00. switchgear protection and power systems_fm.pdf
Distance protection
Info - 1
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection
7SA522 and 7SA6
Productmanager Distance Protection
Michael Claus
EV S V 13 Nürnberg H
Phone: +49 911 433 8261
Fax: +49 911 433 8301
Email: Michael.Claus@ev.siemens.de
Distance protection
Info - 2
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 -
What it means
SIPROTEC 4
is a family of numerical
Protection, Control and Automation
Devices
from
Distance protection
Info - 3
EV S V13/ Claus/ 23.08.00
7SA522
7SA6
7SA510
7SA511
7SA513
SIPROTEC 4
Software System
SIPROTEC 4
Hardware Platform
Distance protection: Past and Present
Distance protection
Info - 4
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection 7SA522 and 7SA6
7SA522 +
7SA6
One family of
distance
protection for
all voltage
applications
Distance protection
Info - 5
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance protection
7SA61 + 7SA522
Protection
4-line display
MV, HV and EHV
7SA612 + 7SA522
7SA611 + 7SA522
7SA610
7SA63
Protection + local control
integrated graphic display
mainly MV
7SA632
7SA631
7SA64
Protection + local control
detached control panel
mainly MV
7SA642
7SA641
All core functions are
available in all the
housing versions
Distance protection
Info - 6
EV S V13/ Claus/ 23.08.00 17.10.97
en513all7
ANSI-No.
21, 21N
68
FL
SIPROTEC 4
Distance Protection, Scope of functions (1)
Distance Protection
full scheme measurement with sophisticated loop selection
fast three phase and single phase tripping
with/without parallel line compensation
special filtering for CVT transients
special algorithm for detection and compensation of CT
saturation Low demand on CT specification
Power swing blocking/out-of-step tripping
Fault Locator with/without parallel line compensation
Distance protection
Info - 7
EV S V13/ Claus/ 23.08.00 17.10.97
en513all8
85-21
50N, 51N,
67N
85-67N
WI
50, 51
50N-2,
51N-2
ANSI-No.
SIPROTEC 4
Distance Protection, Scope of functions (2)
Universal teleprotection interface
(PUTT, POTT, Blocking, Unblocking, DTT...)
High resistance earth fault protection
for earthed systems
Teleprotection interface for earth fault protection
(Directional comparison, Blocking, Unblocking)
Weak infeed protection
(Echo and Trip)
Overcurrent protection DMTL/IDMTL as parallel or
emergency function
Distance protection
Info - 8
EV S V13/ Claus/ 23.08.00
ANSI-No.
59, 27 1)
50HS
50-STUB
79
25
50BF
49 2)
1) 7SA522: Overvoltage, 7SA6: Over- and Undervoltage
2) available only in 7SA6
SIPROTEC 4
Distance Protection, Scope of functions (3)
Voltage protection 1)
Fast tripping with switch-onto-fault condition (12 ms)
STUB Bus Overcurrent protection
Single and three pole multishot automatic reclosure
Synchro-check
Circuit-breaker failure protection
Thermal overload protection 2)
Earth fault detection in compensated/isolated systems 2)
Distance protection
Info - 9
EV S V13/ Claus/ 23.08.00
ANSI-No.
74TC
86
FR
47
* available approx. 1st Q/01
SIPROTEC 4
Distance Protection, Scope of functions (4)
Trip Circuit Supervision
Lock Out
Oscillographic Fault Recording (total length 15 s)
Voltage Phase Sequence
Interfaces
Time synchronization (IRIG-B, DCF77)
User interface#1 (on the front for DIGSI 4)
User-(Service-)interface #2 (on the rear, DIGSI 4/Modem)
System interface (IEC60870-5-103/Profibus FMS/others)
Remote relay interfaces #1 (planned for teleprotection*)
1) Remote relay interfaces #2 (planned for teleprotection*)
1) available only in 7SA522
Distance protection
Info - 10
EV S V13/ Claus/ 23.08.00
Operating system monitoring
Auxiliary voltage failure
Measured value detection
Buffer battery
Hardware–Watchdog
Software–Watchdog
Working memory
Program memory
Parameter memory
Sampling frequency
1/5 A–setting
Calibration data
Earth current
transformer
sensitive/normal
Modules (I/O Boards)
SIPROTEC 4
Distance Protection, Monitoring
Plausibility monitoring
Current sum
Current symmetry
Open conductor
Fuse Failure
1- / 2-pole failures
3-pole failures
Voltage sum
Voltage symmetry
Voltage phase rotation
!
