UPS Electrical Design and Installation

Jason Koffler
Jason KofflerDirector em Critical Power Supplies Ltd

UPS Electrical Design and Installation by Critical Power Supplies. Important considerations for the electrical design and installation of UPS systems in mission critical applications. Where Critical Power applications are concerned, the electrical design and installation of a UPS (uninterruptible power supply) system is crucially important for several reasons. Firstly, it must work in alignment with installations already on site and not interfere with other electrical equipment. This is particularly important for industrial and healthcare installations where there may already be critical equipment (medical and life support, for example) in operation. It all starts with a site survey. A pre-installation site survey will reveal details about the scope of the electrical work to be undertaken. Such information will reveal, for instance, the type of electrical loads, power quality issues, harmonics, whether it is a high, medium or low voltage installation and electrical distribution set up, including the breaker sizes already on site and their discrimination. If you would like more information please contact sales on 0800 978 8988 or email sales@criticalpowersupplies.co.uk

Important considerations for the electrical
design and installation of UPS systems
in mission critical applications
UPS Electrical
Design and
Installation
criticaPOWER SUPPLIES
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928
Where Critical Power applications are concerned, the electrical design and installation of a UPS
(uninterruptible power supply) system is crucially important for several reasons.
 
Firstly, it must work in alignment with installations already on site and not interfere with other electrical
equipment.This is particularly important for industrial and healthcare installations where there may already
be critical equipment (medical and life support, for example) in operation.
 
It all starts with a site survey.
 
A pre-installation site survey will reveal details about the scope of the electrical work to be undertaken.
Such information will reveal, for instance, the type of electrical loads, power quality issues, harmonics, whether it is a
high, medium or low voltage installation and electrical distribution set up, including the breaker sizes already on site
and their discrimination.
 
It is important to mention that all electrical work within critical power installations has to be carried out by suitably
qualified, certified and registered electrical engineers. It should also be carried out in accordance with local, national and
organisational guidelines. In the UK, the latest applicable industry standards are The Institution of Engineering
and Technology (IET) – BS 7671 IEE Wiring Regulations Seventeen Edition and Electricity at Work
Regulations 1989.
 
Electrical work involved
The scope and complexity of the electrical work involved will depend upon the size and intricacy of the installation itself
but it will probably include:
Cable installation (from ac mains power source to UPS; from the UPS output to a distribution system, between
the UPS and battery set, generator and/or other alternative power sources.
The installation of additional power sockets or fused spurs.
Upgrading supply ratings, cable and distribution boards.
Installing electrical switchgear panels and maintenance bypasses.
Running alarm cables to remote panels or network connection points.
 
If you would like to find out more about electrical design, installation, UPS power
protection and energy management, get in touch www.criticalpowersupplies.co.uk
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 39281
There are several items to bear in mind when designing an electrical installation, all of which will influence power quality,
reliability, stability and the installation itself.
 
Elements to bear in mind when designing a UPS Electrical Installation:
 
Protection discrimination
Protection discrimination is how two or more protective devices within a supply circuit are coordinated to ensure any loads
that develop a fault condition (overload, short-circuit or earth fault) are quickly removed without disruption to other loads.
 
Protection discrimination sets out to protect the supply conductors of devices. It basically ensures each section within
a supply distribution system is individually protected.The implementation of a suitable discrimination path is critically
important within a UPS installation for protecting the UPS themselves and also the critical loads attached to them.
 
Devices for protection discrimination include: fuses, circuit-breakers or Residual Current Devices (RCD), which must be chosen
based on their rating and suitability for the application.They have different operating characteristics i.e., speed of response
and different types of circuit-breaker can be rated the same but react differently in overload conditions.
For example, a 20A circuit-breaker type A may disconnect within 0.1 seconds with an overload current of just 100A.Type B
circuit-breaker (also 20A) may not trip until it receives a current of 400A. Care must be taken when selecting the right type
within a UPS application to prevent nuisance tripping at start up.
 
The more robust circuit-breaker, one that can sustain higher overloads for longer periods, is recommended for use with
loads with high inrush currents such as some types of UPS (transformer-based) and motor loads/motor machinery.
The more responsive circuit-breakers are suitable for more sensitive equipment such as computer and telecom loads.
Power quality.
Load types.
Load size.
Type of UPS (Online, line-interactive or offline).
Back-up power system (battery banks) and recharge time.
Voltage optimisations.
Remote environmental management and monitoring.
Upgrades that may be required to the existing electrical infrastructure.
Additional cooling loads.
If you would like to find out more about electrical design, installation, UPS power
protection and energy management, get in touch www.criticalpowersupplies.co.uk
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928 2
The curse of harmonics
As electrical systems get busier with ever increasing equipment added in to already overcrowded distribution networks,
harmonic pollution is on the increase and it needs to be considered from the outset.
 
