty by increasing MD to 2000 kVA from current 750 kVA
• Hence results in opex savings
• Includes cushion of ~35%
750 kVA Voltage (V) Current (A) PF kW kVA
R 238.1 1498 0.83 300 360
Y 239.7 1430 0.81 278 346
B 239.9 1432 0.92 319 348
TOTAL 897 1054
750 kVA MD utilization = 1054/750 = 140.5%, under provisioned
- 22. Agenda
Audit Scope of Work
Contract Demand Diversity Factor
Capacity vs. Utilization (Infrastructure Optimization)
MD
DG
UPS
Consumption (End Loads)
UPS
LDB
AHU
Spilt A/C’s
Potential Power Savings (Infrastructure Optimization)
MD
DG
UPS
Power Quality
Facility Observations
Conclusions and Next Steps
- 23. © 2008-09 Choice Solutions23
Capacity vs. Utilization
Generator (DG 4x 500 kVA, xxx Load)
4x500 kVA Voltage (V) Current (A) PF kW kVA
R 237.6 1531 0.78 284 364
Y 228.9 1526 0.80 280 351
B 228.8 1592 0.80 294 368
TOTAL 858 1083
DG utilization( xxx ) = 1083/2000 = 54%
• 35% capacity is unutilized
• DG is over loaded, heated and tripping even utilization (65%) is less than rated DG capacity
• Current load is < 1300 kVA( Including other tenants of consumption less than 300 kVA)
• Save opex by switching to 3 x750 kVA DG instead of existing old DG
• Lower diesel expenses with auto synchronization switching of the DG sets
• Increase PF to 0.90, for maximum utilization of the rated capacity
• 35% capacity is unutilized
• DG is over loaded, heated and tripping even utilization (65%) is less than rated DG capacity
• Current load is < 1300 kVA( Including other tenants of consumption less than 300 kVA)
• Save opex by switching to 3 x750 kVA DG instead of existing old DG
• Lower diesel expenses with auto synchronization switching of the DG sets
• Increase PF to 0.90, for maximum utilization of the rated capacity
- 24. © 2008-09 Choice Solutions24
Capacity vs. Utilization
Other Tenants Load on 4x 500 kVA DG
4x500 kVA Voltage (V) Current (A) PF kW kVA
R 235.8 349.1 0.83 66.7 80.4
Y 239.6 284.4 0.81 55.4 68.9
B 238.8 298.3 0.80 55.4 69.4
TOTAL 177.5 218.7
DG utilization (other tenants) = 218.7/2000 = 11%
- 25. © 2008-09 Choice Solutions25
Capacity vs. Utilization
xxx Load on 4x 500 kVA DG
Observations and Recommendations:
Replace current 4 x 500 kVA with separate 3 x 750 kVA D.G
Current DG set is old, hence over loaded and tripping even DG utilization is
1280 kVA at 0.8 PF which is less than rated kVA (2000kVA at 0.8 PF)
xxx facilities are asked to switch off first and second floor A/C load, to reduce
over loading on DG set as it is making more sound and heat
For reducing heat, building maintenance people are pouring water on DG
sets, not advisable
Increase PF at DG output to reduce load factor for maximum capacity
utilization
- 26. © 2008-09 Choice Solutions26
Capacity vs. Utilization
UPS 1(120 kVA Server Room source-1)
• Load is 31% in 120 kVA, use 40 kVA with redundancy, to save opex and capex
• This includes 7.5% cushion which supports future expansion
• Load is 31% in 120 kVA, use 40 kVA with redundancy, to save opex and capex
• This includes 7.5% cushion which supports future expansion
UPS utilization = 37.3/120 = 31%
120 kVA Voltage (V) Current (A) PF KW KVA
R 221.1 54.6 0.74 9.0 12.1
Y 225.3 53.5 0.79 9.6 12.1
B 226.7 57.6 0.78 10.2 13.1
TOTAL 28.8 37.3
- 27. © 2008-09 Choice Solutions27
Capacity vs. Utilization
UPS 2 (120 kVA Server Room Source - 2)
UPS utilization = 36.3/120 = 30 %
120 kVA Voltage (V) Current (A) PF KW KVA
R 221.0 51.7 0.74 8.6 11.6
Y 229.4 52.4 0.77 9.3 12.1
B 232.8 54.2 0.75 9.4 12.6
TOTAL 27.3 36.3
• Load is 30% in 120 kVA, use 40 kVA with redundancy, to save opex and capex
• This includes 7.5% cushion which supports future expansion
• Load is 30% in 120 kVA, use 40 kVA with redundancy, to save opex and capex
• This includes 7.5% cushion which supports future expansion
- 28. © 2008-09 Choice Solutions28
Capacity vs. Utilization
UPS 3 (160 kVA Ground Floor Facility)
UPS utilization = 63.9/160 = 40 %
160 kVA Voltage (V) Current (A) PF KW KVA
R 223.1 92.4 0.78 16.1 20.6
Y 225.9 95.0 0.82 17.6 21.4
B 226.9 97.6 0.81 17.7 21.9
TOTAL 51.4 63.9
• Load is 40% in 160 kVA, use 80 kVA with redundancy, to save opex and capex
• This includes 20% cushion which supports future expansion
• Load is 40% in 160 kVA, use 80 kVA with redundancy, to save opex and capex
• This includes 20% cushion which supports future expansion
- 29. © 2008-09 Choice Solutions29
Capacity vs. Utilization
UPS 4 (160 kVA First Floor Facility)
UPS utilization = 73.1/160 = 46 %
160 kVA Voltage (V) Current (A) PF KW KVA
R 226.7 101.0 0.77 17.5 22.7
Y 232.5 106.5 0.83 20.3 24.7
B 235.1 110.1 0.77 19.8 25.7
TOTAL 57.6 73.1
• Load is 46% in 160 kVA, use 80 kVA with redundancy, to save opex and capex
• This includes 8% cushion which supports future expansion
• Load is 46% in 160 kVA, use 80 kVA with redundancy, to save opex and capex
• This includes 8% cushion which supports future expansion
- 30. © 2008-09 Choice Solutions30
Capacity vs. Utilization
UPS 5 (160 kVA Second Floor Facility)
UPS utilization = 79.3 /160 = 50 %
160 kVA Voltage (V) Current (A) PF KW KVA
R 226.0 109.0 0.79 19.5 24.8
Y 231.4 114.8 0.83 22.4 26.9
B 234.3 116.3 0.79 21.9 27.6
TOTAL 63.8 79.3
• Load is 50% in 160 kVA, use 80 kVA with redundancy, to save opex and capex
• This includes no cushion
• Load is 50% in 160 kVA, use 80 kVA with redundancy, to save opex and capex
• This includes no cushion
- 31. © 2008-09 Choice Solutions31
Capacity vs. Utilization