Distance protection
Info - 12
EV S V13/ Claus/ 23.08.00
Quadrilateral Characteristic
5 Zones (time delayed)
optionally:
- Forward
- Reverse
- Non-directional
Prevention of load
encroachment
Dependant Zone Z1b for
Teleprotection and
Auto-recloser
X
R
forwards
f
o
r
w
a
r
d
s
r
e
v
e
r
s
e
reverse
Load
Load
Z1
Z2
Z4
Z3
Z1B
Z5
Line
SIPROTEC 4
Distance Protection
Distance protection
Info - 13
EV S V13/ Claus/ 23.08.00
0
5
10
15
20
25
30
35
40
45
50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
% of zone 1 setting
tripping
time
(ms)
Relay S
SIPROTEC 4, 7SA522 + 7SA6
Relay E
Relay A
SIPROTEC 4
Distance Protection: Overall Trip Time Curves at SIR = 30
G VF
ZL
ZQ
E
If
distance relay
Distance protection
Info - 14
EV S V13/ Claus/ 23.08.00
+ 2 .0 0
+ 1 .6 0
+ 1 .2 0
+ 0 .8 0
+ 0 .4 0
+ 0 .0 0
- 0 .4 0
- 0 .8 0
- 1 .2 0
A
0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0
m s
E s t im a t o r 2 ( n = 6 )
E s t im a t o r 3 ( n = 8 )
E s t im a t o r 4 ( n = 1 0 )
N o r m a l s t a g e 1
( n = 2 1 )
N o r m a l s t a g e 2
( n = 2 6 )
N o r m a l s t a g e 3
ju m p d e t e c t io n
E s t im a t o r 5 ( n = 1 3 )
E s t im a t o r 6 ( n = 1 5 )
Estimator 1 (n=5)
SIPROTEC 4 Distance Protection,
Data window position, Adaptive Measuring Algorithm
Distance protection
Info - 15
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection Function: Difference 7SA522 - 7SA6
7SA522
for solid earthed systems
quadrilateral and/or MHO characteristic
(MHO circle for specific markets, quadrilateral is preferred)
full market introduction: 1999
primary market outside continental Europe
7SA6
for systems with solid grounding or
reactance (compensated) / isolated treatment of system starpoint
fault detection selectable as either I>, Z<, U/I and U/I/
Market introduction: Summer 2000
Primary market continental Europe
Distance protection
Info - 16
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection 7SA522
Mho Characteristic
5 Zones optionally:
- Forward
- Reverse
Prevention of load
encroachment
X
R
Z1
Z2
Z4
Z1B
Z5
Line
Z3 (if revers)
Load Load
Dependant Zone Z1b for
Teleprotection and
Auto-recloser
Distance protection
Info - 17
EV S V13/ Claus/ 23.08.00
SIPROTEC 4, Distance Protection
Parallel-line compensation: connection and setting
Q1
Q3
Q5
Q7
Q2
Q4
Q6
Q8
IL1(A)
IL2(B)
IL3(C)
L1 (A)
L2 (B)
L3 (C)
52 Circuit
breaker
Line
Busbar
52 Circuit
breaker
Parallel line
I4
Distance protection
Info - 20
EV S V13/ Claus/ 23.08.00
Z1 Z1B
L1-E
L2-E
A B
1 1
2 2
Z1
Z1B
A1 trips single-phase in L1 with a phase-segregated L1-receive-signal
Maximum of Selectivity
Note: 3 binary channels for both directions are requested or (in preparation) one serial link
SIPROTEC 4
Distance Protection: Phase segregated Teleprotection
Distance protection
Info - 21
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: Teleprotection with three-terminal lines
Software provides
teleprotection of three-
terminal lines without
additional logic
Distance protection
Info - 22
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
Earth (zero sequence) current protection, 4 stages
3 definite-time stages
1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic
this stage can also be used as a 4th definite-time stage
Directional determination with 3V0 and/or Ipol of an earthed power
transformer
Directional determination with V2 and I2 (negative sequence)
Sensitive 3I0-measurement with a dynamic from 0.003 A to 100 x In
Elimination of higher harmonics with special digital filters
Inrush-stabilisation with I0/100Hz
Teleprotection: Directional comparison, Blocking or Unblocking
Operation with weak infeed trip and echo
Instantaneous trip after switch-onto-fault
Distance protection
Info - 23
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
3I0
T
T3I0>>
3I0>
T3I0>
T3I0>>>
3I0>> 3I0>>>
Definite-time characteristic
Distance protection
Info - 25
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
IEC-characteristic:
normal inverse: Tp
Ip
I
s
t *
1
14
.
0
02
.
0
very inverse: Tp
Ip
I
s
t *
1
5
.
13
extremly inverse: Tp
Ip
I
s
t *
1
80
2
long time inverse: Tp
Ip
I
s
t *
1
120
ANSI-characteristic:
D
B
Ip
I
A
s
t N
*
1
Inverse
short inverse very inverse
long inverse extremly inverse
moderately inverse definite inverse
Logarithmic-inverse characteristic:
P
I
I
P
I
T
P
I
T
s
t
0
3
0
3
ln
*
0
3
max
0
3
for t>T3I0Pmin, otherwise: t[s]=T3I0Pmin
Distance protection
Info - 26
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
Inverse-time characteristic: IEC
3I0/Ip
T
Tp =1
b 20
0 a
Reset: b = 1.045 x 3I0/IP
Pickup: a = 1.1 x 3I0/IP
Distance protection
Info - 27
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
-160
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-30
-20
-10
0
10
dB
0 1 2 3 4 5 6 7 8 9 10 11
f/fn
Filter characteristic for stages 3I0>>> and 3I0>>
Distance protection
Info - 28
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
Filter characteristic for stages 3I0> and Inverse time stage
-170
-160
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-30
-20
-10
0
10
dB
0 1 2 3 4 5 6 7 8 9 10 11
f/fn
Distance protection
Info - 29
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: High Resistance Earth Fault Protection
Earth fault
direction
=
EF IE> Echo
3I0>>>
EF>>> Trip
P
EFp Trip
Inrush-
stabilisation
T(3I0/IN)
T
Tele-
protection
T
SOTF
= &
&
3I0>>> Def. Time Stage
Inverse Time Stage
&
&
P
>EF>>> block
Direc. 3I0>>>
P Direc. 3I0p
>EFp block
P 3I0p
EF Fault Det.