In the EU, the electrical supply industry is required to meet EN 50160 – Voltage Characteristics of Electricity
Supplied by Public Distribution Systems and it includes guidelines on harmonic voltage distortion. In the UK,
permitted harmonic levels are also specified in G5/4-1. Permitted harmonic limits vary depending on whether the supply
is high, medium or low voltage.A high voltage network is likely to have low impedance, which allows a larger harmonic
content load to be connected.
 
The influence of Power Factor
Invariably, power factor correction will be part of most UPS electrical installations these days.Although they are getting
better, some electrical equipment (particularly older devices) will have poor power factor, which means their load is out of
phase with the voltage waveform of the electrical supply.This will result in inefficiencies plus it places additional demands
on supply connections and peripheral equipment such as cabling, conductors, transformers and distribution boards.
 
The closer the input power factor of the UPS is to Unity (1), the lower the amount of reactive power generated and the more
efficiently the UPS system will run. Installing passive harmonic filters can improve things but because of the way in which
a phase-controlled rectifier operates, performance will remain load related.
 
Cable sizing and installation
It is imperative to select and specify the correct type and size of cabling in UPS installations. Failure to do so can result
in overheating, fire risk and premature failure. It is also important to select the best method of installation alongside the
most optimum routing.The same cable sizes should be installed for input and output and the selected cable should provide
continuous full thermal current rating.  A Site Survey will reveal the length of cable required and what voltage drop should
be catered for within the project specification and what size lugs are required.
If you would like to find out more about electrical design, installation, UPS power
protection and energy management, get in touch www.criticalpowersupplies.co.uk
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 39283
Downstream protection
It is important to ensure downstream protection and discrimination is applicable for the type of UPS and how it operates:
normal operation with mains power supply present or battery operation with no mains power supply present.
 
During normal operation with mains power supply present, any fault or short-circuit on the output of the UPS will result in
the load being transferred to the bypass.This will allow the full capacity of the mains power supply to clear the downstream
fault. Once cleared, the UPS will transfer the load back to the inverter and resume normal operation.
 
During battery operation (with no mains power present), a fault condition on the output of the UPS will result in a restriction
on energy available in an attempt to clear the fault. Once cleared, the UPS will continue supplying the loads from the battery
set. If, however, the UPS does not have enough power to clear the load it will shut down in order to protect itself and
connected downstream loads.This is referred to as ‘current limiting’.This means the type and current rating of downstream
devices is an important consideration to ensure discrimination occurs during both modes of operation.There are several
options for downstream protection:
Sized in accordance with the rating for each UPS module to which they are connected (input cables).
Rated to either the supply or the maximum output power available from each UPS module (output cables).
Input and output cables should be the same length to ensure an even power distribution.
Parallel Systems connection
Parallel UPS can be installed with either a single or dual input power supply but the overall rating must be adequate enough
to supply the parallel UPS irrespective of operation (capacity or redundancy).
 
In a parallel capacity system, the ac supply must be rated to the maximum input current of each UPS module, multiplied by
the total UPS units in the system.Within a parallel redundant UPS configuration, the supply rating can be the same as that
used for a parallel capacity system or equal to the total current required by each of the individual UPS modules (plus 10% to
allow for charging and system losses). Cables in a parallel UPS system should be:
Galvanic isolation – how this is set up depends upon where the isolation transformer is to be installed and with
which type of online UPS and whether it has a single or dual input supply.Transformerless UPS require two isolation
transformers on the input side to provide complete neutral separation.
Maintenance bypasses – there are various types of maintenance bypass available, including internal and external.
For UPS below 5kVA, external bypasses are typical and they usually have an additional automatic transfer facility.
Surge protection on mains 1 and 2 (as chosen through discussions with the client).
Lightning protection - modern buildings typically cover this requirement, but it should also be covered in the site
survey just to be sure.
If you would like to find out more about electrical design, installation, UPS power
protection and energy management, get in touch www.criticalpowersupplies.co.uk
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928 4
Dual input connection - fed by unique breakers or linked?
UPS resilience is further increased through the commonly held practice of using dual ac power sources rather than a single
one. Dual input connection allows the rectifier and bypass to be supplied from separate sources, which could be different
sub-stations, to protect against a single point of failure.
 
