SlideShare uma empresa Scribd logo
1 de 42
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung 1
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Überblick
 Einführung
 Energiesparmaßnahmen anwenden
 Methode: Messung und Verifizierung (M&V)
 Theorie
 Definition
 Messbasis
 Kalkulation
 Optionen
 Übungen
 Geschäftsfall
 Beispiel
2Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Einführung.
3Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Measurement and
Verification (M&V)
You perform an energy conservation measure
(ECM).
An ECM can be:
 Installation of insulation
 Replacing windows
 Replacing light bulbs
 Modernisation of heating system
 Modernisation of machinery
 …
Introduction - Theory - Exercises - Business Case - Summary 4
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Messung und Verifikation (M&V)
Sie führen Energieeinsparmaßnahmen (englisch:
(Energy Conservation Measure, ECM) durch.
Ein ECM kann sein:
 Installation von Isolierungen
 Austauschen der Fenster
 Austauschen der Glühbirnen
 Modernisierung der Heizungsanlage
 Modernisierung der Maschinen
 …
5Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Wenn Sie Energiesparmaßnahmen durchführen,
kommen folgende Fragen auf:
 Wie viel Energie spart man?
 Wie kann man die Einsparungen kalkulieren, wenn
sich die Produktion oder Umstände verändern?
 Nach der Einführung des ECM: stellen Sie mehr
oder weniger Produkte her?
 Ihre Produktion läuft auf eine andere Art?
Sie müssen also:
 Ihren Energieverbrauch systematisch messen und
 einen detaillierten Überblick über Ihre
Energieströme entwickeln.
[2]
6Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Messung und Verifikation (M&V)
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Die M&V Methode hilft Ihnen
 Die von der ECM gelieferten Energieeinsparungen
einzugrenzen
 Die Energieeinsparungen zu evaluieren.
Um genau zu sein:
M&V ist das Verfahren, um Energieeinsparungen zu
quantifizieren.
Eine gängige und international verwendete
Methode, um dies zu tun, ist das Internationale
Protokoll für Leistungsmessung und –überprüfung
(IPMVP). Das IPMVP wurde von der Efficiency
Valuation Organization (EVO) entwickelt. Wenn wir
von M&V sprechen, beinhaltet das auch das IPMVP.
[1, 2, 3]
7Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Messung und Verifikation (M&V)
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Messung und
Verifikation hilft Ihnen
Energieeinsparungen zu
identifizieren und zu
kalkulieren.
8Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Theorie.
9Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
10Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Wie viel sparen wir
und sind die
Einsparungen
nachhaltig?
Wichtige Fragen
11Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
M&V eignet sich für alle Arten von Energie.
Esko Strom – ein südafrikanisches Stadtwerk
sagt:
“Das Grundprinzip von M & V ist es den
gemessene Stromverbrauch und den Bedarf
nach der Umsetzung mit dem was vor der
Umsetzung war zu vergleichen, um die
Auswirkungen festzustellen."
[2]
Definition
12Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Maßnahmen:
Vergleichen Sie den Energieverbrauch vor und
nach der Umsetzung einer Energiesparmaßnahme.
 Schwierigkeiten:
Projektpartner sind voreingenommen; sie
vernachlässigen wichtige Schritte oder kalkulieren
zu optimistisch. Für sie kann es schwierig sein eine
objektive Bewertung abzugeben und ein
transparentes Verfahren zu gewährleisten.
 Besser:
Ein unvoreingenommenes Team koordiniert das
M&V.
[3]
Vor dem Start
13Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Messbasis
Das System kann zwischen Vor-und Nach-Implementierung aufgrund von
Faktoren wie Umwelt, Kapazitätsauslastung, Arbeitszeiten usw. geändert
werden
 Maßnahmen:
 Der Verbrauch vor der Implementierung wird als Messbasis
angesehen (ein bekanntes System und bekannte Werte).
 Wenn sich das System nicht verändert, kann der Einsatz nach der
Implementierung direkt mit der Messbasis verglichen werden.
 Wenn sich das System verändert hat müssen Anpassungen kalkuliert
werden.
[3]
14Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Optionen:
Um die Maßnahmen zu überprüfen wählen Sie eine der vier M&V Optionen (auf den
folgenden Folien)
 Maßnahmen:
1. Messen Sie den Energieverbrauch vor der Umsetzung
2. Setzten Sie Energiesparmaßnahmen um
3. Bestimmen Sie Anpassungen
4. Wiederholtes Messen des Energieverbrauchs
5. Kalkulieren Sie die Einsparungen
 Formel:
Einsparungen = Energienutzung Vor-Implementierung
– Energienutzung Nach-Implementierung
± Anpassung [2, 3]
Handeln
15Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Optionen
M&V wird in verschiedenen Komplexitätslevel umgesetzt. Abhängig von dem
Projektumfang und der angestrebten Wirkung entstehen vier Optionen.
 Option A: Partiell gemessene Isolationsnachrüstung
Verwendung wird teilweise gemessen und teilweise festgesetzt/geschätzt
 Option B: Isolationsnachrüstung
Verwendung wird gemessen
 Option C: Gesamtes Gebäude
Die Energienutzung eines gesamten Gebäudes wird gemessen
 Option D: Kalibrierte Simulation
Computersimulation, um die Energienutzung zu prognostizieren
[2, 3, 5]
16Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Option A: Partiell gemessene
Isolationsnachrüstung
 Kalkulation des Energieverbrauchs für die Messwerte über den
gesamten Untersuchungszeitraum.
 Schätzung einiger Parameter
 Anpassungen nach Bedarf
 Geeignet für alle Anlagegrößen, am besten für einzelne Einheiten
Beispiel:
 Messung des Stromverbrauchs der Beleuchtung
 Abschätzung der Betriebsstunden
[2, 3, 5]
17Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Option B: Isolationsnachrüstung
