Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
www.stahl.de Lighting E2/1 2013-02-19·EK00·III·en 
Series ECOLUX 6600 E2 
10032E00 
WebCode 6600A 
> 1- or 2-lamp version: 
– 18 W 
– 36 W 
– 58 W 
> Enclosure in polyester resin, 
glass fibre reinforced and cover 
in polycarbonate, 
impact-resistant 
> Quick fasteners 
The light fittings series 6600 are useable for normal lighting, but also 
as group or centrally-supplied emergency light fitting. 
ATEX / IECEx / 
GOST NEC 505 NEC 506 NEC 500 
Class I Class I Class II Class III 
Zone 0 1 2 20 21 22 Zone 0 1 2 20 21 22 Division 1 2 1 2 1 2 
6600/52 and 
x x x 6600/52 and 
x 6600/52 and 
x x x x x 
6600/54 
6600/54 
6600/54 
for use in 
for use in 
for use in 
6600/56 
for use in 
x x x 6600/56 
for use in 
x 6600/56 
for use in 
x x x x x
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Selection table 
Version Lamps Electronic ballast Order number Weight 
Number of lamps Lamp wattage 
W kg 
ECOLUX 6600 1 18 1 channel ECG 6600/521-8...-6... 2.500 
2 18 1 channel ECG 6600/522-8...-6... 2.500 
1 36 1 channel ECG 6600/541-8...-6... 4.600 
2 36 1 channel ECG 6600/542-8...-6... 4.600 
1 58 1 channel ECG 6600/561-8...-6... 5.800 
2 58 1 channel ECG 6600/562-8...-6... 5.800 
Order number supplement 
Through wiring Standard: without 6600/...-.0..-.... 
Special: with 3 conductors 6600/...-.3..-.... 
Special: with 5 conductors 6600/...-.5..-.... 
Cable entry 6600/...-..2.-.... 
6600/...-..1.-.... 
Standard: M25 x 1.5; 1 cable entry, 
2 stopping plugs 
Special: M20 or M 25 in moulded material 
or metal Specify on order 
Switching off Standard: without 6600/...-...0-.... 
Special: with switch 8080, 2-pole 6600/...-...1-.... 
ECG 220 ... 240 V 1xDC (18 W, 36 W and 58 W; IEC-standard) 6600/...-....-0... 
110 ... 240 V 1xDC (18 W and 36 W; IEC-standard) 6600/...-....-4... 
120 ... 277 V 2xDC (17 W, 32 W and 40 W; NEC-standard) 6600/...-....-8... 
Terminal strip Special: terminal strip 8184, 4 / 6 mm2 solid / finely stranded 6600/...-....-.1.. 
Standard: WAGO 265 2.5 mm2 6600/...-....-.2.. 
Number of terminals Standard: with 3 cores; L1 + N + PE 6600/...-....-..3. 
Special: with 5 cores; L1 + L2 + L3 + N + PE 6600/...-....-..5. 
Address module Standard: without 6600/...-....-...0 
Special: ADR20 ILS 6600/...-....-...2 
Note The light fittings are supplied without tubes and mounting accessories. 
These parts must be ordered separately. 
Explosion protection 
Explosion protection 
Global (IECEx) 
Gas and dust IECEx BVS 07.0023X 
Ex nA II T4 Gc 
Ex tc IIIC T* °C Dc oder Ex tb IIIC T* °C Db 
* surface temperature see test certificate 
Europe (ATEX) 
Gas Zone 2: DMT 01 E 085 X 
Zone 2: E II 3 G Ex nA IIC T4 Gc 
Dust Zone 21: DMT 01 ATEX E 086X 
Zone 22: DMT 01 E 085X 
Zone 21: E II 2D Ex tb IIIC T* °C Db 
Zone 22: E II 3D Ex tc IIIC T* °C Dc 
* surface temperature see test certificate 
Certificates and approvals 
Certificates IECEx, ATEX, Brazil (UL do Brasil), Kazakhstan (GOST-K), Russia (GOST-R), 
USA Canada (FM), Belarus (GOST-B), Taiwan (ITRI) 
Other approvals ship approval (GL) 
E2/2 Lighting 2013-02-19·EK00·III·en
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Technical data 
Electrical data 
Ballast 
6600/5..-....-0... 6600/5..-....-4... 
Lamp start Cold start Cold start 
Voltage 220 ... 240 Vac 110 ... 240 Vac 
Voltage 
DC during switching on 
198 … 264 Vdc 104 … 264 Vdc 
Voltage 
DC during operation 
176 … 264 Vdc 104 … 264 Vdc 
Frequency 0 / 50 … 60 Hz 0 / 50 … 60 Hz 
Operation of the lamps DC with 1 lamp with 2 lamps 
Lamps standard IEC 60081 IEC 60081 
Lamp power 18, 36, 58 W 18, 36 W 
Nominal current 1x18W 85mA 
2x18W 170mA 
1x36W 160mA 
2x36W 320mA 
1x58W 250mA 
2x58W 500mA 
1x18W 85…175mA 
2x18W170…345mA 
1x36W155…330mA 
2x36W 310…660mA 
6600/5..-....-6... 6600/5..-....-8... 
Lamp start Cold start Cold start 
Voltage 220 ... 240 Vac 120 ... 277 Vac 
Voltage 
DC during switching on 
198 … 264 Vdc 113 … 294 Vdc 
Voltage 
DC during operation 
176 … 264 Vdc 113 … 294 Vdc 
Frequency 0 / 50 … 60 Hz 0 / 50 … 60 Hz 
Operation of the lamps DC with 2 lamps with 2 lamps 
Lamps standard IEC 60081 ANSI C78.81 
Lamp power 18, 36, 58 W 17, 32, 40 W 
Nominal current 1x18W 75mA 
2x18W 150mA 
1x36W 150mA 
2x36W 300mA 
1x58W 240mA 
2x58W 480mA 
1x17W 80…155mA 
2x17W 160…305mA 
1x32W 135…285mA 
2x32W 270…570mA 
1x40W 160…360mA 
2x40W 325…715mA 
Power factor cos p cos p ) 0.96 capacitive; additional compensation not required 
Disconnection of the light 
optional 
On opening the diffuser when opening the fastening mechanism of one of the quick fasteners, 
voltage to ballast will be switched off all-pole; contacts are positively 
opening, reconnection when cover and quick fasteners are closed. 
Faulty lamp If lamp is faulty, power supply of lamps is switched off automatically by 
