00. switchgear protection and power systems_fm.pdf

  1. Distance protection Info - 1 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection 7SA522 and 7SA6 Productmanager Distance Protection Michael Claus EV S V 13 Nürnberg H Phone: +49 911 433 8261 Fax: +49 911 433 8301 Email: Michael.Claus@ev.siemens.de
  2. Distance protection Info - 2 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 - What it means SIPROTEC 4 is a family of numerical Protection, Control and Automation Devices from
  3. Distance protection Info - 3 EV S V13/ Claus/ 23.08.00 7SA522 7SA6 7SA510 7SA511 7SA513 SIPROTEC 4 Software System SIPROTEC 4 Hardware Platform Distance protection: Past and Present
  4. Distance protection Info - 4 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection 7SA522 and 7SA6 7SA522 + 7SA6 One family of distance protection for all voltage applications
  5. Distance protection Info - 5 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance protection 7SA61 + 7SA522  Protection  4-line display  MV, HV and EHV 7SA612 + 7SA522 7SA611 + 7SA522 7SA610 7SA63  Protection + local control  integrated graphic display  mainly MV 7SA632 7SA631 7SA64  Protection + local control  detached control panel  mainly MV 7SA642 7SA641 All core functions are available in all the housing versions
  6. Distance protection Info - 6 EV S V13/ Claus/ 23.08.00 17.10.97 en513all7 ANSI-No.  21, 21N  68  FL SIPROTEC 4 Distance Protection, Scope of functions (1)  Distance Protection  full scheme measurement with sophisticated loop selection  fast three phase and single phase tripping  with/without parallel line compensation  special filtering for CVT transients  special algorithm for detection and compensation of CT saturation  Low demand on CT specification  Power swing blocking/out-of-step tripping  Fault Locator with/without parallel line compensation
  7. Distance protection Info - 7 EV S V13/ Claus/ 23.08.00 17.10.97 en513all8  85-21  50N, 51N, 67N  85-67N  WI  50, 51 50N-2, 51N-2 ANSI-No. SIPROTEC 4 Distance Protection, Scope of functions (2)  Universal teleprotection interface (PUTT, POTT, Blocking, Unblocking, DTT...)  High resistance earth fault protection for earthed systems  Teleprotection interface for earth fault protection (Directional comparison, Blocking, Unblocking)  Weak infeed protection (Echo and Trip)  Overcurrent protection DMTL/IDMTL as parallel or emergency function
  8. Distance protection Info - 8 EV S V13/ Claus/ 23.08.00 ANSI-No.  59, 27 1)  50HS  50-STUB  79  25  50BF  49 2) 1) 7SA522: Overvoltage, 7SA6: Over- and Undervoltage 2) available only in 7SA6 SIPROTEC 4 Distance Protection, Scope of functions (3)  Voltage protection 1)  Fast tripping with switch-onto-fault condition (12 ms)  STUB Bus Overcurrent protection  Single and three pole multishot automatic reclosure  Synchro-check  Circuit-breaker failure protection  Thermal overload protection 2)  Earth fault detection in compensated/isolated systems 2)
  9. Distance protection Info - 9 EV S V13/ Claus/ 23.08.00 ANSI-No. 74TC 86 FR 47 * available approx. 1st Q/01 SIPROTEC 4 Distance Protection, Scope of functions (4)  Trip Circuit Supervision  Lock Out  Oscillographic Fault Recording (total length 15 s)  Voltage Phase Sequence  Interfaces  Time synchronization (IRIG-B, DCF77)  User interface#1 (on the front for DIGSI 4)  User-(Service-)interface #2 (on the rear, DIGSI 4/Modem)  System interface (IEC60870-5-103/Profibus FMS/others)  Remote relay interfaces #1 (planned for teleprotection*)  1) Remote relay interfaces #2 (planned for teleprotection*) 1) available only in 7SA522
  10. Distance protection Info - 10 EV S V13/ Claus/ 23.08.00 Operating system monitoring  Auxiliary voltage failure  Measured value detection  Buffer battery  Hardware–Watchdog  Software–Watchdog  Working memory  Program memory  Parameter memory  Sampling frequency  1/5 A–setting  Calibration data  Earth current transformer sensitive/normal  Modules (I/O Boards) SIPROTEC 4 Distance Protection, Monitoring Plausibility monitoring  Current sum  Current symmetry  Open conductor  Fuse Failure  1- / 2-pole failures  3-pole failures  Voltage sum  Voltage symmetry  Voltage phase rotation !
