Explosion hazards mostly arise from
flammable gases and vapours
Instead of avoiding their ignition by explosion protection measures it may
be preferable to detect them before they become ignitable.
DANGER OF EXPLOSION IS LURKING EVERYWHERE
Wherever hazardous situations exist due to the
presence of combustible gases and vapours e.g. in
oil & gas exploration and storage, transportation
and storage of flammable liquids and gases, in
processes involving the use of solvents, or in the
plastics processing industry, we will always
encounter explosion protection measures, mostly
regulated by law, to keep the personnel and plants
safe.
Depending on the application different measuring
principles for the detection of gases and vapours
can be used: Catalytic bead sensors, point or
open-path infrared sensors. When detectors are
used in combination with a central controller such
as Dräger Polytron or Dräger REGARD it is possible
to detect flammable gases and vapours at an early
stage, when concentrations are so low that a
dangerous condition – a risk of explosion – can be
reliably averted.
METHODOLOGY OF EXPLOSION PROTECTION
Flammable gases and vapours can only be ignited
by an ignition source with sufficient high energy or
sufficient high temperature if – under atmospheric
conditions – they exist in a mixture with atmospheric
oxygen in sufficiently high concentrations.
This mixture’s concentration is called LEL:
Lower Explosion Limit.
To have an ignition three conditions have to be met:
1. Concentration of flammable gas or vapour above
the LEL
2. Sufficiently high oxygen concentration
3. Sufficiently high temperature or sufficient energy
of the ignition source
Vice versa this rule reads: If one of the three
conditions is not met it is reliably ensured that no
ignition or explosion can take place.
So, measures of explosion protection can be the
following:
1. Concentration limiting
2. Inertisation
3. Use of explosion protected apparatus
| 03
The safest way of concentration limiting is the
removal of flammable gases and vapours from the
process – this is not normally practical. Where
flammable gases and vapours are used, it is normal
for gas detection systems to be used to limit
concentrations. When the process is closed and
the level of flammable gases or vapours is allowed
to exceed the LEL level, this is acceptable as long
as the oxygen concentration is kept low enough to
control the risk of explosion (inertisation).
If these measures however are not sufficient, all of
the involved electrical devices have to be designed
according to certain explosion protection standards
so they will not act as a source of ignition if
flammable gases or vapours are released.
Further advice concerning the methodology can be
found in the harmonized standard EN 1127-1.
Explosion protection means reliably excluding at
least one of the three prerequisites for ignition.
Gas/vapour
in sufficiently high concentration
(above LEL).
Air/oxygen
in sufficiently high concentration.
Ignition source
e.g. ignition spark with sufficient energy
or sufficiently high temperatures.
ST-1576-2007
04 |
Activation of
compulsory measures
(e.g. shut-down)
Activation of
counter measures
(e.g. ventilation)
Alarm range 2
Alarm range 1
Safe
range
40 %LEL
20 %LEL
0 %LEL
Alarm thresholds
If the gas concentration rises a
counter measure is activated when
reaching the alarm range 1. If the
counter measure is effective the gas
concentration will decrease (blue
curve). If, however, the counter
measure is not effective the concen-
tration will keep on rising (red
curve). When reaching the alarm
range 2 compulsory measures are
activated. Properly designed gas
detection systems will rarely or never
reach the alarm range 2.
ST-1590-2007
Hazardous
Atmospheres
ST-3101-2004
| 05
Preventing potentially explosive
atmospheres –
primary explosion protection.
BELOW THE LEL NO DANGER OF EXPLOSION
Concentration limiting (1) and inertisation (2) are
also called primary measures because the formation
of an ignitable concentration is averted. On the other
hand when using explosion protected instruments (3)
this is a secondary measure because not the for-
mation of ignitable concentrations is averted, but
only its ignition.
Concentration limiting means active dilution, e.g. by
automatically ventilating fresh air into the hazardous
area if concentrations have risen above the 20 %LEL
threshold. If concentrations continue to rise
because the counter measure is ineffective then it
is necessary to automatically activate shut-down
actions at 40 %LEL e.g. by switching off any non-
explosion proof instrument or equipment. Gas
detection systems used for this purpose must be
type approved by a Notified Body in respect to their
compliance with the European Standards (formerly
acc. to EN 50054ff, now acc. to EN 61779 or
EN 60079-29-1). This is true for the sensor and the
transmitter as well as for the central controller unit.
As inertisation is also a preventive explosion
protection measure, oxygen measuring instruments
controlling the inertisation process at least in
Europe also have to be type-approved for this
purpose and shall comply with the relevant
harmonised standards (e.g. EN 50 104).
LEL Scale
The lower the LEL the more danger-
ous is the substance, as ignitable
concentrations can form more easily.
Ammonia
Carbon monoxide
Formic acid
1.2-Dichloro ethylene
Methyl bromide
1.1.1-Trichloro ethane
Methyl chloride
Acetyl chloride
Formaldehyde
1.1-Dichloro ethylene
1.2-Dichloro ethane
Methanol
1.1-Dichloro ethane
Hydrogen cyanide
Methyl amine
Hydrazine
Methane
Hydrogen
Vinylchloride
Ethyl amine
Ethanol
Acetonitrile
Acrylonitrile
Dimethyl ether
Ethylene
Dimethyl formamide
i-Propanol
Propane
i-Butane
n-Butane
n-Butyl acetate
n-Hexane
n-Octane
n-Nonane
n-Decane
15.5 % v/v
15.0 % v/v
11.0 % v/v
10.5 % v/v
10.0 % v/v
9.5 % v/v
9.0 % v/v
8.5 % v/v
8.0 % v/v
7.5 % v/v
7.0 % v/v
6.5 % v/v
6.0% v/v
5.5 % v/v
5.0 % v/v
4.5 % v/v
4.0 % v/v
3.5% v/v
3.0 % v/v
2.5 % v/v
2.0 % v/v
1.5 % v/v
1.0 % v/v
0.5 % v/v
ST-1589-2007
06 |
Safety relevant data of flammable gases
and vapours.
THE LOWER EXPLOSION LIMIT – LEL
For flammable substances there is a limit concen-
tration necessary for ignition. Below this limit a
mixture of the substance in air cannot be ignited
because there is a deficiency of fuel. This limit is
called the Lower Explosion Limit or LEL.
The LEL cannot be calculated but is an empirical
characteristic figure which is established by
standardized methods. With some exceptions the
LEL lies between 0.5 and 15 % by volume.
GASES AND LEL
Matter above its boiling point commonly is called
a gas. Thus the pressure of a pure liquefied gas
is always higher than the atmospheric pressure
so that released gases can very quickly form
concentrations above the LEL causing dangerous
ignitable gas-/air-mixtures.
VAPOURS OF FLAMMABLE LIQUIDS AND
FLASHPOINT
Matter below its boiling point is not only gaseous
but exists in an equilibrium with its liquid (and also
solid) state which depends on the temperature.
The gaseous component of this matter is called
vapour. A vapour’s pressure is always lower than
the atmospheric pressure, and, depending on the
liquid’s temperature, only certain maximum vapour
concentrations can form. Especially the maximum
vapour pressure of a flammable liquid can be so low
that the LEL concentration can only be exceeded
at a certain temperature. Only above this certain
temperature a flammable liquid’s vapour becomes
ignitable. This empirical temperature, established
by standardized methods, is called the flashpoint
which is a very important safety-relevant figure to
assess the hazardous nature of flammable liquids.
For example the flashpoint of pure Ethanol is 12 °C
(so Ethanol is flammable at 20 °C), but for n-Butanol
the flashpoint is 35 °C, so vapours of n-Butanol
cannot be ignited at ambient temperatures of 20 °C,
but above 35 °C they can.
And indeed: As long as the temperature of a
flammable liquid is kept reliably some degrees
below the flashpoint this is a primary explosion
protection measure!
IGNITION TEMPERATURE AND MINIMUM IGNITION
ENERGY
Sparks and arcs produced electrically (or
mechanically) and hot surfaces are the best
known ones of 13 different sources of ignition.
To ignite mixtures of flammable gases or vapours
in air the source of ignition must either have a
temperature higher than the empirical ignition
temperature or sparks must have an energy higher
than the empirical minimum ignition energy.
Both the ignition temperature and ignition energy
characteristics are established by standardized
methods and are relevant when designing or
selecting explosion protected instruments for a
certain application.
ST-6028-2004
| 07
Nitrobenzene
Methyl pyrrolidone
Tetrahydro naphthalene
Dimethyl acetamide
Cyclohexanol
Dimethyl formamide
Trimethyl benzene
Ethylglycol
n-Butanol
Nonane
Chlorobenzene
Ethyl benzene
i-Butyl acetate
Ethanol
Methanol
Toluene
Acetonitrile
Ethyl acetate
Methylethyl ketone
Cyclohexane
Hexane
Allyl amine
80 °C
70 °C
60 °C
50 °C
40 °C
30 °C
20 °C
10 °C
0 °C
– 10 °C
– 20 °C
– 30 °C
Flashpoint Scale
The lower the flashpoint the more dangerous
and easier to inflame is the liquid.
ST-1591-2007
STL-295-2007
LIST OF SAFETY-RELEVANT FIGURES FOR A SELECTION
OF FLAMMABLE GASES AND VAPOURS
Vapour Ignition
Gas / Vapour LEL % v/v LEL g/m3 Flashpoint* pressure* temperature
Acetone 2.5 60.5 < – 20 °C 246 mbar 535 °C
Acetylene 2.3 24.9 Gas Gas 305 °C
Acrylonitrile 2.8 61.9 – 5 °C 117 mbar 480 °C
Ammonia 15.4 109.1 Gas Gas 630 °C
Benzene 1.2 39.1 – 11 °C 100 mbar 555 °C
1.3-Butadiene 1.4 31.6 Gas Gas 415 °C
i-Butane 1.5 36.3 Gas Gas 460 °C
n-Butane 1.4 33.9 Gas Gas 365 °C
n-Butanol 1.7 52.5 35 °C 7 mbar 325 °C
n-Butene 1.2 28.1 Gas Gas 360 °C
n-Butyl acetate 1.2 58.1 27 °C 11 mbar 390 °C
Chlorobenzene 1.3 61.0 28 °C 12 mbar 590 °C
Cyclohexane 1.0 35.1 – 18 °C 104 mbar 260 °C
Cyclopentane 1.4 40.9 – 51 °C 346 mbar 320 °C
Diethylether 1.7 52.5 – 40 °C 586 mbar 175 °C
Dimethylether 2.7 51.9 Gas Gas 240 °C
1.4-Dioxane 1.9 69.7 11 °C 38 mbar 375 °C
Epichlorohydrin 2.3 88.6 28 °C 16 mbar 385 °C
Ethanol 3.1 59.5 12 °C 58 mbar 400 °C
Ethylene 2.4 28.1 Gas Gas 440 °C
Ethyl acetate 2.0 73.4 – 4 °C 98 mbar 470 °C
Ethyl benzene 1.0 44.3 23 °C 10 mbar 430 °C
Ethylene oxide 2.6 47.8 Gas Gas 435 °C
n-Hexane 1.0 35.9 – 22 °C 160 mbar 240 °C
Hydrogen 4.0 3.3 Gas Gas 560 °C
Methane 4.4 29.3 Gas Gas 595 °C
Methanol 6.0 80.0 9 °C 129 mbar 440 °C
Methyl chloride 7.6 159.9 Gas Gas 625 °C
Methylethyl ketone 1.5 45.1 – 10 °C 105 mbar 475 °C
Methyl methacrylate 1.7 70.9 10 °C 40 mbar 430 °C
n-Nonane 0.7 37.4 31 °C 5 mbar 205 °C
n-Octane 0.8 38.1 12 °C 14 mbar 205 °C
n-Pentane 1.4 42.1 – 40 °C 562 mbar 260 °C
Propane 1.7 31.2 Gas Gas 470 °C
i-Propanol 2.0 50.1 12 °C 43 mbar 425 °C
Propylene 1.8 31.6 Gas Gas 485 °C
Styrene 1.0 43.4 32 °C 7 mbar 490 °C
Toluene 1.1 42.2 6 °C 29 mbar 535 °C
* Flashpoint is defined for liquids only, vapour pressure at 20 °C reasonable for liquids only
08 |
Avoiding effective ignition sources –
secondary explosion protection
Without source of ignition no danger of explosion
If the formation of an ignitable atmosphere cannot
safely be averted or cannot effectively be prevented
(e.g. by using gas detection systems), electrical
instruments being used in this area shall not act as
a source of ignition: They need to be designed
such that they cannot inflame these flammable
atmospheres.
TYPES OF PROTECTION
Four of seven standardized types of protection are
applied in the gas detection technology: Flame-
proof (d), intrinsic safety (i), encapsulation (m),
and increased safety (e). By encapsulation hot
surfaces and sparks are prevented mechanically
whereas in intrinsically safe instruments this is
practiced by electrical power limiting. Generally
flameproof accepts internal explosions but is
designed such that it withstands the internal
explosion pressure and reliably avoids a flashback.
Increased safety is limited to passive devices such
as junction boxes, terminals and cable glands.
These are designed such that the risk of forming
hot surfaces or sparks is highly reduced. Explosion
protected instruments have to be type approved
and certified by a Notified Body.
EXPLOSION PROTECTION IS A LAW
In Europe explosion protection has become law by
converting the EU-directives 94/9/EC and
99/92/EC, also known as ATEX 95 and ATEX 137,
into national ordinances. Manufacturers of explosion
protected instruments have to mark these devices
unitarily by a device category showing the permissi-
ble application range, whereas the user of these
instruments is pledged to classify the potentially
explosive atmosphere area into zones depending
on the probability of occurrence of flammable
atmospheres and the nature of flammable matter:
gases or vapours (G) or dust (D).
For example II 2 GD is a typical device category for
instruments which may be used in zone 1 and zone
2 as well as in zone 21 and 22, while instruments
being used in zone 2 must have a marking of
