Fire
A guide to fire alarm systems design
BS 5839 Part 1:2002
The Fire Installers Mate
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 1
2
A guide to
BS 5839 Part 1:2002
Disclaimer
This booklet is not intended to be a
comprehensive guide to all aspects of
fire alarm design but rather a very useful
source of background information.
Whilst every care has been taken to ensure
that the contents of this document are
correct at the time of publication, it should
never be used as any form of substitution
for the BS 5839 standard itself. Cooper
Safety shall be under no liability
whatsoever in respect to such contents.
It should be noted that there may be
specific additional requirements dependent
upon local authority building regulations
and/or fire authority.
Please use this guide in conjunction with
a current issue of the BS 5839 standard.
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 2
3
P1 P2
L1 L2L3L4
Property Protection Fire Systems
P AFD designed to primarily
protect property categories:
P1 AFD installed throughout all
areas
P2 AFD installed only in defined
areas
Life Protection Fire Systems
L AFD designed to primarily
protect human life categories:
L1 M plus AFD installed throughout
all areas
L2 AFD installed in defined areas of
higher risk of ignition, in addition
to L3
L3 M plus AFD installed in escape
routes and rooms opening into
these routes
L4 M plus AFD installed in escape
routes comprising circulation
areas and space such as
corridors and stairways
L5 A non-prescriptive system in
which protected area(s) and/or
the location of detectors is
designed to satisfy a specific fire
risk objective (other than that of
L1 to L4)
M System designed to be operated
manually (no AFD)
AFD - Automatic Fire Detection
Categorisation of fire alarm and detection systems
BS5839Clause5
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 3
4
65dB(A)
@
500Hz to 1000Hz
+5dB(A)
@
500Hz to 1000Hz
Backgroundnoise
The minimum sound level of a sounder device should be 65dB(A) or 5dB(A)
above a background noise (if lasting more than 30 seconds) and at a frequency
between 500Hz and 1000Hz. The maximum sound level should not exceed
120dB(A).
Sounder device cabling should be arranged so that in the event of a fault at
least one sounder located within the vicinity of the control and indicating panel
will remain in operation.
BS5839Clause16.2.1BS5839Clause16.2.1
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 4
60m MAX
45m MAX
The maximum zone floor area should not exceed 2000m2. A person searching
a zone for a fire should not have to travel more than 60m from the zone
entrance to identify the source of the fire.
A person should not have to travel more than 45m along an escape route to
reach a manual callpoint, when the layout of the building is known.
BS5839Section13.2.3BS5839Clause20.2
5
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 5
6
1.4m
(+/-200mm)
2.1m
The centre of the element of the manual callpoint should be positioned 1.4m
(+/-200mm) from floor level (unless a wheelchair user is likely to be the first
person to raise the alarm, when this is applicable it should be noted on any
certification).
Visual alarms such as beacons should always be mounted at a minimum height
of 2.1m from floor level, in a position that is likely to attract attention.
BS5839Clause20.2hBS5839Clause17
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 6
2m
75dB(A)
Unless MICC or armoured cable to BS7846 standard is used, consideration
should be given to the protection against physical damage from floor level to
the height of 2m. Except in relatively benign areas, such as shops, offices and
similar, where cabling can be clipped to robust walls.
For areas where people are sleeping, sounder devices should produce a
minimum 75dB(A) at the bed-head with all doors shut. In buildings likely to
provide sleeping accommodation for the hearing impaired, consideration
should be given to the incorporation of both audio and visual devices.
BS5839Clause26.2BS5839Clause16.2.1
7
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 7
Smoke detectors
5.3m
10.6m x 10.6m = 112m2
10.6m
7.5m
Heat detectors
3.8m
7.5m x 7.5m = 56.3m2
7.5m
5.3m
When mounted on a flat ceiling, smoke detection devices have an individual
coverage of 7.5m radius. However these radii must overlap to ensure there are
no ‘blind spots’. Therefore individual coverage can be represented by a square
measuring 10.6 x 10.6m giving an actual coverage area of 112m2 per device.
When mounted on a flat ceiling, smoke detection devices have an individual
coverage of 5.3m radius. However these radii must overlap to ensure there are
no ‘blind spots’. Therefore individual coverage can be represented by a square
measuring 7.5 x 7.5m giving an actual coverage area of 56.3m2 per device.
BS5839Clause22.3BS5839Clause22.3
8
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 8
In corridors less than 2m wide the horizontal spacing of detectors can be
increased, the area of coverage need not overlap as in the case of a room.
Any corridor over 2m wide is deemed as a room and most adhere as