 Kurz-oder Langzeitmessungen wichtiger Parameter
 Anpassung nach Bedarf
 Geeignet für alle Anlagegrößen, am besten für einzelne Einheiten
Beispiel:
 Messung der Elektrischen Leistung einer Pumpe
 Wiederholte Messung nach dem Austausch der Pumpe
[3]
18Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Option C: Gesamtes Gebäude
 Stromverbrauchsmessung eines ganzen Gebäudes oder einer Anlage
 Wird verwendet, wenn eine Einzelmessung schwierig ist oder eine
Maßnahme sich auf mehrere Elemente einer Anlage auswirkt.
Beispiel
 Erneuerung des Heizsystems und der Isolierung eines gesamten
Gebäudes.
 Eine Langzeitmessung vor der Umsetzung der Energiesparmaßnahme
dient als Referenz / Messbasis.
 Eine wiederholte Maßnahme wird mit der Messbasis verglichen.
[3]
19Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Option D: Kalibrierte Simulation
 Einsparungen werden durch Simulation einer Anlage berechnet.
 Eine Energiemessung vor der Energiemaßnahme ist nicht erforderlich. Zum Beispiel
können Abrechnungsdaten verwendet werden um den Energieverbrauch zu
bestimmen.
 Kalibrierung ist notwendig, um eine Vergleichbarkeit zu schaffen. Die Kalibrierung
kann durch die Anpassung simulierter Werte an die Messwerte erfolgen.
Beispiel
 Eine facettenreiche Energiemaßnahme wird umgesetzt, die sich auf das ganze
Gebäude auswirkt, aber vorher wurde kein Messgerät installiert.
 Die Messbasis der Energienutzung ist simuliert.
 Nach der Installation von Energiezählern kann die Simulation kalibriert werden.
 Die Simulation kann mit der Messung verglichen werden. [3]
20Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Wie man eine M&V Option auswählt
In der Literatur, finden Sie Anleitungen oder Empfehlungen für die Auswahl der
Optionen A, B, C oder D.
21
[3]
Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Sind die Einsparungen dauerhaft?
 Energiemaßnahmen können fehlschlagen (z. B. nur kurzfristige Einsparungen,
„Rebound-Effekt“: geringerer Energieverbrauch führt zu einer vermehrten
Systemnutzung, Beschäftigte handeln unangemessen)
 Geringer Energieverbrauch in einem Bereich oder einer Anwendung kann
zu mehr Energieverbrauch in einem anderen Bereich führen
 Wenn Sie Messgeräte installiert haben: Überwachung der Einsparungen.
Die Methode „Überwachung & Zielbestimmung“ (M&T) kann einem M&V
folgen.
 Verwenden Sie Ihre Modelle um den Energieverbrauch zu überprüfen.
[3]
22Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Übungen.
23Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Wann verwenden Sie Messung
und Verifikation?
a. Wenn eine Energiesparmaßnahme
installiert ist.
b. Wenn der Energieverbrauch höher als
der Durchschnitt ist.
Verwendung von M&V
24Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Wann verwenden Sie Messung
und Verifikation?
a. Wenn eine Energiesparmaßnahme
installiert ist.
b. Wenn der Energieverbrauch höher als
der Durchschnitt ist.
Verwendung von M&V
25Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Lückentext
Eingabe der richtigen, fehlenden Worte.
Einsparungen = Energienutzung Vor-______________
– Energienutzung Nach-______________
± Anpassungen
Messung Simulation Implementation Verifikation
26Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Lückentext
Eingabe der richtigen, fehlenden Worte.
Einsparungen = Energienutzung Vor-______________
– Energienutzung Nach-______________
± Anpassungen
Messung Simulation Implementation Verifikation
27Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Warum benötigt man
Anpassungen bei der
Kalkulation von
Energieeinsparungen?
a. Weil Energiepreise sich während dem
M&V verändern können.
b. Weil sich die Maschinennutzung oder das
Wetter währen dem M&V verändern
können.
Anpassungen
28Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Warum benötigt man
Anpassungen bei der
Kalkulation von
Energieeinsparungen?
a. Weil Energiepreise sich während dem
M&V verändern können.
b. Weil sich die Maschinennutzung oder das
Wetter währen dem M&V verändern
können.
Anpassungen
29Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Option A: Partiell gemessene Isolationsnachrüstung
Verwendung sowohl gemessen als auch festgesetzt/geschätzt
 Option B: Isolationsnachrüstung
Verwendung wird gemessen
 Option C: Gesamtes Gebäude
Die Energienutzung eines gesamten Gebäudes wird gemessen
 Option D: Kalibrierte Simulation
Computersimulation um die Energienutzung zu prognostizieren
Was ist anders zwischen Option A und D?
a. A ist für kleine Unternehmen, B und C für mittlere
Unternehmen, D für große Unternehmen.
b. Sie unterscheiden sich in der Messskala, simulierten und
geschätzte Daten.
Optionen
30Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Option A: Partiell gemessene Isolationsnachrüstung
Verwendung sowohl gemessen als auch festgesetzt/geschätzt
 Option B: Isolationsnachrüstung
Verwendung wird gemessen
 Option C: Gesamtes Gebäude
Die Energienutzung eines gesamten Gebäudes wird gemessen
 Option D: Kalibrierte Simulation
Computersimulation um die Energienutzung zu prognostizieren
Was ist anders zwischen Option A und D?
a. A ist für kleine Unternehmen, B und C für mittlere
Unternehmen, D für große Unternehmen.
b. Sie unterscheiden sich in der Messskala, simulierten und
geschätzte Daten.
Optionen
31Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Denken Sie an ein System in
Ihrem Unternehmen,
welches durch M&V
analysiert werden könnte.
Virtualisieren Sie den M&V
Prozess.
Analyse
32Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Haben Sie berücksichtigt ob der
Energieverbrauch vor dem ECM
gemessen werden kann?
 Haben Sie die Installation von
Messsystemen berücksichtigt?
 Haben Sie eine der vier M&V
Optionen ausgewählt?
Analyse
33Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Geschäftsfall.
34Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Projekt: Verbesserung der Boiler-
Effizienz[3]
 Situation:
– Ein Boileranbieter ersetzt einen Boiler
in einem Bürogebäude.
– Der Anbieter garantiert jährliche Öl-
Einsparungen von min. 25.000€.
– Der Anbieter ist verpflichtet zu einem
Bericht über die Einsparungen und
nach dem M&V Plan vorzugehen.
– Während der M&V Periode gehen
die Veränderungen am
Hauptgebäude weiter.
Praxisbeispiel
35Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Maßnahmen:
– Wahl der Option A, um den Boiler vom Rest des
Gebäudes zu isolieren.
– Systemabgrenzung rund um den Boiler: Öl-
Einspeisung und thermischer Energieausstoß
ohne elektrische Energie.
– Während der drei vordefinierten Standardtage
wird der Wirkungsgrad des Boilers nach und vor
dem Austausch gemessen.
Praxisbeispiel
36Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Einsparungen:
 Gesparte Ölmenge pro Jahr: 45.700 Liter
 Einsparungen pro Jahr: 31.990 € (in der Annahme, dass 0,70
€/Liter)
Vor dem
Austausch
Nach dem
Austausch
Effizienz 65,2 % 80,6 %
Ölverbrauch/Jahr 239.200 Liter 193.500 Liter
Praxisbeispiel
37Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
Zusammenfassung.
38Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Es ist wichtig den Erfolg einer Energiesparmaßnahme zu
überwachen (ECM)
 M&V kann dabei helfen Energieeinsparungen mit dem ECM
zu trennen und die Einsparungen zu bewerten.
 Vergleichen Sie die Energienutzung vor und nach der
Umsetzung eines ECM.
 Änderungen in der Anlage oder der Umwelt führen zu
Anpassungen in der Kalkulation.
 Vier Optionen sind verfügbar, um die Einsparungen zu
kalkulieren.
 Nach der Durchführung von M & V hilft eine
Langzeitüberwachung die Einsparungen zu erhalten.
Wiederholung
39Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
[1] Wikipedia: Measurement and Verification. URL:
http://en.wikipedia.org/wiki/Measurement_and_Verification
[2] Eskom (2010): The Measurement and Verification Guideline for Energy Efficiency and
Demand-Side Management (EEDSM) Projects and Programmes. URL:
http://www.eskom.co.za/IDM/MeasurementVerification/Documents/M_and_V_guideline_v10r
5.pdf
[3] Efficiency Valuation Organization (2012): International Performance Measurement and
Verification Protocol. URL:
http://www.evo-world.org/index.php?option=com_rsform&formId=113&lang=en
[4] U.S. Department of Energy (2008): M&V Guidelines: Measurement and Verification for
Federal Energy Projects, Version 3.0. URL:
http://www1.eere.energy.gov/femp/pdfs/mv_guidelines.pdf
[5] European Commission (2009): Reference Document on Best Available Techniques for
Energy Efficiency. URL: http://eippcb.jrc.ec.europa.eu/reference/BREF/ENE_Adopted_02-
2009.pdf
Lektüre
40Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Folie 1 – Tekke: Stromkosten steigen! – URI:
http://www.flickr.com/photos/tekkebln/8978451063/sizes/k/in/photostream / License: CC BY-ND 2.0
(http://creativecommons.org/licenses/by-nd/2.0/legalcode)
 Folie 3, 22 – Florian Simeth: Arbeiten von zu Hause mit dem Laptop – URI:
http://www.flickr.com/photos/hangout-lifestyle/5865980513/sizes/o/in/photostream/ License: CC BY 2.0
(http://creativecommons.org/licenses/by/2.0/legalcode)
 Folie 4, 5, 6 – dr. friendly: halogen glühlampe – URI:
http://www.flickr.com/photos/57777529@N02/5343580540/sizes/z/in/photostream/ License: CC BY-SA 2.0
(http://creativecommons.org/licenses/by-sa/2.0/legalcode)
 Folie 7 – Tai Viinikka: IMG_1956: The Energy Detective – URI:
http://www.flickr.com/photos/eastpole/2087714870/sizes/l/in/photostream/ License: CC BY-NC-ND 2.0
(http://creativecommons.org/licenses/by-nc-nd/2.0/legalcode)
 Folie 8 – botgirlq: EXTROVERSION CHART – URI:
http://www.flickr.com/photos/botgirlq/2541357441/sizes/o/in/photostream/ License: CC BY-NC 2.0
(http://creativecommons.org/licenses/by-nc/2.0/legalcode)
 Folie 9 – Dennis Skley: *grübel* – URI: http://www.flickr.com/photos/dskley/8627475625/sizes/z/in/photostream/
License: CC BY-ND 2.0 (http://creativecommons.org/licenses/by-nd/2.0/legalcode)
 Folie 10, 23, 27, 29, 31 – Bilal Kamoon: Question Mark Graffiti – URI: http://www.flickr.com/photos/bilal-
kamoon/6835060992/sizes/m/in/photostream/ License: CC BY 2.0
(http://creativecommons.org/licenses/by/2.0/legalcode)
 Folie 12 – AndYaDontStop: The road of life twists and turns and no two directions are ever the same. Yet our
lessons come from the journey, not the destination......365/365 – URI:
http://www.flickr.com/photos/thenovys/3833212599/sizes/m/in/photostream/ License: CC BY 2.0
(http://creativecommons.org/licenses/by/2.0/legalcode)
Bilder -1
41Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
Co-funded by the Intelligent
Energy Europe Programme of
the European Union
 Folie 24, 28, 30, 32 – Photocapy: ! – URI:
http://www.flickr.com/photos/photocapy/3834784192/sizes/m/in/photostream/ License: CC BY-SA 2.0
(http://creativecommons.org/licenses/by-sa/2.0/legalcode)
 Folie 33 – Son of Groucho: Not Our Guide – URI:
http://www.flickr.com/photos/sonofgroucho/3855487710/sizes/z/in/photostream/ License: CC BY 2.0
(http://creativecommons.org/licenses/by/2.0/legalcode)
 Folie 34 – nz_willowherb: Boilers – URI:
http://www.flickr.com/photos/willowherb/354986002/sizes/z/in/photostream/ License: CC BY-NC 2.0
(http://creativecommons.org/licenses/by-nc/2.0/legalcode)
 Folie 37 – Kutchala Sutchi: Repetition, 23.03.'10, Abidjan-Yopougon (4640) – URI:
http://www.flickr.com/photos/kutchala/4469943694/sizes/o/in/photostream/ License: CC BY 2.0
(http://creativecommons.org/licenses/by/2.0/legalcode)
Bilder -2
42Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung

Mais conteúdo relacionado

Destaque

SESEC Versorgungsverträge und Lastverschiebung
SESEC Versorgungsverträge und LastverschiebungSESEC Versorgungsverträge und Lastverschiebung
SESEC Versorgungsverträge und LastverschiebungDITF Denkendorf
 
Praesentation Meinungs Bild
Praesentation Meinungs BildPraesentation Meinungs Bild
Praesentation Meinungs Bildrandomflow
 
Circuitos eléctricos de la escuela san Francisco de Asis
Circuitos eléctricos de la escuela san Francisco de AsisCircuitos eléctricos de la escuela san Francisco de Asis
Circuitos eléctricos de la escuela san Francisco de Asisfabianarivero27
 
BGF-UNESCO-at-UCLA conference - GCE in Cyber Civil Defense
BGF-UNESCO-at-UCLA conference - GCE in Cyber Civil DefenseBGF-UNESCO-at-UCLA conference - GCE in Cyber Civil Defense
BGF-UNESCO-at-UCLA conference - GCE in Cyber Civil DefenseBoston Global Forum
 
Many Ways to Keep the Promise
Many Ways to Keep the PromiseMany Ways to Keep the Promise
Many Ways to Keep the PromiseTeamMates
 
Contenido matematicas basicas 2017
Contenido matematicas basicas 2017Contenido matematicas basicas 2017
Contenido matematicas basicas 2017Rochy Montenegro
 
PetroSync - Financial Assets Valuation for Oil & Gas
PetroSync - Financial Assets Valuation for Oil & GasPetroSync - Financial Assets Valuation for Oil & Gas
PetroSync - Financial Assets Valuation for Oil & GasPetroSync
 
Karen N. Johnson Storytelling (2009)
Karen N. Johnson Storytelling (2009)Karen N. Johnson Storytelling (2009)
Karen N. Johnson Storytelling (2009)Karen N. Johnson
 

Destaque (13)

SESEC Versorgungsverträge und Lastverschiebung
SESEC Versorgungsverträge und LastverschiebungSESEC Versorgungsverträge und Lastverschiebung
SESEC Versorgungsverträge und Lastverschiebung
 
Praesentation Meinungs Bild
Praesentation Meinungs BildPraesentation Meinungs Bild
Praesentation Meinungs Bild
 
Remote office
Remote officeRemote office
Remote office
 
Hybrid-dur-keCq7nCdml
Hybrid-dur-keCq7nCdmlHybrid-dur-keCq7nCdml
Hybrid-dur-keCq7nCdml
 
Circuitos eléctricos de la escuela san Francisco de Asis
Circuitos eléctricos de la escuela san Francisco de AsisCircuitos eléctricos de la escuela san Francisco de Asis
Circuitos eléctricos de la escuela san Francisco de Asis
 
Validacion propuesta-magdalena
Validacion propuesta-magdalenaValidacion propuesta-magdalena
Validacion propuesta-magdalena
 
BGF-UNESCO-at-UCLA conference - GCE in Cyber Civil Defense
BGF-UNESCO-at-UCLA conference - GCE in Cyber Civil DefenseBGF-UNESCO-at-UCLA conference - GCE in Cyber Civil Defense
BGF-UNESCO-at-UCLA conference - GCE in Cyber Civil Defense
 
Many Ways to Keep the Promise
Many Ways to Keep the PromiseMany Ways to Keep the Promise
Many Ways to Keep the Promise
 
Contenido matematicas basicas 2017
Contenido matematicas basicas 2017Contenido matematicas basicas 2017
Contenido matematicas basicas 2017
 
Experience egypt on facebook
Experience egypt on facebookExperience egypt on facebook
Experience egypt on facebook
 
PetroSync - Financial Assets Valuation for Oil & Gas
PetroSync - Financial Assets Valuation for Oil & GasPetroSync - Financial Assets Valuation for Oil & Gas
PetroSync - Financial Assets Valuation for Oil & Gas
 
Floating Markets of Thailand
Floating Markets of ThailandFloating Markets of Thailand
Floating Markets of Thailand
 
Karen N. Johnson Storytelling (2009)
Karen N. Johnson Storytelling (2009)Karen N. Johnson Storytelling (2009)
Karen N. Johnson Storytelling (2009)
 

Mais de DITF Denkendorf

Mais de DITF Denkendorf (20)

SESC Compressed Air
SESC Compressed AirSESC Compressed Air
SESC Compressed Air
 
SESEC EDST
SESEC EDSTSESEC EDST
SESEC EDST
 
SESEC Lighting
SESEC LightingSESEC Lighting
SESEC Lighting
 
SESEC Compressed Air
SESEC Compressed AirSESEC Compressed Air
SESEC Compressed Air
 
SESEC SAT Self Assessment
SESEC SAT Self AssessmentSESEC SAT Self Assessment
SESEC SAT Self Assessment
 