II 3 G at least.
In the USA explosion protection is regulated by
the NEC 505, the relevant marking also implies
application hints by terms like Class and Division.
In the USA instruments using either flameproof or
intrinsically safe methods of protection are pre-
ferred. In most countries the European or American
explosion protection standards are accepted.
Recently there has been a drive towards the IEC-Ex
protection standards, which is based on world-wide
IEC explosion protection standards. Dräger gas
detection instruments meet the explosion protection
requirements of CENELEC (ATEX, Europe),
UL (USA), CSA (Canada) and IEC-Ex (world-wide).
ST-4940-2004
| 09
STL-296-2007
ST-9025-2005
ASSIGNMENT OF TEMPERATURE CLASSES AND EXPLOSION GROUPS AND TYPICAL GASES AND VAPOURS
Temperature class Explosion group
and max. permissible IIA IIB IIC
surface temperature ignition energy greater 0.18 mJ ignition energy 0.06 to 0.18 mJ ignition energy smaller 0.06 mJ
T1 450 °C Acetone, Ammonia, Benzene, Hydrogen cyanide, Town gas Hydrogen
Ethyl acetate, Methane, Methanol,
Propane, Toluene
T2 300 °C i-Amyl acetate, n-Butane, n-Butanol, 1.3-Butadiene, 1.4-Dioxane, Acetylene
1-Butene, Propyl acetate, i-Propanol, Ethylene, Ethylene oxide
Vinyl chloride
T3 200 °C Amyl alcohol, Gasolines, Dimethylether, Ethyl glycol,
Diesel fuel, Fuel oil, n-Hexane Hydrogen sulfide
T4 135 °C Acetaldehyde Diethylether
T5 100 °C
T6 85 °C Carbon disulfide
Example: If a potentially explosive atmosphere is caused by Carbon disulfide, an electrical apparatus is only suitable to be operated in this atmosphere if it is marked by
IIC and T6, whereas for n-Hexane atmospheres electrical devices with the marking IIA T3 are sufficiently protected.
II 2 GD
Type-approved acc. to 94/9/EC
Device category
II (2) G
Type-approved acc. to 94/9/EC
Device category
Explosion protected
Ex dem IIC T4
Type of protection
Explosion group
Temperature class
Explosion protected
Ex ib IIC T4
Type of protection
Explosion group
Temperature class
Typical marking of a gas detection
transmitter acc. to 94/9/EC:
Apparatus for zone 1, 2, 21 and 22.
Typical marking of a safety barrier
or a performance approved central
controller with electrical connections
into the hazardous area (zone 1 or 2),
but not to be operated in the hazardous
area.
Typical explosion protection marking
of an electrical apparatus (e.g. gas
detection transmitter).
Marking of an apparatus acc. to
IEC-Ex. Devices marked like this
are only allowed to be operated in
countries not belonging to the
European Community.
10 |
ST-297-2007
Warning sign mandatory
Warning sign mandatory for places
where explosive atmospheres may
occur (zones). Organizational meas-
ures have to be regarded.
ST-1580-2007
| 11
According to the directive 99/92/EC (ATEX 137) the
operator has to conduct a risk assessment of the
hazardous area and to classify the area into zones
depending on the probability of the occurrence of
potentially explosive atmospheres. Also, he has to
arrange organizational safety measures and provide
evidence by means of an explosion protection
document accordingly. Only suitable instruments
may be used in certain zones.
Employing the use of gas detection systems which
reliably prevent the occurrence of an ignitable
atmosphere, by default reduces the probability that
a flammable atmosphere can occur at all; it is not
likely to occur in normal operation – and this is
defined as zone 2. In other words: By means of a
suitable gas detection system a zone 1 area
converts to a zone 2 area where less complex
designed and mostly less expensive instruments
may be used (e.g. lamps, machines, mobiles, fork
lifters etc.)
An important requirement however is that the
counter measures activated by the gas detection
system are adequately preventing the formation of
flammable concentrations. This might not be the
case in the direct vicinity of a gas leak if the gas is
more quickly released than removed or diluted by
the ventilation. But although the proximal area
around a leak keeps being zone 1, the zone 1 area
shrinks drastically by using a gas detection system
– a great advantage for the customer.
The hazardous areas shrink: Zone 1 becomes zone 2.
By means of gas detection systems the probability
of a formation of explosive atmospheres is reduced
DEFINITION OF ZONES ACC. TO DIRECTIVE 99/92/EC
Hazardous places are classified in terms of zones on the basis of the Minimum requirement
Zone frequency and duration of the occurrence of an explosive atmosphere for device category
Gas 0 A place in which an explosive atmosphere consisting of a mixture with air of II 1G
flammable substances in the form of gas, vapour or mist is present continuously,
or for long periods or frequently
1 A place in which an explosive atmosphere consisting of a mixture with air or II 2G
flammable substances in the form of gas, vapour or mist is likely to occur in
normal operation occasionally
2 A place in which an explosive atmosphere consisting of a mixture with air of II 3G
flammable substances in the form of gas, vapour or mist is not likely to occur in
normal operation but, if it does occur, will persist for a short period only
Dust 20 A place in which an explosive atmosphere in the form of a cloud of combustible II 1D
dust in air is present continuously, or for long periods or frequently
21 A place in which an explosive atmosphere in the form of a cloud of combustible II 2D
dust in air is likely to occur in normal operation occasionally
22 A place in which an explosive atmosphere in the form of a cloud of combustible II 3D
dust in air is not likely to occur in normal operation but, if it does occur,
will persist for a short period only
Example: If an apparatus shall be operated in zone 21, the relevant marking must at least be device category II 2D
Hazardous
Areas
12 |
Proven in gas detection since decades:
Pellistor sensors and Infrared sensors.
PELLISTOR SENSORS
The pellistor sensor (or catalytic bead sensor) is
a relatively inexpensive flameproof sensor the
measuring principle of which is based on a chemical
reaction with oxygen and thus needs at least 12 % v/v.
Without oxygen the pellistor sensor cannot give a
reading, but also – because of oxygen deficiency –
there is no danger of explosion. The pellistor sensor
measures multiple gases and vapours, but with
different sensitivity. If the sensitivity for a substance
is too low the pellistor sensor may not be the correct
measuring principle for a reliable gas detection
system. Infrared sensors may be more applicable.
Catalytic bead principle
The heat-of-reaction measuring principle is based
on the fact that flammable gases and vapours even
below their LEL-concentration can undergo a
flameless oxidation reaction with atmospheric
oxygen, if only a suitable hot catalyst is present.
The additional released heat of reaction is a
measure for the gas concentration.
The pellistor sensor houses two small measuring
beads called pellistors (artificial term coming from
pellet and resistor), because they are used as pre-
cisely measuring temperature-dependent resistors.
Both the pellistors are made of very porous ceramic
material embedding a small platinum wire coil.
The active pellistor additionally contains catalytic
material. By means of an electrical current of
approx. 270 mA on the one hand the platinum coil
heats up the ceramic bead to ca. 450 °C, on the
other hand the platinum coil acts as a measuring
Active pellistor
(shown in half cut, schematic)
The penetrating methane molecule reacts
by means of the heated catalytic bead
material with atmospheric oxygen to
form water vapour and carbon dioxide.
The released heat of reaction causes a
measurable resistance increase of the
embedded platinum coil.
ST-1581-2007
Using
Gas Detection Systems
| 13
INFRARED SENSORS
In contrary to the catalytic bead sensors the
infrared sensors, which are based on a pure
physical measuring principle, are not prone to be
poisoned and do not depend on oxygen content for
measurement. By means of tight optical windows
infrared sensors are separated from the gas to be
detected. Infrared sensors, however, may have
extremely different sensitivities to different gases
and vapours, and some flammable substances
such as vinyl chloride or acetonitrile are, against
one’s expectations, not detectable at all. The
Dräger application laboratory is very experienced
and has worked out sensitivity data for more than
300 gases and vapours for different IR transmitters.
The IR measuring principle is based on the fact
that molecules of flammable gases and vapours
except a few (e.g. H2, NH3, CO, CS2, HCN, H2S,
and hydrides) are mostly hydrocarbons, the
CH-bonding of which can be excited to vibration
by certain wave-lengths (frequencies) of the
IR-spectrum and thus absorb energy. If IR is
radiated into an optical system filled with an
IR-absorbing gas, an increase of IR-absorption
might be detectable in a certain wavelength range,
because normal air does not absorb IR.
The generation of a stable spectrum of near
infrared radiation is easily practiced by glow lamps
operated by under-voltage, whereas the design of a
wavelength-specific IR measuring detector is way
more complex: Pyro-electric crystals, encapsulated
behind an optical interference filter produce very
resistor dependent on the bead’s temperature.
When molecules of a flammable gas penetrate into
a catalytic bead they react with the activated atmo-
spheric oxygen which is absorbed in the porous
ceramic and resultant heat of reaction increases the
pellistor’s temperature e.g. by about 2 °C for 10 %LEL
octane. The resulting increase of the pellistor’s
resistance is in the magnitude of some milli-Ohms
and is proportional to the gas concentration.
Environmental conditions
The increase of temperature, dependent of the gas
concentration, however, can only be used as a
measurement signal if changes of ambient temper-
ature, which might be much greater, are compen-
sated. This is realized by a second pellistor, which
in opposite to the described one does not contain
catalytic material and thus is measuring only the
ambient temperature. As part of a Wheatstone
bridge this passive pellistor compensates for
environmental influences, especially for ambient
temperature. For optimized behaviour both the
pellistors must fit best concerning their measuring
parameters, and they are accordingly matched to
pairs during manufacturing.
Poison resistance
For many decades the pellistors manufactured by
Dräger are of type PR, which means poison resist-
ant. Based on their special construction the sensors
have a longer lifetime compared to conventional
sensors when being exposed to industrial
atmospheres containing catalyst poisons such as
sulphur-, phosphor-, lead- or silicone-compounds.
ST-9068-2005
ST-725-2002
small intensity depending voltage changes when
being exposed to pulsating radiation. These
voltage changes are amplified, linearized and
finally converted to a 4 to 20-mA-signal which is
proportional to the gas concentration.
But not only gas reduces the measurable IR
intensity, but also a contamination of the optical
system by dust or mud causes intensity attenuation.
This effect is compensated by a second IR
measuring detector (reference detector), which
gets the optical information by a beam splitter and
detects the IR intensity in a wavelength range
where flammable gases do not absorb IR. If both
the measuring detector and the reference detector
indicate an IR-absorption this is not caused by a
gas but e.g. by dusty reflectors or else. By this way
of compensation the sensor signal becomes
contamination resistant, and at a certain degree of
contamination additionally a beam block signal or
maintenance signal can be generated. With the
Dräger Polytron IR type 334 or 340 also possible
alterations of the IR-detectors are compensated
by a second IR source (“4-beam-compensation-
method”).
The greater the optical system, the more gas
molecules are involved, and the higher is the
IR-absorption. And by using greater optical systems
lower measuring ranges such as e.g. 10 % of the
LEL can be realized to detect leakages at a very
early stage.
| 14
IR-transmitter
The fact that under normal conditions (no IR-
absorbing gas) there is a high measuring signal,
makes it possible to implement self diagnostic
processes: The IR-transmitter is able to detect
if e.g. the IR source fails or the optical system
is blocked. The transmitter is fail-safe in the
context of the IEC/EN 61508 standard and thus is
suitable to be used in SIL2-rated safety chains.
Dräger Polytron IR Ex
Schematic design (2-beam compensation method).
ST-1582-2007
Only the green part of the
light radiation is filtered out
and its intensity measured.
If a gas absorbs the green
part of the light radiation,
its intensity is measurably
reduced.
ST-1148-2008ST-1149-2008
Dräger Polytron IR type 334
Schematic design (4-beam compensation method).
ST-1583-2007
ST-3919-2004
ST-3719-2003
15 |