specified (see page 8).
Please note: Heat detectors are not recommended for use in corridors that
may be used as escape routes.
9
Smoke detectors15m MAX7.5m MAX
2m
BS5839Clause22.3
For ease of design and assessment of coverage dimensions used for
detectors are usually taken as:
Smoke: 5m to wall / 10m between detectors
Coverage 100m2
Heat: 3.5m to wall / 7m between detectors
Coverage 50m2
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 9
10
X
<1m >1m
Air vent / Air con
Decibel loss occurs through doors: Approximately -20dB(A) through a normal
door, and approximately -30dB(A) through a fire door. Unless a sounder is
installed in a bedroom, it is unlikely that 75dB(A) will be achieved.
Do not site detectors less than 1m from air inlets or air circulating systems.
BS5839Clause22.3
Firedoor
BS5839Clause16.2.1
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 10
Apex < 150mm
Heat detector
Apex < 600mm
Smoke detector
Treat as a flat ceiling
Apex > 600mm
Smoke detector
Apex > 150mm
Heat detector
Ceiling with a apex
For ceilings that feature an apex: As long as the height of the apex from
the rest of the ceiling is less than 150mm for heat detectors or less
than 600mm for smoke detectors, then these can be treated the same
as flat ceilings. For higher apexes, a device should be installed at the
highest point. The distance to adjacent devices can be increased by
1% per degree of angle of the roof up to a maximum of 25%.
BS5839Clause22.3
11
Detector Type Ceiling Heights (m)
General Limits Rapid Attendance*
(category P systems only)
Heat Detectors
EN54-5
9.0 13.5
7.5 12.0
Point Smoke & CO Fire Detectors 10.5 15.0
Aspirating Smoke Normal 10.5 Normal 15.0
Detection Systems Enhanced 12.0 Enhanced 17.0
(category 1) Very high 15.0 Very high 21.0
Optical Beam Smoke Detectors
EN54-2 25.0 40.0
Class A1
Other Classes
* Rapid attendance within 5 minutes
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 11
12
Z x 2
X
ZLight fitting/obstructuion
A device should not be mounted within 500mm of any obstruction. If the top of
a solid partition is less than 300mm from the ceiling then it should be treated
as a wall. Similary, ceiling obstructions such as beams should be treated as
walls if deeper than 10% of the ceiling height (particularly important in voids).
For obstructions less than 250mm deep never mount devices closer than twice
the depth of light fittings or other obstructions in the ceiling.
BS5839Clause22.3
Beam
Partition
>10%
ceiling
height
<500mm
X
<500mm
X <300mm
BS5839Clause22.3
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 12
>800mm
Lift Shaft Lift Shaft
1.5m
Voids less than 800mm in height are required to have a risk assessment to
determine if AFD is required. Voids in excess of 800mm do require independent
coverage.
Vertical shafts like lift shafts and stairways should have a device mounted
within 1.5m of any opening.
BS5839Clause22.2BS5839Clause22.2
13
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 13
14
X
10
20
30
40
50
60
70
80
90
100
Time of day
<29°C
<4°C Maximum temperature
Average ambient temperature
X
X
Temperature
Enclosed stairways should have a detector on the top of the stairway and on
each main landing.
The minimum static response to heat devices should not be less than 29o
C
above the average ambient temperature, or less than 4o
C above the highest
temperature the device can be expected to experience.
BS5839Clause22.2BS5839Clause35.2.3
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 14
Smoke detectors
Optical/Ionisation Chamber
X 25mm
600mm
X
Heat detector
Thermistor
X 25mm
150mm
X
The sensing element of a smoke detection device (optical smoke chamber)
should not be less than 25mm below the ceiling, and not greater than 600mm
below the ceiling.
The sensing element of a heat detection device should not be less than 25mm
below the ceiling, and not greater than 150mm below the ceiling.
BS5839Clause22.3BS5839Clause22.3
15
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 15
16
Second
Ground
First
Zone 1
Zone 2
Zone 3
Zone 4
Zone 1
Zone 2
Zone 3
Zone 4
Zone 2
Zone 3
X
Less than 300m2 can be covered by a single zone. When the total floor area
exceeds 300m2, each floor would require a zone (or zones if the floor area
exceeds 2000m2) with access, stairwells or lifts covered by a zone each.
Zones should not cross floors.
BS5839Clause13.2BS5839Clause13.2
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 16
17
Mains supply
EOL fitted
EOL fitted
To comply with the current version of the BS 5839 Part 1, the use of fire
resistant cables are required for all critical circuits, this includes detection,
sounders and mains supply.
On a loop system, short circuit isolators are required to limit the effect of one
fault to less than 2000m2 floor area. 2 simultaneous faults on a circuit should
not disable protection within an area greater than 10,000m2.
BS5839Clause26BS5839Clause12.2.2
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 17
18
For local isolation during maintenance, a suitable double pole isolator should be provided, suitably
marked (25.2c & f).
