DESIGN AND
ANALYSIS
OF
MULTI-STORIED
BUILDINGS
CONTENTS
INTRODUCTION
CODES
SOFTWARE’S
STATEMENT OF PROJECT
LOADS ON THE STRUCTURES
OBJECTIVES OF STRUCTURAL
DESIGN
DESIGN AND ANALYSIS
REFERENCES
INTRODUCTION
 Our project is based on the design and
analysis of the multi-storied buildings
 Analysis is done through using the STAAD-
PRO
 Notation adopted through out the project is
same as in IS-456-2000
CODES
 IS-456:200 :DESIGN CODE FOR RCC
STRUCTURES
 SP-16 : DESIGN CODE FOR COLUMNS
 IS-875(PART 1) :CODE FOR DEAD
LOADS
 IS-875(PART 2) :CODE FOR IMPOSED
LOADS
 IS-875(PART 3) :CODE FOR WIND LOADS
SOFTWARES
 This project is mainly based on software
and it is essential to know the details about
these software’s
 Staad pro(v8i)
 Auto cad.
 STAAD (Staad stands for structural analysis and design)
 staad is the powerful design software licensed by
bentley . Staad stands for structural analysis and design
 To calculate S.F.D and B.M.D of complex loading beam it takes
about an hour.
 So when it comes up to building with several members it will
taken a week.
 staad pro is a very powerful tool which it does this job in just an
hours staad is a best alternative for high rise buildings.
 Now a days most of the high rise buildings are designed by
staad which makes a compulsion for a civil engineer to know
about this software
Auto cad
 Auto cad is powerful software licensed by auto desk
company and cad stand for computer aided design.
 It is used for drawing different layouts, elevations,
details, sections different sections can be shown in
auto cad .
 We used for drawing the plan of multi stored
building .
 It is very useful for civil, mechanical, and also
electrical engineer.
STATEMENT OF THE PROJECT
1.Utility of building :Residential building
2.No of storeys :G+4
3.No.of staircases :5 no's
4.Shape of the building :rectangular
5.Type of construction : R.C.C framed
structure
5.Type of walls :brick wall
Geometric details:
 Ground floor :3.0M
 Floor height :3.0M
 Height of plinth :1.5M from below foundation