SESEC Steam HR
SESEC Steam HRSESEC Steam HR
SESEC Steam HR
 
SESEC Heating HR
SESEC Heating HRSESEC Heating HR
SESEC Heating HR
 
SESEC approach
SESEC approachSESEC approach
SESEC approach
 
SESEC - Garas
SESEC - GarasSESEC - Garas
SESEC - Garas
 
SESEC - Atsinaujinanti energija ir kogeneracija
SESEC - Atsinaujinanti energija ir kogeneracijaSESEC - Atsinaujinanti energija ir kogeneracija
SESEC - Atsinaujinanti energija ir kogeneracija
 
SESEC - Selbstevaluierungstool SAT
SESEC - Selbstevaluierungstool SATSESEC - Selbstevaluierungstool SAT
SESEC - Selbstevaluierungstool SAT
 
SESEC - Vakuum und Reinigung
SESEC - Vakuum und ReinigungSESEC - Vakuum und Reinigung
SESEC - Vakuum und Reinigung
 
SESEC Klimatechnik und Belüftung
SESEC Klimatechnik und BelüftungSESEC Klimatechnik und Belüftung
SESEC Klimatechnik und Belüftung
 
SESEC Heizung
SESEC HeizungSESEC Heizung
SESEC Heizung
 
SESEC Vacuum LIT
SESEC Vacuum LITSESEC Vacuum LIT
SESEC Vacuum LIT
 
SESEC - Tiekimo kontraktai ir apkrovos keitimas
SESEC - Tiekimo kontraktai ir apkrovos keitimasSESEC - Tiekimo kontraktai ir apkrovos keitimas
SESEC - Tiekimo kontraktai ir apkrovos keitimas
 
SESEC - Erneuerbare Energie & Kraft-Wärme-Kopplung
SESEC - Erneuerbare Energie & Kraft-Wärme-KopplungSESEC - Erneuerbare Energie & Kraft-Wärme-Kopplung
SESEC - Erneuerbare Energie & Kraft-Wärme-Kopplung
 