UPS 6 (160 kVA Standby UPS for all UPS)
UPS utilization = 31.2/160 = 20%
160 kVA Voltage (V) Current (A) PF KW KVA
R 223.2 44.3 0.67 6.6 9.9
Y 227.2 44.3 0.71 7.2 10.1
B 228.7 48.3 0.72 8.0 11.2
TOTAL 21.8 31.2
- 32. Agenda
Audit Scope of Work
Contract Demand Diversity Factor
Capacity vs. Utilization (Infrastructure Optimization)
MD
DG
UPS
Consumption (End Loads)
UPS
LDB
AHU
Spilt A/C’s
Potential Power Savings (Infrastructure Optimization)
MD
DG
UPS
Power Quality
Facility Observations
Conclusions and Next Steps
- 33. © 2008-09 Choice Solutions33
Consumption
Ground Floor Lighting and Raw Power Load
Consumption
Ground Floor Lighting and Raw Power Load
Lighting consumption = 30.30 kVA
Voltage (V) Current (A) PF KW KVA
R 224.0 41.19 0.84 7.57 9.0
Y 228.3 39.80 0.87 7.72 9.1
B 229.5 58.1 0.82 9.7 12.2
TOTAL 25.0 30.30
- 34. © 2008-09 Choice Solutions34
Consumption
First Floor Lighting and Raw Power Load
Lighting consumption = 30 kVA
Voltage (V) Current (A) PF KW KVA
R 221.4 49.17 0.94 8.36 8.91
Y 226.9 31.07 0.90 6.63 7.38
B 228.9 57.7 0.79 10.4 13.2
TOTAL 25.39 29.59
- 35. © 2008-09 Choice Solutions35
Consumption
Second Floor Lighting and Raw Power Load
Lighting consumption = 34.80
Voltage (V) Current (A) PF KW KVA
R 224.9 45.54 0.84 8.6 10.3
Y 229.9 59.9 0.88 11.9 13.5
B 230.6 47.65 0.84 9.22 11.0
TOTAL 29.72 34.80
- 36. © 2008-09 Choice Solutions36
Consumption
Terrace and Cafeteria Load
Lighting consumption = 93.10
Voltage (V) Current (A) PF KW KVA
R 223.3 137.1 0.89 27.4 30.7
Y 226.7 134.7 0.86 25.8 30.2
B 228.1 141.1 0.87 27.9 32.2
TOTAL 81.10 93.10
- 37. © 2008-09 Choice Solutions37
Consumption
Elevator - 4
Elevator consumption = < 1 kVA
Voltage (V) Current (A) PF KW KVA
R 228.0 0.73 0.09 0.02 0.16
Y 231.3 1.18 0.95 0.26 0.27
B 230.6 0.48 0.04 0.00 0.11
TOTAL
- 38. © 2008-09 Choice Solutions38
Consumption
PAC
TR Voltage (V) Current (A) PF kW KVA
R 224.2 86.5 0.81 15.7 19.3
Y 228.4 85.9 0.80 15.7 19.6
B 229.5 76.9 0.77 13.5 17.6
TOTAL 44.90 56.50
Total PAC consumption =56.50 kVA
- 39. © 2008-09 Choice Solutions39
Consumption
Ground Floor AC
TR Voltage (V) Current (A) PF kW KVA
R 223.2 225.7 0.76 38.4 50.3
Y 226.7 216.1 0.78 38.3 49.1
B 228.4 224.3 0.75 38.6 51.3
TOTAL 115.30 150.7
Total AHU consumption = 150.7 kVA
• Multiple number of AHU’s installed in facility
• Needs to increase PF to 0.95, for better AC capacity utilization
• Multiple number of AHU’s installed in facility
• Needs to increase PF to 0.95, for better AC capacity utilization
- 40. © 2008-09 Choice Solutions40
Consumption
First Floor AC
TR Voltage (V) Current (A) PF kW KVA
R 223.0 150.6 0.72 24.2 33.7
Y 226.7 145.7 0.74 24.4 33.0
B 227.7 153.2 0.71 27.2 38.1
TOTAL 75.80 104.80
Total AHU consumption = 104.80 kVA
• Multiple number of small AHU’s installed in facility
• Needs to increase PF to 0.95, for better AC capacity utilization
• Multiple number of small AHU’s installed in facility
• Needs to increase PF to 0.95, for better AC capacity utilization
- 41. © 2008-09 Choice Solutions41
Consumption
Second Floor AC
TR Voltage (V) Current (A) PF kW KVA
R 223.1 229.4 0.72 37.0 51.2
Y 227.0 226.1 0.75 38.6 51.4
B 228.1 236.2 0.68 38.9 54.0
TOTAL 114.50 156.60
Total AHU consumption =156.60 kVA
• Multiple number of small AHU’s installed in facility
• Needs to increase PF to 0.95, for better AC capacity utilization
• Multiple number of small AHU’s installed in facility
• Needs to increase PF to 0.95, for better AC capacity utilization
- 42. Agenda
Audit Scope of Work
Contract Demand Diversity Factor
Capacity vs. Utilization (Infrastructure Optimization)
MD
DG
UPS
Consumption (End Loads)
UPS
LDB
AHU
Spilt A/C’s
Potential Power Savings (Infrastructure Optimization)
MD
DG
UPS
Power Quality
Facility Observations
Conclusions and Next Steps
- 43. © 2008-09 Choice Solutions43
Potential Power Savings
Electricity Bill Incentive and Penalty
# Meter details Bill Date Bill Amount MD Penalty PF Penalty
1 Consumption at HT Meter( 750 kVA MD) Feb 2008 24,23,938.00 2,10,244.00 -
2 Consumption at HT Meter( 750 kVA MD) March 2008 27,65,108.00 2,64,420.00 -
3 Consumption at HT Meter( 750 kVA MD) April 2008 29,86,375.00 3,46,164.00 -
4 Consumption at HT Meter( 750 kVA MD) May 2008 35,17,680.00 4,40,700.00 3,00,745.00
5 Consumption at HT Meter( 750 kVA MD) June 2008 37,72,886.00 4,67,026.00 3,68,358.00
6 Consumption at HT Meter( 750 kVA MD) July 2008 28,66,053.00 2,60,052.00 -
Total 1,83,32,040.00 19,88,606.00 6,69,103.00
• MD crossed average penalty per month is Rs. 3, 31, 434/-
• Average PF penalty per month is Rs. 1,11,517/-
• Total monthly average penalty is Rs.4,42,951/-
• Average penalty per year is Rs.53,15,414/-
• MD crossed average penalty per month is Rs. 3, 31, 434/-
• Average PF penalty per month is Rs. 1,11,517/-
• Total monthly average penalty is Rs.4,42,951/-
• Average penalty per year is Rs.53,15,414/-
- 44. © 2008-09 Choice Solutions44
Potential Power Savings
MD
# Area of Saving Opex (Annual)
1 Shifting to 2000 kVA MD instead of 750 kVA * Rs.33,57,912.00
TOTAL Rs.33,57,912.00
(MD charge/kVA/month of Rs. 218.4/-) x (demand of 750 kVA) = Rs.19,65,600/-
* (MD Penalty charge/kVA/month of Rs. 436.8/-) x (demand difference of 1069 kVA) x (12 months per
year) Rs. 56,04,312/-
Total MD charges including penalty per year Rs. 75,69,912/-
* (MD charge/kVA/month of Rs. 195/-) x (demand difference of 1800 kVA) x (12 months per year) is Rs.