Transformer-based UPS are supplied with dual input terminals as standard.With transformerless UPS, it is slightly different
as the rectifier and bypass supplies require a common neutral connection. It can still be installed with a dual input but with
supplies derived from the same source and the dual input feature is not standard but a factory fit option.
 
Earthing and Bonding for UPS and battery racks
To protect equipment (and the installation itself) from overheating, premature failure and fire risk, it is mandatory that
live conductors are protected from overloads, short-circuits and earth faults.The earthing and bonding of UPS equipment
depends upon the type of electrical supply installed.There are four common types:
 
TN-C-S – the most common and uses Protective Multiple Earthing (PME) in which neutral and earthed
protective conductors are combined in part of the system.
 
TN-C – in which neutral and earthed conductors are combined throughout the system.This type also uses PME.
 
TN-S – in which the neutral and earthed conductors remain separate throughout.
 
TT – in which neutral is earthed at the power source but the electricity supplier does not provide an
earthed protective conductor.
 
It is inadvisable within UPS systems to connect the output neutral to the incoming earth. If neutral-to-earth connection
is required an isolation transformer should be installed on the UPS output.
 
Earthing and bonding for generators
With regard to generators within a UPS power protection system, it is important that care is taken around neutral
connections.This is because UPS and generators rely on breaking the neutral when switching to and from the generator
supply. But this relies on the UPS being able to withstand a break in supply neutral during changeover.
 
The most common form of switching mechanism employed in generator installation uses two individual but electrically
interlocked contactors. Controlled by the AMF (Automatic Mains Failure) panel, these select between incoming mains power
or generator output.This method is relatively inexpensive but it is not necessarily the best, particularly for installations
requiring a fixed neutral between changeover as it is slow and could take several cycles for the change to occur.
 
A better system is a make-before-break contact method that ensures the neutral stays fixed during changeover.Another
option for maintaining a fixed neutral is to install an isolation transformer and this can also help address problems
associated with harmonics.
 
If you would like to find out more about electrical design, installation, UPS power
protection and energy management, get in touch www.criticalpowersupplies.co.uk
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 39285
UPS and Generators
UPS and generators have to be compatible and suitably matched in terms of sizing.The generator must be able to accept the
UPS loads and the UPS (rectifier and static bypass supplies) must be able to operate with and synchronise to the output of
the generator. Generator and UPS interfacing is also an issue that requires consideration. It is often necessary for the UPS to
interface with the generator for control purposes. Cable runs may be needed for both electrical and communications signals
(to make a connection, for example, between the UPS, generator and AMF panel (which may be monitored remotely).
 
Electrical Testing and Certification
 As with all electrical installations, hardwired UPS systems require electrical testing and certification and this has to be
carried out by certified electrical contractors.Testing regimes will vary in accordance with the size and scope of each
installation but they could include Earth fault loop impedance testing.
 
Downstream Distribution and left and right PDUs both on UPS or only one and the type of PDU required as there are
three types.
If you would like to find out more about electrical design, installation, UPS power
protection and energy management, get in touch www.criticalpowersupplies.co.uk
Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928
The whole point of a power protection system is to keep the lights on when mains power goes off and electrical design and
installation plays a key role in ensuring that happens. Get it wrong and you could end up with no power protection at all, get it
right and you could ensure power continuity, increased efficiency and save your customer many £thousands in electricity bills.
A site survey is vital; knowing what you are working with at the outset is a great starting point.After that, it’s a case of
making sure you understand the technology you are working with, have the experience to make it work and know what
the customer wants.The importance of expertise in this area cannot be overstated.At Critical Power Supplies, we have the
experience, knowledge and qualifications to get the job done cost-effectively.We are also manufacturer independent and
supply most of the leading brands available in the market today.We are accredited by the manufacturers to work on their
equipment, which saves you time having to search around for a specialist.
Basic
Monitored
Managed
 
It is worth remembering that Metered PDUs should be considered as a bare minimum to ensure the load
supported by the PDU does not exceed the supply breaker size otherwise overloading could pull the
breaker open thus dropping the load without notice.
6
Critical Power Supplies is a specialist provider of power
protection and energy management products and services.
We work hard to ensure our customers’ uptime, system
availability and optimised energy consumption.
We supply products from leading manufacturers and we
are particularly skilled and experienced in UPS electrical
design and installation. If you’d like to talk to us about
any projects you have coming up – in confidence and
under no obligation – please get in touch.
Data Centres
Finance
IT
Telecommunications
Industrial
Marine
Security
Emergency
Transport
Medical
Markets
Accreditation and Compliance
Our customers often operate in highly regulated industries in which accreditation is a legal requirement.The
fact that we are accredited means customers can rest assured our staff, suppliers, products and services comply
with the latest standards and regulations. In dealing with us, your own regulatory compliance remains in tact.
If you require any further information, or would like an informal chat about power continuity, critical
power, standby power or power protection systems in general, get in touch.We are at your service.
www.criticalpowersupplies.co.uk
Sales: 0800 978 8988
Fax: 0845 519 3639
24 hour Service: 0845 519 3928
criticaPOWER SUPPLIES