SESEC - Beleuchtung
SESEC - BeleuchtungSESEC - Beleuchtung
SESEC - Beleuchtung
 
SESEC - Druckluft
SESEC - DruckluftSESEC - Druckluft
SESEC - Druckluft
 
SESEC - Dampf
SESEC - DampfSESEC - Dampf
SESEC - Dampf
 

SESEC - Messung und Verfizierung

  • 1. Co-funded by the Intelligent Energy Europe Programme of the European Union Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung 1
  • 2. Co-funded by the Intelligent Energy Europe Programme of the European Union Überblick  Einführung  Energiesparmaßnahmen anwenden  Methode: Messung und Verifizierung (M&V)  Theorie  Definition  Messbasis  Kalkulation  Optionen  Übungen  Geschäftsfall  Beispiel 2Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 3. Co-funded by the Intelligent Energy Europe Programme of the European Union Einführung. 3Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 4. Co-funded by the Intelligent Energy Europe Programme of the European Union Measurement and Verification (M&V) You perform an energy conservation measure (ECM). An ECM can be:  Installation of insulation  Replacing windows  Replacing light bulbs  Modernisation of heating system  Modernisation of machinery  … Introduction - Theory - Exercises - Business Case - Summary 4
  • 5. Co-funded by the Intelligent Energy Europe Programme of the European Union Messung und Verifikation (M&V) Sie führen Energieeinsparmaßnahmen (englisch: (Energy Conservation Measure, ECM) durch. Ein ECM kann sein:  Installation von Isolierungen  Austauschen der Fenster  Austauschen der Glühbirnen  Modernisierung der Heizungsanlage  Modernisierung der Maschinen  … 5Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 6. Co-funded by the Intelligent Energy Europe Programme of the European Union Wenn Sie Energiesparmaßnahmen durchführen, kommen folgende Fragen auf:  Wie viel Energie spart man?  Wie kann man die Einsparungen kalkulieren, wenn sich die Produktion oder Umstände verändern?  Nach der Einführung des ECM: stellen Sie mehr oder weniger Produkte her?  Ihre Produktion läuft auf eine andere Art? Sie müssen also:  Ihren Energieverbrauch systematisch messen und  einen detaillierten Überblick über Ihre Energieströme entwickeln. [2] 6Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung Messung und Verifikation (M&V)
  • 7. Co-funded by the Intelligent Energy Europe Programme of the European Union Die M&V Methode hilft Ihnen  Die von der ECM gelieferten Energieeinsparungen einzugrenzen  Die Energieeinsparungen zu evaluieren. Um genau zu sein: M&V ist das Verfahren, um Energieeinsparungen zu quantifizieren. Eine gängige und international verwendete Methode, um dies zu tun, ist das Internationale Protokoll für Leistungsmessung und –überprüfung (IPMVP). Das IPMVP wurde von der Efficiency Valuation Organization (EVO) entwickelt. Wenn wir von M&V sprechen, beinhaltet das auch das IPMVP. [1, 2, 3] 7Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung Messung und Verifikation (M&V)
  • 8. Co-funded by the Intelligent Energy Europe Programme of the European Union Messung und Verifikation hilft Ihnen Energieeinsparungen zu identifizieren und zu kalkulieren. 8Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 9. Co-funded by the Intelligent Energy Europe Programme of the European Union Theorie. 9Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 10. Co-funded by the Intelligent Energy Europe Programme of the European Union 10Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 11. Co-funded by the Intelligent Energy Europe Programme of the European Union Wie viel sparen wir und sind die Einsparungen nachhaltig? Wichtige Fragen 11Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 12. Co-funded by the Intelligent Energy Europe Programme of the European Union M&V eignet sich für alle Arten von Energie. Esko Strom – ein südafrikanisches Stadtwerk sagt: “Das Grundprinzip von M & V ist es den gemessene Stromverbrauch und den Bedarf nach der Umsetzung mit dem was vor der Umsetzung war zu vergleichen, um die Auswirkungen festzustellen." [2] Definition 12Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 13. Co-funded by the Intelligent Energy Europe Programme of the European Union  Maßnahmen: Vergleichen Sie den Energieverbrauch vor und nach der Umsetzung einer Energiesparmaßnahme.  Schwierigkeiten: Projektpartner sind voreingenommen; sie vernachlässigen wichtige Schritte oder kalkulieren zu optimistisch. Für sie kann es schwierig sein eine objektive Bewertung abzugeben und ein transparentes Verfahren zu gewährleisten.  Besser: Ein unvoreingenommenes Team koordiniert das M&V. [3] Vor dem Start 13Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 14. Co-funded by the Intelligent Energy Europe Programme of the European Union Messbasis Das System kann zwischen Vor-und Nach-Implementierung aufgrund von Faktoren wie Umwelt, Kapazitätsauslastung, Arbeitszeiten usw. geändert werden  Maßnahmen:  Der Verbrauch vor der Implementierung wird als Messbasis angesehen (ein bekanntes System und bekannte Werte).  Wenn sich das System nicht verändert, kann der Einsatz nach der Implementierung direkt mit der Messbasis verglichen werden.  Wenn sich das System verändert hat müssen Anpassungen kalkuliert werden. [3] 14Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 15. Co-funded by the Intelligent Energy Europe Programme of the European Union  Optionen: Um die Maßnahmen zu überprüfen wählen Sie eine der vier M&V Optionen (auf den folgenden Folien)  Maßnahmen: 1. Messen Sie den Energieverbrauch vor der Umsetzung 2. Setzten Sie Energiesparmaßnahmen um 3. Bestimmen Sie Anpassungen 4. Wiederholtes Messen des Energieverbrauchs 5. Kalkulieren Sie die Einsparungen  Formel: Einsparungen = Energienutzung Vor-Implementierung – Energienutzung Nach-Implementierung ± Anpassung [2, 3] Handeln 15Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 16. Co-funded by the Intelligent Energy Europe Programme of the European Union Optionen M&V wird in verschiedenen Komplexitätslevel umgesetzt. Abhängig von dem Projektumfang und der angestrebten Wirkung entstehen vier Optionen.  Option A: Partiell gemessene Isolationsnachrüstung Verwendung wird teilweise gemessen und teilweise festgesetzt/geschätzt  Option B: Isolationsnachrüstung Verwendung wird gemessen  Option C: Gesamtes Gebäude Die Energienutzung eines gesamten Gebäudes wird gemessen  Option D: Kalibrierte Simulation Computersimulation, um die Energienutzung zu prognostizieren [2, 3, 5] 16Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 17. Co-funded by the Intelligent Energy Europe Programme of the European Union Option A: Partiell gemessene Isolationsnachrüstung  Kalkulation des Energieverbrauchs für die Messwerte über den gesamten Untersuchungszeitraum.  