Air Sealing, Insulation,
& Thermal Bypass
How heat flows in a
building:
Air Leakage - need an air
barrier to stop flow.
Transmission - need insulation
to stop flow
What is a Building Envelope?
The pressure boundary (air barrier)
AND
The thermal boundary of the house
(insulation)
These must be continuous around the
entire conditioned space
What is a Thermal Bypass?
When heat, air and moisture “bypass” the
thermal envelope of a building due to
missing insulation or air barriers.
Insulation must have an air barrier
touching it on all sides. The exception
is at vented ceilings where only a
barrier between the attic and
conditioned space is required.
Where is the Building Envelope?
• Basement?
• Enclosed porch?
• Attic?
• Where are the ducts?
• Where is the heating system?
• Potential health and safety
concerns
• NEVER the garage
• Designers should examine the drawings and
determine the location of the envelope.
Air Barrier
The Air Barrier:
• Limits air flow between inside and outside
• More difficult to identify
• Not always where you think it is
• Blower door is used to
measure how tight the air
barrier is.
7
BUILDING SCIENCE BASICS
The Thermal Boundary:
• Limits heat flow between inside and outside
• Easy to identify by presence of insulation
• The location of insulation in relation to other
building components is critical to its
effectiveness
• Even small areas of
missing insulation are
very important
• Voids of 7% can
reduce effective R-value
by almost 50%
What Insulation Does
Primary:
Slows down heat flow
measured by R-value
Secondary:
Control air leakage
Control convective loops
(which is a function of it’s density)
Control water vapor
(measured in perm rating)
Cavity Mineral Fiber Batts
Reduce Heat Flow: fair
Control Air Leakage: poor
Control Convective Loops: poor
Control Water Vapor: poor
Dirty insulation is
evidence of air
movement.
Blown / Spray Mineral Fiber
Reduce Heat Flow: good
Control Air Leakage: fair
Control Convective Loops: fair
Control Water Vapor: poor
Blown / Spray Cellulose and Cotton
Reduce Heat Flow: good
Control Air Leakage: good
Control Convective Loops: good
Control Water Vapor: poor
Open Cell (1/2 lb.) Spray Polyurethane
Reduce Heat Flow: good
Control Air Leakage: good
Control Convective Loops: great
Control Water Vapor: depends
Closed Cell (2 lb.) Spray Polyurethane
Reduce Heat Flow: great
Control Air Leakage: great
Control Convective Loops: great
Control Water Vapor: great
Expanded Polystyrene Boards
Reduce Heat Flow: good
Control Air Leakage: great
Control Convective Loops: great
Control Water Vapor: great
Extruded Polystyrene
Reduce Heat Flow: good
Control Air Leakage: great
Control Convective Loops: great
Control Water Vapor: great
Polyisocyanurate
Reduce Heat Flow: great
Control Air Leakage: great
Control Convective Loops: great
Control Water Vapor: great
R-value
is the resistance a material shows to heat flow across
it. Larger numbers show better insulation values.
It must be a tested value from a government lab,
NOT a claimed “effective” value by the manufacturer.
How Is Insulation Measured?
R-value
Radiant barrier products claim that R-value only
measures conductive heat flow and ignores convection
and radiation. In fact, R-values include all three.
Making it a useful way to compare products.
How Is Insulation Measured?
Typical R-Values
Open Cell Foam R- value 3.6/inch
Closed cell Foam R-value 6.5/inch
What Influences the
Performance of Insulation
R value - higher is better
How much air can flow through it
(air impermeability)
Installation - 4% gaps can lead to
30% less effectiveness
Convection heat loss
Insulation Problems
Caused By Poor Installation
Vented vs. non-vented roofs
• 2006 IRC (not the IECC) section R806.4
• Allows for unvented roofs if “air-
impermeable” insulation can be used in
contact with the roof sheathing.
• “air-impermeable” is defined – but
basically it meets the requirements for
an air barrier.
• Spray foam and rigid foam meet the
standard, but cellulose does not.
Vented vs. non-vented roofs
• Section R806.4 allows for a combination
of air-impermeable insulation and air-
permeable insulation as follows:
In climate zones, 5,6, 7 and 8 any air-
impermeable insulation shall be a vapor
retarder, or shall have a vapor retarder
coating or covering in direct contact with
the underside of the insulation.
Vented vs. non-vented roofs
 Either items 5.1, 5.2 or 5.3 are met
depending on the air impermeability of
the insulation directly under the
structural roof sheating.
5.1 Air-impermeable insulation only (rigid
or spray foam) shall be applied in direct
contact with the underside of the
structural roof sheathing to the value in
table R806.4
Vented vs. non-vented roofs
5.2. Air-permeable insulation only must
also include air-impermeable insulation
(rigid board or spray foam) shall be
installed directly ABOVE the structural
roof sheathing as specified in Table
R806.4
5.3. Air-impermeable and air-permeable
insulation. The Air-impermeable shall be
applied in direct contact with the
underside of the structural roof sheathing
Vented vs. non-vented roofs
3. cont….as specified in Table R806.4 for
condensation control. The air-permeable
insulation shall be installed directly under
the air-impermeable insulation.
Vented vs. non-vented roofs
If you insulate with certain types of foam, thick insulation
puts the planet at greater risk than thin insulation!
Download from www.greenbuildingadvisor.com
Choose Palo Santo Designs
for your Custom Home Project
Palo Santo Designs LLC is an Award Winning General
Contractor in Santa Fe, specializing in the design and
construction of Fine Custom Homes, Renovations and
Distinctive Commercial Spaces. Our experience is
unsurpassed in the design and construction of high
performance buildings, utilizing the most effective
methods for energy and water efficiency, sustainability
and comfort. Contact us at palosantodesigns.com.