Recomendados

Electrical Design calculationsElectrical Design calculations
Electrical Design calculationsPankaj Chavan
33.9K visualizações62 slides
Electrical Power substationElectrical Power substation
Electrical Power substationEmran Ali
3.2K visualizações46 slides
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing CalculationsSiddhartha mudgal
2.1K visualizações17 slides
automatic power factor controllerautomatic power factor controller
automatic power factor controllersingh1515
34.7K visualizações37 slides

Mais conteúdo relacionado

Mais procurados

Power factor correctionPower factor correction
Power factor correctionutkarsh srivastav
20.6K visualizações43 slides
Panel designingPanel designing
Panel designingAKANSHA GURELE
34.6K visualizações13 slides
presentation on UPspresentation on UPs
presentation on UPsBipin Choudhary
15.7K visualizações30 slides
Earthing system   Earthing system
Earthing system Dr Ashok Tiwari
5.5K visualizações81 slides
Report on Electrical SafetyReport on Electrical Safety
Report on Electrical Safetyson_nikhil
8.2K visualizações20 slides

Mais procurados(20)

Power factor correctionPower factor correction
Power factor correction
utkarsh srivastav20.6K visualizações
Panel designingPanel designing
Panel designing
AKANSHA GURELE34.6K visualizações
presentation on UPspresentation on UPs
presentation on UPs
Bipin Choudhary15.7K visualizações
Earthing system   Earthing system
Earthing system
Dr Ashok Tiwari5.5K visualizações
Report on Electrical SafetyReport on Electrical Safety
Report on Electrical Safety
son_nikhil8.2K visualizações
ELECTRICAL PROTECTIVE DEVICES-EC.pptxELECTRICAL PROTECTIVE DEVICES-EC.pptx
ELECTRICAL PROTECTIVE DEVICES-EC.pptx
Jaspreetsingh369009113 visualizações
Air circuit breakersAir circuit breakers
Air circuit breakers
Prasant Kumar4.6K visualizações
Electric substation Electric substation
Electric substation
ANNU KUMAR3.3K visualizações
Power system protection devicesPower system protection devices
Power system protection devices
Prakash_1320922.5K visualizações
SubstationsSubstations
Substations
itfakash5.3K visualizações
UPS and DC power training PresentationUPS and DC power training Presentation
UPS and DC power training Presentation
hasboo12.3K visualizações
Motor ProtectionMotor Protection
Motor Protection
michaeljmack7.7K visualizações
PPT ON 33/11KV SUBSTATIONPPT ON 33/11KV SUBSTATION
PPT ON 33/11KV SUBSTATION
Ravi Phadtare26.6K visualizações
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
michaeljmack9.2K visualizações
Breaker Operation & MaintenanceBreaker Operation & Maintenance
Breaker Operation & Maintenance
Sheikh Nazmul Islam944 visualizações
Surge ProtectionSurge Protection
Surge Protection
michaeljmack5.5K visualizações
SUBSTATION OVERVIEW - A presentation on substationSUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substation
raiamitesh835.1K visualizações
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
Power System Operation1.6K visualizações
Electrical 132kv substation project .. shakirElectrical 132kv substation project .. shakir
Electrical 132kv substation project .. shakir
Sheikh Shakir3.1K visualizações

Destaque(18)