Cables used for all critical paths, i.e. detector, sounder and the mains supply should be wired in fire
resistant cable with a minimum cross sectional area of 1 mm² (26.2j).
Enhanced fire resistant cables should be used in unsprinklered buildings where evacuation takes
place in 4 or more phases, where the building is more than 30 m in height, or the risk assessment
deems it necessary (26.2c).
Cables require to be retained in position by a suitable fire resistant method. This requires that
should plastic trunking be used, the cables must be clipped inside the trunking. Also plastic cable
ties should NOT be used (26.2f).
Control equipment should be sited in a position which is easily accessible to both staff and fire-
fighters (23.2.1).
Call points are required at ALL exits to the open air and storey exits. Operation should be of a
similar type (20.2).
If multi sensors are used, if it is possible, select the operation of a particular sensor then the
detectors require to be spaced to suit the space of the lower coverage sensor i.e. a combined heat
/ smoke detector, spacing would be as a heat detector (21.1.6).
All sounders in a building should have a similar sound, this precludes the mixing of bells and
electronic sounders (16.2.1c).
If the background noise exceeds 90 dB(A) or where hearing protection is likely to be used, then
visual alarm devices are required (17.2a).
Disabled persons toilets require to be fitted with visual alarm devices (18.1).
The user of the system should be provided with adequate records and documentation (40.1).
On completion of each process suitable certification should be provided by the organisations
responsible for each stage of the system i.e. design, installation and commissioning (41.2).
Installation Considerations and Key Points
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 18
19
1 The system complies with original specification / design, if any changes have been made
they have been approved by the designer.
2 System has been installed to meet the requirements of specified category, if not specified or
known, commissioning engineer should state category that system appears to be installed to.
3 Wiring of detector / sounder circuits and mains supply wired in required fire resistant
cable, standard or enhanced.
4 Cables are segregated and mechanically protected as required, suitably supported (no
plastic clips, cable ties or trunking as the sole means of support) as per the cable
manufacturers requirements.
5 Mains supply is a dedicated supply, suitably fused, and provides local double pole isolation
which is correctly labelled.
6 Junction boxes are correctly labelled, identified on drawings, and use fire resistant terminal
blocks.
7 All cable continuity and insulation resistance results are recorded.
8 Current requirements of the system under quiescent and alarm conditions are measured
and relevant calculations carried out to ensure standby battery(s) are suitable for system
requirements.
9 All standby batteries are clearly marked with date of installation, such that this date can be
seen without removing batteries from equipment.
10 Minimum of two sounders are installed on a minimum of two sounder circuits
i.e. at least one sounder on each of two sounder circuits.
11 Circuit wiring is correctly labelled and terminated in all control and ancillary equipment.
12 Sound pressure levels have been checked and recorded, and meet the requirements of
BS 5839 Part 1.
13 Detector type and spacing have been checked and are installed to meet the required system
category.
14 Manual call points are located correctly and travel distance is appropriate to the usage of the
building.
15 Remote signalling has been checked to ensure correct operation, to relevant point of reception.
16 Zone chart(s) have been located in all appropriate locations i.e. adjacent to all control
equipment and repeaters.
17 As fitted drawings are complete and have been updated where required.
18 Log book and operating instructions have been given to the responsible person.
19 Relevant certification is provided to user or purchaser of the system.
20 Responsible person(s) have been provided with adequate training in the operation of the
system and the avoidance of false alarms.
Please note that this check list should only be taken as a suggested list and
reference to the appropriate sections of BS 5839 part 1 is advised. Appropriate
certification should also be completed.
Suggested Installation / Commissioning / Handover Checklist
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 19
Cooper Lighting and Safety Ltd - UK
Wheatley Hall Road, Doncaster, South Yorkshire. DN2 4NB.
www.cooperfire.com
Sales
T: +44 (0)1302 303999
F: +44 (0)1302 303333
E: sales@cooperfire.com
Technical
T: +44 (0)1302 303350
F: +44 (0)1302 303332
E: techsupport@cooperfire.com
Export
T: +44 (0)1302 303250
F: +44 (0)1302 303251
E: export@cooperfire.com
Service
T: +44 (0)1302 303352
F: +44 (0)1302 303332
E: mvdo-service@cooperindustries.com
Ireland
T: 00 353 6671 42858
F: 00 353 6671 42861
CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 20

