Task
We are required to select a building as a case study project.
Observe the building services systems taught in this module.
The case study building - PKNS Complex, Shah Alam
1. PKNS Complex,
Shah Alam
Prepared by
Lee Pei Gie 0315653
Yong Seen Yee 0315883
Khoo Xin Yee 0316180
Davin Young Qiao Wei 0321065
Thun Shao Xun 0315919
Tay Sy Min 0320813
Shane Sim Ee Han 0321288
Building Services II (QSB 2714)
Bachelor of Quantity Surveying
2. ’’Oldest commercial
complex in Shah
Alam which houses
offices and shops.
There are hardly any
high street shops. It's
more of a bazaar
with small
shops/stores/stalls.
The Selangor
Immigration Office
here also helps to
cater the crowd
5. Fire extinguisher
• Initial outbreak of fires
• Located at conspicuous
location
• Within 20m from a
potential fire hazard
• ABC type dry powder
fire extinguisher
• Blue colour
Fire Protection System
6. External fire hydrant
• Flow from water main with the
control of a valve
• Two way fire hydrant
• <10m distance to the building
• <10m distance to high voltage
electrical main
• <90m apart along access road
Fire Protection System
7. Hose Reel
• Early stage of fire
• Sited in proper position
• Manually operated and
activated by opening a valve
enabling the water to flow
into hose that is 30m away
Fire Protection System
8. Water storage tank
• Located at roof level
• Pressed steel
• Painted with a red
band of minimum
200mm
• Two compartments
• Level indicator
Fire Protection System
9. Wet riser
• Permanently charged with water
• >30.5 and <70.5m above the fire
appliance access level
• Inlet breeching connector at
ground floor and with landing
valve on each floor
• Air valve automatically open to
release air
• Air valve close when is full of
water
Fire Protection System
10. Sprinkler system
• Small glass bulb with a
glycerine based liquid
• Block the flow of water
• Liquid become hot;
expand; shatter the glass
bulb
• Temperature is
approximately 68°C/155°F
Fire Protection System
11. Fireman’s switch
• Electrical isolation switch
• Permit the disconnection of
electrical power supply
• Located in conspicuous place
• <2.75m from the ground
• Paint in red colour
Fire Protection System
12. Manual call point
• Raising an alarm manually
• Push button / break glass
• Installed at a height of 1.2m
above floor level
• Travel distance from one place
to the nearest call point doesn’t
exceed 30m
Fire Protection System
13. Fire alarm bell
• To alarm people who are at
risk
• It is relatively loud
• Produce a specific sound
pattern to avoid confusion to
successfully warn for
hazards
Fire Protection System
14. Smoke detector
• To detect the fire
• Ionized smoke detector & light scattering smoke
detector
• Reduce current which energies alarm relay and
obstruct the light passing through
• Trigger the alarm bell to give signal
Fire Protection System
15. Voice communication
system
• To communicate critical
information
• Colour in red
• Two way communication
system
• A network of telephone
handsets connected to the
master headset at the Fire
Command Centre
Fire Protection System
16. Fire door
• Allow the flow of traffic
around the building
• A barrier to stop the
spread of fire when door
is closed
• Provide an escape route
for occupants to escape
when the door is open
Fire Protection System
17. Fire escape route
• Emergency exit
• Provides a directional exit signs
• Mounted beside the lift for showing these
escape routes
Fire Protection System
18. Staircase and
compartment
• The number of risers per flight
<16
• Tread & riser dimension are
consistence
• No winders in escape staircase
• Sub-divided into compartment
by using compartment walls
and compartment floors
• Period of insulation >15min
Fire Protection System
20. Main switch board
• Consists of various electric
apparatus that are used to
operate circuits
• To transmit electricity
• It is enclosed
• Sheet steel fabricated
Electrical Supply System
21. Service entrance
• Allow the electric to flow to
the building
• Electric will pass through
the meter and a device
• For overcurrent protection
and electrical current
control
• To avoid occurrence of
overcurrent
Electrical Supply System
22. Branch circuit
• A metal box that filled with
switches
• To supply the power to the
electrical devices in the
shop
• Cut off the power without
affecting the power supply
of the whole building
Electrical Supply System
24. Conduit
• To protect the cables from
physical damage and
heat
• PVC electrical conduit
elbow
• Light
• High strength
• Low cost
Electrical Supply System
25. Mechanical and Air-
conditioning System
• Mechanical Fan
• Air Return Diffuser
• Air Supply Diffuser
• Air Door
• AHU Room
• Cooling Tower
• Ventilation Ducting System
26. Mechanical Fan
CEILING FAN or WALL MOUNTING FAN
Circulate air within a space
Reducing the perceived temperature by method of evaporation
of perspiration on the skin of the occupants.
Mechanical and Air-conditioning System
27. Ventilation Conducting System
FLEXIBLE DUCTWORKS
Insulated with fiberglass to avoid losing valuable conditioned
air
Enhance thermal performance and prevent condensation
and dripping
PKNS COMPLEXMechanical and Air-conditioning System
28. Cooling Tower
Specialized heat exchanger
Located on the roof of PKNS building WHY ?