Only by proper calibration and sensor positioning
a gas detection system’s reliability is ensured
CALIBRATION
Only by calibration with the target gas (“gas to be
detected”) the gas detection transmitter is enabled
to give an individual gas concentration reading. If
several gases or vapours are to be detected the
transmitter has to be calibrated for the substance
which it is least sensitive to. The properly performed
calibration procedure is essential for the reliability
of a gas detection system.
SENSOR POSITIONING
Please refer also to the IEC/EN 60079-29-2,
chapter 8 – Criteria for the placement of sensors
and sampling points.
There are three different sensor placement
strategies:
1. Spot monitoring: The potential sources of leak
(e.g. valves, filling nozzles, flanges, bellows) are
well-known and locatable. So sensors can be
placed such that gas leaks can be detected very
early and reliably.
2. Area monitoring: The potential sources of leak
are spread across a large area and are not
locatable (e.g. in hazardous goods stores). Thus
the sensors should be positioned more or less
equidistantly across the entire area.
3. Fence monitoring: The potential sources of leak
are not locatable and there are no ignition
sources in the area. Thus sensors are positioned
at the outer limit to monitor for hazardous gas
concentrations crossing into neighbouring areas.
Besides the operational experience of the local
plant engineers concerning sensor positioning
also the IEC/EN 60079-29-2 “Guide for selection,
installation, use and maintenance of apparatus for
the detection and measurement of combustible
gases or oxygen” contains a lot of advices to place
gas sensors properly.
It seems to be trivial, but one thing is essential to
know when designing a gas detection system:
A gas detector can only detect a gas which is in
the direct vicinity and which can enter the sensor’s
elements. So it has to be considered that vapours
of flammable liquids are always heavier than air and
spread across the floor rather than rising up, and
they even might condensate in other locations if the
temperature decreases. Also, vapours of flammable
liquids cannot form combustible concentrations
if the ambient temperature is lower than the flash-
point.
Gas detection transmitters for the detection of
flammable vapours and heavy flammable gases
(especially propane and butane belong to this
group) should be placed where these substances
might accumulate, as low as possible above the
ground and/or below the leak. On the other hand
three gases are well known which are very much
lighter than air: Hydrogen, methane, and ammonia.
Commonly these gases will rise under normal
conditions, and sensors should be placed above
the leak.
Methane
n-Hexane
n-Nonane
Ethylene
Ethyl acetate
Hydrogen
n-Octane
Toluene
n-Pentane
Acetone
Propane
100
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
%LEL
%LEL
Methanol
Ethoxypropanol
Ethyl acetate
n-Butyl acetate
Cumene
Methane
Diethylether
Acetone
Propane
100
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
%LEL
%LEL
Pellistor sensor
Different sensitivities of a
Propane-calibrated pellis-
tor sensor (schematic):
50 %LEL n-Nonane
cause a measuring value
of only 23 %LEL Propane
while 50 %LEL Ethylene
cause a measuring value
of 62 %LEL.
Infrared sensor
Different sensitivities of a
Propane-calibrated infrared
sensor (Dräger Polytron IR Ex,
schematic): 50 %LEL Ethyl
acetate cause a measuring
value of only 22 %LEL
Propane while 50 %LEL
Methanol cause a measuring
value of 76 %LEL. A Propane-
calibrated IR Ex is relative
insensitive to Methane.
Hydrogen cannot be detected
at all by IR-technique.
ST-1592-2007
ST-1593-2007
Gas detection systems
16 |
Central Controllers – Centers for your Safety
Generally gas detection systems consist of explosion
protected remote transmitters (gas detection
transmitters), which are installed in the hazardous
area, a central controller unit installed in the safe
area to process the sensor signals and to trigger
alarms and counter measures, and optical and
audible alarm devices which also might be installed
in the hazardous area.
CENTRAL CONTROLLER UNITS
Central controller units are installed in the non-
hazardous area, and on the one hand they supply
the connected gas detection transmitters with the
necessary voltage, on the other hand they receive
their measuring signals and status-information to
process and indicate them. If pre-adjusted alarm
thresholds are exceeded central controllers are to
trigger alarms reliably. To have a high availability
central controllers often are equipped also with an
emergency power supply.
Central controllers might be small single-channel-
units for the connection of only one transmitter
as well as complete cabinets with built-in device
racks for many plug-in modules (channel modules)
connected to many transmitters, and with
customized wired alarm circuits.
The channel modules mostly provide several relays
with voltage-free contacts. Depending on whether
the relays are energized in normal operation or in
case of alarm, the voltage-free contacts can be
configured as NO-contacts (normally open =
closed in case of alarm) or NC-contacts (normally
closed - open in case of alarm).
For primary protection systems at least one relay
for device alarm must be energized in normal
operation (fail-safe principle) so that a mains power
breakdown can be detected. Furthermore, for
relays having a safety function it is recommended
that these relays are also fail-safe (de-energized in
case of alarm or power-off).
The relay contacts – if necessary upgraded by
additional relays to have redundant contacts – can
be used to activate counter measures (ventilation
on/off, ventilation flap open/close, gas supply
on/off, shutdown activation, etc.) and for optical
alarms, to keep the operator informed about the
alarm condition even after having switched off the
audible alarm. Switch-off means acknowledgement,
and in parallel to the automatic measures the
customer has to conduct organizational measures
if necessary.
Furthermore a gas detection system often provides
4 to 20-mA-outputs (“signal repeaters”), e.g. to
print-out or visualize the current gas concentrations
for documentation purposes.
Especially the modular concept of the central con-
troller Dräger REGARD offers numerous possibili-
ties for customized design: Various combinations of
Dräger REGARD Ex and 4 to 20-mA-modules,
Master card for the acknowledgment of special
alarm configurations and connections to PLCs,
HART card as well as a ModBus-Gateway card for
BUS-connection to process control systems and
PCs with 32-bit operating systems for measurement
display and data-logging.
Hazardous area (e.g. zone 1) Safe area
Gas detection transmitters detect a
high vapour concentration
The cloud of vapour
concentration is diluted and
removed by fresh air
Activated by the gas detection
system the ventilator injects fresh air
Leak evaporates
As a counter measure the
ventilation is switched on
Central controller realizes
high vapour concentration
and triggers alarms
Visible alarm
Audible alarm
II (2) G
II 2G II 2G II 2G
ST-1594-2007
| 17
Gas detectors
Based on catalytic bead sensor technology as well
as infrared sensor technology Dräger offers a wide
range of different gas detectors for the detection of
flammable gases and vapours.
ST-5003-2004
ST-6056-2004
GAS DETECTORS
ST-1389-2006
ST-5675-2004
Dräger PEX 3000
4 to 20-mA-transmitter with
pellistor sensor, with built-in
explosion protected 4 to
20-mA-converter, 7-segment-
display and 2-key-operation
(for calibration) to be
connected to central controllers
with 4 to 20-mA-inputs.
ST-5669-2004
Dräger Polytron SE Ex
Sensing head without electro-
nics with pellistor sensor and
mV-measuring signal to be
connected to special central
controllers, measuring range
0 to 100 or 0 to 10 %LEL, also
as high temperature version for
up to 150 °C.
Dräger Polytron FX and
Dräger Polytron 2 XP Ex
4 to 20-mA-transmitter with
pellistor sensor or IR-sensor
(optional), flameproof housing,
with display and magnetic wand
operation, ATEX- or UL-approved,
to be connected to central con-
trollers with 4 to 20-mA-inputs.
ST-3833-2003
ST-8821-2005
DrägerSensor IR
Explosion protected transmitter
with IR-sensor in flameproof
housing, similar to Dräger PIR
3000, but with pellistor-sensor-
emulation for replacement of
pellistor sensors, with mV-output
to be connected to special
central controllers.
ST-11659-2007
Dräger PIR 7000
Explosion protected robust
IR-transmitter with IR-sensor
in flameproof stainless steel
housing for central controllers
with 4 to 20-mA-input, suitable for
safety related systems acc. to SIL2,
certified following IEC 61508,
ATEX,- IECEx- and UL-approved.
Dräger Polytron Ex
Explosion protected transmitter
for pellistor sensor, with
intrinsically safe current circuits
(LC-display, sensor connection,
operating facilities) to be
connected to central controllers
with 4 to 20-mA-inputs.
ST-5643-2004
ST-5651-2004
Dräger Polytron IR type 334
and type 340
Explosion protected robust IR-
transmitter with IR-sensor in flame-
proof stainless steel housing for
central controllers with 4 to 20-mA-
input, suitable for safety related
systems acc. to SIL2, with HART
and RS 485, ATEX- or UL-approved.
ST-8822-2005
Dräger PIR 3000
Explosion protected transmitter
with IR-sensor in flameproof
housing, to be connected to
central controllers with 4 to
20-mA-input, ATEX-, IECEx- and
UL-approved.
Dräger Polytron IR Ex
Explosion protected transmitter
with IR-sensor, with intrinsically
safe current circuits (LC-display,
sensor connection, operating
facilities) to be connected to
central controllers with 4 to 20-
mA-inputs, with open or closed
optical system, different versions.
ST-3932-2005
Dräger Polytron Pulsar
Explosion protected Open Path
gas detector for the detection of
a gas concentration along a line
of sight of up to 200 m.
| 18
Central controllers
Based on different concepts, on the one hand device
rack with channels modules or DIN-rail mounted con-
trollers both to be installed in wall housings or cabinets,
on the other hand stand-alone controller units in IP65-
protected ABS-enclosures, Dräger offers controllers
with different properties, which – in combination with
suitable gas detectors – are dedicated for the reliable
gas detection in the field of explosion protection.
ST-7448-2006
ST-478-2004
CENTRAL CONTROLLERS
48658
Dräger Polytron Controller
Device racks for max. 2,
5, or 12 different
channel modules and one
acknowledgement module,
to be installed in cabinets,
panels or wall housings.
Channel modules with bar
graph display and LED status
information, three configurable
relays per module.
ST-335-2004
Dräger REGARD 1
Stand-alone single channel
controller with ABS-enclosure,
with LC display and status
LEDs, configurable for SE Ex
sensing heads as well as
4 to 20-mA-transmitters,
five relays, three alarm
thresholds and battery
back-up.
ST-5647-2006
ST-340-2004ST-272-2004ST-5738-2006
Dräger REGARD 2410
Central controller to be
clipped on a DIN-rail for
the connection of four
transmitters max.
Dräger REGARD 2400
Stand-alone central
controller for wall mounting
to be operated with four
transmitters max.
Dräger REGARD System
Device rack to take
up 16 different
modules, to be
installed in cabinets,
panels, or wall
housings. Channel
modules with 4 digit
matrix displays and
operation push buttons
for configuration.
Dräger REGARD 3900
Stand-alone central
controller with ABS-
enclosure for 1 to 16
channels, with LC display
and four status LEDs for
each channel, fully
configurable via laptop
or PC to operate with
4 to 20-mA-transmitters.
19 |
Explosion Protection by
Dräger Gas Detection Technology
EXPLOSION PROTECTION WITH DRÄGER
Dräger gas detection technology means sensors,
transmitters, central controllers and competent
support – our system engineers will design a
specific gas detection system for your application.
The product portfolio of Dräger gas detection
transmitters encompass numerous different types:
– catalytic bead or infrared sensor technology
– point- or open-path-detection
– increased safety, intrinsic safety, or flameproof
– analogue 4-20-mA-signal, mV signal
or digital HART or RS 485 signal
– with or without display at site
– with or without onboard relays
– low budget or high end equipment
Select between different central controllers for
your special explosion protection application:
– for mV-signal or 4 to 20-mA-signal
– single-channel or multi-channel controllers
– device racks for cabinet installation or stand-
alone type with ABS-housing
– with or without digital communication
– manually or PC-supported configuration
Dräger REGARD 3900
Stand-alone central controller
with ABS-enclosure for up to
16 channels.
ST-272-2004
Dräger REGARD
A representative customized gas
detection system.
ST-523-98
Tel: +44 (0)191 490 1547
Fax: +44 (0)191 477 5371
Email: northernsales@thorneandderrick.co.uk
Website: www.heattracing.co.uk
www.thorneanderrick.co.uk