electronic ballast; 
when using a 2-channel-ECG power is switched off only to the defective 
lamp. 
2013-02-19·EK00·III·en Lighting E2/3
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Technical data 
Luminous Characteristics 
Measures for light 
guidance 
Standard 
Wide beam, reflector painted white. 
Colour: signal white RAL 9003; prismatic structure for anti-glare in the diffuser sides. 
Special 
Additional reflector (easily mounted), broad deep-beam, aluminium anodized and semi-polished. 
Luminous intensity 
distribution 
Ambient conditions 
Ambient temperature 
Mechanical data 
Version 1-lamp, without reflector 1-lamp, with reflector 
Accuracy 
class 
acc. to LitG 
Version 2-lamp, without reflector 2-lamp, with reflector 
Accuracy 
class 
acc. to LitG 
220 .. 240 V (IEC) 
6600/52.-....-0... - 25 ... + 55 °C + 80 °C - 25 ... + 55 °C + 80 °C 
6600/54.-....-0... - 25 ... + 55 °C + 80 °C - 25 ... + 55 °C + 80 °C 
6600/56.-....-0... - 25 ... + 55 °C + 80 °C - 25 ... + 55 °C + 80 °C 
110 ... 240 V (IEC) 
6600/52.-....-4... - 25 ... + 50 °C + 95 °C - 25 ... + 45 °C + 95 °C 
6600/54.-....-4... - 25 ... + 50 °C + 95 °C - 25 ... + 45 °C + 95 °C 
220 ... 240 V (IEC) 
6600/52.-....-6... - 25 ... + 55 °C + 70 °C - 25 ... + 55 °C + 70 °C 
6600/54.-....-6... - 25 ... + 55 °C + 70 °C - 25 ... + 55 °C + 70 °C 
6600/56.-....-6... - 25 ... + 55 °C + 75 °C - 25 ... + 55 °C + 75 °C 
120 ... 277 V (NEC) 
6600/53.-....-6... - 25 ... + 55 °C + 85 °C 
6600/55.-....-6... - 25 ... + 55 °C + 85 °C 
6600/57.-....-6... - 25 ... + 55 °C + 85 °C 
Degree of protection IP66 
B21 B31 
B21 B31 
without trough wiring with trough wiring 
Ta Ts max Ta Ts max 
(IP64 when using breather 8162) 
Protection class I (with internal PE connection terminal) 
Material 
08258E00 08257E00 
08259E00 08257E00 
Enclosure Polyester resin, glass fibre reinforced, colour white, similar RAL 9010 
Lamp cover Polycarbonate 
Seal Silicone-gasket foamed into diffuser 
Quick-acting locks Polyamide, glass fibre reinforced, black / white 
Assembly parts Polyester resin, glass fibre reinforced, colour white, similar RAL 9010 
Cover options Quick fasteners to open with screw-driver; cover hinged for access. 
E2/4 Lighting 2013-02-19·EK00·III·en
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Technical data 
Mounting / installation 
Mounting 2 x M8 inserts in housing 
Mounting grooves in housing to accommodate bracket fitting and ceiling rails for variable light 
installation. 
Variable mounting distances of light fittings; see dimension drawings 
Cable glands 1 x cable gland 8161, M25 x 1.5, cable dia. range: d 7 ... 17 mm 
2 x stopping plugs 8290, M25 x 1.5 
Entry parts in moulded plastic (8161 / 8290): M20 
Metal glands: M20; M25; 
Metal cable gland earthing via metal adapter plates 
Connection 
Standard Spring cage terminal 
connection cross-section: max. 2 x 2.5 mm2 
3 pole (terminal marking: L1 + N + PE) 
5 pole (terminal marking: L1 + L2 + L3 + N + PE) 
Special Terminal block with screw terminals 
connection cross-section: 
max. 2 x 6 mm2 (solid) 
max. 2 x 4 mm2 (flexible) 
numbers of terminals: 
3 pole (terminal marking: L1 + N + PE) 
5 pole (terminal marking: L1 + L2 + L3 + N + PE) 
Installation notes 
Looping through of 
cables 
There are 2 M25 x 1.5 cable entries on the connection side for looping through of connection 
cable (entry and exit on one side). 
Through wiring Fittings can be supplied with internal through-wiring. 
Entry and exit holes for connection cables are positioned on opposite sides. 
A through-wiring kit can be fitted after manufacture (see accessories). 
Terminals: See technical data top 
Wiring cross-section: 2.5 mm2 for max. 16 A 
Monitoring module 
Function Monitoring and switching module for emergency light systems according to VDE 0108: 
The module is used for the monitoring of individual lights and for the control of network and safety 
lights. 
The module offers the following functions: 
• Control of the light (ON / OFF) and function test 
• Up to 20 addresses can be set for each electric circuit by means of a coding switch 
• The operating mode of the lamp (continuous light, stand-by light or activation by means of a 
switch) is freely programmable 
• Mixed operation within one circuit is possible 
Input voltage (Input between L+ and N-) 
UN 230 (+ 10 % / - 15 %) V AC, 50 Hz 
U DC 175 ... 275 V DC 
Control input (between L and N) 
Connected power (output 
to light) 
Ambient temperature 
UN 230 (+ 10 % / - 15 %) V AC, 50 Hz 
P 4 ... 100 W 
Ta (Module) - 10 ... + 50 °C 
Dimensions L x W x H = 95 x 40 x 32 mm 
2013-02-19·EK00·III·en Lighting E2/5
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Accessories and spare parts 
Designation Figure Description Art. no. Weight 