More Related Content

What's hot

Scada and power system automation
Scada and power system automationScada and power system automation
Scada and power system automationShubham Kapoor
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisationmanogna gwen
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technologyArman Nasar
 
Fire alarm , detection and suppression system
Fire alarm , detection and suppression systemFire alarm , detection and suppression system
Fire alarm , detection and suppression systemKamran Hassan
 
UNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATIONUNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATIONPremanandDesai
 
Basic elements in control systems
Basic elements in control systemsBasic elements in control systems
Basic elements in control systemsSatheeshCS2
 
Building management system (bms)
Building management system (bms)Building management system (bms)
Building management system (bms)AHMED NADIM JILANI
 
Building Service Chapter 1
Building Service Chapter 1Building Service Chapter 1
Building Service Chapter 1Izam Lukman
 
Lighting systems 2014
Lighting systems 2014Lighting systems 2014
Lighting systems 2014ahmed salman
 
Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11grantlerc
 
Building Energy Management Systems
Building Energy Management SystemsBuilding Energy Management Systems
Building Energy Management SystemsPrashanth Dommeti
 
Ices chapter 8 - illumination engineering
Ices   chapter 8 - illumination engineeringIces   chapter 8 - illumination engineering
Ices chapter 8 - illumination engineeringChandrabhan Sharma
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Vijay Kumar
 
Electrical supply &amp; distribution
Electrical supply &amp; distributionElectrical supply &amp; distribution
Electrical supply &amp; distributionYingHongKang
 
Occupancy sensors
Occupancy sensorsOccupancy sensors
Occupancy sensorsJhelum
 
Illumination basic and lightning scheme
Illumination basic and lightning schemeIllumination basic and lightning scheme
Illumination basic and lightning schemeADARSH KUMAR
 

What's hot (20)

Scada and power system automation
Scada and power system automationScada and power system automation
Scada and power system automation
 
Grid synchronisation
Grid synchronisationGrid synchronisation
Grid synchronisation
 
Fire Alarm System, BMS
Fire Alarm System, BMSFire Alarm System, BMS
Fire Alarm System, BMS
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
 
Fire alarm , detection and suppression system
Fire alarm , detection and suppression systemFire alarm , detection and suppression system
Fire alarm , detection and suppression system
 
UNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATIONUNIT - 03 LIGHTING INSTALLATION
UNIT - 03 LIGHTING INSTALLATION
 
PLC Troubleshooting & Maintenance
PLC Troubleshooting & MaintenancePLC Troubleshooting & Maintenance
PLC Troubleshooting & Maintenance
 
Basic elements in control systems
Basic elements in control systemsBasic elements in control systems
Basic elements in control systems
 
Building management system (bms)
Building management system (bms)Building management system (bms)
Building management system (bms)
 
Building Service Chapter 1
Building Service Chapter 1Building Service Chapter 1
Building Service Chapter 1
 
Lighting systems 2014
Lighting systems 2014Lighting systems 2014
Lighting systems 2014
 
Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11Fire basics 1-2-the_nec_11
Fire basics 1-2-the_nec_11
 
Building Energy Management Systems
Building Energy Management SystemsBuilding Energy Management Systems
Building Energy Management Systems
 
Ices chapter 8 - illumination engineering
Ices   chapter 8 - illumination engineeringIces   chapter 8 - illumination engineering
Ices chapter 8 - illumination engineering
 
Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings Guidelines for electrical wiring in residential buildings
Guidelines for electrical wiring in residential buildings
 
Profibus project management, design and component selection andy smith
Profibus project management, design and component selection   andy smithProfibus project management, design and component selection   andy smith
Profibus project management, design and component selection andy smith
 
BMSOverview
BMSOverviewBMSOverview
BMSOverview
 
Electrical supply &amp; distribution
Electrical supply &amp; distributionElectrical supply &amp; distribution
Electrical supply &amp; distribution
 
Occupancy sensors
Occupancy sensorsOccupancy sensors
Occupancy sensors
 
Illumination basic and lightning scheme
Illumination basic and lightning schemeIllumination basic and lightning scheme
Illumination basic and lightning scheme
 

Viewers also liked

fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm systemsingh1515
 
Basic Fire Alarm Systems
Basic Fire Alarm SystemsBasic Fire Alarm Systems
Basic Fire Alarm Systemsmalcolmfd
 
Fire alarm
Fire alarmFire alarm
Fire alarmarjunex
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline1234marvin
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline1234marvin
 
a1-cbiss Gas Detectors Brochure
a1-cbiss Gas Detectors Brochurea1-cbiss Gas Detectors Brochure
a1-cbiss Gas Detectors Brochurea1-cbiss
 
Sprinkler Spacing
Sprinkler SpacingSprinkler Spacing
Sprinkler Spacingsherylwil
 
Fire, flame & smoke detectors
Fire, flame & smoke detectorsFire, flame & smoke detectors
Fire, flame & smoke detectorsAkaash Sahoo
 
Somke detector project presentation
Somke detector project presentationSomke detector project presentation
Somke detector project presentationRija Fatima
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm SystemsJ.T.A.JONES
 