More Related Content

Viewers also liked

Tutor l1 cavity wall construction
Tutor l1 cavity wall constructionTutor l1 cavity wall construction
Tutor l1 cavity wall constructionLuke D'Arcy
 
Teri, bangalore & solar passive techniques(rupesh)
Teri, bangalore & solar passive techniques(rupesh)Teri, bangalore & solar passive techniques(rupesh)
Teri, bangalore & solar passive techniques(rupesh)Rupesh Chaurasia
 
Green Building Case Study on TERI,bangalore.
Green Building Case Study on TERI,bangalore.Green Building Case Study on TERI,bangalore.
Green Building Case Study on TERI,bangalore.Vinay M
 
Chapter 8 duct design and sealing
Chapter 8 duct design and sealingChapter 8 duct design and sealing
Chapter 8 duct design and sealingsahiloct11969
 
Hvac Presentation
Hvac PresentationHvac Presentation
Hvac PresentationChoong KW
 

Viewers also liked (6)

Tutor l1 cavity wall construction
Tutor l1 cavity wall constructionTutor l1 cavity wall construction
Tutor l1 cavity wall construction
 
Teri, bangalore & solar passive techniques(rupesh)
Teri, bangalore & solar passive techniques(rupesh)Teri, bangalore & solar passive techniques(rupesh)
Teri, bangalore & solar passive techniques(rupesh)
 
Green Building Case Study on TERI,bangalore.
Green Building Case Study on TERI,bangalore.Green Building Case Study on TERI,bangalore.
Green Building Case Study on TERI,bangalore.
 
