GIS-NESCL-6

DGM (Electrical maintenance) at NTPC-Simhadri Power Plant em NTPC Limited
26 de Oct de 2015
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
GIS-NESCL-6
1 de 51

Mais conteúdo relacionado

Mais procurados

Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,Gis ppt (gas insulated sub station)  deepak kumar kannaujiya,
Gis ppt (gas insulated sub station) deepak kumar kannaujiya,Sameer Kumar
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1Ronal Parmar
Gas insulated substationGas insulated substation
Gas insulated substationAjay Kuriakose
Gas insulated substationGas insulated substation
Gas insulated substationMOHDFAIZAN75
GAS INSULATED SUB-STATIONGAS INSULATED SUB-STATION
GAS INSULATED SUB-STATIONsujitmandalsk
Aldi widiartono gis eco efficient switchgearAldi widiartono gis eco efficient switchgear
Aldi widiartono gis eco efficient switchgearHariSantoso20

Mais procurados(20)

Destaque

FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARashwini kumar
Substation overviewSubstation overview
Substation overviewBHAGWAN PRASAD
Sub stations-air insulated substationsSub stations-air insulated substations
Sub stations-air insulated substationsbhanu lucky
Presentation for Seminar (fixed)Presentation for Seminar (fixed)
Presentation for Seminar (fixed)Ai' Chaq
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substationIshank Ranjan
33/11 kV substation (u.p.p.c.l.)33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)Prateek Agarwal

Similar a GIS-NESCL-6

Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxChapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxborapring
Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstationraja sukumar
Compact DC switch gearCompact DC switch gear
Compact DC switch gearVeenaVK
substation 101substation 101
substation 101danica11
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationIRJET Journal
GIS PRESENTATION.pdfGIS PRESENTATION.pdf
GIS PRESENTATION.pdfAyazAhmadKhan3

Mais de Nageswar Rao

roof top solarroof top solar
roof top solarNageswar Rao
Indian electricity market and power exchangesIndian electricity market and power exchanges
Indian electricity market and power exchangesNageswar Rao
Energy_conservation_paper_presentationEnergy_conservation_paper_presentation
Energy_conservation_paper_presentationNageswar Rao
Power Quality-Report-5Power Quality-Report-5
Power Quality-Report-5Nageswar Rao
CPRI-Power quality reportCPRI-Power quality report
CPRI-Power quality reportNageswar Rao
Power Quality-ReportPower Quality-Report
Power Quality-ReportNageswar Rao

GIS-NESCL-6

Notas do Editor

  1. The introduction of SF6 gas has revolutionized not only the technology of circuit breakers but also the layout of substations.
  2. 66kV bus provided for 5 no.s of bays
  3. Instead of SF6-to-air as connections into the substation as a whole, the nozzles on the circuit breaker enclosure are directly connected to the adjacent GIS module. The puffer-type technique was introduced for SF6 circuit breakers, wherein the relative movement of a piston and a cylinder linked to the moving part is used to generate the pressure rise necessary to blast the arc via a nozzle made of insulating material (Figure 1). In this technique, the pressure rise is obtained mainly by gas compression. To guarantee simultaneous interruption, the chambers are mechanically connected in series.
  4. CTs inside the enclosure must be shielded from the electric field produced by the high voltage conductor or high transient voltages can appear on the secondary through capacitive coupling. For CTs outside the enclosure, the enclosure itself must be provided with an insulating joint, and enclosure currents shunted around the CT. Both types of construction are in wide use.
  5. Use of fast (High speed) earth switch provides a parallel (low resistance) path to drain the residual static charge quickly, thereby protecting the instrument voltage transformer from the damages that may otherwise be caused. The basic construction of these earth switches is identical. -by direct current flowing through its primary as a consequence of charge stored online
  6. The lightning arrester protects the power utilities from overvoltage due to lightning or surges and prevents the utilities from breakdowns and blackouts.
  7. SF6 –Air Bushings used for connecting to open terminal equipment & Overhead transmission lines. CABLE TERMINATION (Fig -a) High-Voltage cables of various types are connected to SF6 switchgear via cable connection assembly & also it enables the GIS & Cables to be tested separated. Transformer connection(Fig -b) consists of Oil/SF6 bushing, the enclosure, the main circuit end terminal & removable connection. For Hi-Voltage test on GIS, transformer is isolated from switchgear by dismantling the removable connection
  8. The insulating and interrupting capability of the SF6 gas depends on the density of theSF6 gas. The pressure of the SF6 gas varies with temperature, so a mechanical or electronic temperature compensated pressure switch is used to monitor the equivalent of gas density.
  9. The weight and size of the GIS equipment do not change appreciably with the voltage class as the bulk of the current –carrying components and enclosures have identical dimensions for similar thermal and short time current. The additional insulation required for the next voltage class is achieved by increased gas density. Owing to these flexibilities, a few manufacturers offer the same equipment for two voltage classes like 170/145 kV. Even when the GIS equipment is designed for an individual voltage class, the dimensions and weights of the equipment differ marginally.
  10. International Council on Large Electric Systems (CIGRE) H-GIS: IEC 62271-205