Viewers also liked (12)

fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
Basic Fire Alarm Systems
Basic Fire Alarm SystemsBasic Fire Alarm Systems
Basic Fire Alarm Systems
 
Fire alarm
Fire alarmFire alarm
Fire alarm
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline
 
a1-cbiss Gas Detectors Brochure
a1-cbiss Gas Detectors Brochurea1-cbiss Gas Detectors Brochure
a1-cbiss Gas Detectors Brochure
 
Sprinkler Spacing
Sprinkler SpacingSprinkler Spacing
Sprinkler Spacing
 
Fire, flame & smoke detectors
Fire, flame & smoke detectorsFire, flame & smoke detectors
Fire, flame & smoke detectors
 
Fire detection & alarm system
Fire detection & alarm systemFire detection & alarm system
Fire detection & alarm system
 
Basics of Fire fighting
Basics of Fire fightingBasics of Fire fighting
Basics of Fire fighting
 
Somke detector project presentation
Somke detector project presentationSomke detector project presentation
Somke detector project presentation
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
 

Similar to Cc1608 fire systems design guide

Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0Domotica daVinci
 
Edwards Signaling CS405-7A-T Installation Manual
Edwards Signaling CS405-7A-T Installation ManualEdwards Signaling CS405-7A-T Installation Manual
Edwards Signaling CS405-7A-T Installation ManualJMAC Supply
 
Murco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetMurco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetThorne & Derrick UK
 
Proposed_Floorplans_Professional Practice_DS_Group-A0@100 Firesaftey
Proposed_Floorplans_Professional Practice_DS_Group-A0@100 FiresafteyProposed_Floorplans_Professional Practice_DS_Group-A0@100 Firesaftey
Proposed_Floorplans_Professional Practice_DS_Group-A0@100 FiresafteyJermaine Barrett
 
Burglar alarm basics-8
Burglar alarm basics-8Burglar alarm basics-8
Burglar alarm basics-8grantlerc
 
SenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbookSenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbookHans Bronkhorst
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdfssuser06d7b51
 
Drager Flame 3000 - Fixed Flame Detector - Spec Sheet
Drager Flame 3000 - Fixed Flame Detector - Spec SheetDrager Flame 3000 - Fixed Flame Detector - Spec Sheet
Drager Flame 3000 - Fixed Flame Detector - Spec SheetThorne & Derrick UK
 
SenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbookSenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbookHans Bronkhorst
 
Cordex 2301XP Hazardous Area ATEX Certified Digital Camera - User Manual
Cordex 2301XP Hazardous Area ATEX Certified Digital Camera - User ManualCordex 2301XP Hazardous Area ATEX Certified Digital Camera - User Manual
Cordex 2301XP Hazardous Area ATEX Certified Digital Camera - User ManualThorne & Derrick International
 
Kidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLKidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLHans Bronkhorst
 
Emergency Lighting- David Wright
Emergency Lighting- David WrightEmergency Lighting- David Wright
Emergency Lighting- David WrightFagerhult Lighting
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishHans Bronkhorst
 
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Thorne & Derrick International
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Shubham .
 

Similar to Cc1608 fire systems design guide (20)

Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0
 
Edwards Signaling CS405-7A-T Installation Manual
Edwards Signaling CS405-7A-T Installation ManualEdwards Signaling CS405-7A-T Installation Manual
Edwards Signaling CS405-7A-T Installation Manual
 
RIVPF_GB_LOCAL
RIVPF_GB_LOCALRIVPF_GB_LOCAL
RIVPF_GB_LOCAL
 
Murco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetMurco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data Sheet
 
Proposed_Floorplans_Professional Practice_DS_Group-A0@100 Firesaftey
Proposed_Floorplans_Professional Practice_DS_Group-A0@100 FiresafteyProposed_Floorplans_Professional Practice_DS_Group-A0@100 Firesaftey
Proposed_Floorplans_Professional Practice_DS_Group-A0@100 Firesaftey
 
Burglar alarm basics-8
Burglar alarm basics-8Burglar alarm basics-8
Burglar alarm basics-8
 
SenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbookSenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbook
 
Alarmline digital manual
Alarmline digital manualAlarmline digital manual
Alarmline digital manual
 
CINT alarm systems
CINT alarm systemsCINT alarm systems
CINT alarm systems
 
FIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdfFIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdf
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdf
 
Drager Flame 3000 - Fixed Flame Detector - Spec Sheet
Drager Flame 3000 - Fixed Flame Detector - Spec SheetDrager Flame 3000 - Fixed Flame Detector - Spec Sheet
Drager Flame 3000 - Fixed Flame Detector - Spec Sheet
 
