1. We measure it.
Multi-function
measuring instrument
testo 435 – The allrounder for
ventilation and indoor air quality
Large selection of probes (optional):
°C
IAQ probe for evaluating Indoor Air Quality
Thermal probes with integrated temperature and air
humidity measurement %RH
Vane and hot wire probes
Integrated differential pressure probe for Pitot tube
m/s
measurement (see versions)
Wireless probe for temperature and humidity (see versions)
hPa
Easy operation with user profiles
PC software for the analysis, archiving and documentation ppm
CO 2
of measurement data (see versions)
Lux
All HVAC measurement parameters determination of volume flow, you can use all possiblities
The multi-function measuring instrument testo 435 is your for the measurement of flow velocity – such as thermal
reliable partner for analyzing Indoor Air Quality. Indoor Air probes, vanes and Pitot tubes.
Quality has a crucial influence on the well-being of humans The right instrument for every application
at their workplaces, and is also a determining and important The new testo 435 is available in four versions. Depending
factor in storage and production processes. on the application, you can choose from versions with built-
In addition to this, the Indoor Air Quality signals whether the in differential pressure measurement as well as versions
HVAC system is working at optimum energy level, or needs with additional instrument functions such as instrument
to be adjusted using the testo 435. The parameters CO2, memory, PC software and an extended range of probes.
relative humidity and room temperature are available for the
evaluation of Indoor Air Quality.
In addition to this, absolute pressure, draught, Lux, U-value
www.testo.co.uk
and surface temperature can be measured. For the
2. testo 435 We measure it.
Technical data
testo 435-1 testo 435-2
testo 435-1 multi-functional measurement testo 435-2 multi-function measuring instrument for air
instrument for A/C, ventilation and Indoor Air conditioning, ventilation and Indoor Air Quality with data
Quality, battery and calibration protocol included memory, PC software and USB data transfer cable,
includes battery and calibration protocol
Part no. 0560 4351 Part no. 0563 4352
testo 435-3 testo 435-4
testo 435-4 multi-function measuring instrument with
testo 435-3 multi-functional measurement built-in differential pressure measurement for air
instrument with built-in differential pressure conditioning, ventilation and Indoor Air Quality, with
measurement for A/C, ventilation and Indoor Air data memory, PC software and USB data transfer
Quality, battery and calibration protocol included cable, includes battery and calibration protocol
Part no. 0560 4353 Part no. 0563 4354
Improved convenience of operation thanks to user profiles
The operation of testo 435 is easy and efficient: User
profiles are stored for the typical applications duct
measurement and IAQ measurement. This makes
complicated programming of the measuring instrument
unnecessary.
Measure temperature and 2 connections for external probes
humidity values wirelessly over a
Secure measurement data monitoring distance of up to 20m without
obstruction
The measurement data reports provide the customer with
the data from the duct, long-term and degree of turbulence
measurement. The company logo can be integrated into the
form. The testo 435-1 and testo 435-3 allow the
measurement values to be printed cyclically on the Testo
fast printer.
Flexibility thanks to wireless probes General technical data
In addition to classical probes on wires, a wireless
Oper. temp. -20 to +50 °C
measurement up to a distance of 20 m (without obstruction)
Storage temp. -30 to +70 °C
is possible. Damage to the wire or hindrances in usage are
Dimensions 220 x 74 x 46 mm
thus eliminated. A maximum of three wireless probes can
Battery type Alkali manganese, mignon, Type AA
be recorded and displayed with testo 435. The wireless
Battery life 200 h (typical vane measurement)
probes are for the measurement parameters temperature
Weight 428 g
and, depending on the instrument type, humidity. The
Material/Housing ABS/TPE/Metal
optional, easily plugged-in radio module can be retrofitted
Protection class IP54
at any time.
Warranty 2 years
3. testo 435 We measure it.
Technical data
Overview of versions testo 435
The table provides a fast overview of the connectable probes and the instrument equipment per version.