kg 
Fluorescent lamp 
04936E00 
Two-pin cap d 26 mm 
Light colour: universal white 
108952 0.100 
108951 0.200 
108950 0.220 
Diffuser cover 
05329E00 
18 W 1350 Im 
36 W 3350 Im 
58 W 5200 Im 
for light fitting 18 W 124890 0.500 
for light fitting 36 W 124897 0.860 
for light fitting 58 W 124904 0.800 
Switch 
10809E00 
Switching element 8080/1-3-L, 2 normally closed contacts 132527 0.025 
Mounting kit for 
through wiring 
05503E00 
For later installation into standard-light fitting 
DV3, tension clamp terminals 3 x 2.5 mm2, 
max. 16 A terminal marking: L1 + N + PE 
18 W 124925 0.120 
36 W 124927 0.300 
58 W 124929 0.300 
DV5, tension clamp terminals 5 x 2.5 mm2, 
0.000 
max. 16 A terminal marking: L1 + L2 + L3 + N + PE 
18 W 124919 0.300 
36 W 124921 0.300 
58 W 124923 0.300 
DV3, screw terminals 3 x 2.5 mm2, 
max. 16 A terminal marking: L1 + N + PE 
18 W 124912 0.400 
36 W 124915 0.400 
58 W 124917 0.400 
DV5, screw terminals 5 x 2.5 mm2, 
max. 16 A terminal marking: L1 + L2 + L3 + N + PE 
18 W 124895 0.400 
36 W 124902 0.400 
58 W 124909 0.400 
Reflectors 
05324E00 
for later installation, broad deep beam 
For 1-lamp light fittings 18 W 117128 0.082 
For 1-lamp light fittings 36 W 117137 0.172 
For 1-lamp light fittings 58 W 117150 0.218 
For 2-lamps light fittings18 W 117098 0.265 
For 2-lamps light fittings36 W 117115 0.234 
For 2-lamps light fittings 58 W 117145 0.290 
E2/6 Lighting 2013-02-19·EK00·III·en
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Accessories and spare parts 
Designation Figure Description Art. no. Weight 
Adapter plates 
05755E00 
for earth continuity when using metal glands; 
kg 
115815 0.070 
115818 0.070 
115821 0.070 
115824 0.070 
115826 0.060 
115828 0.060 
115829 0.060 
Lamp-holder 
05888E00 
1 x M20 x 1.5 1 piece 
1 x M25 x 1.5 1 piece 
1 x NPT 1/2“ 1 piece 
1 x NPT 3/4“ 1 piece 
2 x M20 x 1.5 1 piece 
2 x M25 x 1.5 1 piece 
2 x NPT 1/2“ 1 piece 
Lamp holder for two-pin cap lamps G 13 107275 0.008 
Mounting rail 
05895E00 
for a variable mounting distance of 1 pair 124894 0.210 
Mounting clamp bra-cket 
05896E00 
124901 0.300 
Ring bolts 
05378E00 
Mounting bracket mounted 
on the mounting rail 
for a variable mounting distance 
of 1 pair 
M8, direct mounting in insert nuts, 1 pair 115736 0.120 
Wall-mounting bra-cket 
05460E00 
to mount the lamps as side-entry lamps using a tube with 
a length of 1300 mm, d 42 mm 
(for pipe clamp R 11/2“) 109281 6.000 
Ceiling mounting bra-cket 
05897E00 
for ceiling suspension of the lamp, 1 pair 124908 0.230 
Pipe clamps 
09402E00 
with mounting rail for a variable mounting distance; 
Material: stainless steel 
R 11/4“ (d 42 mm) 124913 1.140 
R 11/2“ (d 48 mm) 124891 1.160 
R 2“ (d 60 mm) 124898 1.300 
Mounting set ,,Grid 
cable rack’’ 
04361E00 
for grid cable racks, with a cable diameter of 6 mm; 
with mounting rail for a variable mounting distance; 
Material: stainless steel 
124905 1.560 
Ceiling and wall-mounting 
bracket 
05898E00 
mounted on a mounting rail for a variable mounting dis-tance; 
Material: stainless steel 
Lamp can be swiveled in steps of 15° 
1 pair 124910 1.150 
2013-02-19·EK00·III·en Lighting E2/7
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Accessories and spare parts 
Designation Figure Description Art. no. Weight 
Cable gland 
05864E00 
of moulded material, series 8161 
kg 
138518 0.012 
138454 0.600 
138520 0.020 
138456 1.000 
Stopping plug 
04840E00 
8161/5-M20-13 1 piece 
8161/5-M20-13 50 pieces 
8161/5-M25-17 1 piece 
8161/5-M25-17 50 pieces 
of moulded material, series 8290 
143522 0.005 
143543 0.500 
143524 0.007 
143544 0.700 
Breathing gland 
05703E00 
8290/3-M20 1 piece 
8290/3-M20 100 pieces 
8290/3-M25 x 1,5 1 pieces 
8290/3-M25 100 pieces 
for installation in lights; 
in moulded material; without counter nut 
138573 0.010 
138576 0.200 
Thread: M25 x 1.5 1 pc 
Thread: M25 x 1.5 20 pcs 
E2/8 Lighting 2013-02-19·EK00·III·en
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
E2 
Light Fitting for Fluorescent Lamps 
Series ECOLUX 6600 
Dimensional Drawings (All Dimensions in mm) - Subject to Alterations 
04824E00 
Light fittings ECOLUX 6600, 18 W, 36 W, 58 W 
Dimen-sions 
Light fitting 
18 W 36 W 58 W 
L1 700 1310 1610 
L2 1) 400 800 800 
L3 2) 340 ... 460 680 ... 920 795 ... 1030 
1) Fixed mounting distance 
2) Variable mounting distance 
04717E00 04822E00 
Pipe clamp Mounting set grid cable rack 
04716E00 04833E00 
Ceiling- and wall-mounting bracket Ceiling mounting bracket 
04823E00 04715E00 04834E00 
Wall mounting bracket for pole-mounting version Ring bolt Mounting clamp bracket 
Installation accessories 
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. 
The illustrations cannot be considered binding. 
2013-02-19·EK00·III·en Lighting E2/9