Schätzung einiger Parameter  Anpassungen nach Bedarf  Geeignet für alle Anlagegrößen, am besten für einzelne Einheiten Beispiel:  Messung des Stromverbrauchs der Beleuchtung  Abschätzung der Betriebsstunden [2, 3, 5] 17Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 18. Co-funded by the Intelligent Energy Europe Programme of the European Union Option B: Isolationsnachrüstung  Kurz-oder Langzeitmessungen wichtiger Parameter  Anpassung nach Bedarf  Geeignet für alle Anlagegrößen, am besten für einzelne Einheiten Beispiel:  Messung der Elektrischen Leistung einer Pumpe  Wiederholte Messung nach dem Austausch der Pumpe [3] 18Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 19. Co-funded by the Intelligent Energy Europe Programme of the European Union Option C: Gesamtes Gebäude  Stromverbrauchsmessung eines ganzen Gebäudes oder einer Anlage  Wird verwendet, wenn eine Einzelmessung schwierig ist oder eine Maßnahme sich auf mehrere Elemente einer Anlage auswirkt. Beispiel  Erneuerung des Heizsystems und der Isolierung eines gesamten Gebäudes.  Eine Langzeitmessung vor der Umsetzung der Energiesparmaßnahme dient als Referenz / Messbasis.  Eine wiederholte Maßnahme wird mit der Messbasis verglichen. [3] 19Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 20. Co-funded by the Intelligent Energy Europe Programme of the European Union Option D: Kalibrierte Simulation  Einsparungen werden durch Simulation einer Anlage berechnet.  Eine Energiemessung vor der Energiemaßnahme ist nicht erforderlich. Zum Beispiel können Abrechnungsdaten verwendet werden um den Energieverbrauch zu bestimmen.  Kalibrierung ist notwendig, um eine Vergleichbarkeit zu schaffen. Die Kalibrierung kann durch die Anpassung simulierter Werte an die Messwerte erfolgen. Beispiel  Eine facettenreiche Energiemaßnahme wird umgesetzt, die sich auf das ganze Gebäude auswirkt, aber vorher wurde kein Messgerät installiert.  Die Messbasis der Energienutzung ist simuliert.  Nach der Installation von Energiezählern kann die Simulation kalibriert werden.  Die Simulation kann mit der Messung verglichen werden. [3] 20Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 21. Co-funded by the Intelligent Energy Europe Programme of the European Union Wie man eine M&V Option auswählt In der Literatur, finden Sie Anleitungen oder Empfehlungen für die Auswahl der Optionen A, B, C oder D. 21 [3] Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 22. Co-funded by the Intelligent Energy Europe Programme of the European Union Sind die Einsparungen dauerhaft?  Energiemaßnahmen können fehlschlagen (z. B. nur kurzfristige Einsparungen, „Rebound-Effekt“: geringerer Energieverbrauch führt zu einer vermehrten Systemnutzung, Beschäftigte handeln unangemessen)  Geringer Energieverbrauch in einem Bereich oder einer Anwendung kann zu mehr Energieverbrauch in einem anderen Bereich führen  Wenn Sie Messgeräte installiert haben: Überwachung der Einsparungen. Die Methode „Überwachung & Zielbestimmung“ (M&T) kann einem M&V folgen.  Verwenden Sie Ihre Modelle um den Energieverbrauch zu überprüfen. [3] 22Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 23. Co-funded by the Intelligent Energy Europe Programme of the European Union Übungen. 23Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 24. Co-funded by the Intelligent Energy Europe Programme of the European Union Wann verwenden Sie Messung und Verifikation? a. Wenn eine Energiesparmaßnahme installiert ist. b. Wenn der Energieverbrauch höher als der Durchschnitt ist. Verwendung von M&V 24Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 25. Co-funded by the Intelligent Energy Europe Programme of the European Union Wann verwenden Sie Messung und Verifikation? a. Wenn eine Energiesparmaßnahme installiert ist. b. Wenn der Energieverbrauch höher als der Durchschnitt ist. Verwendung von M&V 25Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 26. Co-funded by the Intelligent Energy Europe Programme of the European Union Lückentext Eingabe der richtigen, fehlenden Worte. Einsparungen = Energienutzung Vor-______________ – Energienutzung Nach-______________ ± Anpassungen Messung Simulation Implementation Verifikation 26Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 27. Co-funded by the Intelligent Energy Europe Programme of the European Union Lückentext Eingabe der richtigen, fehlenden Worte. Einsparungen = Energienutzung Vor-______________ – Energienutzung Nach-______________ ± Anpassungen Messung Simulation Implementation Verifikation 27Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 28. Co-funded by the Intelligent Energy Europe Programme of the European Union Warum benötigt man Anpassungen bei der Kalkulation von Energieeinsparungen? a. Weil Energiepreise sich während dem M&V verändern können. b. Weil sich die Maschinennutzung oder das Wetter währen dem M&V verändern können. Anpassungen 28Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 29. Co-funded by the Intelligent Energy Europe Programme of the European Union Warum benötigt man Anpassungen bei der Kalkulation von Energieeinsparungen? a. Weil Energiepreise sich während dem M&V verändern können. b. Weil sich die Maschinennutzung oder das Wetter währen dem M&V verändern können. Anpassungen 29Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 30. Co-funded by the Intelligent Energy Europe Programme of the European Union  Option A: Partiell gemessene Isolationsnachrüstung Verwendung sowohl gemessen als auch festgesetzt/geschätzt  Option B: Isolationsnachrüstung Verwendung wird gemessen  Option C: Gesamtes Gebäude Die Energienutzung eines gesamten Gebäudes wird gemessen  Option D: Kalibrierte Simulation Computersimulation um die Energienutzung zu prognostizieren Was ist anders zwischen Option A und D? a. A ist für kleine Unternehmen, B und C für mittlere Unternehmen, D für große Unternehmen. b. Sie unterscheiden sich in der Messskala, simulierten und geschätzte Daten. Optionen 30Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 31. Co-funded by the Intelligent Energy Europe Programme of the European Union  Option A: Partiell gemessene Isolationsnachrüstung Verwendung sowohl gemessen als auch festgesetzt/geschätzt  Option B: Isolationsnachrüstung Verwendung wird gemessen  Option C: Gesamtes Gebäude Die Energienutzung eines gesamten Gebäudes wird gemessen  Option D: Kalibrierte Simulation Computersimulation um die Energienutzung zu prognostizieren Was ist anders zwischen Option A und D? a. A ist für kleine Unternehmen, B und C für mittlere Unternehmen, D für große Unternehmen. b. Sie unterscheiden sich in der Messskala, simulierten und geschätzte Daten. Optionen 31Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 32. Co-funded by the Intelligent Energy Europe Programme of the European Union Denken Sie an ein System in Ihrem Unternehmen, welches durch M&V analysiert werden könnte. Virtualisieren Sie den M&V Prozess. Analyse 32Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 33. Co-funded by the Intelligent Energy Europe Programme of the European Union  Haben Sie berücksichtigt ob der Energieverbrauch vor dem ECM gemessen werden kann?  