>EF Trip rel.
3I0>> Def. Time Stage
3I0> Def. Time Stage
= Input signal
(binary input)
P = Parameter = Output Signal
(alarm, command)
P3146 AddTdelay
Distance protection
Info - 30
EV S V13/ Claus/ 23.08.00
Z1(A)
T1B
Z1B
A B
Z1(B)
Z1B(A)
Z1B(B)
&
&
&
&
(A)
T1B
Z1B
(B)
OR
OR
OR
OR
TS
Z1 or
further
zones
trans-
mit
re-
ceive
Trip
Trip
re-
ceive
trans-
mit
Z1 or
further
zones
TS
SIPROTEC 4
Distance Protection: Permissive overreach transfer trip (POTT)
TS
Distance protection
Info - 31
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection
STUB protection for 11/2-circuit breaker arrangement
Busbar A
feeder
1
feeder
2
stub fault
IA
IB
Ik = IA+IB line isolator 1
line isolator 2
CB
(A)
CB
(C)
CB
(B)
Busbar B
Release of STUB-stage with open line isolator:
Distance protection
Info - 32
EV S V13/ Claus/ 23.08.00
Auto-reclosure (AR)
ON
OFF
2nd
dead time
T1-act
TRIP
1-pole
3-pole
1st
dead time
RE-
CLOSE
*
RE-
CLOSE
T2-act
TRIP
tzone-delay
ADT = Reclosure, when AR at the remote end was successful
DLC = Reclosure only on dead line
RDT = Reduced dead time, if trip had occurred with zone extension
final
TRIP
*
SIPROTEC 4
Distance Protection: Auto-reclosure
Distance protection
Info - 33
EV S V13/ Claus/ 23.08.00
application examples functions
(separately settable for AR and
- combination with internal or manual closing)
external AR
- program selection via parameters:
- activation also for manual closing synchro-check / U1 > U2 < /
(settable) U1 < U2 > / U1 < U2 < / overrule
- asynchronous switching (settable) - all programs separately settable
via binary inputs
- synchronous monitoring time, after which
the closing will be blocked (settable)
parameters measurement
- voltages U<, U>, U - evaluation of the fundamental wave
- f synchronous switching (0.01 ... 0.03 Hz) - insensitive against harmonics
- f asynchronous switching (0.03 ... 1 Hz) - for dead line check all three phases
are controlled
- (1° ... 60°)
16.10.97
engersyn1
Synchronism-check
Distance protection
Info - 34
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection: Breaker failure protection
2 stages
Internal initiation and via binary inputs
Extremely short reset time: approx. 10ms
End-fault protection
Pole discrepancy supervision
Distance protection
Info - 35
EV S V13/ Claus/ 23.08.00
SIPROTEC 4
Distance Protection
with light
or electrical
exchangeable
upgradeable
7SA522
Distance protection
Info - 37
EV S V13/ Claus/ 23.08.00
User friendly Operation
Safe operation,
reduced training
requirements
Fits all applications
System concept
SIPROTEC and SICAM
Flexible Functionality and
Open Communication
One Family
SIPROTEC 4 -
Distance Protection
Distance protection
Info - 38
EV S V13/ Claus/ 23.08.00
Full Logic
Functionality
Additional logic
Interlocking
Measured values
processing
Log. IN 1
Log. IN 2
Log.IN3
Logic inputs from
the matrix to CFC
Logic outputs to the
configuration matrix
F1
F2
>1
CFC
Log.OUT1
Distance Protection 7SA522
What makes these devices so attractive ?
Distance protection
Info - 39
EV S V13/ Claus/ 23.08.00
Comprehensive
measured value
processing
I1 :400.9A f:50.0Hz
U1:12.22kV
P :+8.03MW cos
Q :+2.64MVar
L1 402.1A Max450.1A
L2 401.2A Max421.2A
L3 401.0A Max431.4A
E 00.0A
% IL UL-E UL-L
L1 100.0 100.4 100.1
L2 100.4 100.3 100.0
L3 100.1 100.1 100.4
Distance Protection 7SA522
What makes these devices so attractive ?
Distance protection
Info - 40
EV S V13/ Claus/ 23.08.00
The easy
handling with
DIGSI 4
Distance Protection 7SA522
What makes these devices so attractive ?