  11. Distance protection Info - 12 EV S V13/ Claus/ 23.08.00 Quadrilateral Characteristic 5 Zones (time delayed) optionally: - Forward - Reverse - Non-directional Prevention of load encroachment Dependant Zone Z1b for Teleprotection and Auto-recloser X R forwards f o r w a r d s r e v e r s e reverse  Load Load Z1 Z2 Z4 Z3 Z1B Z5 Line  SIPROTEC 4 Distance Protection
  12. Distance protection Info - 13 EV S V13/ Claus/ 23.08.00 0 5 10 15 20 25 30 35 40 45 50 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 % of zone 1 setting tripping time (ms) Relay S SIPROTEC 4, 7SA522 + 7SA6 Relay E Relay A SIPROTEC 4 Distance Protection: Overall Trip Time Curves at SIR = 30 G VF ZL ZQ E If distance relay
  13. Distance protection Info - 14 EV S V13/ Claus/ 23.08.00 + 2 .0 0 + 1 .6 0 + 1 .2 0 + 0 .8 0 + 0 .4 0 + 0 .0 0 - 0 .4 0 - 0 .8 0 - 1 .2 0 A 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 m s E s t im a t o r 2 ( n = 6 ) E s t im a t o r 3 ( n = 8 ) E s t im a t o r 4 ( n = 1 0 ) N o r m a l s t a g e 1 ( n = 2 1 ) N o r m a l s t a g e 2 ( n = 2 6 ) N o r m a l s t a g e 3 ju m p d e t e c t io n E s t im a t o r 5 ( n = 1 3 ) E s t im a t o r 6 ( n = 1 5 ) Estimator 1 (n=5) SIPROTEC 4 Distance Protection, Data window position, Adaptive Measuring Algorithm
  14. Distance protection Info - 15 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection Function: Difference 7SA522 - 7SA6  7SA522  for solid earthed systems  quadrilateral and/or MHO characteristic (MHO circle for specific markets, quadrilateral is preferred)  full market introduction: 1999  primary market outside continental Europe  7SA6  for systems with solid grounding or reactance (compensated) / isolated treatment of system starpoint  fault detection selectable as either I>, Z<, U/I and U/I/  Market introduction: Summer 2000  Primary market continental Europe
  15. Distance protection Info - 16 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection 7SA522 Mho Characteristic 5 Zones optionally: - Forward - Reverse Prevention of load encroachment X R  Z1 Z2 Z4 Z1B Z5 Line Z3 (if revers) Load Load Dependant Zone Z1b for Teleprotection and Auto-recloser
  16. Distance protection Info - 17 EV S V13/ Claus/ 23.08.00 SIPROTEC 4, Distance Protection Parallel-line compensation: connection and setting Q1 Q3 Q5 Q7 Q2 Q4 Q6 Q8 IL1(A) IL2(B) IL3(C) L1 (A) L2 (B) L3 (C) 52 Circuit breaker Line Busbar 52 Circuit breaker Parallel line I4
  17. Distance protection Info - 18 EV S V13/ Claus/ 23.08.00 Patented power swing detection provides secure operation with swing frequencies of up to 6 Hz t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 iL1/A -4 -2 0 t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 iL2/A -2 0 t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 iL3/A -2 0 2 t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 uL1/V -50 0 t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 uL2/V -50 0 50 t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 uL3/V -50 0 50 t/s 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 DisTRIP3p Z1Bmf Relay TRIP Relay PICKUP Dis. reverse Dis. forward Dis.T.SEND >DisTel Rec.Ch1 Power Swing Example: 400 kV 400 km fPS  2 Hz 3-pole fault
  18. Distance protection Info - 19 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: Fault locator