Connectable probes (optional) testo 435-1 testo 435-2 testo 435-3 testo 435-4
IAQ probe for the measurement of CO2, air temperature, indoor air humidity X X X X
and absolute pressure
Thermal flow velocity probe with integrated temperature and air humidity X X X X
measurement
Vane and hot wire probes X X X X
Temperature probe for immersion/penetration, air and surface measurements X X X X
Wireless probes for temperature measurements X X X X
Ambient CO probe X X X X
Absolute pressure probe X X X X
Integrated differential pressure measurement for flow velocity measurement X X
with Pitot tube and for monitoring filters (not retro-fittable)
Comfort probe for degree of turbulence measurement for the objective X X
evaluation of the air velocity in a room
Humidity probe for air temperature and air humidity measurements X X
Wireless probe for air temperature and air humidity measurement X X
Lux probe for the measurement of light intensity X X
Temperature probe for determining U-value X X
Instrument equipment
Easy operation with user profiles X X X X
Illuminated display X X X X
Testo fast printer for documenting measurement data (optional) X X X X
Instrument store for 10,000 measurement values (not retro-fittable) X X
PC software for the analysis, archiving and documentation of the readings X X
testo 435-1/-2/-3/-4
Sensor types NTC Type K (NiCr-Ni) Type T (Cu-CuNi) Testo humid. sensor,
cap.
Meas. range -50 to +150 °C -200 to +1370 °C -200 to +400 °C 0 to +100 %RH
Accuracy ±0.2 °C(-25 to +74.9 °C) ±0.3 °C (-60 to +60 °C) ±0.3 °C (-60 to +60 °C) See probe data
±1 digit ±0.4 °C (-50 to -25.1 °C) ±(0.2 °C +0.3% of mv) ±(0.2 °C +0.3% of mv)
±0.4 °C (+75 to +99.9 °C) (remaining range) (remaining range)
±0.5% of mv (remaining
range)
Resolution 0.1 °C 0.1 °C 0.1 °C 0.1 %RH
Vane Hot wire Absolute pressure probe CO2 (IAQ probe)
Meas. range 0 to +60 m/s 0 to +20 m/s 0 to +2000 hPa 0 to +10000 ppm CO2
Accuracy ±1 digit See probe data See probe data See probe data See probe data
Resolution 0.01m/s (60 vane) 0.01 m/s 0.1 hPa 1 ppm CO2
0.1 m/s (16 vane)
testo 435-2/-4 testo 435-3/-4
Sensor types Lux Differential pressure probe, internal
Meas. range 0 to +100000 Lux 0 to +25 hPa
Accuracy See probe data ±0.02 hPa (0 to +2 hPa)
±1 digit 1% of mv (remaining range)
Resolution / Overload 1 Lux; 0.1 Hz 0.01 hPa / 200 hPa
4. testo 435 We measure it.
Accessories
Transport and Protection Part no.
Service case for basic equipment of measuring instrument and probes, dimensions: 400 x 310 x 96 mm 0516 0035
Service case for measuring instrument, probe and accessories, dimensions 520 x 380 x 120 mm 0516 0435
Additional accessories and spare parts
Handle for attachable humidity probe head for connection to testo 635, incl. probe wire, for measurement / calibration 0430 9735
of humidity probe head
testovent 410, volume flow funnel, Ø 340 mm/330x330 mm, incl. case 0554 0410
testovent 415, volume flow funnel, Ø 210 mm/210x210 mm, incl. case 0554 0415
testovent 417 funnel set for disc valve (200x200 mm) and ventilator (330x330 mm) for ingoing and outgoing air 0563 4170
Connection hose; silicone; 5 m long; max. load 700hPa (mbar) 0554 0440
Connection hose silicone-free for differential pressure measurement 0554 0453
Control and adjustment set for Testo humidity probes, salt solution with 11.3% RH and 75.3% RH, incl. adapter for 0554 0660
Testo humidity probes, quick checks or calibration of humidity probe
Sintered PTFE filter, Ø 12 mm, for corrosive media, High humidity range (long-term measurements), high flow velocities. 0554 0756
Stainless steel sintered cap, Ø 12 mm, is screwed onto humidity probe, for measurements at higher flow velocities or in 0554 0647
contaminated air
Plug-in mains adapter, 5 VDC 500 mA with European adapter, 100-250 VAC, 50-60 Hz 0554 0447
Lithium battery button cell, CR2032 AA batteries for radio handle 0515 0028
Adhesive material for fixing and sealing 0554 0761
Printer and Accessories
Testo fast printer IRDA with wireless infrared interface; 1 roll thermal paper; 4 AA batteries; for printing out 0554 0549
measurements on site , for printing out measurements on site
Spare thermal paper for printer (6 rolls), permanent ink 0554 0568
measurement data documentation legible for up to 10 years
Spare thermal paper for printer (6 rolls) 0554 0569
External fast charger for 1-4 AA rech. batteries, incl. 4 Ni-MH rech. batteries with individual cell charging and charge 0554 0610
control display, incl. impulse trickle charging, integrated discharge function, with built-in international mains plug,
100-240 V, 300 mA, 50/60 Hz
Calibration Certificates
ISO calibration certificate/temperature 0520 0071
meas. instr. with surface probe; calibration points +60°C; +120°C; +180°C
ISO calibration certificate humidity 0520 0006
Calibration points 11.3 %RH and 75.3 %RH at +25°C
ISO calibration certificate pressure 0520 0005
differential pressure; 5 points distributed over meas. range
ISO calibration certificate velocity 0520 0024
hot wire, vane anemometer; calibration points 0.5; 0.8; 1; 1.5 m/s
ISO calibration certificate velocity 0520 0004
hot wire, vane anemometer, Pitot tube; calibration points 1; 2; 5; 10 m/s
ISO calibration certificate velocity 0520 0034
hot wire, vane anemometer, Pitot tube; calibration points 5; 10; 15; 20 m/s
ISO calibration certificate/light 0520 0010
Calibration points 0;500;1000;2000;4000 Lux
ISO calibration certificate/CO2 0520 0033
CO2 probes; calibration points 0; 1000; 5000 ppm
5. testo 435 We measure it.