Mais conteúdo relacionado

Mais procurados

Omron e2 a-cylindrical-proximity-sensor-series-datatraceautomation
Omron e2 a-cylindrical-proximity-sensor-series-datatraceautomationOmron e2 a-cylindrical-proximity-sensor-series-datatraceautomation
Omron e2 a-cylindrical-proximity-sensor-series-datatraceautomationcompany Team
 
Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)
Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)
Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)Thorne & Derrick International
 
Catalog Contactor Mitsubishi - Beeteco.com
Catalog Contactor Mitsubishi - Beeteco.comCatalog Contactor Mitsubishi - Beeteco.com
Catalog Contactor Mitsubishi - Beeteco.comBeeteco
 
Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1
Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1
Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1Thorne & Derrick International
 
Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)
Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)
Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)Thorne & Derrick International
 
Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...
Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...
Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...Thorne & Derrick International
 
Zone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt Lamps
Zone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt LampsZone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt Lamps
Zone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt LampsThorne & Derrick International
 
Floodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area Lighting
Floodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area LightingFloodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area Lighting
Floodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area LightingThorne & Derrick International
 
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...Thorne & Derrick International
 
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Thorne & Derrick International
 
Catalog MCCB ELCB Mitsubishi - Beeteco.com
Catalog MCCB ELCB Mitsubishi - Beeteco.comCatalog MCCB ELCB Mitsubishi - Beeteco.com
Catalog MCCB ELCB Mitsubishi - Beeteco.comBeeteco
 
Catalog ELCB Mitsubishi-Beeteco.com
Catalog ELCB Mitsubishi-Beeteco.comCatalog ELCB Mitsubishi-Beeteco.com
Catalog ELCB Mitsubishi-Beeteco.comBeeteco
 
Abtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) Lighting
Abtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) LightingAbtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) Lighting
Abtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) LightingThorne & Derrick International
 
Catalog MCCB LS metasol tổng hợp - beeteco.com
Catalog MCCB LS metasol tổng hợp - beeteco.comCatalog MCCB LS metasol tổng hợp - beeteco.com
Catalog MCCB LS metasol tổng hợp - beeteco.comBeeteco
 

Mais procurados (15)

Omron e2 a-cylindrical-proximity-sensor-series-datatraceautomation
Omron e2 a-cylindrical-proximity-sensor-series-datatraceautomationOmron e2 a-cylindrical-proximity-sensor-series-datatraceautomation
Omron e2 a-cylindrical-proximity-sensor-series-datatraceautomation
 
Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)
Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)
Hadar Lighting - Hazardous Area Zone 1 & Zone 2 Lighting (ATEX Certified)
 
Catalog Contactor Mitsubishi - Beeteco.com
Catalog Contactor Mitsubishi - Beeteco.comCatalog Contactor Mitsubishi - Beeteco.com
Catalog Contactor Mitsubishi - Beeteco.com
 
Catalog mcb fuji electric
Catalog mcb fuji electricCatalog mcb fuji electric
Catalog mcb fuji electric
 
Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1
Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1
Hadar Hazardous Area Lighting - HDL105 - Portable Zone 1
 
Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)
Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)
Zone 1 ATEX Lighting Fluorescent Luminaires - Hadar HDL100 (2 x 18Watt Lamps)
 
Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...
Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...
Stahl C-LUX 6108 Compact Emergency Light Fittings - ATEX Zone 1 Zone 2 Hazard...
 
Zone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt Lamps
Zone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt LampsZone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt Lamps
Zone 1 Floodlight (Ex de) Hazardous Area - Hadar HDL117 500 Watt Lamps
 
Floodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area Lighting
Floodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area LightingFloodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area Lighting
Floodlights Zone 1 & Zone 2 (ATEX) - Hadar Hazardous Area Lighting
 
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...Stahl 6039 Series Tubular Light Fittings  ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl 6039 Series Tubular Light Fittings ATEX Zone 1 Zone 2 Hazardous Area L...
 
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
Stahl 6039 Series Tubular Light Fittings – ATEX Zone 1 Zone 2 Hazardous Area ...
 
Catalog MCCB ELCB Mitsubishi - Beeteco.com
Catalog MCCB ELCB Mitsubishi - Beeteco.comCatalog MCCB ELCB Mitsubishi - Beeteco.com
Catalog MCCB ELCB Mitsubishi - Beeteco.com
 
Catalog ELCB Mitsubishi-Beeteco.com
Catalog ELCB Mitsubishi-Beeteco.comCatalog ELCB Mitsubishi-Beeteco.com
Catalog ELCB Mitsubishi-Beeteco.com
 
Abtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) Lighting
Abtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) LightingAbtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) Lighting
Abtech Lighting - Hazardous Area Zone 1 Zone 2 (ATEX IECEx) Lighting
 
Catalog MCCB LS metasol tổng hợp - beeteco.com
Catalog MCCB LS metasol tổng hợp - beeteco.comCatalog MCCB LS metasol tổng hợp - beeteco.com
Catalog MCCB LS metasol tổng hợp - beeteco.com
 

Semelhante a Stahl 6600 Fluorescent Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting

Stahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area
Stahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous AreaStahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area
Stahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous AreaThorne & Derrick International
 
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...Thorne & Derrick International
 
Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...Thorne & Derrick International
 
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...Thorne & Derrick International
 
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...Thorne & Derrick International
 
Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...
Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...
Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...Thorne & Derrick International
 
Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...
Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...
Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...Thorne & Derrick International
 
Stahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area LightingThorne & Derrick International
 
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...Thorne & Derrick International
 
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area Thorne & Derrick International
 
Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...
Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...
Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...Thorne & Derrick International
 
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnDien Ha The
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abbDien Ha The
 
Datasheet-LED-Area-Light-NOVA-SF-Series.pdf
Datasheet-LED-Area-Light-NOVA-SF-Series.pdfDatasheet-LED-Area-Light-NOVA-SF-Series.pdf
Datasheet-LED-Area-Light-NOVA-SF-Series.pdfMatt Zhao
 
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area Thorne & Derrick International
 
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...Thorne & Derrick International
 
Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...
Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...
Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...Thorne & Derrick International
 
Hadar HDL220 Zone 1 & Zone 21 Fluorescent Luminaire - Ex emb Fluorescent Li...
Hadar HDL220  Zone 1 & Zone 21 Fluorescent Luminaire  - Ex emb Fluorescent Li...Hadar HDL220  Zone 1 & Zone 21 Fluorescent Luminaire  - Ex emb Fluorescent Li...
Hadar HDL220 Zone 1 & Zone 21 Fluorescent Luminaire - Ex emb Fluorescent Li...Thorne & Derrick International
 

Semelhante a Stahl 6600 Fluorescent Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting (20)

Stahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area
Stahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous AreaStahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area
Stahl C-LUX 6100 Compact Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area
 
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
 
Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...
Stahl C-Lux 6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area L...
 
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
Stahl 6100/6500 Compact Light Fittings - ATEX Zone 1 Zone 2 Hazardous Area Li...
 
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
Stahl 6149 LED Hand Lamp With Mains Connection - ATEX Zone 1 Zone 2 Hazardous...
 
Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...
Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...
Stahl 6008 Emergency Light Fitting For Fluorescent Lamps - ATEX Zone 1 Zone 2...
 
Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...
Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...
Stahl ECOLUX 6608 Economy Emergency Light Fitting For FluorescentLamps - ATEX...
 
Stahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area LightingStahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting
Stahl 6788 Bulkhead Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting
 
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
Stahl 8264 CUBEx Reversing Starter Motor Starters – ATEX Zone 1 Zone 2 Hazard...
 
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8264 CUBEx Star Delta Motor Starter – ATEX Zone 1 Zone 2 Hazardous Area
 
Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...
Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...
Stahl Inspection Light LED Series 6149/2 - Hazardous Area Lighting For Zone 1...
 
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abb
 
Datasheet-LED-Area-Light-NOVA-SF-Series.pdf
Datasheet-LED-Area-Light-NOVA-SF-Series.pdfDatasheet-LED-Area-Light-NOVA-SF-Series.pdf
Datasheet-LED-Area-Light-NOVA-SF-Series.pdf
 
Datasheet-LED-Area-Light-NOVA-SF-Series.pdf
Datasheet-LED-Area-Light-NOVA-SF-Series.pdfDatasheet-LED-Area-Light-NOVA-SF-Series.pdf
Datasheet-LED-Area-Light-NOVA-SF-Series.pdf
 
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
Stahl 8220 Star Delta Motor Starters – ATEX Zone 1 Zone 2 Hazardous Area
 
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
Stahl 8220 Star Reversing Starter Motor Starters - ATEX Zone 1 Zone 2 Hazardo...
 
Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...
Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...
Stahl ECOLUX 6608 Emergency Light Litting For Fluorescent Lamps - ATEX Zone 1...
 
Hadar HDL220 Zone 1 & Zone 21 Fluorescent Luminaire - Ex emb Fluorescent Li...
Hadar HDL220  Zone 1 & Zone 21 Fluorescent Luminaire  - Ex emb Fluorescent Li...Hadar HDL220  Zone 1 & Zone 21 Fluorescent Luminaire  - Ex emb Fluorescent Li...
Hadar HDL220 Zone 1 & Zone 21 Fluorescent Luminaire - Ex emb Fluorescent Li...
 
Mcb c60 h dc
Mcb c60 h dcMcb c60 h dc
Mcb c60 h dc
 

Mais de Thorne & Derrick International

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Thorne & Derrick International
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptThorne & Derrick International
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018Thorne & Derrick International
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick InternationalThorne & Derrick International
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-AThorne & Derrick International
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...Thorne & Derrick International
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Thorne & Derrick International
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RoweThorne & Derrick International
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandThorne & Derrick International
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DThorne & Derrick International
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...Thorne & Derrick International
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetThorne & Derrick International
 

Mais de Thorne & Derrick International (20)

Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...Isolation procedures for safe working on electrical systems and equipment by ...
Isolation procedures for safe working on electrical systems and equipment by ...
 
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical EqptTHORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
THORNE & DERRICK LV MV HV Jointing, Earthing, Substation & Electrical Eqpt
 
The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018The Children North East Annual Golf Day Wednesday 9th May 2018
The Children North East Annual Golf Day Wednesday 9th May 2018
 
3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International3M Electrical Products Stocked By Thorne & Derrick International
3M Electrical Products Stocked By Thorne & Derrick International
 
CATU Electrical Safety Catalogue
CATU Electrical Safety CatalogueCATU Electrical Safety Catalogue
CATU Electrical Safety Catalogue
 
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
11kV Cable Termination Heat Shrink Kits 3 Core 16-25sqmm SPS 3TIS-12X-A
 
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
THORNE + DERRICK : LV, MV & HV Cable Installation, Jointing, Substation & Ele...
 
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
Ex d Enclosures - Explosion Proof Hazardous Area Technor EJB Galvanised Steel...
 
Roxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional DrawingRoxtec Cable Transit - B Frame Dimensional Drawing
Roxtec Cable Transit - B Frame Dimensional Drawing
 
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam RowePepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
Pepperl & Fuchs SIL Training Certificate - T&D Adam Rowe
 
T&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive AtmospheresT&D Experts In Equipment For Explosive Atmospheres
T&D Experts In Equipment For Explosive Atmospheres
 
Ultrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification DemandUltrasonic Flow Meters - Customer Specification Demand
Ultrasonic Flow Meters - Customer Specification Demand
 
Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016Emtelle Fibre Optic Cables - Product Catalogue 2016
Emtelle Fibre Optic Cables - Product Catalogue 2016
 
Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016Thorne & Derrick Process Heating Brochure 2016
Thorne & Derrick Process Heating Brochure 2016
 
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282DSIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
SIRAI ASCO Numatics Solenoid Valves WRAS Approved - SIRAI L182D L282D
 
Ripley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation ToolsRipley Utility Tool Cable Preparation Tools
Ripley Utility Tool Cable Preparation Tools
 
RIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas DetectorRIDGID micro CD100 Combustible Gas Detector
RIDGID micro CD100 Combustible Gas Detector
 
Itron Fact Sheet
Itron Fact SheetItron Fact Sheet
Itron Fact Sheet
 
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
United Nations Environment Programme (UNEP) ‘2006 Report of the Refrigeration...
 
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec SheetFiloform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
Filoform FiloSeal+HD Reenterable LV HV Power Cable Duct Seal System - Spec Sheet
 

Último

Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesKari Kakkonen
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024Lonnie McRorey
 
Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)Kaya Weers
 
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxThe Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxLoriGlavin3
 
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesMuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesManik S Magar
 
QCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesQCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesBernd Ruecker
 
2024 April Patch Tuesday
2024 April Patch Tuesday2024 April Patch Tuesday
2024 April Patch TuesdayIvanti
 
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Alkin Tezuysal
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsPixlogix Infotech
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxLoriGlavin3
 
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security ObservabilityGlenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security Observabilityitnewsafrica
 
Bridging Between CAD & GIS: 6 Ways to Automate Your Data Integration
Bridging Between CAD & GIS:  6 Ways to Automate Your Data IntegrationBridging Between CAD & GIS:  6 Ways to Automate Your Data Integration
Bridging Between CAD & GIS: 6 Ways to Automate Your Data Integrationmarketing932765
 
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterMydbops
 
React Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App FrameworkReact Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App FrameworkPixlogix Infotech
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...Wes McKinney
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfIngrid Airi González
 