  19. Distance protection Info - 20 EV S V13/ Claus/ 23.08.00 Z1 Z1B L1-E L2-E A B 1 1 2 2 Z1 Z1B A1 trips single-phase in L1 with a phase-segregated L1-receive-signal  Maximum of Selectivity Note: 3 binary channels for both directions are requested or (in preparation) one serial link SIPROTEC 4 Distance Protection: Phase segregated Teleprotection
  20. Distance protection Info - 21 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: Teleprotection with three-terminal lines Software provides teleprotection of three- terminal lines without additional logic
  21. Distance protection Info - 22 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection  Earth (zero sequence) current protection, 4 stages  3 definite-time stages  1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic this stage can also be used as a 4th definite-time stage  Directional determination with 3V0 and/or Ipol of an earthed power transformer  Directional determination with V2 and I2 (negative sequence)  Sensitive 3I0-measurement with a dynamic from 0.003 A to 100 x In  Elimination of higher harmonics with special digital filters  Inrush-stabilisation with I0/100Hz  Teleprotection: Directional comparison, Blocking or Unblocking  Operation with weak infeed trip and echo  Instantaneous trip after switch-onto-fault
  22. Distance protection Info - 23 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection 3I0 T T3I0>> 3I0> T3I0> T3I0>>> 3I0>> 3I0>>> Definite-time characteristic
  23. Distance protection Info - 24 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection 0 5 10 15 20 25 30 35 0 1 2 3 4 5 6 7 8 9 10 t 3I0 / 3I0p Example: t = 5.8 - 1.35 ln(3I0 / 3I0p) T3I0pmax (P3145) T3I0p (P3144) 3I0p(P3140) T3I0min (P3141) 3I0p Startpoint(P3154) Tripping characteristic Logarithmic Inverse
  24. Distance protection Info - 25 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection IEC-characteristic: normal inverse:     Tp Ip I s t * 1 14 . 0 02 . 0           very inverse:   Tp Ip I s t * 1 5 . 13   extremly inverse:     Tp Ip I s t * 1 80 2           long time inverse:   Tp Ip I s t * 1 120   ANSI-characteristic:   D B Ip I A s t N * 1                          Inverse short inverse very inverse long inverse extremly inverse moderately inverse definite inverse Logarithmic-inverse characteristic:   P I I P I T P I T s t 0 3 0 3 ln * 0 3 max 0 3   for t>T3I0Pmin, otherwise: t[s]=T3I0Pmin
  25. Distance protection Info - 26 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection Inverse-time characteristic: IEC 3I0/Ip T Tp =1 b 20 0 a Reset: b = 1.045 x 3I0/IP Pickup: a = 1.1 x 3I0/IP
  26. Distance protection Info - 27 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection -160 -150 -140 -130 -120 -110 -100 -90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 dB 0 1 2 3 4 5 6 7 8 9 10 11 f/fn Filter characteristic for stages 3I0>>> and 3I0>>
  27. Distance protection Info - 28 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection Filter characteristic for stages 3I0> and Inverse time stage -170 -160 -150 -140 -130 -120 -110 -100 -90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 dB 0 1 2 3 4 5 6 7 8 9 10 11 f/fn
  28. Distance protection Info - 29 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection Earth fault direction = EF IE> Echo 3I0>>> EF>>> Trip P EFp Trip Inrush- stabilisation T(3I0/IN) T Tele- protection T SOTF = & & 3I0>>> Def. Time Stage Inverse Time Stage & & P >EF>>> block Direc. 3I0>>> P Direc. 3I0p >EFp block P 3I0p EF Fault Det. >EF Trip rel. 3I0>> Def. Time Stage 3I0> Def. Time Stage = Input signal (binary input) P = Parameter = Output Signal (alarm, command) P3146 AddTdelay