Probes
Probe type Dimensions Measuring Accuracy t99 Part no.
Probe shaft/probe shaft tip range
IAQ probes (testo 435-1/-2/-3/-4)
IAQ probe to assess Indoor Air 0 to +50 °C ±0.3 °C 0632 1535
0 to +100 %RH ±2 %RH (+2 to +98 %RH)
Quality, CO2, humidity, temperature 0 to +10000 ±(50 ppm CO2 ±2% of mv) (0
and absolute pressure ppm CO2 to +5000 ppm CO2)
measurement, with desk-top stand +600 to +1150 ±(100 ppm CO2 ±3% of mv)
hPa (+5001 to +10000 ppm CO2)
±3 hPa
Ambient CO probe, for detecting 0 to +500 ppm ±5% of mv (+100.1 to +500 0632 1235
CO ppm CO)
CO in buildings and rooms ±5 ppm CO (0 to +100 ppm CO)
Flow velocity probes (testo 435-1/-2/-3/-4)
Thermal velocity probe with built-in -20 to +70 °C ±0.3 °C 0635 1535
0 to +100 %RH ±2 %RH (+2 to +98 %RH)
temperature and humidity 0 to +20 m/s ±(0.03 m/s +4% of mv)
measurement, Ø 12 mm, with
telescopic handle (max. 745 mm)
Vane meas. probe, 16 mm diameter, +0.6 to +40 m/s ±(0.2 m/s +1.5% of mv) 0635 9535
with telescopic handle max. 890 Oper. temp.
mm, e.g. for meas. in ducts, can be 0 to +60 °C
used from 0 to +60 °C
Vane meas. probe, 60 mm +0.25 to +20 ±(0.1 m/s +1.5% of mv) 0635 9335
m/s
diameter, with telescopic handle
max. 910 mm, e.g. for meas. at Oper. temp.
duct exit, can be used from 0 to 0 to +60 °C
+60 °C
Hot wire probe for m/s and °C, Ø 0 to +20 m/s ±(0.03 m/s +5% of mv) 0635 1025
-20 to +70 °C ±0.3 °C (-20 to +70 °C)
probe head 7.5 mm, with
telescopic handle (max. 820 mm)
Funnel measurement (testo 435-1/-2/-3/-4)
Vane meas. probe, 100 mm +0.3 to +20 m/s ±(0.1 m/s +1.5% of mv) 0635 9435
0 to +50 °C ±0.5 °C
diameter, for measurements with
funnel set 0563 4170
testovent 417 funnel set for disc 0563 4170
valve (200x200 mm) and ventilator
(330x330 mm) for ingoing and
outgoing air
Absolute pressure probes (testo 435-1/-2/-3/-4)
Absolute pressure probe 2000 hPa 0 to +2000 hPa ±5 hPa 0638 1835
2)
Air probes (testo 435-1/-2/-3/-4)
Efficient, robust NTC air probe, -50 to +125 °C ±0.2 °C (-25 to +80 °C) 60 s 0613 1712
115 mm 50 mm ±0.4 °C (remaining range)
Fixed cable 1.2 m
Ø 5 mm Ø 4 mm
2) More temperature probes on the internet at www.testo.com
6. testo 435 We measure it.