 Depth of foundation :500MM
Material details:
 Concrete Grade : M25
 All steel grade : Fe500 grade
 Type of steel bars : HYSD
 Bearing capacity of Soil : >180 KN/M2
DIFFERENT TYPES OF LOADS ON THE STRUCTURES
Dead loads
Imposed loads
Wind loads
Dead loads
Involves self weight of
 RCC slab
 Beams & columns
 Plinth
 Walls
Imposed loads
 Imposed also known live loads
 Loads over the floor i.e. Load of persons it is
calculated as 1 KN/m2
 This load is applied over the length of
structure
Wind loads
 Wind is air in motion
 Wind loads are calculated according to IS:875(part
3)
 Intensity of wind and exposure are applied in the
direction as required
Load combinations
 The structures should be analysed for
combination of loads as in practice we have
numbers of loads in various directions act
 Some of the combinations to be checked
are
 1.5(DL+LL)
 1.5(DL+WL)
 1.5(DL+LL+WL)
OBJECTIVES OF STRUCURAL DEIGN
 Structure designed should satisfy the
criteration of ultimate strength.
 Structures should satisfy the servicablity
 It should satisfy the stability against
overturning, sliding, and buckling
The main objective of the design are
Foundation design
Column design
Beam design
Slab design
DESIGN PRINCIPLE, ASSUMPTION AND
NOTATION ASSUMED
 The notation adopted through out the work is same
as in IS 456-2000
 Using partial safety factors for loads in accordance
with clause 36.4 of IS 456-2000
 Partial safety factor for material in accordance with
clause 36.4.2 IS456-2000 is taken as 1.5 for
concrete and 1.15 for steel
 Using partial safety factors in accordance with
clause 36.4 of IS 456-2000 combination of load
 (D.L+L.L) 1.5
 (D.L +L.L+W.L) 1.2
Density of materials used
MATERIAL Density
1.Plain concrete 24.0 kn /m3
2.Reinforced 25.0 k /m3
3.Flooring material(c.m) 20.0kn/m3
4.Brick masonry 19.0kn/m3
5.Fly ash 5.0kn/m3
LIVE LOADS: In accordance with IS 875-86
1.Live load on slab =3.0kn/m3
2.Live load on passage =3.0kn/m3
3.Live load on stair =3.0kn/m3
Structural design
 For slab, depth is 125 mm provided.
 For beams, after calculations are done . the
dimensions of beam is 230*530mm factored
load on beam is 15.87kn/m
Shape of column is rectangular
For columns, the dimension of
column is 300*600mm
Factored load on column
1090.10kn
For footings, the bearing capacity
of soil is 175kn/m2
To provide the dimensions of
footing is 12.5m*2.7m
ANALYSIS
 Analysis is done using STAD PRO
developed by BENTLEY
 Once the loads and load combinations are
assigned to the structures, analysis is to be
done
 Analysis is done for RCC structure
ASSIGN THE PROPERTIES OF
STRUCTURES
ASSIGN LOADS ON
THE SLAB
LOAD ASSIGN ON
THE WALLS
ASSIGN WIND LOAD
ON THE
STRUCTURES
(X+VE DIRECTION)
ASSIGN WIND LOAD
ON THE
STRUCTURES
(X-VE DIRECTION)
ASSIGN WIND LOAD
ON THE
STRUCTURES
(Z +VE DIRECTION)
ASSIGN WIND LOAD
ON THE
STRUCTURES
(Z -VE DIRECTION)
RCC analysis
 Code is assigned as IS:456-2000
 The parameters are assigned to the
structure
 Commands to be given are
1. concrete design
2. define parameters
3. command
CONCLUSIONS:
 The design of slab, beam, column, rectangular
footing and staircase are done in limit state
method which is safe at control of deflection
and in all aspects
 Using staad.pro software, the design
consideration has been taken as per the is
codes. The design is safe in all conditions
 On comparison with drawing, manual design
and the geometrical model using staad.pro the
area of AST required for the beam, column,
footing and slab are comparatively similar to
that of the requriment
REFERENCES
 Structural analysis by S.RAMAMRUTHAM
 For load calculation on structure by pankaj
agrawal
 IS456-2000 CODE used
 SP16 CODE used
 AUTO CAD & STAAD PRO packages
 Design of RCC structures by B.C PUNMIA
PRESENTED BY:
Avuthu Charitesh Reddy
Meer Musharaf Ali
CH Naresh Babu
K Jaya Sai Teja
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO

More Related Content

What's hot

Structural analysis and design of multi storey ppt
Structural analysis and design of multi storey pptStructural analysis and design of multi storey ppt
Structural analysis and design of multi storey pptSHIVUNAIKA B
 
DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...
DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...
DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...Mahammad2251
 
Design of R.C.C Beam
Design of R.C.C BeamDesign of R.C.C Beam
Design of R.C.C BeamAr. Aakansha
 
G+3 APARTMENT BUILDING PROJECT REPORT
G+3 APARTMENT BUILDING  PROJECT  REPORTG+3 APARTMENT BUILDING  PROJECT  REPORT
G+3 APARTMENT BUILDING PROJECT REPORTFresher Thinking
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic AnalysisKrishnagnr
 
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABSANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABSila vamsi krishna
 
Staad Pro Intro
Staad Pro IntroStaad Pro Intro
Staad Pro IntroSolai Raja
 
Design and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staadDesign and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staadgopichand's
 
Design of steel structures Introduction
Design of steel structures IntroductionDesign of steel structures Introduction
Design of steel structures IntroductionPrakash Kumar Sekar
 
Design of industrial roof truss
Design of industrial roof truss Design of industrial roof truss
Design of industrial roof truss Sudhir Gayake
 