Panel
PanelPanel
Panel
 
SenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbookSenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbook
 
Cordex 2301XP Hazardous Area ATEX Certified Digital Camera - User Manual
Cordex 2301XP Hazardous Area ATEX Certified Digital Camera - User ManualCordex 2301XP Hazardous Area ATEX Certified Digital Camera - User Manual
Cordex 2301XP Hazardous Area ATEX Certified Digital Camera - User Manual
 
Kidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NLKidde Alarmline SenseTek-NL
Kidde Alarmline SenseTek-NL
 
Emergency Lighting- David Wright
Emergency Lighting- David WrightEmergency Lighting- David Wright
Emergency Lighting- David Wright
 
SenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet englishSenseTek FFE fireray 2000e exd datasheet english
SenseTek FFE fireray 2000e exd datasheet english
 
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 

Recently uploaded

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 

Recently uploaded (20)

Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 

Cc1608 fire systems design guide

  • 1. Fire A guide to fire alarm systems design BS 5839 Part 1:2002 The Fire Installers Mate CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 1
  • 2. 2 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects of fire alarm design but rather a very useful source of background information. Whilst every care has been taken to ensure that the contents of this document are correct at the time of publication, it should never be used as any form of substitution for the BS 5839 standard itself. Cooper Safety shall be under no liability whatsoever in respect to such contents. It should be noted that there may be specific additional requirements dependent upon local authority building regulations and/or fire authority. Please use this guide in conjunction with a current issue of the BS 5839 standard. CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 2
  • 3. 3 P1 P2 L1 L2L3L4 Property Protection Fire Systems P AFD designed to primarily protect property categories: P1 AFD installed throughout all areas P2 AFD installed only in defined areas Life Protection Fire Systems L AFD designed to primarily protect human life categories: L1 M plus AFD installed throughout all areas L2 AFD installed in defined areas of higher risk of ignition, in addition to L3 L3 M plus AFD installed in escape routes and rooms opening into these routes L4 M plus AFD installed in escape routes comprising circulation areas and space such as corridors and stairways L5 A non-prescriptive system in which protected area(s) and/or the location of detectors is designed to satisfy a specific fire risk objective (other than that of L1 to L4) M System designed to be operated manually (no AFD) AFD - Automatic Fire Detection Categorisation of fire alarm and detection systems BS5839Clause5 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 3
  • 4. 4 65dB(A) @ 500Hz to 1000Hz +5dB(A) @ 500Hz to 1000Hz Backgroundnoise The minimum sound level of a sounder device should be 65dB(A) or 5dB(A) above a background noise (if lasting more than 30 seconds) and at a frequency between 500Hz and 1000Hz. The maximum sound level should not exceed 120dB(A). Sounder device cabling should be arranged so that in the event of a fault at least one sounder located within the vicinity of the control and indicating panel will remain in operation. BS5839Clause16.2.1BS5839Clause16.2.1 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 4
  • 5. 60m MAX 45m MAX The maximum zone floor area should not exceed 2000m2. A person searching a zone for a fire should not have to travel more than 60m from the zone entrance to identify the source of the fire. A person should not have to travel more than 45m along an escape route to reach a manual callpoint, when the layout of the building is known. BS5839Section13.2.3BS5839Clause20.2 5 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 5
  • 6. 6 1.4m (+/-200mm) 2.1m The centre of the element of the manual callpoint should be positioned 1.4m (+/-200mm) from floor level (unless a wheelchair user is likely to be the first person to raise the alarm, when this is applicable it should be noted on any certification). Visual alarms such as beacons should always be mounted at a minimum height of 2.1m from floor level, in a position that is likely to attract attention. BS5839Clause20.2hBS5839Clause17 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 6
  • 7. 2m 75dB(A) Unless MICC or armoured cable to BS7846 standard is used, consideration should be given to the protection against physical damage from floor level to the height of 2m. Except in relatively benign areas, such as shops, offices and similar, where cabling can be clipped to robust walls. For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at the bed-head with all doors shut. In buildings likely to provide sleeping accommodation for the hearing impaired, consideration should be given to the incorporation of both audio and visual devices. BS5839Clause26.2BS5839Clause16.2.1 7 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:56 Page 7