Probes
Probe type Dimensions Measuring Accuracy t99 Part no.
Probe shaft/probe shaft tip range
2)
Surface probes (testo 435-1/-2/-3/-4)
Fast-action surface probe with -60 to +300 °C Class 2 1) 3s 0602 0393
115 mm
sprung thermocouple strip, also for
uneven surfaces, measurement
range short-term to +500°C, TC Ø 5 mm Ø 12 mm
Type K, Fixed cable
Pipe wrap probe for pipe diameter -60 to +130 °C Class 2 1) 5s 0602 4592
5 to 65 mm, with exchangeable
measuring head. Meas. range
short-term to +280°C, TC Type K,
Fixed cable
Clamp probe for measurements on -50 to +100 °C Class 2 1) 5s 0602 4692
pipes, pipe diameter 15 to 25 mm
(max. 1"), meas. range short-term
up to +130°C, TC Type K, Fixed
cable
Fast-reaction paddle surface 0 to +300 °C Class 2 1) 5s 0602 0193
145 mm 40 mm
probe, for measurements in
inaccessible places, e.g. narrow
Ø 7 mm
apertures and slots, TC Type K, Ø 8 mm
Fixed cable
2)
Immers./penetr. probes (testo 435-1/-2/-3/-4)
Waterproof immersion/penetration -60 to +400 °C Class 2 1) 7s 0602 1293
114 mm 50 mm
probe, TC Type K, Fixed cable 1.2 m
Ø 5 mm Ø 3.7 mm
IAQ probes (testo 435-2/-4)
Comfort level probe for degree of 0 to +50 °C ±0.3 °C 0628 0109
max. 820 mm 0 to +5 m/s ±(0.03 m/s +4% of mv)
turbulence measurement with
telescopic handle (max. 820 mm)
and stand, meets EN 13779
requirements
Lux probe, for measuring light 0 to 100.000 Accuracy acc. to DIN 13032-1: 0635 0545
Lux f1 = 6% = V(Lambda)
intensity 0 to 300 Hz adjustment
f2 = 5% = cos-like weighting,
Class C
Humidity probes (testo 435-2/-4)
Humidity/temperature probe -20 to +70 °C ±0.3 °C 0636 9735
0 to +100 %RH ±2 %RH (+2 to +98 %RH)
Ø 12 mm
2)
Surface probes (testo 435-2/-4)
Temperature probe to determine U- -20 to +70 °C Class 11) 0614 1635
U-value: ±0.1 ±2% of fsv*
value, triple sensor system for
measuring wall temperature, Note: An additional probe for measuring outer temperatures is
modelling clay included required when determining the U-value e.g. 0602 1793 or 0613
1001 or 0613 1002.
*when used with an NTC or wireless humidity probe for
measuring outside temperature and 20 K difference between
the air inside and outside
Prandtl's Pitot tubes (testo 435-3/-4)
Pitot tube, 350 mm long, Ø 7 mm, Oper. temp. 0635 2145
350 mm / 500 mm / 1000 mm 0 to +600 °C
stainless steel, measures flow
speed In conjunction with 0638
1347 / 0638 1447 / 0638 1547 0635 2045
pressure probes or testo 521, with Ø 7 mm
internal sensor
Pitot tube, 500 mm long 0635 2345
Pitot tube, 1000 mm long
1) According to standard EN 60584-2, the accuracy of Class 2 refers to -40 to +1200 °C.
2) More temperature probes on the internet at www.testo.com
7. testo 435 We measure it.
Radio probes
Radio probes for immersion/penetration measurements Part no.
Radio immersion/penetration probe, NTC, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, DK, FI, HU, 0613 1001
CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NO; Radio freq. 869.85 MHz FSK
Radio immersion/penetration probe, NTC, approval for USA, CA, CL; Radio freq. 915.00 MHz FSK 0613 1002
Dimensions Measuring Accuracy Resolution t99
Probe shaft/probe shaft tip range
105 mm 30 mm -50 to +275 °C ±0.5 °C (-20 to +80 °C) 0.1 °C t99 (in
±0.8 °C (-50 to -20.1 °C) water)
Ø 5 mm Ø 3.4 mm ±0.8 °C (+80.1 to +200 °C) 12 s
±1.5 °C (remaining range)
Radio handles with probe head for air-/ immersion-penetration-meas. Part no.
