More Related Content
Similar to Data Acquisition PCU400 Network Manager rel1.ppt (20)
Data Acquisition PCU400 Network Manager rel1.ppt
- 2. ©
ABB
Power
Technologies
-
2
Network Manager - Data Acquisition
Facilitates Real-time Supervisory Control of
Power Stations
Substations
Key information points in a distributed power network
Development of Process Communication
Interfacing RTUs, SA- and IED-systems
Use of standardized protocols;
WAN instead of leased line to the station
Deregulation leads to need for flexibility and versatility
IT-security
Data Communications
Redundant Solutions
Enterprise Wide
PCU400 is the solution for Network Manager
- 3. ©
ABB
Power
Technologies
-
3
Functions:
Front-End for Network Manager
RSP protocol to Application Servers (AS)
Down line loading of database from AS
1–24 multi-drop lines to RTUs
Protocol configurable per line
Various communication media
Distributed configuration is supported
Redundancy
Application
Servers
RSP protocol over
Ethernet LAN or WAN
NG
WT
ZG
1
15
PCU400
RTU or
SCS system
Available RTU protocols
Can be distributed
over WAN
PCU400 as Front-End to Network Manager
- 4. ©
ABB
Power
Technologies
-
4
PCU400 Distributed Functionality
The Data Acquisition System is distributed
in two software components:
RCS Application
Supervision of PCU connection via TCP/IP comports
Handling of line switchover
Handling of redundant lines
Interfaces the SCADA application
Communication statistics
Handling of telephone connections and modem pools
Scaling of measurands
RSP Master
Database loading
PCU400
Protocol translation
Time synchronization
RSP slave
PCU400
RCS Application
- 5. ©
ABB
Power
Technologies
-
5
PCU400 in Network Manager
PCU400 A
RTU lines
PCU400 B
Other Applications Other Applications
RSP Links
LAN or WAN
Real-time
Database
(Avanti)
Real-time
Database
(Avanti)
RCS Application RCS Application
Main Server A Main Server B
- 6. ©
ABB
Power
Technologies
-
6
PCU400 Mainframe
Industrial PC Chassis or Desktop
PCI slot, half or full length
Hard disc or Flash memory (embedded)
CDRW-device
Intel Pentium 4 compatible CPU
Minimum 256Mb Memory
Redundant Ethernet ports for Dual-LAN
Ethernet port for Communication Modules
Graphic card
Wall or 19” Rack-mount
PCU400 embedded version is without
moving parts
- 8. ©
ABB
Power
Technologies
-
8
PCU400 Embedded - specification
H6023-based (Hectronic), CPU is Geode GX1-300, 300MHz
2 - 6 COM, 1 - 3 Ethernet
RAM 256MB
CompactFlash 256 MB - 1GB
Power 7-28V DC
Temperature range +5ºC to 45ºC
Size is about 220mm x 110mm x 77mm
Operating System Windows XP embedded
Option 1) Extended temperature range -40ºC to 80ºC
Option 2) Two additional Ethernet interfaces plus four additional COM-
ports
With option 2 included a complete 6 channel PCU400 with redundant LANs is realized. A
third Ethernet interface extends with more COM-ports using the OCC2 Communication HUB.
- 9. ©
ABB
Power
Technologies
-
9
PCU400 Communication Module
Communication Module
8 channels per unit, max 8 units per CPU (=64 channels)
64 kbps per channel in parallel
Byte and Bit-sampling
Protocol support for Indactic33, Sinaut8, ADLP80 and asynchronous
Ethernet connection to PCU mainframe, allows distribution
DIN-mounted
DC powered
- 10. ©
ABB
Power
Technologies
-
10
PCU400 Communication Functionality
Asynchronous UART communication (speed 50 – 64000 bps)
Bit synchronous communication (bit sampling 50 – 4800 bps)
Dial-up (phone) Low level driver support of Hayes
commands used with RP570
RS232 (control signals supported)
LAN (single, dual), NetRAIN –
Redundant Array of Independent Network adaptors (two
interfaces appears using the same IP-address)
Security arrangement same as the operating system
- 11. ©
ABB
Power
Technologies
-
11
Communication Lines in Network Manager
LAN or WAN
Database - Object level
Hardware level
Line Pool
Line Unit #1
Line Unit #2
Line Unit #3
Line Switch
Line Pool # 1 = COM-line 1
A B
Line Unit #1
A B
Line Unit #2
A B
Line Unit #x
Ch. 1A Ch. 2A Ch. xA
PCU # 1
Ch. 1B Ch. 2B Ch. xB
PCU # 2 Each Line Unit side is
connected to a PCU number
The PCU can be distributed
Each RTU belongs to one
Line Pool
Line switch only if
redundant PCUs
Line 1, to RTU
- 13. ©
ABB
Power
Technologies
-
13