42,12,000/-
Total MD charges saving by upgrading to 1800 kVA is Rs. 33,57,912/- year
- 45. © 2008-09 Choice Solutions45
Potential Power Savings
PFC
# Area of Saving Opex (Annual)
2 By Correcting the PF from 0.81 to 0.92**
Direct savings10% on monthly billing
Rs. 13,38,204.00
TOTAL Rs. 13,38,204.00
** (Rs1,11,517 / month) x (12 months per year) equals Rs. 13,38,204/-
Capacitor required to correct the PF is kVAR = 897 { Tan[ cos-1( 0.81)] – Tan [ cos -1 ( 0.95)]}= 354
kVAR approximately 400 KVAR
- 46. © 2008-09 Choice Solutions46
Potential Power Savings
DG
# Area of Saving Opex (Annual)
3 Use 3x750 kVA instead of 4 x 500 kVA ***
Diesel consumption savings
(270lts vs. 240lts/hr) *** Rs.1,08,000.00
TOTAL Rs.1,08,000.00
** Based on new Cummins 500 kVA and 750 kVA DG set diesel consumption
*** (Rs. 30 per lt diesel) x (30 lts/hr difference) x (120 hrs power cut per year) equals to Rs. 1, 08, 000/-
Assuming 2x750 kVA run instead of 3x500 kVA at 75% load
- 47. © 2008-09 Choice Solutions47
Potential Power Savings
UPS (Server)
# Area of Saving Opex (Annual)
4 Replace 2x120 kVA UPS with 2x60 kVA ****
Savings from No load losses *****
3,31,776.00
UPS AMC charges savings ******
. 60,000.00
Savings in cooling the UPS *******
1,16,121.00
TOTAL Rs. 5,07,897.00
**** Requirement is met by 2x60 kVA (this includes 40% cushion and redundancy with 1x160 KVA i.e UPS 6)
***** For the2x120 kVA and 2 x60 kVA UPS Efficiency difference, 9.6 kW per hour x Rs. 4 per hr x 24 hrs x
30 days per month x 12 months per year
****** For the 120 kVA and 60 kVA UPS AMC charges difference, Rs. 30,000 per year x 2 No of UPS
******* For the 2x120 kVA and 2x60 kVA UPS cooling requirements difference, 3.36 kW per hr x Rs. 4 per hr
x 24 hrs x 30 days per month x 12 months per year
- 48. © 2008-09 Choice Solutions48
Potential Power Savings
UPS (Facility)
# Area of Saving Opex (Annual)
5 Replace 3x160 kVA UPS with 3x80 kVA ****
Savings from No load losses *****
4,42,368.00
UPS AMC charges savings ******
.1,00,000.00
Savings in cooling the UPS *******
1,54,828.00
TOTAL Rs.6,97,196.00
**** Requirement is met by 2x160 kVA (this includes 25% cushion and redundancy with 1x160KVA i.e UPS
6)
***** For the3x160kVA and 2 x160kVA UPS Efficiency difference, 12.8 kW per hour x Rs. 4 per hr x 24 hrs x
30 days per month x 12 months per year
****** For the 120kVA and 60 kVA UPS AMC charges difference, Rs. 30,000 per year x 2 No of UPS
******* For the 2x120kVA and 2x60kVA UPS cooling requirements difference, 4.48 kW per hr x Rs. 4 per hr x
24 hrs x 30 days per month x 12 months per year
- 49. © 2008-09 Choice Solutions49
Potential Power Savings
Summary
# Area of Saving Opex (Annual)
1 Shifting to 2000 kVA MD instead of 750 kVA * 33,57,912.00
2 By Correcting the PF from 0.81 to 0.92**
Direct savings10% on monthly billing .3,38,204.00
3 Use 3x750 kVA instead of 4 x 500 kVA ***
Diesel consumption savings
(270lts vs. 240lts/hr) ***
1,08,000.00
4
Replace 2x120 kVA UPS with 2x60 kVA ****
(Server)
Savings from No load losses ***** 3,31,776.00
UPS AMC charges savings ****** . 60,000.00
5 Replace 3x160 kVA UPS with 3x80 kVA ****
Savings from No load losses ***** 4,42,368.00
UPS AMC charges savings ****** .1,00,000.00
Savings in cooling the UPS ******* 1,54,828.00
TOTAL Rs. 48,93,088
- 50. © 2008-09 Choice Solutions50
Potential Power Savings
Summary
(MD Penalty charge/kVA/month of Rs. 436.8/-) x (demand difference of 1069 kVA) x (12 months per
year) Rs. 56,04,312/-
Total MD charges includes penalty per year Rs. 75,69,912/-
* (MD charge/kVA/month of Rs. 195/-) x (demand difference of 1800 kVA) x (12 months per year) is Rs.