Mais conteúdo relacionado

Mais procurados

Explosion protection theory and practice
Explosion protection   theory and practiceExplosion protection   theory and practice
Explosion protection theory and practiceDavid Pires
 
AIRFIRE WORLDWIDE Inert Fire Suppression Systems
AIRFIRE WORLDWIDE Inert Fire Suppression SystemsAIRFIRE WORLDWIDE Inert Fire Suppression Systems
AIRFIRE WORLDWIDE Inert Fire Suppression SystemsAirfire Worldwide
 
Hazardous area
Hazardous areaHazardous area
Hazardous areaumaji129
 
Hazardous area classification and Elecrtical, Instrument and Process Engineer...
Hazardous area classification and Elecrtical, Instrument and Process Engineer...Hazardous area classification and Elecrtical, Instrument and Process Engineer...
Hazardous area classification and Elecrtical, Instrument and Process Engineer...Kathiresan Nadar
 
Compare fm200 co2-argonite
Compare fm200 co2-argoniteCompare fm200 co2-argonite
Compare fm200 co2-argonitephathuynhdwt
 
Gas tester
Gas testerGas tester
Gas tester智 李
 
The Practical Guide to Hazardous Area Classification eBook
The Practical Guide to Hazardous Area Classification eBookThe Practical Guide to Hazardous Area Classification eBook
The Practical Guide to Hazardous Area Classification eBookBusiness Industrial Network
 
Different system of fire suppression
Different system of fire suppressionDifferent system of fire suppression
Different system of fire suppressionKamran Hassan
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selectionMowaten Masry
 
AraGasPlus - Example Report
AraGasPlus - Example ReportAraGasPlus - Example Report
AraGasPlus - Example ReportMike Marrington
 
CD#0160 Basic Fire Fighting
CD#0160 Basic Fire FightingCD#0160 Basic Fire Fighting
CD#0160 Basic Fire FightingChairil Anam
 
AIRFIRE WORLDWIDE Chemical Fire Suppression Systems
AIRFIRE WORLDWIDE Chemical Fire Suppression SystemsAIRFIRE WORLDWIDE Chemical Fire Suppression Systems
AIRFIRE WORLDWIDE Chemical Fire Suppression SystemsAirfire Worldwide
 
Fire & safety
Fire & safetyFire & safety
Fire & safetyReliance
 
Hazards Symposium Xxii 2011
Hazards Symposium Xxii 2011Hazards Symposium Xxii 2011
Hazards Symposium Xxii 2011MichaelRupp
 
Active and passive fire protection system
Active and passive fire protection systemActive and passive fire protection system
Active and passive fire protection systemKamran Hassan
 
Fire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_RevisedFire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_RevisedGan Chun Chet
 
Coal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power PlantCoal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power PlantSyed Aqeel Ahmed
 

Mais procurados (20)

Explosion protection theory and practice
Explosion protection   theory and practiceExplosion protection   theory and practice
Explosion protection theory and practice
 
AIRFIRE WORLDWIDE Inert Fire Suppression Systems
AIRFIRE WORLDWIDE Inert Fire Suppression SystemsAIRFIRE WORLDWIDE Inert Fire Suppression Systems
AIRFIRE WORLDWIDE Inert Fire Suppression Systems
 
Basics of atex
Basics of atexBasics of atex
Basics of atex
 
Hazardous area
Hazardous areaHazardous area
Hazardous area
 
Hazardous area classification and Elecrtical, Instrument and Process Engineer...
Hazardous area classification and Elecrtical, Instrument and Process Engineer...Hazardous area classification and Elecrtical, Instrument and Process Engineer...
Hazardous area classification and Elecrtical, Instrument and Process Engineer...
 
Compare fm200 co2-argonite
Compare fm200 co2-argoniteCompare fm200 co2-argonite
Compare fm200 co2-argonite
 
Gas tester
Gas testerGas tester
Gas tester
 
The Practical Guide to Hazardous Area Classification eBook
The Practical Guide to Hazardous Area Classification eBookThe Practical Guide to Hazardous Area Classification eBook
The Practical Guide to Hazardous Area Classification eBook
 
Different system of fire suppression
Different system of fire suppressionDifferent system of fire suppression
Different system of fire suppression
 
49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection49574055 burner-management-system-safety-integrity-level-selection
49574055 burner-management-system-safety-integrity-level-selection
 
Hazardous classified locations
Hazardous classified locationsHazardous classified locations
Hazardous classified locations
 
Types of gas detection system
Types of gas detection systemTypes of gas detection system
Types of gas detection system
 
AraGasPlus - Example Report
AraGasPlus - Example ReportAraGasPlus - Example Report
AraGasPlus - Example Report
 
CD#0160 Basic Fire Fighting
CD#0160 Basic Fire FightingCD#0160 Basic Fire Fighting
CD#0160 Basic Fire Fighting
 
AIRFIRE WORLDWIDE Chemical Fire Suppression Systems
AIRFIRE WORLDWIDE Chemical Fire Suppression SystemsAIRFIRE WORLDWIDE Chemical Fire Suppression Systems
AIRFIRE WORLDWIDE Chemical Fire Suppression Systems
 
Fire & safety
Fire & safetyFire & safety
Fire & safety
 
Hazards Symposium Xxii 2011
Hazards Symposium Xxii 2011Hazards Symposium Xxii 2011
Hazards Symposium Xxii 2011
 
Active and passive fire protection system
Active and passive fire protection systemActive and passive fire protection system
Active and passive fire protection system
 
Fire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_RevisedFire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_Revised
 
Coal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power PlantCoal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power Plant
 

Semelhante a Drager Fixed Gas Detector - Explosion Protection Brochure

CHAPTER 17- EXPOSICIÓN INGLES.pptx
CHAPTER 17- EXPOSICIÓN INGLES.pptxCHAPTER 17- EXPOSICIÓN INGLES.pptx
CHAPTER 17- EXPOSICIÓN INGLES.pptxLEOPOLDOVAZQUEZ10
 
Fire and Electrical Safety.ppsx
Fire and Electrical Safety.ppsxFire and Electrical Safety.ppsx
Fire and Electrical Safety.ppsxArpan Sheth
 
15._SGW -_GAS_TESTING__MONITORING .pptx
15._SGW -_GAS_TESTING__MONITORING  .pptx15._SGW -_GAS_TESTING__MONITORING  .pptx
15._SGW -_GAS_TESTING__MONITORING .pptxsafetygoodwe
 
Aviation Turbine Fuel - Tribute Aviation
Aviation Turbine Fuel - Tribute AviationAviation Turbine Fuel - Tribute Aviation
Aviation Turbine Fuel - Tribute AviationTribute Aviation
 
Jet-A with Prist Additive Safety Data Sheet
Jet-A with Prist Additive Safety Data SheetJet-A with Prist Additive Safety Data Sheet
Jet-A with Prist Additive Safety Data SheetTribute Aviation
 
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems BrochureDrager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems BrochureThorne & Derrick UK
 
Handbook:Lightweight Respiratory Protection
Handbook:Lightweight Respiratory ProtectionHandbook:Lightweight Respiratory Protection
Handbook:Lightweight Respiratory ProtectionDräger
 
Gas Safety Training N JHA pptx.pptx
Gas Safety Training N JHA pptx.pptxGas Safety Training N JHA pptx.pptx
Gas Safety Training N JHA pptx.pptxSShivaPavan
 
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh RajputInspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh RajputGaurav Singh Rajput
 
David Woolgar DSEAR and gas safety
David Woolgar  DSEAR and gas safetyDavid Woolgar  DSEAR and gas safety
David Woolgar DSEAR and gas safetyJessica Allan
 
MSA Safety Fixed Gas Detectors & Flame Detectors - Brochure
MSA Safety Fixed Gas Detectors & Flame Detectors - BrochureMSA Safety Fixed Gas Detectors & Flame Detectors - Brochure
MSA Safety Fixed Gas Detectors & Flame Detectors - BrochureThorne & Derrick UK
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classificationdebuddit
 
Safety &amp; Safety Management
Safety &amp; Safety ManagementSafety &amp; Safety Management
Safety &amp; Safety ManagementHasnain Ali
 
Combustible dust
Combustible dust Combustible dust
Combustible dust anfelogo03
 

Semelhante a Drager Fixed Gas Detector - Explosion Protection Brochure (20)

CHAPTER 17- EXPOSICIÓN INGLES.pptx
CHAPTER 17- EXPOSICIÓN INGLES.pptxCHAPTER 17- EXPOSICIÓN INGLES.pptx
CHAPTER 17- EXPOSICIÓN INGLES.pptx
 
Explosion Protection
Explosion ProtectionExplosion Protection
Explosion Protection
 
Fire and Electrical Safety.ppsx
Fire and Electrical Safety.ppsxFire and Electrical Safety.ppsx
Fire and Electrical Safety.ppsx
 
Chemical Hazards
Chemical HazardsChemical Hazards
Chemical Hazards
 
15._SGW -_GAS_TESTING__MONITORING .pptx
15._SGW -_GAS_TESTING__MONITORING  .pptx15._SGW -_GAS_TESTING__MONITORING  .pptx
15._SGW -_GAS_TESTING__MONITORING .pptx
 
Aviation Turbine Fuel - Tribute Aviation
Aviation Turbine Fuel - Tribute AviationAviation Turbine Fuel - Tribute Aviation
Aviation Turbine Fuel - Tribute Aviation
 
Jet-A with Prist Additive Safety Data Sheet
Jet-A with Prist Additive Safety Data SheetJet-A with Prist Additive Safety Data Sheet
Jet-A with Prist Additive Safety Data Sheet
 
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems BrochureDrager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
Drager Fixed Gas Detector - At The Heart Of Gas Detection Systems Brochure
 
Handbook:Lightweight Respiratory Protection
Handbook:Lightweight Respiratory ProtectionHandbook:Lightweight Respiratory Protection
Handbook:Lightweight Respiratory Protection
 
Gas Safety Training N JHA pptx.pptx
Gas Safety Training N JHA pptx.pptxGas Safety Training N JHA pptx.pptx
Gas Safety Training N JHA pptx.pptx
 
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh RajputInspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
Inspection of Fire Fighting Equipments | NFPA Regulations | Gaurav Singh Rajput
 
fire protection
fire protectionfire protection
fire protection
 
David Woolgar DSEAR and gas safety
David Woolgar  DSEAR and gas safetyDavid Woolgar  DSEAR and gas safety
David Woolgar DSEAR and gas safety
 
Flue gas analysis
Flue gas analysisFlue gas analysis
Flue gas analysis
 
ACA-02
ACA-02ACA-02
ACA-02
 
MSA Safety Fixed Gas Detectors & Flame Detectors - Brochure
MSA Safety Fixed Gas Detectors & Flame Detectors - BrochureMSA Safety Fixed Gas Detectors & Flame Detectors - Brochure
MSA Safety Fixed Gas Detectors & Flame Detectors - Brochure
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 
Safety &amp; Safety Management
Safety &amp; Safety ManagementSafety &amp; Safety Management
Safety &amp; Safety Management
 
22711.pdf
22711.pdf22711.pdf
22711.pdf
 
Combustible dust
Combustible dust Combustible dust
Combustible dust
 

Mais de Thorne & Derrick UK

Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...
Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...
Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...Thorne & Derrick UK
 
Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...
Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...
Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...Thorne & Derrick UK
 
Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016
Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016
Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016Thorne & Derrick UK
 
Wolf - Hazardous Area Portable & Temporary Lighting - Brochure
Wolf - Hazardous Area Portable & Temporary Lighting - BrochureWolf - Hazardous Area Portable & Temporary Lighting - Brochure
Wolf - Hazardous Area Portable & Temporary Lighting - BrochureThorne & Derrick UK
 
VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...
VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...
VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...Thorne & Derrick UK
 
Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...
Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...
Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...Thorne & Derrick UK
 
