Electrical Machines I

7

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Testing of Transformers
The structure of the circuit equivalent of a practical transformer is developed earlier.

The performance parameters of interest can be obtained by solving that circuit for any load
conditions. The equivalent circuit parameters are available to the designer of the transformers
from the various expressions that he uses for designing the transformers. But for a user
these are not available most of the times. Also when a transformer is rewound with diļ¬€erent
primary and secondary windings the equivalent circuit also changes. In order to get the
equivalent circuit parameters test methods are heavily depended upon. From the analysis of
the equivalent circuit one can determine the electrical parameters. But if the temperature
rise of the transformer is required, then test method is the most dependable one. There are
several tests that can be done on the transformer; however a few common ones are discussed
here.

7.1

Winding resistance test
This is nothing but the resistance measurement of the windings by applying a small

d.c voltage to the winding and measuring the current through the same. The ratio gives
the winding resistance, more commonly feasible with high voltage windings. For low voltage
windings a resistance-bridge method can be used. From the d.c resistance one can get the
a.c. resistance by applying skin eļ¬€ect corrections.

44

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

V3
S

A2

Vs

~

a2

a2

V1

+

A2
+

V2

V
-

A1

a1
A1

(a)A.C.test

a1
(b)D.C.test

Figure 18: Polarity Test

7.2

Polarity Test
This is needed for identifying the primary and secondary phasor polarities. It is

a must for poly phase connections. Both a.c. and d.c methods can be used for detecting
the polarities of the induced emfs. The dot method discussed earlier is used to indicate the
polarities. The transformer is connected to a low voltage a.c. source with the connections
made as shown in the ļ¬g. 18(a). A supply voltage Vs is applied to the primary and the
readings of the voltmeters V1 , V2 and V3 are noted. V1 : V2 gives the turns ratio. If V3 reads
V1 āˆ’V2 then assumed dot locations are correct (for the connection shown). The beginning and
end of the primary and secondary may then be marked by A1 āˆ’ A2 and a1 āˆ’ a2 respectively.
If the voltage rises from A1 to A2 in the primary, at any instant it does so from a1 to a2 in
the secondary. If more secondary terminals are present due to taps taken from the windings
they can be labeled as a3 , a4 , a5 , a6 . It is the voltage rising from smaller number towards
larger ones in each winding. The same thing holds good if more secondaries are present.
45

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Fig. 18(b) shows the d.c. method of testing the polarity. When the switch S is closed if the
secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity
is correct. If the meter kicks back the assumed polarity is wrong.

7.3

Open Circuit Test

W
A
V1

Io

V2

V

Im
V1

jXm

Ic
Rc

(a)Physical Arrangement
(b)Equivalent Circuit
Figure 19: No Load Test

As the name suggests, the secondary is kept open circuited and nominal value
of the input voltage is applied to the primary winding and the input current and power are
measured. In Fig. 19(a) V, A, W are the voltmeter, ammeter and wattmeter respectively.
Let these meters read V1 , I0 and W0 respectively.Fig. 19(b) shows the equivalent circuit of
the transformer under this test. The no load current at rated voltage is less than 1 percent of
nominal current and hence the loss and drop that take place in primary impedance r1 + jxl1
due to the no load current I0 is negligible. The active component Ic of the no load current I0
46

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

represents the core losses and reactive current Im is the current needed for the magnetization.
Thus the watt meter reading
W0 = V1 Ic = Pcore

(38)

W0
V1

(39)

āˆ“ Ic =
āˆ“ Im =
Rc =

2
2
I0 āˆ’ Ic

V1
Ic

or

andXm =

(40)
V1
Im

(41)

V1

Io
Figure 20: Open Circuit Characteristics

The parameters measured already are in terms of the primary. Sometimes the primary voltage required may be in kilo-Volts and it may not be feasible to apply nominal
voltage to primary from the point of safety to personnel and equipment. If the secondary
voltage is low, one can perform the test with LV side energized keeping the HV side open
circuited. In this case the parameters that are obtained are in terms of LV . These have to
be referred to HV side if we need the equivalent circuit referred to HV side.