ADVANTAGES OF CAVITY WALLS
ADVANTAGES OF CAVITY WALLSADVANTAGES OF CAVITY WALLS
ADVANTAGES OF CAVITY WALLS
 
Chapter 8 duct design and sealing
Chapter 8 duct design and sealingChapter 8 duct design and sealing
Chapter 8 duct design and sealing
 
Hvac Presentation
Hvac PresentationHvac Presentation
Hvac Presentation
 

Recently uploaded

9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 60009891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000teencall080
 
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579diyaspanoida
 
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.riyadelhic riyadelhic
 
Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...
Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...
Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...Sheetaleventcompany
 
VAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIRVAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIRNiteshKumar82226
 
Russian Call Girls in Goa %(9316020077)# Russian Call Girls in Goa By Russi...
Russian Call Girls  in Goa %(9316020077)# Russian Call Girls  in Goa By Russi...Russian Call Girls  in Goa %(9316020077)# Russian Call Girls  in Goa By Russi...
Russian Call Girls in Goa %(9316020077)# Russian Call Girls in Goa By Russi...Goa Call Girls Service Goa escort agency
 
Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.
Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.
Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.riyadelhic riyadelhic
 
CALL GIRLS 9999288940 women seeking men Locanto No Advance North Goa
CALL GIRLS 9999288940 women seeking men Locanto No Advance North GoaCALL GIRLS 9999288940 women seeking men Locanto No Advance North Goa
CALL GIRLS 9999288940 women seeking men Locanto No Advance North Goadelhincr993
 
+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...teencall080
 
Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...
Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...
Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...aakahthapa70
 
Girls For Night in Islamabad | 03274100048 🔞
Girls For Night in Islamabad | 03274100048 🔞Girls For Night in Islamabad | 03274100048 🔞
Girls For Night in Islamabad | 03274100048 🔞Ifra Zohaib
 
Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848Ifra Zohaib
 
DIGHA CALL GIRL 92628/1154 DIGHA CALL GI
DIGHA CALL GIRL 92628/1154 DIGHA CALL GIDIGHA CALL GIRL 92628/1154 DIGHA CALL GI
DIGHA CALL GIRL 92628/1154 DIGHA CALL GINiteshKumar82226
 
Radhika Call Girls In Jaipur 9358660226 Escorts service
Radhika Call Girls In Jaipur 9358660226 Escorts serviceRadhika Call Girls In Jaipur 9358660226 Escorts service
Radhika Call Girls In Jaipur 9358660226 Escorts servicerahul222jai
 
KAKINADA CALL GIRL 92628/71154 KAKINADA C
KAKINADA CALL GIRL 92628/71154 KAKINADA CKAKINADA CALL GIRL 92628/71154 KAKINADA C
KAKINADA CALL GIRL 92628/71154 KAKINADA CNiteshKumar82226
 
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...riyasharma00119
 
Call US Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...
Call US  Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...Call US  Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...
Call US Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...Pooja Nehwal
 
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...aakahthapa70
 

Recently uploaded (20)

9953056974 Call Girls In Ashok Nagar, Escorts (Delhi) NCR.
9953056974 Call Girls In Ashok Nagar, Escorts (Delhi) NCR.9953056974 Call Girls In Ashok Nagar, Escorts (Delhi) NCR.
9953056974 Call Girls In Ashok Nagar, Escorts (Delhi) NCR.
 
Call Girls In Goa For Fun 9316020077 By Goa Call Girls For Pick Up Night
Call Girls In  Goa  For Fun 9316020077 By  Goa  Call Girls For Pick Up NightCall Girls In  Goa  For Fun 9316020077 By  Goa  Call Girls For Pick Up Night
Call Girls In Goa For Fun 9316020077 By Goa Call Girls For Pick Up Night
 
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 60009891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
 
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
 
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
 
Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...
Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...
Call Girl Rohini ❤️7065000506 Pooja@ Rohini Call Girls Near Me ❤️♀️@ Sexy Cal...
 
VAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIRVAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIR
 
Russian Call Girls in Goa %(9316020077)# Russian Call Girls in Goa By Russi...
Russian Call Girls  in Goa %(9316020077)# Russian Call Girls  in Goa By Russi...Russian Call Girls  in Goa %(9316020077)# Russian Call Girls  in Goa By Russi...
Russian Call Girls in Goa %(9316020077)# Russian Call Girls in Goa By Russi...
 
Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.
Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.
Call Now ☎9870417354|| Call Girls in Noida Sector 12 Escort Service Noida N.C.R.
 
CALL GIRLS 9999288940 women seeking men Locanto No Advance North Goa
CALL GIRLS 9999288940 women seeking men Locanto No Advance North GoaCALL GIRLS 9999288940 women seeking men Locanto No Advance North Goa
CALL GIRLS 9999288940 women seeking men Locanto No Advance North Goa
 
+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9310611641 Russian Call Girls In New Delhi Independent Russian Call Girls...
 
Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...
Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...
Call Girls In {Connaught Place Delhi} 9667938988 IndianRussian High Profile E...
 
Girls For Night in Islamabad | 03274100048 🔞
Girls For Night in Islamabad | 03274100048 🔞Girls For Night in Islamabad | 03274100048 🔞
Girls For Night in Islamabad | 03274100048 🔞
 
Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848
 
DIGHA CALL GIRL 92628/1154 DIGHA CALL GI
DIGHA CALL GIRL 92628/1154 DIGHA CALL GIDIGHA CALL GIRL 92628/1154 DIGHA CALL GI
DIGHA CALL GIRL 92628/1154 DIGHA CALL GI
 
Radhika Call Girls In Jaipur 9358660226 Escorts service
Radhika Call Girls In Jaipur 9358660226 Escorts serviceRadhika Call Girls In Jaipur 9358660226 Escorts service
Radhika Call Girls In Jaipur 9358660226 Escorts service
 
KAKINADA CALL GIRL 92628/71154 KAKINADA C
KAKINADA CALL GIRL 92628/71154 KAKINADA CKAKINADA CALL GIRL 92628/71154 KAKINADA C
KAKINADA CALL GIRL 92628/71154 KAKINADA C
 
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
 
Call US Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...
Call US  Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...Call US  Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...
Call US Pooja📞 9892124323 ✅Call Girls In Mira Road ( Mumbai ) secure service...
 