  29. Distance protection Info - 30 EV S V13/ Claus/ 23.08.00 Z1(A) T1B Z1B A B Z1(B) Z1B(A) Z1B(B) & & & & (A) T1B Z1B (B) OR OR OR OR TS Z1 or further zones trans- mit re- ceive Trip Trip re- ceive trans- mit Z1 or further zones TS SIPROTEC 4 Distance Protection: Permissive overreach transfer trip (POTT) TS
  30. Distance protection Info - 31 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection STUB protection for 11/2-circuit breaker arrangement Busbar A feeder 1 feeder 2 stub fault IA IB Ik = IA+IB line isolator 1 line isolator 2 CB (A) CB (C) CB (B) Busbar B Release of STUB-stage with open line isolator:
  31. Distance protection Info - 32 EV S V13/ Claus/ 23.08.00 Auto-reclosure (AR) ON OFF 2nd dead time T1-act TRIP 1-pole 3-pole 1st dead time RE- CLOSE * RE- CLOSE T2-act TRIP tzone-delay ADT = Reclosure, when AR at the remote end was successful DLC = Reclosure only on dead line RDT = Reduced dead time, if trip had occurred with zone extension final TRIP * SIPROTEC 4 Distance Protection: Auto-reclosure
  32. Distance protection Info - 33 EV S V13/ Claus/ 23.08.00 application examples functions (separately settable for AR and - combination with internal or manual closing) external AR - program selection via parameters: - activation also for manual closing synchro-check / U1 > U2 < / (settable) U1 < U2 > / U1 < U2 < / overrule - asynchronous switching (settable) - all programs separately settable via binary inputs - synchronous monitoring time, after which the closing will be blocked (settable) parameters measurement - voltages U<, U>, U - evaluation of the fundamental wave - f synchronous switching (0.01 ... 0.03 Hz) - insensitive against harmonics - f asynchronous switching (0.03 ... 1 Hz) - for dead line check all three phases are controlled -  (1° ... 60°) 16.10.97 engersyn1 Synchronism-check
  33. Distance protection Info - 34 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection: Breaker failure protection  2 stages  Internal initiation and via binary inputs  Extremely short reset time: approx. 10ms  End-fault protection  Pole discrepancy supervision
  34. Distance protection Info - 35 EV S V13/ Claus/ 23.08.00 SIPROTEC 4 Distance Protection with light or electrical  exchangeable  upgradeable 7SA522
  35. Distance protection Info - 37 EV S V13/ Claus/ 23.08.00 User friendly Operation Safe operation, reduced training requirements Fits all applications System concept SIPROTEC and SICAM Flexible Functionality and Open Communication One Family SIPROTEC 4 - Distance Protection
  36. Distance protection Info - 38 EV S V13/ Claus/ 23.08.00 Full Logic Functionality Additional logic Interlocking Measured values processing Log. IN 1 Log. IN 2 Log.IN3 Logic inputs from the matrix to CFC Logic outputs to the configuration matrix F1 F2 >1 CFC Log.OUT1 Distance Protection 7SA522 What makes these devices so attractive ?
  37. Distance protection Info - 39 EV S V13/ Claus/ 23.08.00 Comprehensive measured value processing I1 :400.9A f:50.0Hz U1:12.22kV P :+8.03MW cos Q :+2.64MVar L1 402.1A Max450.1A L2 401.2A Max421.2A L3 401.0A Max431.4A E 00.0A % IL UL-E UL-L L1 100.0 100.4 100.1 L2 100.4 100.3 100.0 L3 100.1 100.1 100.4 Distance Protection 7SA522 What makes these devices so attractive ?
  38. Distance protection Info - 40 EV S V13/ Claus/ 23.08.00 The easy handling with DIGSI 4 Distance Protection 7SA522 What makes these devices so attractive ?