Cable Tray Installation 211215Cable Tray Installation 211215
Cable Tray Installation 211215
MUHAMMAD MAJID14.8K visualizações
Lighting & power design citamLighting & power design citam
Lighting & power design citam
Wambasi Fred1.1K visualizações
BEAMA Best Practice Guide to Cable Ladder & Cable Tray SystemsBEAMA Best Practice Guide to Cable Ladder & Cable Tray Systems
BEAMA Best Practice Guide to Cable Ladder & Cable Tray Systems
Thorne & Derrick International6.1K visualizações
Cable sizing part 2Cable sizing part 2
Cable sizing part 2
Febrian Sasi Kirana5.3K visualizações
Curriculum Vita Curriculum Vita
Curriculum Vita
Hamdi Yahyaoui108 visualizações
Huawei ups product and solution 02 (20140318)Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)
Jason Koffler1.3K visualizações
Illumination Example 3Illumination Example 3
Illumination Example 3
Vijay Raskar3K visualizações
Huawei Modular UPS Systems UPS5000E SereisHuawei Modular UPS Systems UPS5000E Sereis
Huawei Modular UPS Systems UPS5000E Sereis
Robin Koffler MBA CDCEP1.4K visualizações
Illumination Example 6Illumination Example 6
Illumination Example 6
Vijay Raskar5.3K visualizações
Commercial ProjectCommercial Project
Commercial Project
Ckurdi2K visualizações
Illumination Example 4Illumination Example 4
Illumination Example 4
Vijay Raskar12.4K visualizações
Electrical DesignElectrical Design
Electrical Design
anjal37532.3K visualizações
Illumination Example 1Illumination Example 1
Illumination Example 1
Vijay Raskar9K visualizações
Cable Mgr cable tray Introduction Cable Mgr cable tray Introduction
Cable Mgr cable tray Introduction
Gabriel Vasquez8.3K visualizações
Job Hunting for Electrical EngineersJob Hunting for Electrical Engineers
Job Hunting for Electrical Engineers
SSU Career Services1.1K visualizações
Introduction & design cable pathwaysIntroduction & design cable pathways
Introduction & design cable pathways
Jeffrey Lam2.4K visualizações
unchacharunchachar
unchachar
Aditi Tiwari942 visualizações

Similar a UPS Electrical Design and Installation

Wsp hospital eWsp hospital e
Wsp hospital eJac van Megen
215 visualizações3 slides
UPS Working, UPS TypesUPS Working, UPS Types
UPS Working, UPS TypesBhim Avarade
610 visualizações6 slides
Wsp data center eWsp data center e
Wsp data center eJac van Megen
276 visualizações3 slides
Data center power infrastructureData center power infrastructure
Data center power infrastructureLivin Jose
574 visualizações9 slides

Similar a UPS Electrical Design and Installation(20)

 Running UPS in Economy Mode To Save Energy Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy
jerianasmith257 visualizações
Wsp hospital eWsp hospital e
Wsp hospital e
Jac van Megen215 visualizações
UPS Working, UPS TypesUPS Working, UPS Types
UPS Working, UPS Types
Bhim Avarade610 visualizações
Wsp data center eWsp data center e
Wsp data center e
Jac van Megen276 visualizações
Data center power infrastructureData center power infrastructure
Data center power infrastructure
Livin Jose574 visualizações
UPSUPS
UPS
Joseph D Souza2.4K visualizações
Uninterrupted power supplyUninterrupted power supply
Uninterrupted power supply
ashrafulislam293120 visualizações
Uninterruptable power supply Uninterruptable power supply
Uninterruptable power supply
atikul islam ashik120 visualizações
Wsp supermarkets eWsp supermarkets e
Wsp supermarkets e
Jac van Megen331 visualizações
Riello master-wrap-around-static-bypassRiello master-wrap-around-static-bypass
Riello master-wrap-around-static-bypass
Electrical and renewable energy engineering500 visualizações
Unit 3- power suppliesUnit 3- power supplies
Unit 3- power supplies
Balaji Bhanu46 visualizações
Electric vehicle and charging infra by link vue systemElectric vehicle and charging infra by link vue system
Electric vehicle and charging infra by link vue system
Mahesh Chandra Manav59 visualizações
Link vue system and solar pv power plant protectionLink vue system and solar pv power plant protection
Link vue system and solar pv power plant protection
Mahesh Chandra Manav123 visualizações
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen
42U Data Center Solutions112 visualizações
Advancements  in inverter technologyAdvancements  in inverter technology
Advancements in inverter technology
Bhanu Teja14.3K visualizações
Inverter docInverter doc
Inverter doc
Pavan Kumar Mallepoola251 visualizações
The working principle of upsThe working principle of ups
The working principle of ups
jayonline_4u66.8K visualizações
Riello master-mps-ups-datasheetRiello master-mps-ups-datasheet
Riello master-mps-ups-datasheet
Electrical and renewable energy engineering903 visualizações

Último(20)