Radio handle for plug-in probe heads, incl. T/C adapter, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, 0554 0189
DK, FI, HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NO; Radio freq. 869.85 MHz FSK
T/C probe head for air/immersion/penetration measurement, attachable to radio handle, T/C Type K 0602 0293
Radio handle for plug-in probe heads, incl. T/C adapter, approval for USA, CA, CL; Radio freq. 915.00 MHz FSK 0554 0191
T/C probe head for air/immersion/penetration measurement, attachable to radio handle, T/C Type K 0602 0293
Dimensions Measuring Accuracy Resolution t99
Probe shaft/probe shaft tip range
100 mm 30 mm -50 to +350 °C Radio handle: 0.1 °C (-50 to t99 (in
Short-term to ±(0.5 °C +0.3% of mv) (-40 to +500 °C) +199.9 °C) water)
Ø 5 mm Ø 3,4 mm +500 °C ±(0.7 °C +0.5% of mv) (remaining range) 1.0 °C (remaining 10 s
T/C probe head: Class 2 range)
Radio handles with probe head for surface measurement Part no.
Radio handle for plug-in probe heads, incl. T/C adapter, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, 0554 0189
DK, FI, HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NO; Radio freq. 869.85 MHz FSK
T/C probe head for surface measurement, attachable to radio handle, T/C Type K 0602 0394
Radio handle for plug-in probe heads, incl. T/C adapter, approval for USA, CA, CL; Radio freq. 915.00 MHz FSK 0554 0191
T/C probe head for surface measurement, attachable to radio handle, T/C Type K 0602 0394
Dimensions Measuring Accuracy Resolution t99
Probe shaft/probe shaft tip range
120 mm 40 mm -50 to +350 °C Radio handle: 0.1 °C (-50 to 5s
Short-term to ±(0.5 °C +0.3% of mv) (-40 to +500 °C) +199.9 °C)
Ø 5 mm Ø 12 mm +500 °C ±(0.7 °C +0.5% of mv) (remaining range) 1.0 °C (remaining
T/C probe head: Class 2 range)
Radio probes incl. humidity probe head Part no.
Radio handle for plug-in probe heads, incl. T/C adapter, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, 0554 0189
DK, FI, HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NO; Radio freq. 869.85 MHz FSK
Humidity probe head, attachable to radio handle 0636 9736
Radio handle for plug-in probe heads, incl. T/C adapter, approval for USA, CA, CL; Radio freq. 915.00 MHz FSK 0554 0191
Humidity probe head, attachable to radio handle 0636 9736
Dimensions Measuring Accuracy Resolution
Probe shaft/probe shaft tip range
0 to +100 %RH ±2 %RH (+2 to +98 %RH) 0.1 %RH
-20 to +70 °C ±0.3 °C 0.1 °C
Radio handles for attachable T/C probes Part no.
Radio handle for plug-in probe heads, incl. T/C adapter, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, 0554 0189
DK, FI, HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NO ; Radio freq. 869.85 MHz FSK
Radio handle for plug-in probe heads, incl. T/C adapter, approval for USA, CA, CL; Radio freq. 915.00 MHz FSK 0554 0191
Illustration Measuring Accuracy Resolution
range
-50 to +1000 °C ±(0.7 °C +0.3% of mv) (-40 to +900 °C) 0.1 °C (-50 to +199.9 °C)
±(0.9 °C +0.5% of mv) (remaining range) 1.0 °C (remaining range)
8. testo 435 We measure it.
Radio probes
Radio module for upgrading measuring instrument with radio option Part no.
Radio module for measuring instrument, 869.85 MHz, approval for the countries: DE, FR, UK, BE, NL, ES, IT, SE, AT, 0554 0188
DK, FI, HU, CZ, PL, GR, CH, PT, SI, MT, CY, SK, LU, EE, LT, IE, LV, NO
Radio module for measuring instrument, 915.00 MHz FSK, approval for USA, CA, CL 0554 0190
Technical data Radio probes
Radio immersion/penetration probe, NTC Common Technical Data
Battery type 2 x 3V button cell (CR 2032) Measuring rate 0.5 s or 10 s, adjustable on handle
Battery life 150 h (meas. rate 0.5 s)
2 months (meas. rate 10 s)
Radio coverage Up to 20 m (without obstructions)
Radio handle Radio transmission Unidirectional
Battery type 2 AAA micro batteries Oper. temp. -20 to +50 °C
Battery life 215 h (meas. rate 0.5 s) Storage temp. -40 to +70 °C
6 months (meas. rate 10 s)
Protection class IP54
Subject to change without notice.