SIRAI - Solenoid Valves (WRAS Approved) - Overview Catalogue
SIRAI - Solenoid Valves (WRAS Approved) - Overview CatalogueSIRAI - Solenoid Valves (WRAS Approved) - Overview Catalogue
SIRAI - Solenoid Valves (WRAS Approved) - Overview CatalogueThorne & Derrick UK
 
Sika Measuring Metering Calibration Instruments
Sika Measuring Metering Calibration InstrumentsSika Measuring Metering Calibration Instruments
Sika Measuring Metering Calibration InstrumentsThorne & Derrick UK
 
SICK - Sensors & Sensor Solutions - Catalogue
SICK - Sensors & Sensor Solutions - CatalogueSICK - Sensors & Sensor Solutions - Catalogue
SICK - Sensors & Sensor Solutions - CatalogueThorne & Derrick UK
 
Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...
Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...
Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...Thorne & Derrick UK
 
Patol Analogue Linear Heat Detection Cable
Patol Analogue Linear Heat Detection CablePatol Analogue Linear Heat Detection Cable
Patol Analogue Linear Heat Detection CableThorne & Derrick UK
 
Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...
Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...
Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...Thorne & Derrick UK
 
MSA Gas Detectors – Portable & Fixed Gas Detection - Brochure
MSA Gas Detectors – Portable & Fixed Gas Detection - BrochureMSA Gas Detectors – Portable & Fixed Gas Detection - Brochure
MSA Gas Detectors – Portable & Fixed Gas Detection - BrochureThorne & Derrick UK
 
Flow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp On
Flow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp OnFlow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp On
Flow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp OnThorne & Derrick UK
 
LMK Thermosafe Hazardous Area Drum & IBC Product Overview
LMK Thermosafe Hazardous Area Drum & IBC Product OverviewLMK Thermosafe Hazardous Area Drum & IBC Product Overview
LMK Thermosafe Hazardous Area Drum & IBC Product OverviewThorne & Derrick UK
 
Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...
Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...
Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...Thorne & Derrick UK
 
Katronic - Ultrasonic Flow Measurement & Flowmeters - Product Brochure
Katronic - Ultrasonic Flow Measurement & Flowmeters - Product BrochureKatronic - Ultrasonic Flow Measurement & Flowmeters - Product Brochure
Katronic - Ultrasonic Flow Measurement & Flowmeters - Product BrochureThorne & Derrick UK
 
Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...
Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...
Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...Thorne & Derrick UK
 
Itron - Gas, Water & Heat Meters - Corporate Brochure
Itron - Gas, Water & Heat Meters - Corporate BrochureItron - Gas, Water & Heat Meters - Corporate Brochure
Itron - Gas, Water & Heat Meters - Corporate BrochureThorne & Derrick UK
 

Mais de Thorne & Derrick UK (20)

Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...
Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...
Marechal Electric - Plugs & Sockets (Industrial & Hazardous Area (Explosion P...
 
Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...
Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...
Rotronic Instruments Temperature, Humidity, Flow, Pressure & Carbon Dioxide M...
 
Dart Valley Systems Catalogue
Dart Valley Systems CatalogueDart Valley Systems Catalogue
Dart Valley Systems Catalogue
 
Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016
Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016
Cistermiser Water Efficient Washroom Controls - Specification Catalogue 2016
 
Wolf - Hazardous Area Portable & Temporary Lighting - Brochure
Wolf - Hazardous Area Portable & Temporary Lighting - BrochureWolf - Hazardous Area Portable & Temporary Lighting - Brochure
Wolf - Hazardous Area Portable & Temporary Lighting - Brochure
 
VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...
VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...
VEGA – Level, Point Level & Pressure Measurement Sensors, Instruments & Trans...
 
Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...
Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...
Thermon – Heat Tracing Cables (Self Regulating, Power Limiting, Constant Watt...
 
SIRAI - Solenoid Valves (WRAS Approved) - Overview Catalogue
SIRAI - Solenoid Valves (WRAS Approved) - Overview CatalogueSIRAI - Solenoid Valves (WRAS Approved) - Overview Catalogue
SIRAI - Solenoid Valves (WRAS Approved) - Overview Catalogue
 
Sika Measuring Metering Calibration Instruments
Sika Measuring Metering Calibration InstrumentsSika Measuring Metering Calibration Instruments
Sika Measuring Metering Calibration Instruments
 
SICK - Sensors & Sensor Solutions - Catalogue
SICK - Sensors & Sensor Solutions - CatalogueSICK - Sensors & Sensor Solutions - Catalogue
SICK - Sensors & Sensor Solutions - Catalogue
 
Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...
Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...
Rotronic Instruments - Temperature, Humidity, Flow, Pressure & Carbon Dioxide...
 
Patol Analogue Linear Heat Detection Cable
Patol Analogue Linear Heat Detection CablePatol Analogue Linear Heat Detection Cable
Patol Analogue Linear Heat Detection Cable
 
Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...
Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...
Murco - Gas Detection (Refrigerant Gas Leak Detectors & Sensors) - Product Br...
 
MSA Gas Detectors – Portable & Fixed Gas Detection - Brochure
MSA Gas Detectors – Portable & Fixed Gas Detection - BrochureMSA Gas Detectors – Portable & Fixed Gas Detection - Brochure
MSA Gas Detectors – Portable & Fixed Gas Detection - Brochure
 
Flow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp On
Flow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp OnFlow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp On
Flow Meters Micronics Portable Fixed Flow Meters Ultrasonic Clamp On
 
LMK Thermosafe Hazardous Area Drum & IBC Product Overview
LMK Thermosafe Hazardous Area Drum & IBC Product OverviewLMK Thermosafe Hazardous Area Drum & IBC Product Overview
LMK Thermosafe Hazardous Area Drum & IBC Product Overview
 
Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...
Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...
Krohne Hazardous Area Process Instrumentation Meters Measurement - Product Ov...
 
Katronic - Ultrasonic Flow Measurement & Flowmeters - Product Brochure
Katronic - Ultrasonic Flow Measurement & Flowmeters - Product BrochureKatronic - Ultrasonic Flow Measurement & Flowmeters - Product Brochure
Katronic - Ultrasonic Flow Measurement & Flowmeters - Product Brochure
 
Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...
Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...
Kamstrup - Heat Meters & Water Meters Ultrasonic (RHI Compliant MID Class 2 H...
 
Itron - Gas, Water & Heat Meters - Corporate Brochure
Itron - Gas, Water & Heat Meters - Corporate BrochureItron - Gas, Water & Heat Meters - Corporate Brochure
Itron - Gas, Water & Heat Meters - Corporate Brochure
 

Último

Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxGo for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxRakhi Bazaar
 
NAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors DataNAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors DataExhibitors Data
 
Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...
Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...
Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...Aggregage
 
How to Conduct a Service Gap Analysis for Your Business
How to Conduct a Service Gap Analysis for Your BusinessHow to Conduct a Service Gap Analysis for Your Business
How to Conduct a Service Gap Analysis for Your BusinessHelp Desk Migration
 
Excvation Safety for safety officers reference
Excvation Safety for safety officers referenceExcvation Safety for safety officers reference
Excvation Safety for safety officers referencessuser2c065e
 
Psychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh JiPsychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh Jiastral oracle
 
Interoperability and ecosystems: Assembling the industrial metaverse
Interoperability and ecosystems:  Assembling the industrial metaverseInteroperability and ecosystems:  Assembling the industrial metaverse
Interoperability and ecosystems: Assembling the industrial metaverseSiemens
 
Simplify Your Funding: Quick and Easy Business Loans
Simplify Your Funding: Quick and Easy Business LoansSimplify Your Funding: Quick and Easy Business Loans
Simplify Your Funding: Quick and Easy Business LoansNugget Global
 
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...Operational Excellence Consulting
 
Customizable Contents Restoration Training
Customizable Contents Restoration TrainingCustomizable Contents Restoration Training
Customizable Contents Restoration TrainingCalvinarnold843
 
Neha Jhalani Hiranandani: A Guide to Her Life and Career
Neha Jhalani Hiranandani: A Guide to Her Life and CareerNeha Jhalani Hiranandani: A Guide to Her Life and Career
Neha Jhalani Hiranandani: A Guide to Her Life and Careerr98588472
 
Technical Leaders - Working with the Management Team
Technical Leaders - Working with the Management TeamTechnical Leaders - Working with the Management Team
Technical Leaders - Working with the Management TeamArik Fletcher
 
Data Analytics Strategy Toolkit and Templates
Data Analytics Strategy Toolkit and TemplatesData Analytics Strategy Toolkit and Templates
Data Analytics Strategy Toolkit and TemplatesAurelien Domont, MBA
 
Unveiling the Soundscape Music for Psychedelic Experiences
Unveiling the Soundscape Music for Psychedelic ExperiencesUnveiling the Soundscape Music for Psychedelic Experiences
Unveiling the Soundscape Music for Psychedelic ExperiencesDoe Paoro
 
Paul Turovsky - Real Estate Professional
Paul Turovsky - Real Estate ProfessionalPaul Turovsky - Real Estate Professional
Paul Turovsky - Real Estate ProfessionalPaul Turovsky
 
How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...
How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...
How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...Hector Del Castillo, CPM, CPMM
 
71368-80-4.pdf Fast delivery good quality
71368-80-4.pdf Fast delivery  good quality71368-80-4.pdf Fast delivery  good quality
71368-80-4.pdf Fast delivery good qualitycathy664059
 
WSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfWSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfJamesConcepcion7
 
MEP Plans in Construction of Building and Industrial Projects 2024
MEP Plans in Construction of Building and Industrial Projects 2024MEP Plans in Construction of Building and Industrial Projects 2024
MEP Plans in Construction of Building and Industrial Projects 2024Chandresh Chudasama
 

Último (20)

Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptxGo for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
Go for Rakhi Bazaar and Pick the Latest Bhaiya Bhabhi Rakhi.pptx
 
NAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors DataNAB Show Exhibitor List 2024 - Exhibitors Data
NAB Show Exhibitor List 2024 - Exhibitors Data
 
Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...
Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...
Strategic Project Finance Essentials: A Project Manager’s Guide to Financial ...
 
How to Conduct a Service Gap Analysis for Your Business
How to Conduct a Service Gap Analysis for Your BusinessHow to Conduct a Service Gap Analysis for Your Business
How to Conduct a Service Gap Analysis for Your Business
 
Excvation Safety for safety officers reference
Excvation Safety for safety officers referenceExcvation Safety for safety officers reference
Excvation Safety for safety officers reference
 
Psychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh JiPsychic Reading | Spiritual Guidance – Astro Ganesh Ji
Psychic Reading | Spiritual Guidance – Astro Ganesh Ji
 
Interoperability and ecosystems: Assembling the industrial metaverse
Interoperability and ecosystems:  Assembling the industrial metaverseInteroperability and ecosystems:  Assembling the industrial metaverse
Interoperability and ecosystems: Assembling the industrial metaverse
 
The Bizz Quiz-E-Summit-E-Cell-IITPatna.pptx
The Bizz Quiz-E-Summit-E-Cell-IITPatna.pptxThe Bizz Quiz-E-Summit-E-Cell-IITPatna.pptx
The Bizz Quiz-E-Summit-E-Cell-IITPatna.pptx
 
Simplify Your Funding: Quick and Easy Business Loans
Simplify Your Funding: Quick and Easy Business LoansSimplify Your Funding: Quick and Easy Business Loans
Simplify Your Funding: Quick and Easy Business Loans
 
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
The McKinsey 7S Framework: A Holistic Approach to Harmonizing All Parts of th...
 
Customizable Contents Restoration Training
Customizable Contents Restoration TrainingCustomizable Contents Restoration Training
Customizable Contents Restoration Training
 
Neha Jhalani Hiranandani: A Guide to Her Life and Career
Neha Jhalani Hiranandani: A Guide to Her Life and CareerNeha Jhalani Hiranandani: A Guide to Her Life and Career
Neha Jhalani Hiranandani: A Guide to Her Life and Career
 
Technical Leaders - Working with the Management Team
Technical Leaders - Working with the Management TeamTechnical Leaders - Working with the Management Team
Technical Leaders - Working with the Management Team
 
Data Analytics Strategy Toolkit and Templates
Data Analytics Strategy Toolkit and TemplatesData Analytics Strategy Toolkit and Templates
Data Analytics Strategy Toolkit and Templates
 
Unveiling the Soundscape Music for Psychedelic Experiences
Unveiling the Soundscape Music for Psychedelic ExperiencesUnveiling the Soundscape Music for Psychedelic Experiences
Unveiling the Soundscape Music for Psychedelic Experiences
 
Paul Turovsky - Real Estate Professional
Paul Turovsky - Real Estate ProfessionalPaul Turovsky - Real Estate Professional
Paul Turovsky - Real Estate Professional
 
How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...
How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...
How Generative AI Is Transforming Your Business | Byond Growth Insights | Apr...
 