Haben Sie die Installation von Messsystemen berücksichtigt?  Haben Sie eine der vier M&V Optionen ausgewählt? Analyse 33Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 34. Co-funded by the Intelligent Energy Europe Programme of the European Union Geschäftsfall. 34Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 35. Co-funded by the Intelligent Energy Europe Programme of the European Union  Projekt: Verbesserung der Boiler- Effizienz[3]  Situation: – Ein Boileranbieter ersetzt einen Boiler in einem Bürogebäude. – Der Anbieter garantiert jährliche Öl- Einsparungen von min. 25.000€. – Der Anbieter ist verpflichtet zu einem Bericht über die Einsparungen und nach dem M&V Plan vorzugehen. – Während der M&V Periode gehen die Veränderungen am Hauptgebäude weiter. Praxisbeispiel 35Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 36. Co-funded by the Intelligent Energy Europe Programme of the European Union  Maßnahmen: – Wahl der Option A, um den Boiler vom Rest des Gebäudes zu isolieren. – Systemabgrenzung rund um den Boiler: Öl- Einspeisung und thermischer Energieausstoß ohne elektrische Energie. – Während der drei vordefinierten Standardtage wird der Wirkungsgrad des Boilers nach und vor dem Austausch gemessen. Praxisbeispiel 36Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 37. Co-funded by the Intelligent Energy Europe Programme of the European Union  Einsparungen:  Gesparte Ölmenge pro Jahr: 45.700 Liter  Einsparungen pro Jahr: 31.990 € (in der Annahme, dass 0,70 €/Liter) Vor dem Austausch Nach dem Austausch Effizienz 65,2 % 80,6 % Ölverbrauch/Jahr 239.200 Liter 193.500 Liter Praxisbeispiel 37Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 38. Co-funded by the Intelligent Energy Europe Programme of the European Union Zusammenfassung. 38Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 39. Co-funded by the Intelligent Energy Europe Programme of the European Union  Es ist wichtig den Erfolg einer Energiesparmaßnahme zu überwachen (ECM)  M&V kann dabei helfen Energieeinsparungen mit dem ECM zu trennen und die Einsparungen zu bewerten.  Vergleichen Sie die Energienutzung vor und nach der Umsetzung eines ECM.  Änderungen in der Anlage oder der Umwelt führen zu Anpassungen in der Kalkulation.  Vier Optionen sind verfügbar, um die Einsparungen zu kalkulieren.  Nach der Durchführung von M & V hilft eine Langzeitüberwachung die Einsparungen zu erhalten. Wiederholung 39Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 40. Co-funded by the Intelligent Energy Europe Programme of the European Union [1] Wikipedia: Measurement and Verification. URL: http://en.wikipedia.org/wiki/Measurement_and_Verification [2] Eskom (2010): The Measurement and Verification Guideline for Energy Efficiency and Demand-Side Management (EEDSM) Projects and Programmes. URL: http://www.eskom.co.za/IDM/MeasurementVerification/Documents/M_and_V_guideline_v10r 5.pdf [3] Efficiency Valuation Organization (2012): International Performance Measurement and Verification Protocol. URL: http://www.evo-world.org/index.php?option=com_rsform&formId=113&lang=en [4] U.S. Department of Energy (2008): M&V Guidelines: Measurement and Verification for Federal Energy Projects, Version 3.0. URL: http://www1.eere.energy.gov/femp/pdfs/mv_guidelines.pdf [5] European Commission (2009): Reference Document on Best Available Techniques for Energy Efficiency. URL: http://eippcb.jrc.ec.europa.eu/reference/BREF/ENE_Adopted_02- 2009.pdf Lektüre 40Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 41. Co-funded by the Intelligent Energy Europe Programme of the European Union  Folie 1 – Tekke: Stromkosten steigen! – URI: http://www.flickr.com/photos/tekkebln/8978451063/sizes/k/in/photostream / License: CC BY-ND 2.0 (http://creativecommons.org/licenses/by-nd/2.0/legalcode)  Folie 3, 22 – Florian Simeth: Arbeiten von zu Hause mit dem Laptop – URI: http://www.flickr.com/photos/hangout-lifestyle/5865980513/sizes/o/in/photostream/ License: CC BY 2.0 (http://creativecommons.org/licenses/by/2.0/legalcode)  Folie 4, 5, 6 – dr. friendly: halogen glühlampe – URI: http://www.flickr.com/photos/57777529@N02/5343580540/sizes/z/in/photostream/ License: CC BY-SA 2.0 (http://creativecommons.org/licenses/by-sa/2.0/legalcode)  Folie 7 – Tai Viinikka: IMG_1956: The Energy Detective – URI: http://www.flickr.com/photos/eastpole/2087714870/sizes/l/in/photostream/ License: CC BY-NC-ND 2.0 (http://creativecommons.org/licenses/by-nc-nd/2.0/legalcode)  Folie 8 – botgirlq: EXTROVERSION CHART – URI: http://www.flickr.com/photos/botgirlq/2541357441/sizes/o/in/photostream/ License: CC BY-NC 2.0 (http://creativecommons.org/licenses/by-nc/2.0/legalcode)  Folie 9 – Dennis Skley: *grübel* – URI: http://www.flickr.com/photos/dskley/8627475625/sizes/z/in/photostream/ License: CC BY-ND 2.0 (http://creativecommons.org/licenses/by-nd/2.0/legalcode)  Folie 10, 23, 27, 29, 31 – Bilal Kamoon: Question Mark Graffiti – URI: http://www.flickr.com/photos/bilal- kamoon/6835060992/sizes/m/in/photostream/ License: CC BY 2.0 (http://creativecommons.org/licenses/by/2.0/legalcode)  Folie 12 – AndYaDontStop: The road of life twists and turns and no two directions are ever the same. Yet our lessons come from the journey, not the destination......365/365 – URI: http://www.flickr.com/photos/thenovys/3833212599/sizes/m/in/photostream/ License: CC BY 2.0 (http://creativecommons.org/licenses/by/2.0/legalcode) Bilder -1 41Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung
  • 42. Co-funded by the Intelligent Energy Europe Programme of the European Union  Folie 24, 28, 30, 32 – Photocapy: ! – URI: http://www.flickr.com/photos/photocapy/3834784192/sizes/m/in/photostream/ License: CC BY-SA 2.0 (http://creativecommons.org/licenses/by-sa/2.0/legalcode)  Folie 33 – Son of Groucho: Not Our Guide – URI: http://www.flickr.com/photos/sonofgroucho/3855487710/sizes/z/in/photostream/ License: CC BY 2.0 (http://creativecommons.org/licenses/by/2.0/legalcode)  Folie 34 – nz_willowherb: Boilers – URI: http://www.flickr.com/photos/willowherb/354986002/sizes/z/in/photostream/ License: CC BY-NC 2.0 (http://creativecommons.org/licenses/by-nc/2.0/legalcode)  Folie 37 – Kutchala Sutchi: Repetition, 23.03.'10, Abidjan-Yopougon (4640) – URI: http://www.flickr.com/photos/kutchala/4469943694/sizes/o/in/photostream/ License: CC BY 2.0 (http://creativecommons.org/licenses/by/2.0/legalcode) Bilder -2 42Einführung - Theorie - Übungen - Geschäftsfall- Zusammenfassung

Notas do Editor

  1. Tip: There are two meanings of „measure“: “measure” as a substantive in the meaning of action/procedure/step/method/task “to measure” as a verb in the meaning of gauge/meter/quantify/detect