CXL at OCPCXL at OCP
CXL at OCP
CXL Forum158 visualizações
Liqid: Composable CXL PreviewLiqid: Composable CXL Preview
Liqid: Composable CXL Preview
CXL Forum114 visualizações
MemVerge: Memory Viewer SoftwareMemVerge: Memory Viewer Software
MemVerge: Memory Viewer Software
CXL Forum106 visualizações
Green Leaf Consulting: Capabilities DeckGreen Leaf Consulting: Capabilities Deck
Green Leaf Consulting: Capabilities Deck
GreenLeafConsulting147 visualizações
Java Platform Approach 1.0 - Picnic MeetupJava Platform Approach 1.0 - Picnic Meetup
Java Platform Approach 1.0 - Picnic Meetup
Rick Ossendrijver20 visualizações
Photowave Presentation Slides - 11.8.23.pptxPhotowave Presentation Slides - 11.8.23.pptx
Photowave Presentation Slides - 11.8.23.pptx
CXL Forum110 visualizações
AMD: 4th Generation EPYC CXL DemoAMD: 4th Generation EPYC CXL Demo
AMD: 4th Generation EPYC CXL Demo
CXL Forum113 visualizações

UPS Electrical Design and Installation

  • 1. Important considerations for the electrical design and installation of UPS systems in mission critical applications UPS Electrical Design and Installation criticaPOWER SUPPLIES Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928
  • 2. Where Critical Power applications are concerned, the electrical design and installation of a UPS (uninterruptible power supply) system is crucially important for several reasons.   Firstly, it must work in alignment with installations already on site and not interfere with other electrical equipment.This is particularly important for industrial and healthcare installations where there may already be critical equipment (medical and life support, for example) in operation.   It all starts with a site survey.   A pre-installation site survey will reveal details about the scope of the electrical work to be undertaken. Such information will reveal, for instance, the type of electrical loads, power quality issues, harmonics, whether it is a high, medium or low voltage installation and electrical distribution set up, including the breaker sizes already on site and their discrimination.   It is important to mention that all electrical work within critical power installations has to be carried out by suitably qualified, certified and registered electrical engineers. It should also be carried out in accordance with local, national and organisational guidelines. In the UK, the latest applicable industry standards are The Institution of Engineering and Technology (IET) – BS 7671 IEE Wiring Regulations Seventeen Edition and Electricity at Work Regulations 1989.   Electrical work involved The scope and complexity of the electrical work involved will depend upon the size and intricacy of the installation itself but it will probably include: Cable installation (from ac mains power source to UPS; from the UPS output to a distribution system, between the UPS and battery set, generator and/or other alternative power sources. The installation of additional power sockets or fused spurs. Upgrading supply ratings, cable and distribution boards. Installing electrical switchgear panels and maintenance bypasses. Running alarm cables to remote panels or network connection points.   If you would like to find out more about electrical design, installation, UPS power protection and energy management, get in touch www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 39281
  • 3. There are several items to bear in mind when designing an electrical installation, all of which will influence power quality, reliability, stability and the installation itself.   Elements to bear in mind when designing a UPS Electrical Installation:   Protection discrimination Protection discrimination is how two or more protective devices within a supply circuit are coordinated to ensure any loads that develop a fault condition (overload, short-circuit or earth fault) are quickly removed without disruption to other loads.   Protection discrimination sets out to protect the supply conductors of devices. It basically ensures each section within a supply distribution system is individually protected.The implementation of a suitable discrimination path is critically important within a UPS installation for protecting the UPS themselves and also the critical loads attached to them.   Devices for protection discrimination include: fuses, circuit-breakers or Residual Current Devices (RCD), which must be chosen based on their rating and suitability for the application.They have different operating characteristics i.e., speed of response and different types of circuit-breaker can be rated the same but react differently in overload conditions. For example, a 20A circuit-breaker type A may disconnect within 0.1 seconds with an overload current of just 100A.Type B circuit-breaker (also 20A) may not trip until it receives a current of 400A. Care must be taken when selecting the right type within a UPS application to prevent nuisance tripping at start up.   The more robust circuit-breaker, one that can sustain higher overloads for longer periods, is recommended for use with loads with high inrush currents such as some types of UPS (transformer-based) and motor loads/motor machinery. The more responsive circuit-breakers are suitable for more sensitive equipment such as computer and telecom loads. Power quality. Load types. Load size. Type of UPS (Online, line-interactive or offline). Back-up power system (battery banks) and recharge time. Voltage optimisations. Remote environmental management and monitoring. Upgrades that may be required to the existing electrical infrastructure. Additional cooling loads. If you would like to find out more about electrical design, installation, UPS power protection and energy management, get in touch www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928 2