Noise and vibration they generate, the tower should be
isolated acoustically from the frame of the building and
noise sensitive areas
Mechanical and Air-conditioning System
29. AHU Room
Located in a large mechanical room
AHU connects to the ductwork that distributes the conditioned air
throughout the areas of the building
Warmed air is returned to the AHU room to be cooled after going
through the cooling coil and filter
Mechanical and Air-conditioning System
30. Air Door
Installed air doors at every entrance or customer entryways
Help keep flying insects out by creating forceful turbulence
Help keep out outside air and prevent loss of cool air, thus
reducing infiltration through the opening
Mechanical and Air-conditioning System
31. Air Supply Diffuser
CONE DIFFUSER
Mounted on the ceiling
Cones can be taken out
by pushing inward, turn
around and pull down
4 - WAYS LOUVER
BLADED DIFFUSER
Mounted on the ceiling
Provide excellent
diffusion performance
Mechanical and Air-conditioning System
32. Air Return Diffuser
Attached to the wall as well as mounted on the ceiling
Connects to ductwork that allows air to return to any cooling
or heating system
The openings that connect to ducts and other spaces for
the returning air are covered with grillwork.
Mechanical and Air-conditioning System
34. ESCALATOR
Located at the center of ground floor and second floor
Double bank in two travel direction
Used in the objects in which persons travel in two opposite direction
Normally use in major department stores where transportation time
between several levels should be kept to a minimum
Vertical Transport System
35. ELEVATOR
Three fire fighter lift and three electric lifts
The elevators can support up to 800kg, 11 people can go in at one time
The speed of these elevators is between 100-150 feet per minute
Fire Lift and
Electirc Lift Fire Lift and
Electirc Lift
Vertical Transport System
36. ELEVATOR
Call Buttons are used to request an elevator
Hall lanterns or position indicators are used to indicate the arriving
elevator and the direction it will travel
Audible signals sound once for elevators going up and sound twice
for elevators going down
Hall Lantern Hall Lantern
Vertical Transport System
37. ELEVATOR
Equipped with lighting and ventilation fan
Floor Selection Buttons are used to select floors that the elevator
will stop at
Operation and Emergency Buttons are offset below the floor
selection buttons. These buttons include door open, door close,
emergency stop and emergency alarm. All these button panels
are clear and easily reached at appropriate level
Vertical Transport System
40. 1.Fire Alarm System
• Most of the fire alarm trigger system are
not functioning
Problems on Fire Protection System
41. Only a few of the old
alarm were replaced by
new ones.
• lacking of
visible
indicator
alarm
signal
which one
of the
requirement
stated in
UBBL 241.
• To notify
deaf people
during a fire
Fire alarm within
the building
visible indicator alarm
signal that the building
should have
Problems on Fire Protection System
42. 2. Voice communication System
Telephone for users to
contact the control
centre looks very dirty
and faulty.
There is no key to
access the
telephone in it.
Problems on Fire Protection System
43. The command and control centre which is
closed and looked abandoned
• violates the requirement of UBBL 239 part 3 - voice
communication system is required in every office area
exceeding 92.9m2
• violates the requirement of UBBL 238 - not having a
command and control system in such a big building.
Problems on Fire Protection System
44. 3. Fire Extinguisher
• Fire extinguishers can found at almost
every corner of the building especially at
fre hazards area.
• However, most of them are left
unsecured while some of them are hard
to excess.
Problems on Fire Protection System
46. 4. Sprinkler System
• Very poorly maintained.
• Almost every visible sprinkler is covered
with a thick layer of dust.
• Could result in a false alarm to trigger.
Problems on Fire Protection System
47. • Moreover, there are even some sprinkles
then are badly corroded.
• This will impact the functionality of the
system and also result in leakage.
Corroded
Sprinklers
Problems on Fire Protection System
48. 5. Firemen Lift
• There are no signs indicating which is the
firemen lift.
• All the lifts including the firemen lift have
very small capacity.
• Very inconvenient for firemen to use
during a fire.
Problems on Fire Protection System
49. No signs indicating
which is the
firemen lift.
Lift with small
capacity
Problems on Fire Protection System
50. 6. Escape Route
• diffusers of the staircase pressurization
system are covered with a very layer of
dust.
• The stairs will not be pressurised the way it
should.
• Smoke can enter the escape route.
• Besides, few of the lockset of fire doors
which leads to the escape route is broken.
Problems on Fire Protection System
51. Diffusers covered with a lot of dust
Fire doors with broken lockset
Problems on Fire Protection System
55. Cooling tower
located at the top
floor in the
middle of the
building is not
functioning.
Fans are used
on the entire
ground floor
level.