42,12,000/-
Total MD charges saving by upgrading to 1800 kVA is Rs. 33,57,912/- year
(MD charge/kVA/month of Rs. 218.4/-) x (demand of 750 kVA) = Rs.19,65,600/-
** (Rs1,11,517 / month) x (12 months per year) equals Rs. 13,38,204/-
Capacitor required to correct the PF is KVAR = 897 { Tan[ cos-1( 0.81)] – Tan [ cos -1 ( 0.95)]}= 354
kVAR approximately 400 KVAR
** (Rs1,11,517 / month) x (12 months per year) equals Rs. 13,38,204/-
Capacitor required to correct the PF is KVAR = 897 { Tan[ cos-1( 0.81)] – Tan [ cos -1 ( 0.95)]}= 354
kVAR approximately 400 KVAR
Contd…
- 51. © 2008-09 Choice Solutions51
Potential Power Savings
Summary
**** Requirement is met by 2x60 kVA (this includes 40% cushion and redundancy with 1x160 KVA i.e UPS 6)
***** For the2x120 kVA and 2 x60 kVA UPS Efficiency difference, 9.6 kW per hour x Rs. 4 per hr x 24 hrs x 30
days per month x 12 months per year
****** For the 120kVA and 60 kVA UPS AMC charges difference, Rs. 30,000 per year x 2 No of UPS
******* For the 2x120kVA and 2x60kVA UPS cooling requirements difference, 3.36 kW per hr x Rs. 4 per hr x
24 hrs x 30 days per month x 12 months per year
**** Requirement is met by 2x160 kVA (this includes 25% cushion and redundancy with 1x160KVA i.e UPS 6)
***** For the3x160kVA and 2 x160kVA UPS Efficiency difference, 12.8 kW per hour x Rs. 4 per hr x 24 hrs x 30
days per month x 12 months per year
****** For the 120kVA and 60 kVA UPS AMC charges difference, Rs. 30,000 per year x 2 No of UPS
******* For the 2x120kVA and 2x60kVA UPS cooling requirements difference, 4.48 kW per hr x Rs. 4 per hr x
24 hrs x 30 days per month x 12 months per year
- 52. Agenda
Audit Scope of Work
Contract Demand Diversity Factor
Capacity vs. Utilization (Infrastructure Optimization)
MD
DG
UPS
Consumption (End Loads)
UPS
LDB
AHU
Spilt A/C’s
Potential Power Savings (Infrastructure Optimization)
MD
DG
UPS
Power Quality
Facility Observations
Conclusions and Next Steps
- 53. Main PCC Panel Readings
xxx Panel readings
DG Readings
PFC Readings
Main LT Panel Readings
- 55. © 2008-09 Choice Solutions55
Building Common PCC Panel
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.81 > 0.95 Low PF, causes cable heating and high demand rating
Waveform Unstable Stable Bad impact on loads
- 56. © 2008-09 Choice Solutions56
Building Common PCC Panel
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 57. © 2008-09 Choice Solutions57
Building Common PCC Panel
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.82 > 0.95 Low PF, causes cable heating and high demand rating
Waveform Stable Unstable Bad impact on loads
- 58. © 2008-09 Choice Solutions58
Building Common PCC Panel
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 59. © 2008-09 Choice Solutions59
Building Common PCC Panel
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 > 0.95 Low PF, causes cable heating and high demand rating
Waveform Stable Unstable Bad impact on loads
- 60. © 2008-09 Choice Solutions60
Building Common PCC Panel
B-Phase: Voltage and Current Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage Harmonic 5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 10.6%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 61. © 2008-09 Choice Solutions61
Building Common PCC Panel
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 1.4 V < 3 V E-N voltage is within limits
Waveform Unstable Stable Abnormal, reduce equipment performance
- 62. © 2008-09 Choice Solutions62
Building Common PCC Panel
N-E: Voltage and Current Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage Harmonic 45.1% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 54.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Increases cable losses
- 64. © 2008-09 Choice Solutions64
xxx Panel
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.87 > 0.95 Low PF, causes cable heating and high demand rating
Waveform Stable Stable Bad Impact on loads
- 65. © 2008-09 Choice Solutions65
xxx Panel
R-Phase: Voltage and Current Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage Harmonic 4.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 66. © 2008-09 Choice Solutions66
xxx Panel
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.86 > 0.95 Low PF, causes cable heating and high demand rating
Waveform Stable Stable Bad impact on loads
- 67. © 2008-09 Choice Solutions67
xxx Panel
Y-Phase: Voltage and Current Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage Harmonic 4.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 12.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 68. © 2008-09 Choice Solutions68
xxx Panel
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.84% > 0.95 Low PF, causes cable heating and high demand rating
Waveform Stable Stable Bad impact on loads
- 69. © 2008-09 Choice Solutions69
xxx Panel
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.4% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 70. © 2008-09 Choice Solutions70
xxx Panel
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 2.50 V < 3 V E-N voltage is within limits
Waveform Unstable Stable PFC behavior
- 71. © 2008-09 Choice Solutions71
xxx Panel
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
36.1% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 71.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Increases cable losses
- 72. © 2008-09 Choice Solutions72
Maximum Load of xxx
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.83 > 0.95 Low PF, causes cable heating and high demand rating
Waveform Unstable Stable Bad impact on loads
- 73. © 2008-09 Choice Solutions73
Maximum load of xxx
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.81 >0.85 Low PF, causes cable heating and high demand rating
Waveform Unstable Stable Bad impact on loads
- 74. © 2008-09 Choice Solutions74
Maximum load of xxx
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.92 >0.85 Low PF, causes cable heating and high demand rating
Waveform Unstable Stable Bad impact on loads
- 76. © 2008-09 Choice Solutions76
DG 1 (with first and second floor AC being off)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.67 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Unstable Stable
Without capacitor bank, If same power feeding load, may
damage equipment
- 77. © 2008-09 Choice Solutions77
DG 1 (with first and second floor AC being off)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 9.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 78. © 2008-09 Choice Solutions78
DG 1 (with first and second floor AC being off)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.62 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Unstable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 79. © 2008-09 Choice Solutions79
DG 1 (with first and second floor AC being off)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 13.1 %
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 80. © 2008-09 Choice Solutions80
DG 1 (with first and second floor AC being off)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.49 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform unstable Stable
Without capacitor bank, If same power feeding load, may
damage
equipment
- 81. © 2008-09 Choice Solutions81
DG 1 (with first and second floor AC being off)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 13.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 82. © 2008-09 Choice Solutions82
DG 1 (with first and second floor AC being off)
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 3.07 V < 3 V E-N voltage is within limits
Waveform Unstable Stable Back feeding harmonics causes damaging the equipments
- 83. © 2008-09 Choice Solutions83
DG 1 (with first and second floor AC being off)
N-E: Voltage and Current Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage Harmonic 34.8% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 22.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Increases cable losses
- 84. © 2008-09 Choice Solutions84
DG 2 (with first and second floor AC being off)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 85. © 2008-09 Choice Solutions85