AN INTERNSHIP REPORT ON RESIDENTIAL BUILDING CONSTRUCTION
AN INTERNSHIP  REPORT  ON  RESIDENTIAL  BUILDING  CONSTRUCTIONAN INTERNSHIP  REPORT  ON  RESIDENTIAL  BUILDING  CONSTRUCTION
AN INTERNSHIP REPORT ON RESIDENTIAL BUILDING CONSTRUCTIONAbhishek Singh
 
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...Bala Balaji
 
Design of multistorey building
Design of multistorey buildingDesign of multistorey building
Design of multistorey buildingSivaji Djpk
 
Summer Internship Report of Civil Engineering in Construction Site
Summer Internship Report of Civil Engineering in Construction SiteSummer Internship Report of Civil Engineering in Construction Site
Summer Internship Report of Civil Engineering in Construction SiteRAVI KUMAR
 
SUMMER TRAINING REPORT ON BUILDING CONSTRUCTION
SUMMER TRAINING REPORT ON BUILDING CONSTRUCTIONSUMMER TRAINING REPORT ON BUILDING CONSTRUCTION
SUMMER TRAINING REPORT ON BUILDING CONSTRUCTIONVed Jangid
 
Analysis and design of a multi storey reinforced concrete
Analysis and design of a multi storey reinforced concreteAnalysis and design of a multi storey reinforced concrete
Analysis and design of a multi storey reinforced concreteSurat Construction PVT LTD
 

What's hot (20)

Shear wall and its design guidelines
Shear wall and its design guidelinesShear wall and its design guidelines
Shear wall and its design guidelines
 
Structural analysis and design of multi storey ppt
Structural analysis and design of multi storey pptStructural analysis and design of multi storey ppt
Structural analysis and design of multi storey ppt
 
DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...
DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...
DESIGN AND ANALYSIS OF G+3 RESIDENTIAL BUILDING BY S.MAHAMMAD FROM RAJIV GAND...
 
Design of R.C.C Beam
Design of R.C.C BeamDesign of R.C.C Beam
Design of R.C.C Beam
 
staad pro
staad prostaad pro
staad pro
 
G+3 APARTMENT BUILDING PROJECT REPORT
G+3 APARTMENT BUILDING  PROJECT  REPORTG+3 APARTMENT BUILDING  PROJECT  REPORT
G+3 APARTMENT BUILDING PROJECT REPORT
 
Seismic Analysis
Seismic AnalysisSeismic Analysis
Seismic Analysis
 
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABSANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
ANALYSIS AND DESIGN OF HIGH RISE BUILDING BY USING ETABS
 
Staad Pro Intro
Staad Pro IntroStaad Pro Intro
Staad Pro Intro
 
Design and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staadDesign and analasys of a g+3 residential building using staad
Design and analasys of a g+3 residential building using staad
 
IRC-6-2016.pdf
IRC-6-2016.pdfIRC-6-2016.pdf
IRC-6-2016.pdf
 
Design of steel structures Introduction
Design of steel structures IntroductionDesign of steel structures Introduction
Design of steel structures Introduction
 
Design of industrial roof truss
Design of industrial roof truss Design of industrial roof truss
Design of industrial roof truss
 
AN INTERNSHIP REPORT ON RESIDENTIAL BUILDING CONSTRUCTION
AN INTERNSHIP  REPORT  ON  RESIDENTIAL  BUILDING  CONSTRUCTIONAN INTERNSHIP  REPORT  ON  RESIDENTIAL  BUILDING  CONSTRUCTION
AN INTERNSHIP REPORT ON RESIDENTIAL BUILDING CONSTRUCTION
 
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
 
Design of multistorey building
Design of multistorey buildingDesign of multistorey building
Design of multistorey building
 
Summer Internship Report of Civil Engineering in Construction Site
Summer Internship Report of Civil Engineering in Construction SiteSummer Internship Report of Civil Engineering in Construction Site
Summer Internship Report of Civil Engineering in Construction Site
 