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxLoriGlavin3
 
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyesHow to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyesThousandEyes
 

Último (20)

Testing tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examplesTesting tools and AI - ideas what to try with some tool examples
Testing tools and AI - ideas what to try with some tool examples
 
TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024TeamStation AI System Report LATAM IT Salaries 2024
TeamStation AI System Report LATAM IT Salaries 2024
 
Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)Design pattern talk by Kaya Weers - 2024 (v2)
Design pattern talk by Kaya Weers - 2024 (v2)
 
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptxThe Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
The Role of FIDO in a Cyber Secure Netherlands: FIDO Paris Seminar.pptx
 
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotesMuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
MuleSoft Online Meetup Group - B2B Crash Course: Release SparkNotes
 
QCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architecturesQCon London: Mastering long-running processes in modern architectures
QCon London: Mastering long-running processes in modern architectures
 
2024 April Patch Tuesday
2024 April Patch Tuesday2024 April Patch Tuesday
2024 April Patch Tuesday
 
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
Unleashing Real-time Insights with ClickHouse_ Navigating the Landscape in 20...
 
The Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and ConsThe Ultimate Guide to Choosing WordPress Pros and Cons
The Ultimate Guide to Choosing WordPress Pros and Cons
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
 
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security ObservabilityGlenn Lazarus- Why Your Observability Strategy Needs Security Observability
Glenn Lazarus- Why Your Observability Strategy Needs Security Observability
 
Bridging Between CAD & GIS: 6 Ways to Automate Your Data Integration
Bridging Between CAD & GIS:  6 Ways to Automate Your Data IntegrationBridging Between CAD & GIS:  6 Ways to Automate Your Data Integration
Bridging Between CAD & GIS: 6 Ways to Automate Your Data Integration
 
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL Router
 
React Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App FrameworkReact Native vs Ionic - The Best Mobile App Framework
React Native vs Ionic - The Best Mobile App Framework
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
 
Generative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdfGenerative Artificial Intelligence: How generative AI works.pdf
Generative Artificial Intelligence: How generative AI works.pdf
 
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptxThe Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
The Fit for Passkeys for Employee and Consumer Sign-ins: FIDO Paris Seminar.pptx
 
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyesHow to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
How to Effectively Monitor SD-WAN and SASE Environments with ThousandEyes
 

Stahl 6600 Fluorescent Light Fitting - ATEX Zone 1 Zone 2 Hazardous Area Lighting