DG 2 (with first and second floor AC being off)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 10.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 86. © 2008-09 Choice Solutions86
DG 2 (with first and second floor AC being off)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.74 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 87. © 2008-09 Choice Solutions87
DG 2 (with first and second floor AC being off)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 10.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 88. © 2008-09 Choice Solutions88
DG 2 (with first and second floor AC being off)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.76 > 0.95 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 89. © 2008-09 Choice Solutions89
DG 2 (with first and second floor AC being off)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 90. © 2008-09 Choice Solutions90
DG 2 (with first and second floor AC being off)
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 3.61 V < 3 V Need to check and set the earth pit
Waveform Stable Stable Normal and no bad Impact on loads
- 91. © 2008-09 Choice Solutions91
DG 2 (with first and second floor AC being off)
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
46.8% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 10.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics with in limits
- 92. © 2008-09 Choice Solutions92
DG 3 (with first and second floor AC being off)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 93. © 2008-09 Choice Solutions93
DG 3 (with first and second floor AC being off)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 94. © 2008-09 Choice Solutions94
DG 3 (with first and second floor AC being off)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.79 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 95. © 2008-09 Choice Solutions95
DG 3 (with first and second floor AC being off)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.4% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 96. © 2008-09 Choice Solutions96
DG 3 (with first and second floor AC being off)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 > 0.95 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may
damage
equipment
- 97. © 2008-09 Choice Solutions97
DG 3 (with first and second floor AC being off)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 98. © 2008-09 Choice Solutions98
DG 3 (with first and second floor AC being off)
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 3.42 V < 3 V E-N voltage is within limits
Waveform Stable Stable Normal and no bad Impact on loads
- 99. © 2008-09 Choice Solutions99
DG 3 (with first and second floor AC being off)
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
E-N Voltage 3.42 V < 3 V E-N voltage is within limits
Waveform Stable Stable Normal and no bad Impact on loads
- 100. © 2008-09 Choice Solutions100
DG 4 (with first and second floor AC being off)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.99 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 101. © 2008-09 Choice Solutions101
DG 4 (with first and second floor AC being off)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.4% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 13.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 102. © 2008-09 Choice Solutions102
DG 4 (with first and second floor AC being off)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.99 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 103. © 2008-09 Choice Solutions103
DG 4 (with first and second floor AC being off)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 13.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 104. © 2008-09 Choice Solutions104
DG 4 (with first and second floor AC being off)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.99 > 0.95 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 105. © 2008-09 Choice Solutions105
DG 4 (with first and second floor AC being off)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 14.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 106. © 2008-09 Choice Solutions106
Other tenants load on DG (with first and second floor AC being off)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.83 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 107. © 2008-09 Choice Solutions107
Other tenants load on DG (with first and second floor AC being off)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.81 >0.85 PF with in limits should Not be less than 0.85
Waveform Stable Stable If unstable, leads to flickering/damaging of CRTs
- 108. © 2008-09 Choice Solutions108
Other tenants load on DG (with first and second floor AC being off)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 > 0.95 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may
damage
equipment
- 109. © 2008-09 Choice Solutions109
Maximum Load on DG
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 >0.85 Low PF leads to cable heating and de-rating of DG
Waveform Stable Stable
Without capacitor bank, If same power feeding load, may damage
equipment
- 110. © 2008-09 Choice Solutions110
Maximum Load on DG
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 >0.85 PF with in limits should Not be less than 0.85
Waveform Stable Stable If unstable, leads to flickering/damaging of CRTs
- 111. © 2008-09 Choice Solutions111
Maximum Load on DG
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 > 0.95 PF with in limits should Not be less than 0.85
Waveform Stable Stable Normal and no impact on load
- 113. © 2008-09 Choice Solutions113
PFC Bank - 1
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.93 <1 kW
Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 114. © 2008-09 Choice Solutions114
PFC Bank - 1
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 33.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Cable gets heated up
Frequent failure of fuses
- 115. © 2008-09 Choice Solutions115
PFC Bank - 1
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.80 <1 kW
Consumption of active power is a symptom of faulty
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 116. © 2008-09 Choice Solutions116
PFC Bank – 1
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 31.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics Not in limits
- 117. © 2008-09 Choice Solutions117
PFC Bank - 1
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 0 kW <1 kW Capacitor is not working
Waveform Stable Capacitor is not working
- 118. © 2008-09 Choice Solutions118
PFC Bank - 1
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 51.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 119. © 2008-09 Choice Solutions119
PFC Bank - 1
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 8.53 <1 kW
Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 120. © 2008-09 Choice Solutions120
PFC Bank - 1
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.6% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 32.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 121. © 2008-09 Choice Solutions121
PFC Bank - 2
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 5.94 <1 kW
Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 122. © 2008-09 Choice Solutions122
PFC Bank – 2
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.6% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 32.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 123. © 2008-09 Choice Solutions123
PFC Bank – 2
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 0.20 <1 kW Capacitor is working fine and correcting PF.
Waveform Zigzag Stable It may causes damage to equipment
- 124. © 2008-09 Choice Solutions124
PFC Bank - 2
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.6% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 31.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 125. © 2008-09 Choice Solutions125
PFC Bank - 2
Capacitor : Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 0.18 <1 kW Capacitor is working fine and correcting PF.
