This document outlines the components and options available for United Metal Products' air handling units. It discusses the materials, gauges, and coatings used for base frames, casings, doors, louvers, dampers, coils, fans, and other components. It also summarizes the company's commitment to fair dealings, cutting-edge technology, and high-quality engineering and manufacturing.
1. OUR COMMITMENT
• To deal fairly and honestly in all situations and business relationships.
• To consistently innovate cutting-edge, green technology to meet the most unique
cooling and heating demands.
• To provide the highest level of engineering and manufacturing techniques in order
to deliver the best cooling/heating solutions and products possible.
2. Components
Base Frame & Floor
Base Frame Material:
6” or 8” tubular galvanized steel
Floor Material:
14 gauge G-90 galvanized steel
Capped watertight
Floor Openings:
Walkway bar grating is provided on all accessible floor openings
Lifting Lugs:
Permanent, welded on lifting lugs are standard.
3. Components
Base Frame & Floor – Options
Base Materials: Lifting Lugs:
Removable / bolt-on type
304 Stainless steel
316 Stainless steel
Insulation:
Aluminum
4” x 3# pcf
Floor Materials:
Options:
12 or 10 gauge G-90 galvanized
Auxiliary floor drains (non-piped or piped to side of unit)
14, 12 or 10 gauge 304 stainless Steel
Continuous welded floor
14, 12 or 10 gauge 316 stainless Steel
Aluminum
Optional Floor Grates:
Treadplate (galvanized, aluminum or stainless)
304 stainless steel
316 stainless steel
Aluminum
4. Components
Unit Casing
Standard Casing: Standard Internal Framing:
2” Galvanized - 18 Gauge G-90 2 x 1 x 16 gauge G-90 galvanized
tubing.
Standard Liner:
22 Gauge G-90 galvanized liner
Standard Insulation:
Standard Finish:
2” x 1.56# pcf (3# equivalent)
Pre-paint enamel finish
Color “desert beige”
5. Components
Casing and Liner Options
Optional Casing Materials: Optional Casing Construction:
All Casings are available in 4” thickness Thermal break
16 Gauge – G-90 galvanized steel
16 Gauge – #304 or #316 stainless steel
.060” Aluminum
Optional Insulation:
2” or 4” x 1.5# pcf Fiberglass w/ neoprene coating
Liner Options: 2” or 4” x 3# pcf with or without neoprene coating
Solid 22 gauge in either #304, #316 stainless or
2” or 4” 3# pcf rigid insulation
aluminum
Perforated 20 gauge in either G-90 galvanized, #304 ,
Demounts:
#316 stainless or aluminum
Available as needed per site conditions.
7. Components
Demounts
Standard on units over 138”wide and 540” long.
Optional demounts: Available as needed by site conditions.
(Demounted sections have j-box and flexible whip on either side of demount when electrical is present in that section. All
fasteners and gasketing material is shipped loose with the unit for field installation by installing contractor.)
8. Components
Doors
Standard Doors: Door Options:
18 Gauge G-90 galvanized steel exterior Ventlock #310 handles
12” x 12” view ports
22 Gauge G-90 galvanized liner View port with desiccant pouch
Thermal break construction
2” x 1.56# pcf insulation Micro-door switch
18 Gauge 304 or 316 stainless exterior
Heavy duty stainless steel butt type hinges 16 Gauge G-90 galvanized, #304 or #316 stainless
exterior
Bulb type gasket .060 Aluminum exterior
22 Gauge 304 or 316 stainless liner
Ventlock #260 handles 20 Gauge G-90 galvanized, 304 or 316 stainless
Stainless steel hinges
9. Components
Louvers & Weather Hoods
Louvers: Weather Hoods:
Standard: Intake
Standard: 4” formed galvanized double drainable
Snorkel Type
Epoxy powder coated with bird screen
18 Gauge G-90 Galvanized Steel with Bird screen
Nominal velocity of 500 FPM
Nominal Velocities to 750 FPM
Standard: Discharge
Optional Louvers:
Angle Type
High Velocity (Vertical Vane) – Storm proof
18 Gauge G-90 Galvanized Steel w/ Bird screen
Velocities up to 1000 FPM (Nominal)
Nominal Velocities to 1,200 FPM.
4” aluminum double drainable
6” Formed Galvanized or 304, 316 Stainless - Drainable
Optional Materials:
Velocities to 600 FPM
0.060” Aluminum
16 Gauge 304 or 316 Stainless Steel with Matching
Bird screen.
10. Components
Dampers
Standard: Airfoil – Galvanized Blade – with
Edge & Jamb Seals
Options:
Actuators – 2-Position, Modulating, Spring Return or Non-Spring Return
Actuators can be mounted and wired or just mounted
Airfoil – Extruded Aluminum – Ultra Low Leakage
Dual Deck or Triple Deck Multi-zone Damper – Extruded Aluminum – Zones in multiples of 6”
Actuators can be wired for either 24v or 120v
12. Components
Filtration
Filtration Options: Framing Options:
Permanent aluminum washable filters 1” or 2” depth Standard frame is G-90 galvanized &
30% efficient pre-filters (2” or 4” Depth) gasketed. Front access is required.