  • 1. E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 Light Fitting for Fluorescent Lamps Series ECOLUX 6600 www.stahl.de Lighting E2/1 2013-02-19·EK00·III·en Series ECOLUX 6600 E2 10032E00 WebCode 6600A > 1- or 2-lamp version: – 18 W – 36 W – 58 W > Enclosure in polyester resin, glass fibre reinforced and cover in polycarbonate, impact-resistant > Quick fasteners The light fittings series 6600 are useable for normal lighting, but also as group or centrally-supplied emergency light fitting. ATEX / IECEx / GOST NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone 0 1 2 20 21 22 Zone 0 1 2 20 21 22 Division 1 2 1 2 1 2 6600/52 and x x x 6600/52 and x 6600/52 and x x x x x 6600/54 6600/54 6600/54 for use in for use in for use in 6600/56 for use in x x x 6600/56 for use in x 6600/56 for use in x x x x x
  • 2. Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Selection table Version Lamps Electronic ballast Order number Weight Number of lamps Lamp wattage W kg ECOLUX 6600 1 18 1 channel ECG 6600/521-8...-6... 2.500 2 18 1 channel ECG 6600/522-8...-6... 2.500 1 36 1 channel ECG 6600/541-8...-6... 4.600 2 36 1 channel ECG 6600/542-8...-6... 4.600 1 58 1 channel ECG 6600/561-8...-6... 5.800 2 58 1 channel ECG 6600/562-8...-6... 5.800 Order number supplement Through wiring Standard: without 6600/...-.0..-.... Special: with 3 conductors 6600/...-.3..-.... Special: with 5 conductors 6600/...-.5..-.... Cable entry 6600/...-..2.-.... 6600/...-..1.-.... Standard: M25 x 1.5; 1 cable entry, 2 stopping plugs Special: M20 or M 25 in moulded material or metal Specify on order Switching off Standard: without 6600/...-...0-.... Special: with switch 8080, 2-pole 6600/...-...1-.... ECG 220 ... 240 V 1xDC (18 W, 36 W and 58 W; IEC-standard) 6600/...-....-0... 110 ... 240 V 1xDC (18 W and 36 W; IEC-standard) 6600/...-....-4... 120 ... 277 V 2xDC (17 W, 32 W and 40 W; NEC-standard) 6600/...-....-8... Terminal strip Special: terminal strip 8184, 4 / 6 mm2 solid / finely stranded 6600/...-....-.1.. Standard: WAGO 265 2.5 mm2 6600/...-....-.2.. Number of terminals Standard: with 3 cores; L1 + N + PE 6600/...-....-..3. Special: with 5 cores; L1 + L2 + L3 + N + PE 6600/...-....-..5. Address module Standard: without 6600/...-....-...0 Special: ADR20 ILS 6600/...-....-...2 Note The light fittings are supplied without tubes and mounting accessories. These parts must be ordered separately. Explosion protection Explosion protection Global (IECEx) Gas and dust IECEx BVS 07.0023X Ex nA II T4 Gc Ex tc IIIC T* °C Dc oder Ex tb IIIC T* °C Db * surface temperature see test certificate Europe (ATEX) Gas Zone 2: DMT 01 E 085 X Zone 2: E II 3 G Ex nA IIC T4 Gc Dust Zone 21: DMT 01 ATEX E 086X Zone 22: DMT 01 E 085X Zone 21: E II 2D Ex tb IIIC T* °C Db Zone 22: E II 3D Ex tc IIIC T* °C Dc * surface temperature see test certificate Certificates and approvals Certificates IECEx, ATEX, Brazil (UL do Brasil), Kazakhstan (GOST-K), Russia (GOST-R), USA Canada (FM), Belarus (GOST-B), Taiwan (ITRI) Other approvals ship approval (GL) E2/2 Lighting 2013-02-19·EK00·III·en
  • 3. E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Technical data Electrical data Ballast 6600/5..-....-0... 6600/5..-....-4... Lamp start Cold start Cold start Voltage 220 ... 240 Vac 110 ... 240 Vac Voltage DC during switching on 198 … 264 Vdc 104 … 264 Vdc Voltage DC during operation 176 … 264 Vdc 104 … 264 Vdc Frequency 0 / 50 … 60 Hz 0 / 50 … 60 Hz Operation of the lamps DC with 1 lamp with 2 lamps Lamps standard IEC 60081 IEC 60081 Lamp power 18, 36, 58 W 18, 36 W Nominal current 1x18W 85mA 2x18W 170mA 1x36W 160mA 2x36W 320mA 1x58W 250mA 2x58W 500mA 1x18W 85…175mA 2x18W170…345mA 1x36W155…330mA 2x36W 310…660mA 6600/5..-....-6... 6600/5..-....-8... Lamp start Cold start Cold start Voltage 220 ... 240 Vac 120 ... 277 Vac Voltage DC during switching on 198 … 264 Vdc 113 … 294 Vdc Voltage DC during operation 176 … 264 Vdc 113 … 294 Vdc Frequency 0 / 50 … 60 Hz 0 / 50 … 60 Hz Operation of the lamps DC with 2 lamps with 2 lamps Lamps standard IEC 60081 ANSI C78.81 Lamp power 18, 36, 58 W 17, 32, 40 W Nominal current 1x18W 75mA 2x18W 150mA 1x36W 150mA 2x36W 300mA 1x58W 240mA 2x58W 480mA 1x17W 80…155mA 2x17W 160…305mA 1x32W 135…285mA 2x32W 270…570mA 1x40W 160…360mA 2x40W 325…715mA Power factor cos p cos p ) 0.96 capacitive; additional compensation not required Disconnection of the light optional On opening the diffuser when opening the fastening mechanism of one of the quick fasteners, voltage to ballast will be switched off all-pole; contacts are positively opening, reconnection when cover and quick fasteners are closed. Faulty lamp If lamp is faulty, power supply of lamps is switched off automatically by electronic ballast; when using a 2-channel-ECG power is switched off only to the defective lamp. 2013-02-19·EK00·III·en Lighting E2/3
  • 4. Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Technical data Luminous Characteristics Measures for light guidance Standard Wide beam, reflector painted white. Colour: signal white RAL 9003; prismatic structure for anti-glare in the diffuser sides. Special Additional reflector (easily mounted), broad deep-beam, aluminium anodized and semi-polished. Luminous intensity distribution Ambient conditions Ambient temperature Mechanical data Version 1-lamp, without reflector 1-lamp, with reflector Accuracy class acc. to LitG Version 2-lamp, without reflector 2-lamp, with reflector Accuracy class acc. to LitG 220 .. 240 V (IEC) 6600/52.-....-0... - 25 ... + 55 °C + 80 °C - 25 ... + 55 °C + 80 °C 6600/54.-....-0... - 25 ... + 55 °C + 80 °C - 25 ... + 55 °C + 80 °C 6600/56.-....-0... - 25 ... + 55 °C + 80 °C - 25 ... + 55 °C + 80 °C 110 ... 240 V (IEC) 6600/52.-....-4... - 25 ... + 50 °C + 95 °C - 25 ... + 45 °C + 95 °C 6600/54.-....-4... - 25 ... + 50 °C + 95 °C - 25 ... + 45 °C + 95 °C 220 ... 240 V (IEC) 6600/52.-....-6... - 25 ... + 55 °C + 70 °C - 25 ... + 55 °C + 70 °C 6600/54.-....-6... - 25 ... + 55 °C + 70 °C - 25 ... + 55 °C + 70 °C 6600/56.-....-6... - 25 ... + 55 °C + 75 °C - 25 ... + 55 °C + 75 °C 120 ... 277 V (NEC) 6600/53.-....-6... - 25 ... + 55 °C + 85 °C 6600/55.-....-6... - 25 ... + 55 °C + 85 °C 6600/57.-....-6... - 25 ... + 55 °C + 85 °C Degree of protection IP66 B21 B31 B21 B31 without trough wiring with trough wiring Ta Ts max Ta Ts max (IP64 when using breather 8162) Protection class I (with internal PE connection terminal) Material 08258E00 08257E00 08259E00 08257E00 Enclosure Polyester resin, glass fibre reinforced, colour white, similar RAL 9010 Lamp cover Polycarbonate Seal Silicone-gasket foamed into diffuser Quick-acting locks Polyamide, glass fibre reinforced, black / white Assembly parts Polyester resin, glass fibre reinforced, colour white, similar RAL 9010 Cover options Quick fasteners to open with screw-driver; cover hinged for access. E2/4 Lighting 2013-02-19·EK00·III·en