Waveform Zigzag Stable It may causes damage to equipment
- 126. © 2008-09 Choice Solutions126
PFC Bank - 2
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 33.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 127. © 2008-09 Choice Solutions127
PFC Bank - 2
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 6.97 <1 kW
Consumption of active power is a symptom of faulty
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 128. © 2008-09 Choice Solutions128
PFC Bank - 2
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 33.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 129. © 2008-09 Choice Solutions129
PFC Bank - 3
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.52 <1 kW Consumption of active power is a symptom of faulty
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 130. © 2008-09 Choice Solutions130
PFC Bank - 3
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 32.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 131. © 2008-09 Choice Solutions131
PFC Bank - 3
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 17.3 <1 kW Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 132. © 2008-09 Choice Solutions132
PFC Bank - 3
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 33.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 133. © 2008-09 Choice Solutions133
PFC Bank - 3
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 6.71 <1 kW
Consumption of active power is a symptom of faulty
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 134. © 2008-09 Choice Solutions134
PFC Bank - 3
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 34.6%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 135. © 2008-09 Choice Solutions135
PFC Bank – 4
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 8.99 <1 kW Consumption of active power is a symptom of faulty
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 136. © 2008-09 Choice Solutions136
PFC Bank - 4
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 30.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 137. © 2008-09 Choice Solutions137
PFC Bank - 5
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.22 <1 kW
Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 138. © 2008-09 Choice Solutions138
PFC Bank - 5
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 32.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 139. © 2008-09 Choice Solutions139
PFC Bank - 5
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.99 <1 kW
Consumption of active power is a symptom of faulty
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 140. © 2008-09 Choice Solutions140
PFC Bank - 5
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 32.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 141. © 2008-09 Choice Solutions141
PFC Bank - 5
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.46 <1 kW
Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 142. © 2008-09 Choice Solutions142
PFC Bank - 6
Capacitor: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 32.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 143. © 2008-09 Choice Solutions143
PFC Bank - 6
Capacitor: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
kW 9.52 <1 kW
Consumption of active power is a symptom of faulty .
Will not correct the PF
Waveform Zigzag Stable It may causes damage to equipment
- 144. © 2008-09 Choice Solutions144
PFC Bank - 6
Capacitor : Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 31.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 145. © 2008-09 Choice Solutions145
Main L.T.Panel individual loads
UPS Incomer
Lighting and other load
AC load
- 146. © 2008-09 Choice Solutions146
UPS Incomer Details in Main L.T. Panel
UPS-1 input readings-3 phase system
UPS-2,4,5 input readings-3 phase and neutral system
UPS-3 input readings-3 phase system
UPS -6 input readings- 3 phase system
- 147. © 2008-09 Choice Solutions147
UPS - 1 Input (120 kVA)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.74 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 148. © 2008-09 Choice Solutions148
UPS - 1 Input (120 kVA)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 4.6% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 49.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 149. © 2008-09 Choice Solutions149
UPS - 1 Input (120 kVA)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.74 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS and resulting in less efficiency
- 150. © 2008-09 Choice Solutions150
UPS - 1 Input (120 kVA)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 48.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 151. © 2008-09 Choice Solutions151
UPS - 1 Input (120 kVA)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 152. © 2008-09 Choice Solutions152
UPS - 1 Input (120 kVA)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 45.7%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 153. © 2008-09 Choice Solutions153
UPS - 2, 4, 5 Common Incomer
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.83 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS and resulting in less efficiency
- 154. © 2008-09 Choice Solutions154
UPS - 2, 4, 5 Common Incomer
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 35.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 155. © 2008-09 Choice Solutions155
UPS - 2, 4, 5 Common Incomer
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.85 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 156. © 2008-09 Choice Solutions156
UPS - 2, 4, 5 Common Incomer
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 34.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 157. © 2008-09 Choice Solutions157
UPS - 2, 4, 5 Common Incomer
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.82 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 158. © 2008-09 Choice Solutions158
UPS - 2, 4, 5 Common Incomer
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 33.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 159. © 2008-09 Choice Solutions159
UPS - 2, 4, 5 Common Incomer
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 1.068 V <3 V E-N voltage within limits
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 160. © 2008-09 Choice Solutions160
UPS - 2, 4, 5 Common Incomer
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
57.8% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 17.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heating and losses
- 161. © 2008-09 Choice Solutions161
UPS - 3 Input (160 kVA)
R-Phase Input: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 162. © 2008-09 Choice Solutions162
UPS - 3 Input (160 kVA)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 44.1%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses
- 163. © 2008-09 Choice Solutions163
UPS - 3 Input (160 kVA)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.82 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 164. © 2008-09 Choice Solutions164
UPS - 3 Input (160 kVA)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 41.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 165. © 2008-09 Choice Solutions165
UPS - 3 Input (160 kVA)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.81 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 166. © 2008-09 Choice Solutions166
UPS - 3 Input (160 kVA)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 40.7%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 167. © 2008-09 Choice Solutions167
UPS - 6 Input (160 kVA)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.67 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 168. © 2008-09 Choice Solutions168
UPS - 6 Input (160 kVA)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.16% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 59.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 169. © 2008-09 Choice Solutions169
UPS - 6 Input (160 kVA)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.71 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 170. © 2008-09 Choice Solutions170
UPS - 6 Input (160 kVA)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 59.8%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses
- 171. © 2008-09 Choice Solutions171
UPS - 6 Input (160 kVA)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.72 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 172. © 2008-09 Choice Solutions172
UPS - 6 Input (160 kVA)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 56.7%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 173. © 2008-09 Choice Solutions173
UPS - 2 Input (120 kVA)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.74 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 174. © 2008-09 Choice Solutions174
UPS - 2 Input (120 kVA)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 51.4%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 175. © 2008-09 Choice Solutions175
UPS - 2 Input (120 kVA)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.77 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 176. © 2008-09 Choice Solutions176
UPS - 2 Input (120 kVA)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 49.8%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses
- 177. © 2008-09 Choice Solutions177
UPS - 2 Input (120 kVA)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.75 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 178. © 2008-09 Choice Solutions178
UPS - 2 Input (120 kVA)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 48.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 179. © 2008-09 Choice Solutions179
UPS - 4 Input (160 kVA)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.77 > 0.95 Low PF leads to high input current and harmonics
Waveform Unstable Stable Causes heating of UPS thus results in less efficiency
- 180. © 2008-09 Choice Solutions180