71368-80-4.pdf Fast delivery good quality
71368-80-4.pdf Fast delivery  good quality71368-80-4.pdf Fast delivery  good quality
71368-80-4.pdf Fast delivery good quality
 
WSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdfWSMM Technology February.March Newsletter_vF.pdf
WSMM Technology February.March Newsletter_vF.pdf
 
MEP Plans in Construction of Building and Industrial Projects 2024
MEP Plans in Construction of Building and Industrial Projects 2024MEP Plans in Construction of Building and Industrial Projects 2024
MEP Plans in Construction of Building and Industrial Projects 2024
 

Drager Fixed Gas Detector - Explosion Protection Brochure

  • 1. Explosion Protection ST-6057-2004 GAS DETECTION SYSTEMS Tel: +44 (0)191 490 1547 Fax: +44 (0)191 477 5371 Email: northernsales@thorneandderrick.co.uk Website: www.heattracing.co.uk www.thorneanderrick.co.uk
  • 2. 02 | Explosion hazards mostly arise from flammable gases and vapours Instead of avoiding their ignition by explosion protection measures it may be preferable to detect them before they become ignitable. DANGER OF EXPLOSION IS LURKING EVERYWHERE Wherever hazardous situations exist due to the presence of combustible gases and vapours e.g. in oil & gas exploration and storage, transportation and storage of flammable liquids and gases, in processes involving the use of solvents, or in the plastics processing industry, we will always encounter explosion protection measures, mostly regulated by law, to keep the personnel and plants safe. Depending on the application different measuring principles for the detection of gases and vapours can be used: Catalytic bead sensors, point or open-path infrared sensors. When detectors are used in combination with a central controller such as Dräger Polytron or Dräger REGARD it is possible to detect flammable gases and vapours at an early stage, when concentrations are so low that a dangerous condition – a risk of explosion – can be reliably averted. METHODOLOGY OF EXPLOSION PROTECTION Flammable gases and vapours can only be ignited by an ignition source with sufficient high energy or sufficient high temperature if – under atmospheric conditions – they exist in a mixture with atmospheric oxygen in sufficiently high concentrations. This mixture’s concentration is called LEL: Lower Explosion Limit. To have an ignition three conditions have to be met: 1. Concentration of flammable gas or vapour above the LEL 2. Sufficiently high oxygen concentration 3. Sufficiently high temperature or sufficient energy of the ignition source Vice versa this rule reads: If one of the three conditions is not met it is reliably ensured that no ignition or explosion can take place. So, measures of explosion protection can be the following: 1. Concentration limiting 2. Inertisation 3. Use of explosion protected apparatus
  • 3. | 03 The safest way of concentration limiting is the removal of flammable gases and vapours from the process – this is not normally practical. Where flammable gases and vapours are used, it is normal for gas detection systems to be used to limit concentrations. When the process is closed and the level of flammable gases or vapours is allowed to exceed the LEL level, this is acceptable as long as the oxygen concentration is kept low enough to control the risk of explosion (inertisation). If these measures however are not sufficient, all of the involved electrical devices have to be designed according to certain explosion protection standards so they will not act as a source of ignition if flammable gases or vapours are released. Further advice concerning the methodology can be found in the harmonized standard EN 1127-1. Explosion protection means reliably excluding at least one of the three prerequisites for ignition. Gas/vapour in sufficiently high concentration (above LEL). Air/oxygen in sufficiently high concentration. Ignition source e.g. ignition spark with sufficient energy or sufficiently high temperatures. ST-1576-2007
  • 4. 04 | Activation of compulsory measures (e.g. shut-down) Activation of counter measures (e.g. ventilation) Alarm range 2 Alarm range 1 Safe range 40 %LEL 20 %LEL 0 %LEL Alarm thresholds If the gas concentration rises a counter measure is activated when reaching the alarm range 1. If the counter measure is effective the gas concentration will decrease (blue curve). If, however, the counter measure is not effective the concen- tration will keep on rising (red curve). When reaching the alarm range 2 compulsory measures are activated. Properly designed gas detection systems will rarely or never reach the alarm range 2. ST-1590-2007 Hazardous Atmospheres ST-3101-2004
  • 5. | 05 Preventing potentially explosive atmospheres – primary explosion protection. BELOW THE LEL NO DANGER OF EXPLOSION Concentration limiting (1) and inertisation (2) are also called primary measures because the formation of an ignitable concentration is averted. On the other hand when using explosion protected instruments (3) this is a secondary measure because not the for- mation of ignitable concentrations is averted, but only its ignition. Concentration limiting means active dilution, e.g. by automatically ventilating fresh air into the hazardous area if concentrations have risen above the 20 %LEL threshold. If concentrations continue to rise because the counter measure is ineffective then it is necessary to automatically activate shut-down actions at 40 %LEL e.g. by switching off any non- explosion proof instrument or equipment. Gas detection systems used for this purpose must be type approved by a Notified Body in respect to their compliance with the European Standards (formerly acc. to EN 50054ff, now acc. to EN 61779 or EN 60079-29-1). This is true for the sensor and the transmitter as well as for the central controller unit. As inertisation is also a preventive explosion protection measure, oxygen measuring instruments controlling the inertisation process at least in Europe also have to be type-approved for this purpose and shall comply with the relevant harmonised standards (e.g. EN 50 104). LEL Scale The lower the LEL the more danger- ous is the substance, as ignitable concentrations can form more easily. Ammonia Carbon monoxide Formic acid 1.2-Dichloro ethylene Methyl bromide 1.1.1-Trichloro ethane Methyl chloride Acetyl chloride Formaldehyde 1.1-Dichloro ethylene 1.2-Dichloro ethane Methanol 1.1-Dichloro ethane Hydrogen cyanide Methyl amine Hydrazine Methane Hydrogen Vinylchloride Ethyl amine Ethanol Acetonitrile Acrylonitrile Dimethyl ether Ethylene Dimethyl formamide i-Propanol Propane i-Butane n-Butane n-Butyl acetate n-Hexane n-Octane n-Nonane n-Decane 15.5 % v/v 15.0 % v/v 11.0 % v/v 10.5 % v/v 10.0 % v/v 9.5 % v/v 9.0 % v/v 8.5 % v/v 8.0 % v/v 7.5 % v/v 7.0 % v/v 6.5 % v/v 6.0% v/v 5.5 % v/v 5.0 % v/v 4.5 % v/v 4.0 % v/v 3.5% v/v 3.0 % v/v 2.5 % v/v 2.0 % v/v 1.5 % v/v 1.0 % v/v 0.5 % v/v ST-1589-2007
  • 6. 06 | Safety relevant data of flammable gases and vapours. THE LOWER EXPLOSION LIMIT – LEL For flammable substances there is a limit concen- tration necessary for ignition. Below this limit a mixture of the substance in air cannot be ignited because there is a deficiency of fuel. This limit is called the Lower Explosion Limit or LEL. The LEL cannot be calculated but is an empirical characteristic figure which is established by standardized methods. With some exceptions the LEL lies between 0.5 and 15 % by volume. GASES AND LEL Matter above its boiling point commonly is called a gas. Thus the pressure of a pure liquefied gas is always higher than the atmospheric pressure so that released gases can very quickly form concentrations above the LEL causing dangerous ignitable gas-/air-mixtures. VAPOURS OF FLAMMABLE LIQUIDS AND FLASHPOINT Matter below its boiling point is not only gaseous but exists in an equilibrium with its liquid (and also solid) state which depends on the temperature. The gaseous component of this matter is called vapour. A vapour’s pressure is always lower than the atmospheric pressure, and, depending on the liquid’s temperature, only certain maximum vapour concentrations can form. Especially the maximum vapour pressure of a flammable liquid can be so low that the LEL concentration can only be exceeded at a certain temperature. Only above this certain temperature a flammable liquid’s vapour becomes ignitable. This empirical temperature, established by standardized methods, is called the flashpoint which is a very important safety-relevant figure to assess the hazardous nature of flammable liquids. For example the flashpoint of pure Ethanol is 12 °C (so Ethanol is flammable at 20 °C), but for n-Butanol the flashpoint is 35 °C, so vapours of n-Butanol cannot be ignited at ambient temperatures of 20 °C, but above 35 °C they can. And indeed: As long as the temperature of a flammable liquid is kept reliably some degrees below the flashpoint this is a primary explosion protection measure! IGNITION TEMPERATURE AND MINIMUM IGNITION ENERGY Sparks and arcs produced electrically (or mechanically) and hot surfaces are the best known ones of 13 different sources of ignition. To ignite mixtures of flammable gases or vapours in air the source of ignition must either have a temperature higher than the empirical ignition temperature or sparks must have an energy higher than the empirical minimum ignition energy. Both the ignition temperature and ignition energy characteristics are established by standardized methods and are relevant when designing or selecting explosion protected instruments for a certain application. ST-6028-2004
  • 7. | 07 Nitrobenzene Methyl pyrrolidone Tetrahydro naphthalene Dimethyl acetamide Cyclohexanol Dimethyl formamide Trimethyl benzene Ethylglycol n-Butanol Nonane Chlorobenzene Ethyl benzene i-Butyl acetate Ethanol Methanol Toluene Acetonitrile Ethyl acetate Methylethyl ketone Cyclohexane Hexane Allyl amine 80 °C 70 °C 60 °C 50 °C 40 °C 30 °C 20 °C 10 °C 0 °C – 10 °C – 20 °C – 30 °C Flashpoint Scale The lower the flashpoint the more dangerous and easier to inflame is the liquid. ST-1591-2007 STL-295-2007 LIST OF SAFETY-RELEVANT FIGURES FOR A SELECTION OF FLAMMABLE GASES AND VAPOURS Vapour Ignition Gas / Vapour LEL % v/v LEL g/m3 Flashpoint* pressure* temperature Acetone 2.5 60.5 < – 20 °C 246 mbar 535 °C Acetylene 2.3 24.9 Gas Gas 305 °C Acrylonitrile 2.8 61.9 – 5 °C 117 mbar 480 °C Ammonia 15.4 109.1 Gas Gas 630 °C Benzene 1.2 39.1 – 11 °C 100 mbar 555 °C 1.3-Butadiene 1.4 31.6 Gas Gas 415 °C i-Butane 1.5 36.3 Gas Gas 460 °C n-Butane 1.4 33.9 Gas Gas 365 °C n-Butanol 1.7 52.5 35 °C 7 mbar 325 °C n-Butene 1.2 28.1 Gas Gas 360 °C n-Butyl acetate 1.2 58.1 27 °C 11 mbar 390 °C Chlorobenzene 1.3 61.0 28 °C 12 mbar 590 °C Cyclohexane 1.0 35.1 – 18 °C 104 mbar 260 °C Cyclopentane 1.4 40.9 – 51 °C 346 mbar 320 °C Diethylether 1.7 52.5 – 40 °C 586 mbar 175 °C Dimethylether 2.7 51.9 Gas Gas 240 °C 1.4-Dioxane 1.9 69.7 11 °C 38 mbar 375 °C Epichlorohydrin 2.3 88.6 28 °C 16 mbar 385 °C Ethanol 3.1 59.5 12 °C 58 mbar 400 °C Ethylene 2.4 28.1 Gas Gas 440 °C Ethyl acetate 2.0 73.4 – 4 °C 98 mbar 470 °C Ethyl benzene 1.0 44.3 23 °C 10 mbar 430 °C Ethylene oxide 2.6 47.8 Gas Gas 435 °C n-Hexane 1.0 35.9 – 22 °C 160 mbar 240 °C Hydrogen 4.0 3.3 Gas Gas 560 °C Methane 4.4 29.3 Gas Gas 595 °C Methanol 6.0 80.0 9 °C 129 mbar 440 °C Methyl chloride 7.6 159.9 Gas Gas 625 °C Methylethyl ketone 1.5 45.1 – 10 °C 105 mbar 475 °C Methyl methacrylate 1.7 70.9 10 °C 40 mbar 430 °C n-Nonane 0.7 37.4 31 °C 5 mbar 205 °C n-Octane 0.8 38.1 12 °C 14 mbar 205 °C n-Pentane 1.4 42.1 – 40 °C 562 mbar 260 °C Propane 1.7 31.2 Gas Gas 470 °C i-Propanol 2.0 50.1 12 °C 43 mbar 425 °C Propylene 1.8 31.6 Gas Gas 485 °C Styrene 1.0 43.4 32 °C 7 mbar 490 °C Toluene 1.1 42.2 6 °C 29 mbar 535 °C * Flashpoint is defined for liquids only, vapour pressure at 20 °C reasonable for liquids only
  • 8. 08 | Avoiding effective ignition sources – secondary explosion protection Without source of ignition no danger of explosion If the formation of an ignitable atmosphere cannot safely be averted or cannot effectively be prevented (e.g. by using gas detection systems), electrical instruments being used in this area shall not act as a source of ignition: They need to be designed such that they cannot inflame these flammable atmospheres. TYPES OF PROTECTION Four of seven standardized types of protection are applied in the gas detection technology: Flame- proof (d), intrinsic safety (i), encapsulation (m), and increased safety (e). By encapsulation hot surfaces and sparks are prevented mechanically whereas in intrinsically safe instruments this is practiced by electrical power limiting. Generally flameproof accepts internal explosions but is designed such that it withstands the internal explosion pressure and reliably avoids a flashback. Increased safety is limited to passive devices such as junction boxes, terminals and cable glands. These are designed such that the risk of forming hot surfaces or sparks is highly reduced. Explosion protected instruments have to be type approved and certified by a Notified Body. EXPLOSION PROTECTION IS A LAW In Europe explosion protection has become law by converting the EU-directives 94/9/EC and 99/92/EC, also known as ATEX 95 and ATEX 137, into national ordinances. Manufacturers of explosion protected instruments have to mark these devices unitarily by a device category showing the permissi- ble application range, whereas the user of these instruments is pledged to classify the potentially explosive atmosphere area into zones depending on the probability of occurrence of flammable atmospheres and the nature of flammable matter: gases or vapours (G) or dust (D). For example II 2 GD is a typical device category for instruments which may be used in zone 1 and zone 2 as well as in zone 21 and 22, while instruments being used in zone 2 must have a marking of II 3 G at least. In the USA explosion protection is regulated by the NEC 505, the relevant marking also implies application hints by terms like Class and Division. In the USA instruments using either flameproof or intrinsically safe methods of protection are pre- ferred. In most countries the European or American explosion protection standards are accepted. Recently there has been a drive towards the IEC-Ex protection standards, which is based on world-wide IEC explosion protection standards. Dräger gas detection instruments meet the explosion protection requirements of CENELEC (ATEX, Europe), UL (USA), CSA (Canada) and IEC-Ex (world-wide). ST-4940-2004