SUMMER TRAINING REPORT ON BUILDING CONSTRUCTION
SUMMER TRAINING REPORT ON BUILDING CONSTRUCTIONSUMMER TRAINING REPORT ON BUILDING CONSTRUCTION
SUMMER TRAINING REPORT ON BUILDING CONSTRUCTION
 
Analysis and design of a multi storey reinforced concrete
Analysis and design of a multi storey reinforced concreteAnalysis and design of a multi storey reinforced concrete
Analysis and design of a multi storey reinforced concrete
 
Design of footing as per IS 456-2000
Design of footing as per IS 456-2000Design of footing as per IS 456-2000
Design of footing as per IS 456-2000
 

Viewers also liked

Analysis and Desin of Multi purpose Auditorium
Analysis and Desin of Multi purpose AuditoriumAnalysis and Desin of Multi purpose Auditorium
Analysis and Desin of Multi purpose AuditoriumKrishna Madhukar Vadla
 
Multi storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingMulti storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingRazes Dhakal
 
Tutorial Staad-Pro
Tutorial Staad-ProTutorial Staad-Pro
Tutorial Staad-ProNabeh Wildan
 
Calculation of dead load
Calculation of dead loadCalculation of dead load
Calculation of dead loadRidhdhi Gandhi
 
Design and analysis of reinforced concrete multistory commercial building usi...
Design and analysis of reinforced concrete multistory commercial building usi...Design and analysis of reinforced concrete multistory commercial building usi...
Design and analysis of reinforced concrete multistory commercial building usi...Estisharaat Company
 

Viewers also liked (8)

Is 456 2000
Is 456 2000Is 456 2000
Is 456 2000
 
Analysis and Desin of Multi purpose Auditorium
Analysis and Desin of Multi purpose AuditoriumAnalysis and Desin of Multi purpose Auditorium
Analysis and Desin of Multi purpose Auditorium
 
Multi storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingMulti storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial building
 
Staad pro
Staad proStaad pro
Staad pro
 
Tutorial Staad-Pro
Tutorial Staad-ProTutorial Staad-Pro
Tutorial Staad-Pro
 
Calculation of dead load
Calculation of dead loadCalculation of dead load
Calculation of dead load
 
Design and analysis of reinforced concrete multistory commercial building usi...
Design and analysis of reinforced concrete multistory commercial building usi...Design and analysis of reinforced concrete multistory commercial building usi...
Design and analysis of reinforced concrete multistory commercial building usi...
 
Design and analasys of a g+2 residential building
Design and analasys of a g+2 residential building Design and analasys of a g+2 residential building
Design and analasys of a g+2 residential building
 

Similar to DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO

mini-project.powerpoint.pptx
mini-project.powerpoint.pptxmini-project.powerpoint.pptx
mini-project.powerpoint.pptxShankyMavi
 
Analysis and design of commercial building
Analysis and design of commercial buildingAnalysis and design of commercial building
Analysis and design of commercial buildingSatrudhan11240
 
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Sunil Kumar Meena
 
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01Ramil Artates
 
Computer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdf
Computer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdfComputer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdf
Computer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdfArjunanChandrasekara
 
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWAREREPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARERakeshDas161
 
Final
FinalFinal
FinalHfygh
 
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Sunil Kumar Meena
 
Comparative Study on CFST and RC Column in the RC Frame Structure
Comparative Study on CFST and RC Column in the RC Frame StructureComparative Study on CFST and RC Column in the RC Frame Structure
Comparative Study on CFST and RC Column in the RC Frame StructureIRJET Journal
 
Training on Structural designing by CADD centre
Training on Structural designing by CADD centreTraining on Structural designing by CADD centre
Training on Structural designing by CADD centreyashvant meena
 
Analysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingAnalysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingIRJET Journal
 