UPS - 4 Input (160 kVA)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 43.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 181. © 2008-09 Choice Solutions181
UPS - 4 Input (160 kVA)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.83 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Causes heating of UPS thus results in less efficiency
- 182. © 2008-09 Choice Solutions182
UPS - 4 Input (160 kVA)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
7.1% IEEE 519 harmonic limit is 3-5%
High Harmonics leads to equipment
damage
Current Harmonic 41.4%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses
- 183. © 2008-09 Choice Solutions183
UPS - 4 Input (160 kVA)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.77 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Causes heating of UPS thus results in less efficiency
- 184. © 2008-09 Choice Solutions184
UPS - 4 Input (160 kVA)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 38.7%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 185. © 2008-09 Choice Solutions185
UPS - 5 Input (160 kVA)
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.79 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Causes heating of UPS thus results in less efficiency
- 186. © 2008-09 Choice Solutions186
UPS - 5 Input (160 kVA)
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 39.7%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 187. © 2008-09 Choice Solutions187
UPS - 5 Input (160 kVA)
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.83 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Causes heating of UPS thus results in less efficiency
- 188. © 2008-09 Choice Solutions188
UPS - 5 Input (160 kVA)
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
7.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 37.8%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 189. © 2008-09 Choice Solutions189
UPS - 5 Input (160 kVA)
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.79 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Causes heating of UPS thus results in less efficiency
- 190. © 2008-09 Choice Solutions190
UPS - 5 Input (160 kVA)
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
6.8% IEEE 519 harmonic limit is 3-5%
High harmonics leads to equipment
damage
Current Harmonic 35.6%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses
- 192. © 2008-09 Choice Solutions192
Ground Floor Lighting and Raw power
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.84 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 193. © 2008-09 Choice Solutions193
Ground Floor Lighting and Raw Power
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 9.6%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 194. © 2008-09 Choice Solutions194
Ground Floor Lighting and Raw Power
Y-Phase: Voltage, Current and Power
Parameter Readin
g
Standard Observation/Impact
PF 0.87 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 195. © 2008-09 Choice Solutions195
Ground Floor Lighting and Raw Power
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 9.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 196. © 2008-09 Choice Solutions196
Ground Floor Lighting and Raw Power
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.82 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 197. © 2008-09 Choice Solutions197
Ground Floor Lighting and Raw Power
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 7.2%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 198. © 2008-09 Choice Solutions198
Ground Floor Lighting and Raw Power
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 0.858 V < 3 V E-N voltage is within limits
Waveform Unstable Stable Causes damage the equipments
- 199. © 2008-09 Choice Solutions199
Ground Floor Lighting and Raw Power
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
73.2% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 54.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 200. © 2008-09 Choice Solutions200
First Floor Lighting and Raw power
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.94 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 201. © 2008-09 Choice Solutions201
First Floor Lighting and Raw Power
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 12.8%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 202. © 2008-09 Choice Solutions202
First Floor Lighting and Raw Power
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.90 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 203. © 2008-09 Choice Solutions203
First Floor Lighting and Raw Power
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.9%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 204. © 2008-09 Choice Solutions204
First Floor Lighting and Raw Power
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.79 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 205. © 2008-09 Choice Solutions205
First Floor Lighting and Raw Power
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 7.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 206. © 2008-09 Choice Solutions206
First Floor Lighting and Raw Power
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 1.392 V < 3 V E-N voltage is within limits
Waveform Unstable Stable Causes equipment damage
- 207. © 2008-09 Choice Solutions207
First Floor Lighting and Raw Power
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
43.4% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 30.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 208. © 2008-09 Choice Solutions208
Second Floor Lighting and Raw Power
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.84 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 209. © 2008-09 Choice Solutions209
Second Floor Lighting and Raw Power
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 10.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 210. © 2008-09 Choice Solutions210
Second Floor Lighting and Raw Power
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.88 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 211. © 2008-09 Choice Solutions211
Second Floor Lighting and Raw Power
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 10.6%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 212. © 2008-09 Choice Solutions212
Second Floor Lighting and Raw Power
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.84 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 213. © 2008-09 Choice Solutions213
Second Floor Lighting and Raw Power
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 9.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 214. © 2008-09 Choice Solutions214
Second Floor Lighting and Raw Power
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N voltage 1.368 V < 3 V E-N voltage is within limits
Waveform Unstable Stable Causes equipment damage
- 215. © 2008-09 Choice Solutions215
Second Floor Lighting and Raw Power
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
51.0% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 66.4%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and
losses
- 216. © 2008-09 Choice Solutions216
Elevator - 4
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.09 > 0.95 PF within limits , No load
Waveform Stable Stable Normal and no bad Impact on loads
- 217. © 2008-09 Choice Solutions217
Elevator - 4
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 35.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Causes heat and losses
- 218. © 2008-09 Choice Solutions218
Elevator - 4
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.95 > 0.95 PF within limits
Waveform Unstable Stable Normal and no bad Impact on loads
- 219. © 2008-09 Choice Solutions219
Elevator - 4
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 26.2%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses.
- 220. © 2008-09 Choice Solutions220
Elevator - 4
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.04 > 0.95 Low PF leads to high input current
Waveform Stable Stable Normal and no bad Impact on loads
- 221. © 2008-09 Choice Solutions221
Elevator - 4
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 50.8%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Causes heat and losses
- 222. © 2008-09 Choice Solutions222
Elevator - 4
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
N-E 0.830v < 3v E-N voltage is within limits
Waveform Unstable Stable Causes equipment damage
- 223. © 2008-09 Choice Solutions223
Elevator - 4
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
65.7 IEEE 519 harmonic limit is 3-5% causes equipment damage
Current Harmonic 98.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 224. © 2008-09 Choice Solutions224
Terrace and Cafeteria
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.89 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable No bad impact on loads
- 225. © 2008-09 Choice Solutions225
Terrace and Cafeteria
R-Phase: Voltage, Current and Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.6% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 7.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 226. © 2008-09 Choice Solutions226
Terrace and Cafeteria
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.86 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and No bad impact
- 227. © 2008-09 Choice Solutions227
Terrace and Cafeteria
Y-Phase: Voltage, Current and Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 7.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 228. © 2008-09 Choice Solutions228
Terrace and Cafeteria
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.87 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and No bad impact
- 229. © 2008-09 Choice Solutions229
Terrace and Cafeteria
B-Phase: Voltage, Current and Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 6.4%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 230. © 2008-09 Choice Solutions230
Terrace and Cafeteria
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
E-N Voltage 1.356v < 3 V E-N voltage within limits