  • 9. | 09 STL-296-2007 ST-9025-2005 ASSIGNMENT OF TEMPERATURE CLASSES AND EXPLOSION GROUPS AND TYPICAL GASES AND VAPOURS Temperature class Explosion group and max. permissible IIA IIB IIC surface temperature ignition energy greater 0.18 mJ ignition energy 0.06 to 0.18 mJ ignition energy smaller 0.06 mJ T1 450 °C Acetone, Ammonia, Benzene, Hydrogen cyanide, Town gas Hydrogen Ethyl acetate, Methane, Methanol, Propane, Toluene T2 300 °C i-Amyl acetate, n-Butane, n-Butanol, 1.3-Butadiene, 1.4-Dioxane, Acetylene 1-Butene, Propyl acetate, i-Propanol, Ethylene, Ethylene oxide Vinyl chloride T3 200 °C Amyl alcohol, Gasolines, Dimethylether, Ethyl glycol, Diesel fuel, Fuel oil, n-Hexane Hydrogen sulfide T4 135 °C Acetaldehyde Diethylether T5 100 °C T6 85 °C Carbon disulfide Example: If a potentially explosive atmosphere is caused by Carbon disulfide, an electrical apparatus is only suitable to be operated in this atmosphere if it is marked by IIC and T6, whereas for n-Hexane atmospheres electrical devices with the marking IIA T3 are sufficiently protected. II 2 GD Type-approved acc. to 94/9/EC Device category II (2) G Type-approved acc. to 94/9/EC Device category Explosion protected Ex dem IIC T4 Type of protection Explosion group Temperature class Explosion protected Ex ib IIC T4 Type of protection Explosion group Temperature class Typical marking of a gas detection transmitter acc. to 94/9/EC: Apparatus for zone 1, 2, 21 and 22. Typical marking of a safety barrier or a performance approved central controller with electrical connections into the hazardous area (zone 1 or 2), but not to be operated in the hazardous area. Typical explosion protection marking of an electrical apparatus (e.g. gas detection transmitter). Marking of an apparatus acc. to IEC-Ex. Devices marked like this are only allowed to be operated in countries not belonging to the European Community.
  • 10. 10 | ST-297-2007 Warning sign mandatory Warning sign mandatory for places where explosive atmospheres may occur (zones). Organizational meas- ures have to be regarded. ST-1580-2007
  • 11. | 11 According to the directive 99/92/EC (ATEX 137) the operator has to conduct a risk assessment of the hazardous area and to classify the area into zones depending on the probability of the occurrence of potentially explosive atmospheres. Also, he has to arrange organizational safety measures and provide evidence by means of an explosion protection document accordingly. Only suitable instruments may be used in certain zones. Employing the use of gas detection systems which reliably prevent the occurrence of an ignitable atmosphere, by default reduces the probability that a flammable atmosphere can occur at all; it is not likely to occur in normal operation – and this is defined as zone 2. In other words: By means of a suitable gas detection system a zone 1 area converts to a zone 2 area where less complex designed and mostly less expensive instruments may be used (e.g. lamps, machines, mobiles, fork lifters etc.) An important requirement however is that the counter measures activated by the gas detection system are adequately preventing the formation of flammable concentrations. This might not be the case in the direct vicinity of a gas leak if the gas is more quickly released than removed or diluted by the ventilation. But although the proximal area around a leak keeps being zone 1, the zone 1 area shrinks drastically by using a gas detection system – a great advantage for the customer. The hazardous areas shrink: Zone 1 becomes zone 2. By means of gas detection systems the probability of a formation of explosive atmospheres is reduced DEFINITION OF ZONES ACC. TO DIRECTIVE 99/92/EC Hazardous places are classified in terms of zones on the basis of the Minimum requirement Zone frequency and duration of the occurrence of an explosive atmosphere for device category Gas 0 A place in which an explosive atmosphere consisting of a mixture with air of II 1G flammable substances in the form of gas, vapour or mist is present continuously, or for long periods or frequently 1 A place in which an explosive atmosphere consisting of a mixture with air or II 2G flammable substances in the form of gas, vapour or mist is likely to occur in normal operation occasionally 2 A place in which an explosive atmosphere consisting of a mixture with air of II 3G flammable substances in the form of gas, vapour or mist is not likely to occur in normal operation but, if it does occur, will persist for a short period only Dust 20 A place in which an explosive atmosphere in the form of a cloud of combustible II 1D dust in air is present continuously, or for long periods or frequently 21 A place in which an explosive atmosphere in the form of a cloud of combustible II 2D dust in air is likely to occur in normal operation occasionally 22 A place in which an explosive atmosphere in the form of a cloud of combustible II 3D dust in air is not likely to occur in normal operation but, if it does occur, will persist for a short period only Example: If an apparatus shall be operated in zone 21, the relevant marking must at least be device category II 2D Hazardous Areas
  • 12. 12 | Proven in gas detection since decades: Pellistor sensors and Infrared sensors. PELLISTOR SENSORS The pellistor sensor (or catalytic bead sensor) is a relatively inexpensive flameproof sensor the measuring principle of which is based on a chemical reaction with oxygen and thus needs at least 12 % v/v. Without oxygen the pellistor sensor cannot give a reading, but also – because of oxygen deficiency – there is no danger of explosion. The pellistor sensor measures multiple gases and vapours, but with different sensitivity. If the sensitivity for a substance is too low the pellistor sensor may not be the correct measuring principle for a reliable gas detection system. Infrared sensors may be more applicable. Catalytic bead principle The heat-of-reaction measuring principle is based on the fact that flammable gases and vapours even below their LEL-concentration can undergo a flameless oxidation reaction with atmospheric oxygen, if only a suitable hot catalyst is present. The additional released heat of reaction is a measure for the gas concentration. The pellistor sensor houses two small measuring beads called pellistors (artificial term coming from pellet and resistor), because they are used as pre- cisely measuring temperature-dependent resistors. Both the pellistors are made of very porous ceramic material embedding a small platinum wire coil. The active pellistor additionally contains catalytic material. By means of an electrical current of approx. 270 mA on the one hand the platinum coil heats up the ceramic bead to ca. 450 °C, on the other hand the platinum coil acts as a measuring Active pellistor (shown in half cut, schematic) The penetrating methane molecule reacts by means of the heated catalytic bead material with atmospheric oxygen to form water vapour and carbon dioxide. The released heat of reaction causes a measurable resistance increase of the embedded platinum coil. ST-1581-2007 Using Gas Detection Systems
  • 13. | 13 INFRARED SENSORS In contrary to the catalytic bead sensors the infrared sensors, which are based on a pure physical measuring principle, are not prone to be poisoned and do not depend on oxygen content for measurement. By means of tight optical windows infrared sensors are separated from the gas to be detected. Infrared sensors, however, may have extremely different sensitivities to different gases and vapours, and some flammable substances such as vinyl chloride or acetonitrile are, against one’s expectations, not detectable at all. The Dräger application laboratory is very experienced and has worked out sensitivity data for more than 300 gases and vapours for different IR transmitters. The IR measuring principle is based on the fact that molecules of flammable gases and vapours except a few (e.g. H2, NH3, CO, CS2, HCN, H2S, and hydrides) are mostly hydrocarbons, the CH-bonding of which can be excited to vibration by certain wave-lengths (frequencies) of the IR-spectrum and thus absorb energy. If IR is radiated into an optical system filled with an IR-absorbing gas, an increase of IR-absorption might be detectable in a certain wavelength range, because normal air does not absorb IR. The generation of a stable spectrum of near infrared radiation is easily practiced by glow lamps operated by under-voltage, whereas the design of a wavelength-specific IR measuring detector is way more complex: Pyro-electric crystals, encapsulated behind an optical interference filter produce very resistor dependent on the bead’s temperature. When molecules of a flammable gas penetrate into a catalytic bead they react with the activated atmo- spheric oxygen which is absorbed in the porous ceramic and resultant heat of reaction increases the pellistor’s temperature e.g. by about 2 °C for 10 %LEL octane. The resulting increase of the pellistor’s resistance is in the magnitude of some milli-Ohms and is proportional to the gas concentration. Environmental conditions The increase of temperature, dependent of the gas concentration, however, can only be used as a measurement signal if changes of ambient temper- ature, which might be much greater, are compen- sated. This is realized by a second pellistor, which in opposite to the described one does not contain catalytic material and thus is measuring only the ambient temperature. As part of a Wheatstone bridge this passive pellistor compensates for environmental influences, especially for ambient temperature. For optimized behaviour both the pellistors must fit best concerning their measuring parameters, and they are accordingly matched to pairs during manufacturing. Poison resistance For many decades the pellistors manufactured by Dräger are of type PR, which means poison resist- ant. Based on their special construction the sensors have a longer lifetime compared to conventional sensors when being exposed to industrial atmospheres containing catalyst poisons such as sulphur-, phosphor-, lead- or silicone-compounds. ST-9068-2005 ST-725-2002
  • 14. small intensity depending voltage changes when being exposed to pulsating radiation. These voltage changes are amplified, linearized and finally converted to a 4 to 20-mA-signal which is proportional to the gas concentration. But not only gas reduces the measurable IR intensity, but also a contamination of the optical system by dust or mud causes intensity attenuation. This effect is compensated by a second IR measuring detector (reference detector), which gets the optical information by a beam splitter and detects the IR intensity in a wavelength range where flammable gases do not absorb IR. If both the measuring detector and the reference detector indicate an IR-absorption this is not caused by a gas but e.g. by dusty reflectors or else. By this way of compensation the sensor signal becomes contamination resistant, and at a certain degree of contamination additionally a beam block signal or maintenance signal can be generated. With the Dräger Polytron IR type 334 or 340 also possible alterations of the IR-detectors are compensated by a second IR source (“4-beam-compensation- method”). The greater the optical system, the more gas molecules are involved, and the higher is the IR-absorption. And by using greater optical systems lower measuring ranges such as e.g. 10 % of the LEL can be realized to detect leakages at a very early stage. | 14 IR-transmitter The fact that under normal conditions (no IR- absorbing gas) there is a high measuring signal, makes it possible to implement self diagnostic processes: The IR-transmitter is able to detect if e.g. the IR source fails or the optical system is blocked. The transmitter is fail-safe in the context of the IEC/EN 61508 standard and thus is suitable to be used in SIL2-rated safety chains. Dräger Polytron IR Ex Schematic design (2-beam compensation method). ST-1582-2007 Only the green part of the light radiation is filtered out and its intensity measured. If a gas absorbs the green part of the light radiation, its intensity is measurably reduced. ST-1148-2008ST-1149-2008 Dräger Polytron IR type 334 Schematic design (4-beam compensation method). ST-1583-2007 ST-3919-2004 ST-3719-2003