Comparative study of a multi – storied building with and without shear wall b...
Comparative study of a multi – storied building with and without shear wall b...Comparative study of a multi – storied building with and without shear wall b...
Comparative study of a multi – storied building with and without shear wall b...IRJET Journal
 
Analysis of G+2 building with seismic load using Etabs
Analysis of G+2 building with seismic load using EtabsAnalysis of G+2 building with seismic load using Etabs
Analysis of G+2 building with seismic load using EtabsIRJET Journal
 
Analysis and Design of an Earthquake Resistant Structure using STADD. Pro
Analysis and Design of an Earthquake Resistant Structure using STADD. ProAnalysis and Design of an Earthquake Resistant Structure using STADD. Pro
Analysis and Design of an Earthquake Resistant Structure using STADD. ProIRJET Journal
 
IRJET- A Comparative Study on Pre Engineered Building by using STAAD PRO
IRJET- A Comparative Study on Pre Engineered Building by using STAAD PROIRJET- A Comparative Study on Pre Engineered Building by using STAAD PRO
IRJET- A Comparative Study on Pre Engineered Building by using STAAD PROIRJET Journal
 
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic ZonesIRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic ZonesIRJET Journal
 
IRJET- Planning, Analysis and Design of an Auditorium Building
IRJET- Planning, Analysis and Design of an Auditorium BuildingIRJET- Planning, Analysis and Design of an Auditorium Building
IRJET- Planning, Analysis and Design of an Auditorium BuildingIRJET Journal
 

Similar to DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO (20)

Hostel
HostelHostel
Hostel
 
Villa
VillaVilla
Villa
 
mini-project.powerpoint.pptx
mini-project.powerpoint.pptxmini-project.powerpoint.pptx
mini-project.powerpoint.pptx
 
Dbr kashmiri gate
Dbr kashmiri gateDbr kashmiri gate
Dbr kashmiri gate
 
Analysis and design of commercial building
Analysis and design of commercial buildingAnalysis and design of commercial building
Analysis and design of commercial building
 
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
 
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
 
Computer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdf
Computer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdfComputer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdf
Computer_Aided_Analysis_and_Design_of_Multi-Storeyed_Buildings.pdf
 
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWAREREPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
 
Final
FinalFinal
Final
 
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
 
Comparative Study on CFST and RC Column in the RC Frame Structure
Comparative Study on CFST and RC Column in the RC Frame StructureComparative Study on CFST and RC Column in the RC Frame Structure
Comparative Study on CFST and RC Column in the RC Frame Structure
 
Training on Structural designing by CADD centre
Training on Structural designing by CADD centreTraining on Structural designing by CADD centre
Training on Structural designing by CADD centre
 
Analysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingAnalysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential Building
 
Comparative study of a multi – storied building with and without shear wall b...
Comparative study of a multi – storied building with and without shear wall b...Comparative study of a multi – storied building with and without shear wall b...
Comparative study of a multi – storied building with and without shear wall b...
 
Analysis of G+2 building with seismic load using Etabs
Analysis of G+2 building with seismic load using EtabsAnalysis of G+2 building with seismic load using Etabs
Analysis of G+2 building with seismic load using Etabs
 
Analysis and Design of an Earthquake Resistant Structure using STADD. Pro
Analysis and Design of an Earthquake Resistant Structure using STADD. ProAnalysis and Design of an Earthquake Resistant Structure using STADD. Pro
Analysis and Design of an Earthquake Resistant Structure using STADD. Pro
 
IRJET- A Comparative Study on Pre Engineered Building by using STAAD PRO
IRJET- A Comparative Study on Pre Engineered Building by using STAAD PROIRJET- A Comparative Study on Pre Engineered Building by using STAAD PRO
IRJET- A Comparative Study on Pre Engineered Building by using STAAD PRO
 
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic ZonesIRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
 
IRJET- Planning, Analysis and Design of an Auditorium Building
IRJET- Planning, Analysis and Design of an Auditorium BuildingIRJET- Planning, Analysis and Design of an Auditorium Building
IRJET- Planning, Analysis and Design of an Auditorium Building
 