Bag filters w/ efficiency ratings of 65%, 85% & 95%.
Depths available are 15”, 22”, 30” & 36”. Slide rails are provided for side access.
Rigid filters w/ efficiency ratings of 65%, 85% & 95%. Nominal
12” deep. #304 or #316 Stainless frames are
HEPA filters w/ efficiency ratings of 99.9%, 99.99% & 99.999%. available.
DOP rating is also available.
Magnehelic gauges are available with all filter arrangements. HEPA filters must use a special sealing
All outdoor units with magnehelic gauges have a sun cover to frame. These frames are G-90 galvanized
protect the dial from fading. steel.
Any special filtration needs can also be accommodated
13. Components
Coils
Water & DX Coils: Steam Coils:
½” or 5/8” with 0.020” cooper tubes 5/8” or 1” with 0.025” copper tubes
0.006” aluminum fins 0.0075” aluminum fins and 16
16 gauge galvanized casing. Gauge galvanized casing
Tube walls 0.025”, 0.035”, 0.049” Optional tube walls:
Fin thickness 0.0075” or .0090” 0.035” & 0.049”
Optional fin material – copper Optional Fin Thickness 0.0090”
Optional Casing: Stainless Steel Optional Fin Material - Copper
All cooling coils over 48” are stacked with an Optional Casing: Stainless Steel
intermediate drain pan and copper downspouts
All drain pans are IAQ double slope insulated
Stainless steel is standard
14. Components
Fans
Available Fans: Optional Fan Coatings:
Airfoil plenum Air dried or baked epoxy, air dried or baked
Quiet airfoil plenum heresite or phenolic coating
Airfoil DWDI
Optional Fan Materials:
Backward Incline DWDI
Forward curved DWDI Aluminum wheel, housing and/or frame
#304 or #316 stainless steel housing, wheel
Available Motor Types: (backward incline DWDI only) and/or shaft
ODP – High efficiency Isolation:
ODP – Premium efficiency Standard 1” deflection housed isolators optional 2” & 3”
TEFC – High efficiency All fans are mounted on structural isolation bases
TEFC – Premium efficiency
15. Components
Specialty Fans
Hostile Environment Available Construction:
AMCA spark ‘B’ construction
Specialty Motor Types:
Mill and chemical duty explosion proof
Additional specialty fans and motor arrangements are also available
16. Components
Furnaces
Various Types of Furnaces are Available for Installation Control Options:
Indirect (Duct Type) – Indoor or outdoor On-Off
Indirect – drum & tube power burner Hi-Lo-Off
Electric resistance Modulation (mechanical, electronic, or external
control signal)
Direct fired
*Heat exchanger materials are 400 series
stainless steel, except for electric
resistance type.
17. Components
Evaporative Cooling
Standards:
16 Gauge 304 stainless sump
16 & 18 Gauge 304 stainless casings
Type ‘L’ copper piping w/ manual
Balancing valve & metered bleed
Stainless steel pump
(304 stainless pumps are available)
Additional horse powers are also available.
Media is available in CelDek or Class II fire rated
Standard piping is copper. Schedule 40 or 80 PVC is available
18. Components
Humidification
Types of Humidifiers Available for Installation:
Self-generating Steam
Steam to steam
Steam dispersion
Multi-stage evaporative
19. Components
Acoustics
Options:
Various types of traps can be installed.
Client’s have the option of having an acoustical
analysis performed based on the components
selected.