  • 8. Smoke detectors 5.3m 10.6m x 10.6m = 112m2 10.6m 7.5m Heat detectors 3.8m 7.5m x 7.5m = 56.3m2 7.5m 5.3m When mounted on a flat ceiling, smoke detection devices have an individual coverage of 7.5m radius. However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented by a square measuring 10.6 x 10.6m giving an actual coverage area of 112m2 per device. When mounted on a flat ceiling, smoke detection devices have an individual coverage of 5.3m radius. However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented by a square measuring 7.5 x 7.5m giving an actual coverage area of 56.3m2 per device. BS5839Clause22.3BS5839Clause22.3 8 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 8
  • 9. In corridors less than 2m wide the horizontal spacing of detectors can be increased, the area of coverage need not overlap as in the case of a room. Any corridor over 2m wide is deemed as a room and most adhere as specified (see page 8). Please note: Heat detectors are not recommended for use in corridors that may be used as escape routes. 9 Smoke detectors15m MAX7.5m MAX 2m BS5839Clause22.3 For ease of design and assessment of coverage dimensions used for detectors are usually taken as: Smoke: 5m to wall / 10m between detectors Coverage 100m2 Heat: 3.5m to wall / 7m between detectors Coverage 50m2 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 9
  • 10. 10 X <1m >1m Air vent / Air con Decibel loss occurs through doors: Approximately -20dB(A) through a normal door, and approximately -30dB(A) through a fire door. Unless a sounder is installed in a bedroom, it is unlikely that 75dB(A) will be achieved. Do not site detectors less than 1m from air inlets or air circulating systems. BS5839Clause22.3 Firedoor BS5839Clause16.2.1 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 10
  • 11. Apex < 150mm Heat detector Apex < 600mm Smoke detector Treat as a flat ceiling Apex > 600mm Smoke detector Apex > 150mm Heat detector Ceiling with a apex For ceilings that feature an apex: As long as the height of the apex from the rest of the ceiling is less than 150mm for heat detectors or less than 600mm for smoke detectors, then these can be treated the same as flat ceilings. For higher apexes, a device should be installed at the highest point. The distance to adjacent devices can be increased by 1% per degree of angle of the roof up to a maximum of 25%. BS5839Clause22.3 11 Detector Type Ceiling Heights (m) General Limits Rapid Attendance* (category P systems only) Heat Detectors EN54-5 9.0 13.5 7.5 12.0 Point Smoke & CO Fire Detectors 10.5 15.0 Aspirating Smoke Normal 10.5 Normal 15.0 Detection Systems Enhanced 12.0 Enhanced 17.0 (category 1) Very high 15.0 Very high 21.0 Optical Beam Smoke Detectors EN54-2 25.0 40.0 Class A1 Other Classes * Rapid attendance within 5 minutes CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 11
  • 12. 12 Z x 2 X ZLight fitting/obstructuion A device should not be mounted within 500mm of any obstruction. If the top of a solid partition is less than 300mm from the ceiling then it should be treated as a wall. Similary, ceiling obstructions such as beams should be treated as walls if deeper than 10% of the ceiling height (particularly important in voids). For obstructions less than 250mm deep never mount devices closer than twice the depth of light fittings or other obstructions in the ceiling. BS5839Clause22.3 Beam Partition >10% ceiling height <500mm X <500mm X <300mm BS5839Clause22.3 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 12
  • 13. >800mm Lift Shaft Lift Shaft 1.5m Voids less than 800mm in height are required to have a risk assessment to determine if AFD is required. Voids in excess of 800mm do require independent coverage. Vertical shafts like lift shafts and stairways should have a device mounted within 1.5m of any opening. BS5839Clause22.2BS5839Clause22.2 13 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 13
  • 14. 14 X 10 20 30 40 50 60 70 80 90 100 Time of day <29°C <4°C Maximum temperature Average ambient temperature X X Temperature Enclosed stairways should have a detector on the top of the stairway and on each main landing. The minimum static response to heat devices should not be less than 29o C above the average ambient temperature, or less than 4o C above the highest temperature the device can be expected to experience. BS5839Clause22.2BS5839Clause35.2.3 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 14
  • 15. Smoke detectors Optical/Ionisation Chamber X 25mm 600mm X Heat detector Thermistor X 25mm 150mm X The sensing element of a smoke detection device (optical smoke chamber) should not be less than 25mm below the ceiling, and not greater than 600mm below the ceiling. The sensing element of a heat detection device should not be less than 25mm below the ceiling, and not greater than 150mm below the ceiling. BS5839Clause22.3BS5839Clause22.3 15 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 15
  • 16. 16 Second Ground First Zone 1 Zone 2 Zone 3 Zone 4 Zone 1 Zone 2 Zone 3 Zone 4 Zone 2 Zone 3 X Less than 300m2 can be covered by a single zone. When the total floor area exceeds 300m2, each floor would require a zone (or zones if the floor area exceeds 2000m2) with access, stairwells or lifts covered by a zone each. Zones should not cross floors. BS5839Clause13.2BS5839Clause13.2 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:57 Page 16
  • 17. 17 Mains supply EOL fitted EOL fitted To comply with the current version of the BS 5839 Part 1, the use of fire resistant cables are required for all critical circuits, this includes detection, sounders and mains supply. On a loop system, short circuit isolators are required to limit the effect of one fault to less than 2000m2 floor area. 2 simultaneous faults on a circuit should not disable protection within an area greater than 10,000m2. BS5839Clause26BS5839Clause12.2.2 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 17