Recently uploaded

Vishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsVishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsSachinPawar510423
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
lifi-technology with integration of IOT.pptx
lifi-technology with integration of IOT.pptxlifi-technology with integration of IOT.pptx
lifi-technology with integration of IOT.pptxsomshekarkn64
 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncssuser2ae721
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...121011101441
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Piping Basic stress analysis by engineering
Piping Basic stress analysis by engineeringPiping Basic stress analysis by engineering
Piping Basic stress analysis by engineeringJuanCarlosMorales19600
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 

Recently uploaded (20)

Vishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documentsVishratwadi & Ghorpadi Bridge Tender documents
Vishratwadi & Ghorpadi Bridge Tender documents
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
lifi-technology with integration of IOT.pptx
lifi-technology with integration of IOT.pptxlifi-technology with integration of IOT.pptx
lifi-technology with integration of IOT.pptx
 
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsyncWhy does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
Why does (not) Kafka need fsync: Eliminating tail latency spikes caused by fsync
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...Instrumentation, measurement and control of bio process parameters ( Temperat...
Instrumentation, measurement and control of bio process parameters ( Temperat...
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Piping Basic stress analysis by engineering
Piping Basic stress analysis by engineeringPiping Basic stress analysis by engineering
Piping Basic stress analysis by engineering
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 

DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO

  • 2. CONTENTS INTRODUCTION CODES SOFTWARE’S STATEMENT OF PROJECT LOADS ON THE STRUCTURES OBJECTIVES OF STRUCTURAL DESIGN DESIGN AND ANALYSIS REFERENCES
  • 3. INTRODUCTION  Our project is based on the design and analysis of the multi-storied buildings  Analysis is done through using the STAAD- PRO  Notation adopted through out the project is same as in IS-456-2000
  • 4. CODES  IS-456:200 :DESIGN CODE FOR RCC STRUCTURES  SP-16 : DESIGN CODE FOR COLUMNS  IS-875(PART 1) :CODE FOR DEAD LOADS  IS-875(PART 2) :CODE FOR IMPOSED LOADS  IS-875(PART 3) :CODE FOR WIND LOADS
  • 5. SOFTWARES  This project is mainly based on software and it is essential to know the details about these software’s  Staad pro(v8i)  Auto cad.
  • 6.  STAAD (Staad stands for structural analysis and design)  staad is the powerful design software licensed by bentley . Staad stands for structural analysis and design  To calculate S.F.D and B.M.D of complex loading beam it takes about an hour.  So when it comes up to building with several members it will taken a week.  staad pro is a very powerful tool which it does this job in just an hours staad is a best alternative for high rise buildings.  Now a days most of the high rise buildings are designed by staad which makes a compulsion for a civil engineer to know about this software
  • 7. Auto cad  Auto cad is powerful software licensed by auto desk company and cad stand for computer aided design.  It is used for drawing different layouts, elevations, details, sections different sections can be shown in auto cad .  We used for drawing the plan of multi stored building .  It is very useful for civil, mechanical, and also electrical engineer.
  • 8. STATEMENT OF THE PROJECT 1.Utility of building :Residential building 2.No of storeys :G+4 3.No.of staircases :5 no's 4.Shape of the building :rectangular 5.Type of construction : R.C.C framed structure 5.Type of walls :brick wall
  • 9. Geometric details:  Ground floor :3.0M  Floor height :3.0M  Height of plinth :1.5M from below foundation   Depth of foundation :500MM
  • 10. Material details:  Concrete Grade : M25  All steel grade : Fe500 grade  Type of steel bars : HYSD  Bearing capacity of Soil : >180 KN/M2
  • 11. DIFFERENT TYPES OF LOADS ON THE STRUCTURES Dead loads Imposed loads Wind loads
  • 12. Dead loads Involves self weight of  RCC slab  Beams & columns  Plinth  Walls
  • 13. Imposed loads  Imposed also known live loads  Loads over the floor i.e. Load of persons it is calculated as 1 KN/m2  This load is applied over the length of structure
  • 14. Wind loads  Wind is air in motion  Wind loads are calculated according to IS:875(part 3)  Intensity of wind and exposure are applied in the direction as required
  • 15. Load combinations  The structures should be analysed for combination of loads as in practice we have numbers of loads in various directions act  Some of the combinations to be checked are  1.5(DL+LL)  1.5(DL+WL)  1.5(DL+LL+WL)
  • 16. OBJECTIVES OF STRUCURAL DEIGN  Structure designed should satisfy the criteration of ultimate strength.  Structures should satisfy the servicablity  It should satisfy the stability against overturning, sliding, and buckling
  • 17. The main objective of the design are Foundation design Column design Beam design Slab design
  • 18. DESIGN PRINCIPLE, ASSUMPTION AND NOTATION ASSUMED  The notation adopted through out the work is same as in IS 456-2000  Using partial safety factors for loads in accordance with clause 36.4 of IS 456-2000  Partial safety factor for material in accordance with clause 36.4.2 IS456-2000 is taken as 1.5 for concrete and 1.15 for steel  Using partial safety factors in accordance with clause 36.4 of IS 456-2000 combination of load  (D.L+L.L) 1.5  (D.L +L.L+W.L) 1.2
  • 19. Density of materials used MATERIAL Density 1.Plain concrete 24.0 kn /m3 2.Reinforced 25.0 k /m3 3.Flooring material(c.m) 20.0kn/m3 4.Brick masonry 19.0kn/m3 5.Fly ash 5.0kn/m3 LIVE LOADS: In accordance with IS 875-86 1.Live load on slab =3.0kn/m3 2.Live load on passage =3.0kn/m3 3.Live load on stair =3.0kn/m3
  • 20. Structural design  For slab, depth is 125 mm provided.  For beams, after calculations are done . the dimensions of beam is 230*530mm factored load on beam is 15.87kn/m
  • 21. Shape of column is rectangular For columns, the dimension of column is 300*600mm Factored load on column 1090.10kn For footings, the bearing capacity of soil is 175kn/m2 To provide the dimensions of footing is 12.5m*2.7m
  • 22. ANALYSIS  Analysis is done using STAD PRO developed by BENTLEY  Once the loads and load combinations are assigned to the structures, analysis is to be done  Analysis is done for RCC structure
  • 23. ASSIGN THE PROPERTIES OF STRUCTURES
  • 24.
  • 26.
  • 28.
  • 29. ASSIGN WIND LOAD ON THE STRUCTURES (X+VE DIRECTION)
  • 30.
  • 31. ASSIGN WIND LOAD ON THE STRUCTURES (X-VE DIRECTION)
  • 32.
  • 33. ASSIGN WIND LOAD ON THE STRUCTURES (Z +VE DIRECTION)
  • 34.
  • 35. ASSIGN WIND LOAD ON THE STRUCTURES (Z -VE DIRECTION)
  • 36.
  • 37. RCC analysis  Code is assigned as IS:456-2000  The parameters are assigned to the structure  Commands to be given are 1. concrete design 2. define parameters 3. command
  • 38. CONCLUSIONS:  The design of slab, beam, column, rectangular footing and staircase are done in limit state method which is safe at control of deflection and in all aspects  Using staad.pro software, the design consideration has been taken as per the is codes. The design is safe in all conditions  On comparison with drawing, manual design and the geometrical model using staad.pro the area of AST required for the beam, column, footing and slab are comparatively similar to that of the requriment
  • 39. REFERENCES  Structural analysis by S.RAMAMRUTHAM  For load calculation on structure by pankaj agrawal  IS456-2000 CODE used  SP16 CODE used  AUTO CAD & STAAD PRO packages  Design of RCC structures by B.C PUNMIA
  • 40. PRESENTED BY: Avuthu Charitesh Reddy Meer Musharaf Ali CH Naresh Babu K Jaya Sai Teja