  • 4. The curse of harmonics As electrical systems get busier with ever increasing equipment added in to already overcrowded distribution networks, harmonic pollution is on the increase and it needs to be considered from the outset.   In the EU, the electrical supply industry is required to meet EN 50160 – Voltage Characteristics of Electricity Supplied by Public Distribution Systems and it includes guidelines on harmonic voltage distortion. In the UK, permitted harmonic levels are also specified in G5/4-1. Permitted harmonic limits vary depending on whether the supply is high, medium or low voltage.A high voltage network is likely to have low impedance, which allows a larger harmonic content load to be connected.   The influence of Power Factor Invariably, power factor correction will be part of most UPS electrical installations these days.Although they are getting better, some electrical equipment (particularly older devices) will have poor power factor, which means their load is out of phase with the voltage waveform of the electrical supply.This will result in inefficiencies plus it places additional demands on supply connections and peripheral equipment such as cabling, conductors, transformers and distribution boards.   The closer the input power factor of the UPS is to Unity (1), the lower the amount of reactive power generated and the more efficiently the UPS system will run. Installing passive harmonic filters can improve things but because of the way in which a phase-controlled rectifier operates, performance will remain load related.   Cable sizing and installation It is imperative to select and specify the correct type and size of cabling in UPS installations. Failure to do so can result in overheating, fire risk and premature failure. It is also important to select the best method of installation alongside the most optimum routing.The same cable sizes should be installed for input and output and the selected cable should provide continuous full thermal current rating.  A Site Survey will reveal the length of cable required and what voltage drop should be catered for within the project specification and what size lugs are required. If you would like to find out more about electrical design, installation, UPS power protection and energy management, get in touch www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 39283
  • 5. Downstream protection It is important to ensure downstream protection and discrimination is applicable for the type of UPS and how it operates: normal operation with mains power supply present or battery operation with no mains power supply present.   During normal operation with mains power supply present, any fault or short-circuit on the output of the UPS will result in the load being transferred to the bypass.This will allow the full capacity of the mains power supply to clear the downstream fault. Once cleared, the UPS will transfer the load back to the inverter and resume normal operation.   During battery operation (with no mains power present), a fault condition on the output of the UPS will result in a restriction on energy available in an attempt to clear the fault. Once cleared, the UPS will continue supplying the loads from the battery set. If, however, the UPS does not have enough power to clear the load it will shut down in order to protect itself and connected downstream loads.This is referred to as ‘current limiting’.This means the type and current rating of downstream devices is an important consideration to ensure discrimination occurs during both modes of operation.There are several options for downstream protection: Sized in accordance with the rating for each UPS module to which they are connected (input cables). Rated to either the supply or the maximum output power available from each UPS module (output cables). Input and output cables should be the same length to ensure an even power distribution. Parallel Systems connection Parallel UPS can be installed with either a single or dual input power supply but the overall rating must be adequate enough to supply the parallel UPS irrespective of operation (capacity or redundancy).   In a parallel capacity system, the ac supply must be rated to the maximum input current of each UPS module, multiplied by the total UPS units in the system.Within a parallel redundant UPS configuration, the supply rating can be the same as that used for a parallel capacity system or equal to the total current required by each of the individual UPS modules (plus 10% to allow for charging and system losses). Cables in a parallel UPS system should be: Galvanic isolation – how this is set up depends upon where the isolation transformer is to be installed and with which type of online UPS and whether it has a single or dual input supply.Transformerless UPS require two isolation transformers on the input side to provide complete neutral separation. Maintenance bypasses – there are various types of maintenance bypass available, including internal and external. For UPS below 5kVA, external bypasses are typical and they usually have an additional automatic transfer facility. Surge protection on mains 1 and 2 (as chosen through discussions with the client). Lightning protection - modern buildings typically cover this requirement, but it should also be covered in the site survey just to be sure. If you would like to find out more about electrical design, installation, UPS power protection and energy management, get in touch www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928 4