  • 5. E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Technical data Mounting / installation Mounting 2 x M8 inserts in housing Mounting grooves in housing to accommodate bracket fitting and ceiling rails for variable light installation. Variable mounting distances of light fittings; see dimension drawings Cable glands 1 x cable gland 8161, M25 x 1.5, cable dia. range: d 7 ... 17 mm 2 x stopping plugs 8290, M25 x 1.5 Entry parts in moulded plastic (8161 / 8290): M20 Metal glands: M20; M25; Metal cable gland earthing via metal adapter plates Connection Standard Spring cage terminal connection cross-section: max. 2 x 2.5 mm2 3 pole (terminal marking: L1 + N + PE) 5 pole (terminal marking: L1 + L2 + L3 + N + PE) Special Terminal block with screw terminals connection cross-section: max. 2 x 6 mm2 (solid) max. 2 x 4 mm2 (flexible) numbers of terminals: 3 pole (terminal marking: L1 + N + PE) 5 pole (terminal marking: L1 + L2 + L3 + N + PE) Installation notes Looping through of cables There are 2 M25 x 1.5 cable entries on the connection side for looping through of connection cable (entry and exit on one side). Through wiring Fittings can be supplied with internal through-wiring. Entry and exit holes for connection cables are positioned on opposite sides. A through-wiring kit can be fitted after manufacture (see accessories). Terminals: See technical data top Wiring cross-section: 2.5 mm2 for max. 16 A Monitoring module Function Monitoring and switching module for emergency light systems according to VDE 0108: The module is used for the monitoring of individual lights and for the control of network and safety lights. The module offers the following functions: • Control of the light (ON / OFF) and function test • Up to 20 addresses can be set for each electric circuit by means of a coding switch • The operating mode of the lamp (continuous light, stand-by light or activation by means of a switch) is freely programmable • Mixed operation within one circuit is possible Input voltage (Input between L+ and N-) UN 230 (+ 10 % / - 15 %) V AC, 50 Hz U DC 175 ... 275 V DC Control input (between L and N) Connected power (output to light) Ambient temperature UN 230 (+ 10 % / - 15 %) V AC, 50 Hz P 4 ... 100 W Ta (Module) - 10 ... + 50 °C Dimensions L x W x H = 95 x 40 x 32 mm 2013-02-19·EK00·III·en Lighting E2/5
  • 6. Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Accessories and spare parts Designation Figure Description Art. no. Weight kg Fluorescent lamp 04936E00 Two-pin cap d 26 mm Light colour: universal white 108952 0.100 108951 0.200 108950 0.220 Diffuser cover 05329E00 18 W 1350 Im 36 W 3350 Im 58 W 5200 Im for light fitting 18 W 124890 0.500 for light fitting 36 W 124897 0.860 for light fitting 58 W 124904 0.800 Switch 10809E00 Switching element 8080/1-3-L, 2 normally closed contacts 132527 0.025 Mounting kit for through wiring 05503E00 For later installation into standard-light fitting DV3, tension clamp terminals 3 x 2.5 mm2, max. 16 A terminal marking: L1 + N + PE 18 W 124925 0.120 36 W 124927 0.300 58 W 124929 0.300 DV5, tension clamp terminals 5 x 2.5 mm2, 0.000 max. 16 A terminal marking: L1 + L2 + L3 + N + PE 18 W 124919 0.300 36 W 124921 0.300 58 W 124923 0.300 DV3, screw terminals 3 x 2.5 mm2, max. 16 A terminal marking: L1 + N + PE 18 W 124912 0.400 36 W 124915 0.400 58 W 124917 0.400 DV5, screw terminals 5 x 2.5 mm2, max. 16 A terminal marking: L1 + L2 + L3 + N + PE 18 W 124895 0.400 36 W 124902 0.400 58 W 124909 0.400 Reflectors 05324E00 for later installation, broad deep beam For 1-lamp light fittings 18 W 117128 0.082 For 1-lamp light fittings 36 W 117137 0.172 For 1-lamp light fittings 58 W 117150 0.218 For 2-lamps light fittings18 W 117098 0.265 For 2-lamps light fittings36 W 117115 0.234 For 2-lamps light fittings 58 W 117145 0.290 E2/6 Lighting 2013-02-19·EK00·III·en
  • 7. E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Accessories and spare parts Designation Figure Description Art. no. Weight Adapter plates 05755E00 for earth continuity when using metal glands; kg 115815 0.070 115818 0.070 115821 0.070 115824 0.070 115826 0.060 115828 0.060 115829 0.060 Lamp-holder 05888E00 1 x M20 x 1.5 1 piece 1 x M25 x 1.5 1 piece 1 x NPT 1/2“ 1 piece 1 x NPT 3/4“ 1 piece 2 x M20 x 1.5 1 piece 2 x M25 x 1.5 1 piece 2 x NPT 1/2“ 1 piece Lamp holder for two-pin cap lamps G 13 107275 0.008 Mounting rail 05895E00 for a variable mounting distance of 1 pair 124894 0.210 Mounting clamp bra-cket 05896E00 124901 0.300 Ring bolts 05378E00 Mounting bracket mounted on the mounting rail for a variable mounting distance of 1 pair M8, direct mounting in insert nuts, 1 pair 115736 0.120 Wall-mounting bra-cket 05460E00 to mount the lamps as side-entry lamps using a tube with a length of 1300 mm, d 42 mm (for pipe clamp R 11/2“) 109281 6.000 Ceiling mounting bra-cket 05897E00 for ceiling suspension of the lamp, 1 pair 124908 0.230 Pipe clamps 09402E00 with mounting rail for a variable mounting distance; Material: stainless steel R 11/4“ (d 42 mm) 124913 1.140 R 11/2“ (d 48 mm) 124891 1.160 R 2“ (d 60 mm) 124898 1.300 Mounting set ,,Grid cable rack’’ 04361E00 for grid cable racks, with a cable diameter of 6 mm; with mounting rail for a variable mounting distance; Material: stainless steel 124905 1.560 Ceiling and wall-mounting bracket 05898E00 mounted on a mounting rail for a variable mounting dis-tance; Material: stainless steel Lamp can be swiveled in steps of 15° 1 pair 124910 1.150 2013-02-19·EK00·III·en Lighting E2/7
  • 8. Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Accessories and spare parts Designation Figure Description Art. no. Weight Cable gland 05864E00 of moulded material, series 8161 kg 138518 0.012 138454 0.600 138520 0.020 138456 1.000 Stopping plug 04840E00 8161/5-M20-13 1 piece 8161/5-M20-13 50 pieces 8161/5-M25-17 1 piece 8161/5-M25-17 50 pieces of moulded material, series 8290 143522 0.005 143543 0.500 143524 0.007 143544 0.700 Breathing gland 05703E00 8290/3-M20 1 piece 8290/3-M20 100 pieces 8290/3-M25 x 1,5 1 pieces 8290/3-M25 100 pieces for installation in lights; in moulded material; without counter nut 138573 0.010 138576 0.200 Thread: M25 x 1.5 1 pc Thread: M25 x 1.5 20 pcs E2/8 Lighting 2013-02-19·EK00·III·en
  • 9. E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 Light Fitting for Fluorescent Lamps Series ECOLUX 6600 Dimensional Drawings (All Dimensions in mm) - Subject to Alterations 04824E00 Light fittings ECOLUX 6600, 18 W, 36 W, 58 W Dimen-sions Light fitting 18 W 36 W 58 W L1 700 1310 1610 L2 1) 400 800 800 L3 2) 340 ... 460 680 ... 920 795 ... 1030 1) Fixed mounting distance 2) Variable mounting distance 04717E00 04822E00 Pipe clamp Mounting set grid cable rack 04716E00 04833E00 Ceiling- and wall-mounting bracket Ceiling mounting bracket 04823E00 04715E00 04834E00 Wall mounting bracket for pole-mounting version Ring bolt Mounting clamp bracket Installation accessories We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding. 2013-02-19·EK00·III·en Lighting E2/9