  • 18. 18 For local isolation during maintenance, a suitable double pole isolator should be provided, suitably marked (25.2c & f). Cables used for all critical paths, i.e. detector, sounder and the mains supply should be wired in fire resistant cable with a minimum cross sectional area of 1 mm² (26.2j). Enhanced fire resistant cables should be used in unsprinklered buildings where evacuation takes place in 4 or more phases, where the building is more than 30 m in height, or the risk assessment deems it necessary (26.2c). Cables require to be retained in position by a suitable fire resistant method. This requires that should plastic trunking be used, the cables must be clipped inside the trunking. Also plastic cable ties should NOT be used (26.2f). Control equipment should be sited in a position which is easily accessible to both staff and fire- fighters (23.2.1). Call points are required at ALL exits to the open air and storey exits. Operation should be of a similar type (20.2). If multi sensors are used, if it is possible, select the operation of a particular sensor then the detectors require to be spaced to suit the space of the lower coverage sensor i.e. a combined heat / smoke detector, spacing would be as a heat detector (21.1.6). All sounders in a building should have a similar sound, this precludes the mixing of bells and electronic sounders (16.2.1c). If the background noise exceeds 90 dB(A) or where hearing protection is likely to be used, then visual alarm devices are required (17.2a). Disabled persons toilets require to be fitted with visual alarm devices (18.1). The user of the system should be provided with adequate records and documentation (40.1). On completion of each process suitable certification should be provided by the organisations responsible for each stage of the system i.e. design, installation and commissioning (41.2). Installation Considerations and Key Points CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 18
  • 19. 19 1 The system complies with original specification / design, if any changes have been made they have been approved by the designer. 2 System has been installed to meet the requirements of specified category, if not specified or known, commissioning engineer should state category that system appears to be installed to. 3 Wiring of detector / sounder circuits and mains supply wired in required fire resistant cable, standard or enhanced. 4 Cables are segregated and mechanically protected as required, suitably supported (no plastic clips, cable ties or trunking as the sole means of support) as per the cable manufacturers requirements. 5 Mains supply is a dedicated supply, suitably fused, and provides local double pole isolation which is correctly labelled. 6 Junction boxes are correctly labelled, identified on drawings, and use fire resistant terminal blocks. 7 All cable continuity and insulation resistance results are recorded. 8 Current requirements of the system under quiescent and alarm conditions are measured and relevant calculations carried out to ensure standby battery(s) are suitable for system requirements. 9 All standby batteries are clearly marked with date of installation, such that this date can be seen without removing batteries from equipment. 10 Minimum of two sounders are installed on a minimum of two sounder circuits i.e. at least one sounder on each of two sounder circuits. 11 Circuit wiring is correctly labelled and terminated in all control and ancillary equipment. 12 Sound pressure levels have been checked and recorded, and meet the requirements of BS 5839 Part 1. 13 Detector type and spacing have been checked and are installed to meet the required system category. 14 Manual call points are located correctly and travel distance is appropriate to the usage of the building. 15 Remote signalling has been checked to ensure correct operation, to relevant point of reception. 16 Zone chart(s) have been located in all appropriate locations i.e. adjacent to all control equipment and repeaters. 17 As fitted drawings are complete and have been updated where required. 18 Log book and operating instructions have been given to the responsible person. 19 Relevant certification is provided to user or purchaser of the system. 20 Responsible person(s) have been provided with adequate training in the operation of the system and the avoidance of false alarms. Please note that this check list should only be taken as a suggested list and reference to the appropriate sections of BS 5839 part 1 is advised. Appropriate certification should also be completed. Suggested Installation / Commissioning / Handover Checklist CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 19
  • 20. Cooper Lighting and Safety Ltd - UK Wheatley Hall Road, Doncaster, South Yorkshire. DN2 4NB. www.cooperfire.com Sales T: +44 (0)1302 303999 F: +44 (0)1302 303333 E: sales@cooperfire.com Technical T: +44 (0)1302 303350 F: +44 (0)1302 303332 E: techsupport@cooperfire.com Export T: +44 (0)1302 303250 F: +44 (0)1302 303251 E: export@cooperfire.com Service T: +44 (0)1302 303352 F: +44 (0)1302 303332 E: mvdo-service@cooperindustries.com Ireland T: 00 353 6671 42858 F: 00 353 6671 42861 CC1608_Fire Systems Design Guide_Update1_Layout 1 11/03/2010 09:58 Page 20