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
 

Air Sealing and Insulation

  • 1. Air Sealing, Insulation, & Thermal Bypass
  • 2. How heat flows in a building: Air Leakage - need an air barrier to stop flow. Transmission - need insulation to stop flow
  • 3. What is a Building Envelope? The pressure boundary (air barrier) AND The thermal boundary of the house (insulation) These must be continuous around the entire conditioned space
  • 4. What is a Thermal Bypass? When heat, air and moisture “bypass” the thermal envelope of a building due to missing insulation or air barriers. Insulation must have an air barrier touching it on all sides. The exception is at vented ceilings where only a barrier between the attic and conditioned space is required.
  • 5. Where is the Building Envelope? • Basement? • Enclosed porch? • Attic? • Where are the ducts? • Where is the heating system? • Potential health and safety concerns • NEVER the garage • Designers should examine the drawings and determine the location of the envelope.
  • 6.
  • 7. Air Barrier The Air Barrier: • Limits air flow between inside and outside • More difficult to identify • Not always where you think it is • Blower door is used to measure how tight the air barrier is. 7 BUILDING SCIENCE BASICS
  • 8. The Thermal Boundary: • Limits heat flow between inside and outside • Easy to identify by presence of insulation • The location of insulation in relation to other building components is critical to its effectiveness • Even small areas of missing insulation are very important • Voids of 7% can reduce effective R-value by almost 50%
  • 9.
  • 10.
  • 11.
  • 12.
  • 13.
  • 14. What Insulation Does Primary: Slows down heat flow measured by R-value Secondary: Control air leakage Control convective loops (which is a function of it’s density) Control water vapor (measured in perm rating)
  • 15. Cavity Mineral Fiber Batts Reduce Heat Flow: fair Control Air Leakage: poor Control Convective Loops: poor Control Water Vapor: poor
  • 16. Dirty insulation is evidence of air movement.
  • 17. Blown / Spray Mineral Fiber Reduce Heat Flow: good Control Air Leakage: fair Control Convective Loops: fair Control Water Vapor: poor
  • 18. Blown / Spray Cellulose and Cotton Reduce Heat Flow: good Control Air Leakage: good Control Convective Loops: good Control Water Vapor: poor
  • 19. Open Cell (1/2 lb.) Spray Polyurethane Reduce Heat Flow: good Control Air Leakage: good Control Convective Loops: great Control Water Vapor: depends
  • 20. Closed Cell (2 lb.) Spray Polyurethane Reduce Heat Flow: great Control Air Leakage: great Control Convective Loops: great Control Water Vapor: great
  • 21. Expanded Polystyrene Boards Reduce Heat Flow: good Control Air Leakage: great Control Convective Loops: great Control Water Vapor: great
  • 22. Extruded Polystyrene Reduce Heat Flow: good Control Air Leakage: great Control Convective Loops: great Control Water Vapor: great
  • 23. Polyisocyanurate Reduce Heat Flow: great Control Air Leakage: great Control Convective Loops: great Control Water Vapor: great
  • 24. R-value is the resistance a material shows to heat flow across it. Larger numbers show better insulation values. It must be a tested value from a government lab, NOT a claimed “effective” value by the manufacturer. How Is Insulation Measured?
  • 25. R-value Radiant barrier products claim that R-value only measures conductive heat flow and ignores convection and radiation. In fact, R-values include all three. Making it a useful way to compare products. How Is Insulation Measured?
  • 26. Typical R-Values Open Cell Foam R- value 3.6/inch Closed cell Foam R-value 6.5/inch
  • 27. What Influences the Performance of Insulation R value - higher is better How much air can flow through it (air impermeability) Installation - 4% gaps can lead to 30% less effectiveness
  • 28.
  • 29.
  • 30.
  • 31. Convection heat loss Insulation Problems Caused By Poor Installation
  • 32.
  • 33.
  • 34.
  • 35.
  • 36. Vented vs. non-vented roofs • 2006 IRC (not the IECC) section R806.4 • Allows for unvented roofs if “air- impermeable” insulation can be used in contact with the roof sheathing. • “air-impermeable” is defined – but basically it meets the requirements for an air barrier. • Spray foam and rigid foam meet the standard, but cellulose does not.
  • 37. Vented vs. non-vented roofs • Section R806.4 allows for a combination of air-impermeable insulation and air- permeable insulation as follows: In climate zones, 5,6, 7 and 8 any air- impermeable insulation shall be a vapor retarder, or shall have a vapor retarder coating or covering in direct contact with the underside of the insulation.
  • 38. Vented vs. non-vented roofs  Either items 5.1, 5.2 or 5.3 are met depending on the air impermeability of the insulation directly under the structural roof sheating. 5.1 Air-impermeable insulation only (rigid or spray foam) shall be applied in direct contact with the underside of the structural roof sheathing to the value in table R806.4
  • 39. Vented vs. non-vented roofs 5.2. Air-permeable insulation only must also include air-impermeable insulation (rigid board or spray foam) shall be installed directly ABOVE the structural roof sheathing as specified in Table R806.4 5.3. Air-impermeable and air-permeable insulation. The Air-impermeable shall be applied in direct contact with the underside of the structural roof sheathing
  • 40. Vented vs. non-vented roofs 3. cont….as specified in Table R806.4 for condensation control. The air-permeable insulation shall be installed directly under the air-impermeable insulation.
  • 42. If you insulate with certain types of foam, thick insulation puts the planet at greater risk than thin insulation! Download from www.greenbuildingadvisor.com
  • 43. Choose Palo Santo Designs for your Custom Home Project Palo Santo Designs LLC is an Award Winning General Contractor in Santa Fe, specializing in the design and construction of Fine Custom Homes, Renovations and Distinctive Commercial Spaces. Our experience is unsurpassed in the design and construction of high performance buildings, utilizing the most effective methods for energy and water efficiency, sustainability and comfort. Contact us at palosantodesigns.com.