PCU400 Implemented protocols
Slave Protocols Master Protocols Master Protocols cont´d
IEC 60870-5-101 IEC 60870-5-101 TG709
IEC 60870-5-104 IEC 60870-5-104 TG065
ADLP180 ADLP80 USART
RP570 ADLP180 SINAUT 8 FW (DPDM)
Teleconnect III RP570/571 Indactic 35
DNP 3.0 Indactic 33,33/41A WISP
OPC server Indactic 2033 WISP+
Conitel 300 Teleconnect III
MODBUS RTU Netcon 8830
Field Buses TG800 HNZ
LON DNP 3.0 Teleconnect II
SPA-bus Mobitex ECMA 24
GCOM Siemens ST1 DDE and OPC client
- 16. ©
ABB
Power
Technologies
-
16
Application Program Interface (API) for Openess
APIs gives flexibility to integrate protocol libraries
PCU400 optionally provides
A DDE interface
An OPC-client interface
An interface from ASE (USA-based company)
ABB will add more APIs
PCU400 users may add protocols using:
DDE
OPC
ASE
Toolkit
- 21. ©
ABB
Power
Technologies
-
21
Data Acquisition, Security
5
4
LAN 1
LAN 2
Application Server A Application Server B
RCS Application B
RCS Application A
1
PCU400 A PCU400 B
Line switch
RTU
1. Redundant PCUs
2. Dual LAN
3. Line Unit, A and B
side
4. Logging between
RCS applications in
a redundant system
5. Logging between
Application Servers
… Connection if dual
LANs
RSP lines
RTU lines
2
3 3
- 23. ©
ABB
Power
Technologies
-
23
Dual ported memory
Communication Board
PCU400, Time synchronization
Minute pulse
Time message Free running counter
Clock Server
Protocol
Driver
Write the Time message
to com board
Write number of tics until
sending should occur
The board stops transmission
until the tics are executed. Then
sending occurs
Time fetch via
DLL
- 24. ©
ABB
Power
Technologies
-
24
Functions:
Data Gateway/Concentrator
Web-interface
Local Station Control
Local configuration via MS Excel
Allow connection to existing systems
NG
WT
ZG
1
15
Configuration Tool
WEB-interface
Local Control
Remote Master Systems
RTU or Protection relay
E.g. IEC 870-5-101
REC 561 REL 5x1
PCU400 as Gateway for SA and SCADA systems
- 25. ©
ABB
Power
Technologies
-
25
PCU400 SA & SCADA Connectivity
NG
WT
ZG
1
15
NG
WT
ZG
1
15
NG
WT
ZG
1
15
NG
WT
ZG
1
15
REC 561 REL 5x1
RTU
LON
RTU protocol
TCP/IP
OPC
XML
WEB-Interface
Base Level
Network Manager
High Level
Industrial IT
PLC Connect
Operate IT
Medium Level
PCU400 Gateway
RSP
- 26. ©
ABB
Power
Technologies
-
26
Functions:
Connection of new RTU to old Master System
Connection of old RTUs to new Master System
One line to RTUs / Protection relays
Redundant lines to the Master system
Media converter (dial-up to leased line)
Local configuration
NG
WT
ZG
1
15
Remote
Master System
RTU or
SA system
E.g. IEC 870-5-104
E.g. RP570
Configuration Tool
PCU400 as Converter
Example
Connection of an RTU211 to an IEC870-5-104
network by using the PCU400 embedded.
- 27. ©
ABB
Power
Technologies
-
27
OPC400 Server
API-Data Access 2.0 (DA)
API-Alarm and Event (AE)
All protocols will be available through the OPC-server
OPC Client also available
RSP bus
OPC DA OPC AE Slave
Plug-In
XML
DDE Master
Protocol
OPC
3rd
LON
3rd part
Control Center Communication
Process Equipment Communication
FTP/HD
EXCEL
Engineering Tool
- 28. ©
ABB
Power
Technologies
-
28
PCU400 Data Engineering
Local in PCU
COM-port definitions
Protocol per line (and characteristics)
Socket TCP/IP address and port
Runtime database Loaded via RSP or XML
Loaded per line from RCS Application
(or via PCU400 internal X05 in case of XML)
Which RTUs on which lines
I/O for each RTU (logical and possibly physical)
- 32. ©
ABB
Power
Technologies
-
32
LAN
The specification of the comport is done in
the files linunit.ini and lu_xxx.ini
Following items defines the COM-port
COM-port number (1-255)
TCP-port
(Socket connection to the PCU SW)
PCU
PCU
Software
Socket
connection
(TCP-port)
Comport
#1
RTU
TCP/IP port and Comport
- 34. ©
ABB
Power
Technologies
-
34
RSP Address
Each Line Unit is assigned to a RSP address
The RSP address is unique within the Comport
The RSP address is the same for Line Unit A & B side
Every node in a RCS system must have an address
The RSP address is within range 1 .. 255. Typically the
following intervals applies:
[1..127] RTU lines
[128..199] Emulator lines
[200..255] Master Lines
Frame type
Datatype
Length
Sequence number
Source line number
Destination line number
RTU number