  • 6. Dual input connection - fed by unique breakers or linked? UPS resilience is further increased through the commonly held practice of using dual ac power sources rather than a single one. Dual input connection allows the rectifier and bypass to be supplied from separate sources, which could be different sub-stations, to protect against a single point of failure.   Transformer-based UPS are supplied with dual input terminals as standard.With transformerless UPS, it is slightly different as the rectifier and bypass supplies require a common neutral connection. It can still be installed with a dual input but with supplies derived from the same source and the dual input feature is not standard but a factory fit option.   Earthing and Bonding for UPS and battery racks To protect equipment (and the installation itself) from overheating, premature failure and fire risk, it is mandatory that live conductors are protected from overloads, short-circuits and earth faults.The earthing and bonding of UPS equipment depends upon the type of electrical supply installed.There are four common types:   TN-C-S – the most common and uses Protective Multiple Earthing (PME) in which neutral and earthed protective conductors are combined in part of the system.   TN-C – in which neutral and earthed conductors are combined throughout the system.This type also uses PME.   TN-S – in which the neutral and earthed conductors remain separate throughout.   TT – in which neutral is earthed at the power source but the electricity supplier does not provide an earthed protective conductor.   It is inadvisable within UPS systems to connect the output neutral to the incoming earth. If neutral-to-earth connection is required an isolation transformer should be installed on the UPS output.   Earthing and bonding for generators With regard to generators within a UPS power protection system, it is important that care is taken around neutral connections.This is because UPS and generators rely on breaking the neutral when switching to and from the generator supply. But this relies on the UPS being able to withstand a break in supply neutral during changeover.   The most common form of switching mechanism employed in generator installation uses two individual but electrically interlocked contactors. Controlled by the AMF (Automatic Mains Failure) panel, these select between incoming mains power or generator output.This method is relatively inexpensive but it is not necessarily the best, particularly for installations requiring a fixed neutral between changeover as it is slow and could take several cycles for the change to occur.   A better system is a make-before-break contact method that ensures the neutral stays fixed during changeover.Another option for maintaining a fixed neutral is to install an isolation transformer and this can also help address problems associated with harmonics.   If you would like to find out more about electrical design, installation, UPS power protection and energy management, get in touch www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 39285
  • 7. UPS and Generators UPS and generators have to be compatible and suitably matched in terms of sizing.The generator must be able to accept the UPS loads and the UPS (rectifier and static bypass supplies) must be able to operate with and synchronise to the output of the generator. Generator and UPS interfacing is also an issue that requires consideration. It is often necessary for the UPS to interface with the generator for control purposes. Cable runs may be needed for both electrical and communications signals (to make a connection, for example, between the UPS, generator and AMF panel (which may be monitored remotely).   Electrical Testing and Certification  As with all electrical installations, hardwired UPS systems require electrical testing and certification and this has to be carried out by certified electrical contractors.Testing regimes will vary in accordance with the size and scope of each installation but they could include Earth fault loop impedance testing.   Downstream Distribution and left and right PDUs both on UPS or only one and the type of PDU required as there are three types. If you would like to find out more about electrical design, installation, UPS power protection and energy management, get in touch www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928 The whole point of a power protection system is to keep the lights on when mains power goes off and electrical design and installation plays a key role in ensuring that happens. Get it wrong and you could end up with no power protection at all, get it right and you could ensure power continuity, increased efficiency and save your customer many £thousands in electricity bills. A site survey is vital; knowing what you are working with at the outset is a great starting point.After that, it’s a case of making sure you understand the technology you are working with, have the experience to make it work and know what the customer wants.The importance of expertise in this area cannot be overstated.At Critical Power Supplies, we have the experience, knowledge and qualifications to get the job done cost-effectively.We are also manufacturer independent and supply most of the leading brands available in the market today.We are accredited by the manufacturers to work on their equipment, which saves you time having to search around for a specialist. Basic Monitored Managed   It is worth remembering that Metered PDUs should be considered as a bare minimum to ensure the load supported by the PDU does not exceed the supply breaker size otherwise overloading could pull the breaker open thus dropping the load without notice. 6
  • 8. Critical Power Supplies is a specialist provider of power protection and energy management products and services. We work hard to ensure our customers’ uptime, system availability and optimised energy consumption. We supply products from leading manufacturers and we are particularly skilled and experienced in UPS electrical design and installation. If you’d like to talk to us about any projects you have coming up – in confidence and under no obligation – please get in touch. Data Centres Finance IT Telecommunications Industrial Marine Security Emergency Transport Medical Markets Accreditation and Compliance Our customers often operate in highly regulated industries in which accreditation is a legal requirement.The fact that we are accredited means customers can rest assured our staff, suppliers, products and services comply with the latest standards and regulations. In dealing with us, your own regulatory compliance remains in tact. If you require any further information, or would like an informal chat about power continuity, critical power, standby power or power protection systems in general, get in touch.We are at your service. www.criticalpowersupplies.co.uk Sales: 0800 978 8988 Fax: 0845 519 3639 24 hour Service: 0845 519 3928 criticaPOWER SUPPLIES