Problems on Mechanical and Air-conditioning System
56. Big fans are
used in
shoppinng
complex
Problems on Mechanical and Air-conditioning System
61. 1. Fire Alarm System
Employees have to stay alert if there is any broken
system
to prevent it from not functioning during an event
of fire which will cause loss of lives within the
complex
Recommendation on Fire Protection System
62. The volume of the siren may be increased when
the fire alarm system is activated
the occupants can clearly hear the directions
that are being given
Recommendation on Fire Protection System
63. Some frequent maintenance should also be
carried out
such as battery changing and cleaning it to
make it free from dust
Recommendation on Fire Protection System
64. Decrease the distance between alarms
it would take a long time for the occupants to
hear the fire alarm which the valuable escape
time would be lost because of this.
Recommendation on Fire Protection System
65. Quantity of fire alarm system within the complex
may also be increased.
if some fire alarms are broken down, at least
there are a few more still can carry out its
function in the case of emergency.
Recommendation on Fire Protection System
66. 2. Voice Communication System
Can be improved by frequent testing and
maintenance
to ensure it can be functioned
Recommendation on Fire Protection System
67. Prepare more spare keys which can access the
telephones for users to contact the control centre
as the size of key is usually small which could be
lost easily.
Recommendation on Fire Protection System
68. Telephone should also be cleaned frequently so
that it would not be covered with dust or unwanted
rubbish
which may hiding them away or mixing them
with other items and lead to the confusion for
people in the complex in the case of emergency.
Recommendation on Fire Protection System
69. Ensure that the connection line of control centre is
still working
because it could assist to contact fire fighters
during emergencies
Recommendation on Fire Protection System
70. The command and control centre should be
reopened
To receive information from the occupants when
there is an event of fire for them to contact the
fire fighters immediately without delaying the
time.
Recommendation on Fire Protection System
71. 3. Fire Extinguisher
Test the extinguisher during annual fire protection
inspections
ensure that it can be functioned because the
extinguisher would have easily been knocked
and damaged.
Recommendation on Fire Protection System
72. All the employees should have training lesson on
how to use the fire extinguisher correctly
so they can use it to prevent the spread of fire
Recommendation on Fire Protection System
73. Ensure that the fire extinguishers are always in
place with accessible keys beside
it may only take a few seconds to remove the
blockage on the extinguisher, but every second
is vital in the event of a fire
Recommendation on Fire Protection System
74. The date of issue in their label of the extinguisher
should be checked frequently
If they are out of date, they are useless and the
employees need to replace them
Recommendation on Fire Protection System
75. Check fire extinguishers’ hose
If there are any signs of breakage, holes or
cracks, the extinguisher must be replaced
Recommendation on Fire Protection System
76. 4. Sprinkler System
Increase the water volume that can be spread out
from the sprinkler
stop the fire in a short time
Recommendation on Fire Protection System
77. Sprinklers should be cleaned frequently
dust will block the sprinkler head
Recommendation on Fire Protection System
78. Old rusted sprinkler should be replaced to a new
one
when the sprinkler is rusted, this can interfere
with the valves or even stop them breaking
altogether.
Recommendation on Fire Protection System
79. Frequent checking of the condition of the piping
system of sprinkler should also be carried out
as closed sprinkler valve is the most common
cause of failure in a sprinkler system
Recommendation on Fire Protection System
80. Sensitivity of sprinkler should be tested and
maintenance is required for broken sprinkler.
checked weekly to ensure they are open, and a
full flow test should be conducted at least yearly.
Recommendation on Fire Protection System
81. 5. Fireman Lift
Should be identified by placing a sign stated
‘FIREMAN LIFT’
because the obfuscating signage in any way will
make this more difficult for people who are not
familiar with the layout of the building
Recommendation on Fire Protection System
82. Size of the fireman lift should be enlarged
more fire fighters can be sent to upper floor to
control the fire spread the save the occupants
who are trapped in the fire.
Recommendation on Fire Protection System
83. Velocity of the lift should be slightly increased
reduce the time taken for fire fighters to stop the
spread of fire on the upper floor.
Recommendation on Fire Protection System
84. Make sure installation and maintenance are
carried out properly
the maintenance of fireman life should be done
frequently to prevent it from not functioning
Recommendation on Fire Protection System
85. Fire resistance coating can also be applied for
internal and external wall surface of the lift
form a barrier to stop the spread of fire
Recommendation on Fire Protection System
86. 6. Escape Route
Provide the diagrams to show the route to escape
well displayed signs can quickly guide everyone
to safety.
Recommendation on Fire Protection System
87. Diffusers should be cleaned weekly by the cleaner
residues inside diffuser combined with heat can
cause serious life-threatening fires.
Recommendation on Fire Protection System
88. Change the fire door lockset if it is broken
it could lead to very dangerous situation if
people are trying to the fire door in a panic
Recommendation on Fire Protection System
89. Do monthly check up of the condition of the fire
door.
If there is a hole or crack on the fire resistant
door, the door is considered as useless because
smoke will be able to come through the cracks
and the fire will continue to spread to other
places
Recommendation on Fire Protection System
90. Ensure that the fire door is accessible
so that when people are trying to escape from
the complex, they do not need to interfere with
any equipment, tools or objects that could cause
them further harm.
Recommendation on Fire Protection System