  • 15. 15 | Only by proper calibration and sensor positioning a gas detection system’s reliability is ensured CALIBRATION Only by calibration with the target gas (“gas to be detected”) the gas detection transmitter is enabled to give an individual gas concentration reading. If several gases or vapours are to be detected the transmitter has to be calibrated for the substance which it is least sensitive to. The properly performed calibration procedure is essential for the reliability of a gas detection system. SENSOR POSITIONING Please refer also to the IEC/EN 60079-29-2, chapter 8 – Criteria for the placement of sensors and sampling points. There are three different sensor placement strategies: 1. Spot monitoring: The potential sources of leak (e.g. valves, filling nozzles, flanges, bellows) are well-known and locatable. So sensors can be placed such that gas leaks can be detected very early and reliably. 2. Area monitoring: The potential sources of leak are spread across a large area and are not locatable (e.g. in hazardous goods stores). Thus the sensors should be positioned more or less equidistantly across the entire area. 3. Fence monitoring: The potential sources of leak are not locatable and there are no ignition sources in the area. Thus sensors are positioned at the outer limit to monitor for hazardous gas concentrations crossing into neighbouring areas. Besides the operational experience of the local plant engineers concerning sensor positioning also the IEC/EN 60079-29-2 “Guide for selection, installation, use and maintenance of apparatus for the detection and measurement of combustible gases or oxygen” contains a lot of advices to place gas sensors properly. It seems to be trivial, but one thing is essential to know when designing a gas detection system: A gas detector can only detect a gas which is in the direct vicinity and which can enter the sensor’s elements. So it has to be considered that vapours of flammable liquids are always heavier than air and spread across the floor rather than rising up, and they even might condensate in other locations if the temperature decreases. Also, vapours of flammable liquids cannot form combustible concentrations if the ambient temperature is lower than the flash- point. Gas detection transmitters for the detection of flammable vapours and heavy flammable gases (especially propane and butane belong to this group) should be placed where these substances might accumulate, as low as possible above the ground and/or below the leak. On the other hand three gases are well known which are very much lighter than air: Hydrogen, methane, and ammonia. Commonly these gases will rise under normal conditions, and sensors should be placed above the leak. Methane n-Hexane n-Nonane Ethylene Ethyl acetate Hydrogen n-Octane Toluene n-Pentane Acetone Propane 100 90 80 70 60 50 40 30 20 10 0 0 10 20 30 40 50 60 70 80 90 100 %LEL %LEL Methanol Ethoxypropanol Ethyl acetate n-Butyl acetate Cumene Methane Diethylether Acetone Propane 100 90 80 70 60 50 40 30 20 10 0 0 10 20 30 40 50 60 70 80 90 100 %LEL %LEL Pellistor sensor Different sensitivities of a Propane-calibrated pellis- tor sensor (schematic): 50 %LEL n-Nonane cause a measuring value of only 23 %LEL Propane while 50 %LEL Ethylene cause a measuring value of 62 %LEL. Infrared sensor Different sensitivities of a Propane-calibrated infrared sensor (Dräger Polytron IR Ex, schematic): 50 %LEL Ethyl acetate cause a measuring value of only 22 %LEL Propane while 50 %LEL Methanol cause a measuring value of 76 %LEL. A Propane- calibrated IR Ex is relative insensitive to Methane. Hydrogen cannot be detected at all by IR-technique. ST-1592-2007 ST-1593-2007
  • 16. Gas detection systems 16 | Central Controllers – Centers for your Safety Generally gas detection systems consist of explosion protected remote transmitters (gas detection transmitters), which are installed in the hazardous area, a central controller unit installed in the safe area to process the sensor signals and to trigger alarms and counter measures, and optical and audible alarm devices which also might be installed in the hazardous area. CENTRAL CONTROLLER UNITS Central controller units are installed in the non- hazardous area, and on the one hand they supply the connected gas detection transmitters with the necessary voltage, on the other hand they receive their measuring signals and status-information to process and indicate them. If pre-adjusted alarm thresholds are exceeded central controllers are to trigger alarms reliably. To have a high availability central controllers often are equipped also with an emergency power supply. Central controllers might be small single-channel- units for the connection of only one transmitter as well as complete cabinets with built-in device racks for many plug-in modules (channel modules) connected to many transmitters, and with customized wired alarm circuits. The channel modules mostly provide several relays with voltage-free contacts. Depending on whether the relays are energized in normal operation or in case of alarm, the voltage-free contacts can be configured as NO-contacts (normally open = closed in case of alarm) or NC-contacts (normally closed - open in case of alarm). For primary protection systems at least one relay for device alarm must be energized in normal operation (fail-safe principle) so that a mains power breakdown can be detected. Furthermore, for relays having a safety function it is recommended that these relays are also fail-safe (de-energized in case of alarm or power-off). The relay contacts – if necessary upgraded by additional relays to have redundant contacts – can be used to activate counter measures (ventilation on/off, ventilation flap open/close, gas supply on/off, shutdown activation, etc.) and for optical alarms, to keep the operator informed about the alarm condition even after having switched off the audible alarm. Switch-off means acknowledgement, and in parallel to the automatic measures the customer has to conduct organizational measures if necessary. Furthermore a gas detection system often provides 4 to 20-mA-outputs (“signal repeaters”), e.g. to print-out or visualize the current gas concentrations for documentation purposes. Especially the modular concept of the central con- troller Dräger REGARD offers numerous possibili- ties for customized design: Various combinations of Dräger REGARD Ex and 4 to 20-mA-modules, Master card for the acknowledgment of special alarm configurations and connections to PLCs, HART card as well as a ModBus-Gateway card for BUS-connection to process control systems and PCs with 32-bit operating systems for measurement display and data-logging. Hazardous area (e.g. zone 1) Safe area Gas detection transmitters detect a high vapour concentration The cloud of vapour concentration is diluted and removed by fresh air Activated by the gas detection system the ventilator injects fresh air Leak evaporates As a counter measure the ventilation is switched on Central controller realizes high vapour concentration and triggers alarms Visible alarm Audible alarm II (2) G II 2G II 2G II 2G ST-1594-2007
  • 17. | 17 Gas detectors Based on catalytic bead sensor technology as well as infrared sensor technology Dräger offers a wide range of different gas detectors for the detection of flammable gases and vapours. ST-5003-2004 ST-6056-2004 GAS DETECTORS ST-1389-2006 ST-5675-2004 Dräger PEX 3000 4 to 20-mA-transmitter with pellistor sensor, with built-in explosion protected 4 to 20-mA-converter, 7-segment- display and 2-key-operation (for calibration) to be connected to central controllers with 4 to 20-mA-inputs. ST-5669-2004 Dräger Polytron SE Ex Sensing head without electro- nics with pellistor sensor and mV-measuring signal to be connected to special central controllers, measuring range 0 to 100 or 0 to 10 %LEL, also as high temperature version for up to 150 °C. Dräger Polytron FX and Dräger Polytron 2 XP Ex 4 to 20-mA-transmitter with pellistor sensor or IR-sensor (optional), flameproof housing, with display and magnetic wand operation, ATEX- or UL-approved, to be connected to central con- trollers with 4 to 20-mA-inputs. ST-3833-2003 ST-8821-2005 DrägerSensor IR Explosion protected transmitter with IR-sensor in flameproof housing, similar to Dräger PIR 3000, but with pellistor-sensor- emulation for replacement of pellistor sensors, with mV-output to be connected to special central controllers. ST-11659-2007 Dräger PIR 7000 Explosion protected robust IR-transmitter with IR-sensor in flameproof stainless steel housing for central controllers with 4 to 20-mA-input, suitable for safety related systems acc. to SIL2, certified following IEC 61508, ATEX,- IECEx- and UL-approved. Dräger Polytron Ex Explosion protected transmitter for pellistor sensor, with intrinsically safe current circuits (LC-display, sensor connection, operating facilities) to be connected to central controllers with 4 to 20-mA-inputs. ST-5643-2004 ST-5651-2004 Dräger Polytron IR type 334 and type 340 Explosion protected robust IR- transmitter with IR-sensor in flame- proof stainless steel housing for central controllers with 4 to 20-mA- input, suitable for safety related systems acc. to SIL2, with HART and RS 485, ATEX- or UL-approved. ST-8822-2005 Dräger PIR 3000 Explosion protected transmitter with IR-sensor in flameproof housing, to be connected to central controllers with 4 to 20-mA-input, ATEX-, IECEx- and UL-approved. Dräger Polytron IR Ex Explosion protected transmitter with IR-sensor, with intrinsically safe current circuits (LC-display, sensor connection, operating facilities) to be connected to central controllers with 4 to 20- mA-inputs, with open or closed optical system, different versions. ST-3932-2005 Dräger Polytron Pulsar Explosion protected Open Path gas detector for the detection of a gas concentration along a line of sight of up to 200 m.
  • 18. | 18 Central controllers Based on different concepts, on the one hand device rack with channels modules or DIN-rail mounted con- trollers both to be installed in wall housings or cabinets, on the other hand stand-alone controller units in IP65- protected ABS-enclosures, Dräger offers controllers with different properties, which – in combination with suitable gas detectors – are dedicated for the reliable gas detection in the field of explosion protection. ST-7448-2006 ST-478-2004 CENTRAL CONTROLLERS 48658 Dräger Polytron Controller Device racks for max. 2, 5, or 12 different channel modules and one acknowledgement module, to be installed in cabinets, panels or wall housings. Channel modules with bar graph display and LED status information, three configurable relays per module. ST-335-2004 Dräger REGARD 1 Stand-alone single channel controller with ABS-enclosure, with LC display and status LEDs, configurable for SE Ex sensing heads as well as 4 to 20-mA-transmitters, five relays, three alarm thresholds and battery back-up. ST-5647-2006 ST-340-2004ST-272-2004ST-5738-2006 Dräger REGARD 2410 Central controller to be clipped on a DIN-rail for the connection of four transmitters max. Dräger REGARD 2400 Stand-alone central controller for wall mounting to be operated with four transmitters max. Dräger REGARD System Device rack to take up 16 different modules, to be installed in cabinets, panels, or wall housings. Channel modules with 4 digit matrix displays and operation push buttons for configuration. Dräger REGARD 3900 Stand-alone central controller with ABS- enclosure for 1 to 16 channels, with LC display and four status LEDs for each channel, fully configurable via laptop or PC to operate with 4 to 20-mA-transmitters.
  • 19. 19 | Explosion Protection by Dräger Gas Detection Technology EXPLOSION PROTECTION WITH DRÄGER Dräger gas detection technology means sensors, transmitters, central controllers and competent support – our system engineers will design a specific gas detection system for your application. The product portfolio of Dräger gas detection transmitters encompass numerous different types: – catalytic bead or infrared sensor technology – point- or open-path-detection – increased safety, intrinsic safety, or flameproof – analogue 4-20-mA-signal, mV signal or digital HART or RS 485 signal – with or without display at site – with or without onboard relays – low budget or high end equipment Select between different central controllers for your special explosion protection application: – for mV-signal or 4 to 20-mA-signal – single-channel or multi-channel controllers – device racks for cabinet installation or stand- alone type with ABS-housing – with or without digital communication – manually or PC-supported configuration Dräger REGARD 3900 Stand-alone central controller with ABS-enclosure for up to 16 channels. ST-272-2004 Dräger REGARD A representative customized gas detection system. ST-523-98 Tel: +44 (0)191 490 1547 Fax: +44 (0)191 477 5371 Email: northernsales@thorneandderrick.co.uk Website: www.heattracing.co.uk www.thorneanderrick.co.uk