20. Components
Low Temperature Cooling Tower
Options: Construction:
Low Temperature Tower with evaporative Sump: 12 gauge 304 Stainless Steel
cooling
Casing: 16 & 18 gauge 304 stainless steel
Cooling technology to lower water
temperature within 2-3 degrees of Media: CelDek or GlasDek
wet-bulb
Pump: end suction w/ stainless housing
Typical efficiencies of 70-
75% are normal Piping: Copper or PVC
23. Components
Electrical
Sss
Options:
Motors wired to J-box
Single point electrical w/ starters
Single point electrical w/ VFD’s
Complete custom controls system
Special Purpose Enclosures
24. Testing Options
Unit Testing
Testing Options:
All units are run tested before being loaded for
shipment
Test reports are available upon request
ETL Tested
25. Custom Air Handling
Custom-Air ®
Benefits and Features:
Double/single wall construction Chilled water cooling coils
Evaporative cooling Hot water heating coils
Special filtration Steam heating coils
Humidity control Gas heat Controls
DX coils
26. Custom Air Handling
Modular Air Handling Unit (MAHU)
2” and 4” double wall construction, perforated or solid
Benefits and Features: lined
Modular design - can be split between any section 26 standard cabinet sizes
Low profile design suitable for ceiling or floor mounting Inlet / mixing modules – all duct locations available
Indoor and outdoor units Panel and box filters up to MERV 14
Low-leak cabinet construction - less than 1% CFM HW, CW, DX and steam coils available up to 10 rows
cabinet leakage at a positive pressure of 6″WG TSP deep
Complements UMPs larger custom-air range #304 SS double sloped drain pans
Internally isolated direct drive plug fan for quiet operation Gas or electric heat options
and zero belt maintenance ETL listed and labeled in accordance with UL1995
500 to 11,000 CFM @ up to 6.00″ TSP
27. Custom Air Handling
Vertical Air Handling Unit (VAHU)
Benefits and Features:
Small footprint with main access on one side
4 standard cabinet sizes
Internally isolated direct drive plug fan for
Inlet / Mixing modules Panel and 4” box filters up to MERV 14
quiet operation and zero belt maintenance
14 HW and CW coils as standard #304 SS double sloped
500 to 5,400 CFM @ up to 6.00″ TSP
drain pans
2” double wall construction, perforated or
Pre-wired for single point power connection
solid lined
ETL listed and labeled in accordance with UL1995
18 gauge G90 galvanized steel cabinet -
stainless steel or Hybralume™ available
28. Energy Recovery
Energy Recovery Unit ™ (ERU)
Benefits and Features:
Energy recovery: heat pipe, air to air, air to water, heat
0-100% outside air
wheels
5,000 to 40,000 CFM and higher
Engineered primarily for high outside air requirements:
Production or custom design
30%–100%
Energy recovery: heat pipe, air to air, air to water,
ETL labeling available
heat wheels
Engineered primarily for high outside air
requirements: 30%-100%
29. Energy Recovery
Energy Recovery
Figure 1 The Wet Bulb Energy Recovery
System
Wet Bulb Energy Recovery
United Metal Products is the industry innovator and leader with regards to effective energy recovery in high dry
bulb regions. UMP has spent the last fifteen years perfecting the technology called “Wet Bulb Energy
Recovery.” The key to super efficient energy recovery efficiency in the high dry bulb regions of the world is
moving the temperature exchange at the wet bulb temperature as opposed to the dry bulb level when the air exits
the unit. When this cutting edge method is implemented, energy recovery efficiencies of over 100% can be
attained. Not only does this translate into a smaller carbon footprint left on the environment, but it can also mean
an increase in an organization’s bottom line.
30. Wet Bulb Energy Recovery
The Wet Bulb Energy Recovery System
31. Components
Energy Recovery Options
Cross Flow Heat Pipes Heat Wheel
These systems are the most These systems run between 55%- These systems run up to 65%
efficient with regards to sensible 65% efficient with regards to efficient with regards to sensible
energy recovery as they can sensible energy recovery. The energy recovery. The main
provide up to 75% efficiency. main advantage of these units is advantage of the heat wheel is that
They also have no moving parts, that they have no moving parts it has minimal moving parts.
an extremely compact design, and which means very little However, the size of the heat wheel
a competitive cost. maintenance is necessary. They determines the size of the unit and
provide the highest CFM of the this limits design flexibility.
energy recovery units and are
offered in custom configurations.
32. Evaporative Technologies
Cel-Air ®
Benefits and Features:
120 cataloged sizes from 6,000-100,000 CFM
2″ double wall or single wall construction
Galvanized, aluminum, stainless steel materials
5,000-100,000 CFM and above
Evaporative cooling
ETL Labeled under UL1995 Standards
33. Evaporative Technologies
Fan-Air ®
Benefits and Features:
Commercial and industrial applications Low profile
Models UMP-700 Series are AMCA Licensed ETL - labeled under UL 507
Up to 60% energy savings over other evaporative Powder coated
coolers Gas Heat options available
34. Innovative Design
Direct Replacement Unit ™ (DRU)
Benefits and Features:
Direct replacement for UMP FanAir coolers Double-sloped drain pan under cooling coil
15 Ton / 6000cfm supply air Direct drive blower plenum fan with VFD
Other sizes in development drive
Supply/Return duct and drum louver diffuser Single or dual point power connections
available Supply and return air smoke detectors
1” double wall Hybralume™ construction R-410A refrigerant
Hinged access doors ETL listed and labeled in accordance with
Economizer and recovery UL1995
2” pre-filters up to MERV 8
35. Packaged Central Plant
Chil-Pak ®
Benefits and Features:
Saves labor in installation, single point c.w., controls and
Pre-engineered package saves on valuable lead
electricity
Economical for projects down to 150 tons
Single point of responsibility
Water side plate and frame economizer option
2” double wall construction
Pre-tested, labeled, and listed under ETL
Sound Secure System