Waveform Stable Stable Normal and No bad impact on loads
- 231. © 2008-09 Choice Solutions231
Terrace and Cafeteria
N-E: Voltage, Current and Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
41.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 11.7%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 233. © 2008-09 Choice Solutions233
First Floor PAC Load
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.81 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 234. © 2008-09 Choice Solutions234
First Floor PAC Load
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 9.5%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 235. © 2008-09 Choice Solutions235
First Floor PAC Load
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.80 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 236. © 2008-09 Choice Solutions236
First Floor PAC Load
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 9.0%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 237. © 2008-09 Choice Solutions237
First Floor PAC Load
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.77 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 238. © 2008-09 Choice Solutions238
First Floor PAC Load
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
51% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 239. © 2008-09 Choice Solutions239
First Floor PAC Load
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
N-E Votage 1.114 V < 3 V N-E voltage within limits
N Current 12.01 0A High neutral current is due to load unbalancing
- 240. © 2008-09 Choice Solutions240
First Floor PAC Load
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
49.6% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 46.7%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Increases the cable losses
- 241. © 2008-09 Choice Solutions241
Ground Floor A/C
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.76 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 242. © 2008-09 Choice Solutions242
Ground Floor A/C
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 243. © 2008-09 Choice Solutions243
Ground Floor A/C
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 244. © 2008-09 Choice Solutions244
Ground Floor A/C
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.2% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 7.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 245. © 2008-09 Choice Solutions245
Ground Floor A/C
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.75 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and no bad Impact on loads
- 246. © 2008-09 Choice Solutions246
Ground Floor A/C
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.6%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Harmonics within limits
- 247. © 2008-09 Choice Solutions247
Ground Floor A/C
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
N-E Voltage 1.254 V < 3 V NE voltage is in limits
N Current 8.84 A 0 High neutral current is due to unbalanced load
- 248. © 2008-09 Choice Solutions248
Ground Floor A/C
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
35.9% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 20.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75
A
Increases cable losses and heating
- 249. © 2008-09 Choice Solutions249
First Floor A/C
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.72 > 0.95 Low PF leads to high input current
Waveform Stable Stable Normal and No bad Impact on loads
- 250. © 2008-09 Choice Solutions250
First Floor A/C
R-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 4.9% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.7%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 251. © 2008-09 Choice Solutions251
First Floor A/C
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.74 > 0.95 Low PF leads to high input current
Waveform Stable Stable Normal and No bad Impact on loads
- 252. © 2008-09 Choice Solutions252
First Floor A/C
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.1% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.7%
IEC 61000-3-12 current harmonic limit is
15% for current in the range 16-75 A
Harmonics within limits
- 253. © 2008-09 Choice Solutions253
First Floor A/C
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.71 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and No bad Impact on loads
- 254. © 2008-09 Choice Solutions254
First Floor A/C
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 255. © 2008-09 Choice Solutions255
First Floor A/C
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
N-E Voltage 1.041 V < 3 V N-E voltage is within limits
N Current 6.27 A 0 High neutral current is due to unbalanced load
- 256. © 2008-09 Choice Solutions256
First Floor A/C
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
47.1% IEEE 519 harmonic limit is 3-5% Neutral getting heated
Current Harmonic 8.2%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 257. © 2008-09 Choice Solutions257
Second Floor A/C
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.72 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and No bad Impact on loads
- 258. © 2008-09 Choice Solutions258
Second Floor A/C
R-Phase: Voltage and Current Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage
Harmonic
4.7% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 259. © 2008-09 Choice Solutions259
Second Floor A/C
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.75 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and No bad Impact on loads
- 260. © 2008-09 Choice Solutions260
Second Floor A/C
Y-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
5.0% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 261. © 2008-09 Choice Solutions261
Second Floor A/C
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.75 > 0.95 Low PF leads to high input current and harmonics
Waveform Stable Stable Normal and No bad Impact on loads
- 262. © 2008-09 Choice Solutions262
Second Floor A/C
B-Phase: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
4.8% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 8.4%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 263. © 2008-09 Choice Solutions263
Second Floor A/C
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
N-E Voltage 1.082 V < 3 V N-E voltage within limits
N current 3.42 A 0 High neutral current is due to load unbalancing
Waveform Unstable Stable Leads to equipment damage
- 264. © 2008-09 Choice Solutions264
Second Floor A/C
N-E: Voltage and Current Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
57.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 3.3%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Harmonics within limits
- 266. © 2008-09 Choice Solutions266
Ground Floor Readings
UPS Output panel
Lighting and Raw Power panel
AC panel
- 268. © 2008-09 Choice Solutions268
UPS Output Breaker - 1
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.77 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 269. © 2008-09 Choice Solutions269
UPS Output Breaker - 1
R-Phase: Voltage, Current and Power Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage Harmonic 1.4% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 63.1%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 270. © 2008-09 Choice Solutions270
UPS Output Breaker - 1
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 271. © 2008-09 Choice Solutions271
UPS Output Breaker - 1
Y-Phase: Voltage, Current and Power Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
1.1 % IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 59.5 %
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 272. © 2008-09 Choice Solutions272
UPS Output Breaker - 1
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.41 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 273. © 2008-09 Choice Solutions273
UPS Output Breaker - 1
B-Phase: Voltage, Current and Power Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
1.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 99.9 %
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 274. © 2008-09 Choice Solutions274
UPS Output Breaker - 1
N-E: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 1 > 0.95 PF within limits
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 275. © 2008-09 Choice Solutions275
UPS Output Breaker - 2
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 276. © 2008-09 Choice Solutions276
UPS Output Breaker - 2
R-Phase: Voltage, Current and Power Harmonics
Parameter Reading Standard Observation/Impact
Voltage
Harmonic
1.3% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 62.6 %
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 277. © 2008-09 Choice Solutions277
UPS Output Breaker - 2
Y-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.74 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 278. © 2008-09 Choice Solutions278
UPS Output Breaker - 2
Y-Phase: Voltage, Current and Power Harmonics
Parameter Reading Standard Observation/Impact
Voltage Harmonic 1.2 % IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 66.4 %
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 279. © 2008-09 Choice Solutions279
UPS Output Breaker - 2
B-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.75 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs
- 280. © 2008-09 Choice Solutions280
UPS Output Breaker - 2
B-Phase: Voltage, Current and Power Harmonics
Parameter
Readin
g
Standard Observation/Impact
Voltage
Harmonic
1.5% IEEE 519 harmonic limit is 3-5% Harmonics within limits
Current Harmonic 64.9%
IEC 61000-3-12 current harmonic limit
is 15% for current in the range 16-75 A
Causes heat and losses
- 281. © 2008-09 Choice Solutions281
UPS Output Breaker - 3
R-Phase: Voltage, Current and Power
Parameter Reading Standard Observation/Impact
PF 0.78 > 0.95 Use PF corrected SMPS to improve PF
Waveform Unstable Stable If unstable, leads to flickering/damaging of CRTs