47

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Sometimes the nominal value of high voltage itself may not be known, or in doubt,
especially in a rewound transformer. In such cases an open circuit characteristics is ļ¬rst
obtained, which is a graph showing the applied voltage as a function of the no load current.
This is a non linear curve as shown in Fig. 20. This graph is obtained by noting the current
drawn by transformer at diļ¬€erent applied voltage, keeping the secondary open circuited. The
usual operating point selected for operation lies at some standard voltage around the knee
point of the characteristic. After this value is chosen as the nominal value the parameters
are calculated as mentioned above.

7.4

Short Circuit Test
The purpose of this test is to determine the series branch parameters of the equiv-

alent circuit of Fig. 21(b). As the name suggests, in this test primary applied voltage, the
current and power input are measured keeping the secondary terminals short circuited. Let
these values be Vsc , Isc and Wsc respectively. The supply voltage required to circulate rated
current through the transformer is usually very small and is of the order of a few percent
of the nominal voltage. The excitation current which is only 1 percent or less even at rated
voltage becomes negligibly small during this test and hence is neglected. The shunt branch
ā€²

is thus assumed to be absent. Also I1 = I2 as I0 ā‰ƒ 0. Therefore Wsc is the sum of the
copper losses in primary and secondary put together. The reactive power consumed is that
absorbed by the leakage reactance of the two windings.
ā€²

2
Wsc = Isc (r1 + r2 )

Zsc =

Vsc
Isc

ā€²

(43)
ā€²

(xl1 + xl2 ) =

2
Zsc āˆ’ (r1 + r2 )2

48

Indian Institute of Technology Madras

(42)

(44)
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

W

A
Vsc

V

(a)Physical Arrangement

Isc

r1

jxl1

rā€™2

Vsc

(b)Equivalent Circuit
Figure 21: Short Circuit Test

49

Indian Institute of Technology Madras

jxā€™l2
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

If the approximate equivalent circuit is required then there is no need to separate r1
ā€²

ā€²

and r2 or xl1 and xl2 . However if the exact equivalent circuit is needed then either r1 or
ā€²

r2 is determined from the resistance measurement and the other separated from the total.
ā€²

As for the separation of xl1 and xl2 is concerned, they are assumed to be equal. This is a
fairly valid assumption for many types of transformer windings as the leakage ļ¬‚ux paths are
through air and are similar.

7.5

Load Test
Load Test helps to determine the total loss that takes place, when the transformer

is loaded. Unlike the tests described previously, in the present case nominal voltage is applied
across the primary and rated current is drown from the secondary. Load test is used mainly
1. to determine the rated load of the machine and the temperature rise
2. to determine the voltage regulation and eļ¬ƒciency of the transformer.
Rated load is determined by loading the transformer on a continuous basis and observing the steady state temperature rise. The losses that are generated inside the transformer
on load appear as heat. This heats the transformer and the temperature of the transformer
increases. The insulation of the transformer is the one to get aļ¬€ected by this rise in the
temperature. Both paper and oil which are used for insulation in the transformer start getting degenerated and get decomposed. If the ļ¬‚ash point of the oil is reached the transformer
goes up in ļ¬‚ames. Hence to have a reasonable life expectancy the loading of the transformer
must be limited to that value which gives the maximum temperature rise tolerated by the
insulation. This aspect of temperature rise cannot be guessed from the electrical equivalent
circuit. Further, the losses like dielectric losses and stray load losses are not modeled in the
50

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

equivalent circuit and the actual loss under load condition will be in error to that extent.
Many external means of removal of heat from the transformer in the form of diļ¬€erent cooling
methods give rise to diļ¬€erent values for temperature rise of insulation. Hence these permit
diļ¬€erent levels of loading for the same transformer. Hence the only sure way of ascertaining
the rating is by conducting a load test.

It is rather easy to load a transformer of small ratings. As the rating increases it
becomes diļ¬ƒcult to ļ¬nd a load that can absorb the requisite power and a source to feed the
necessary current. As the transformers come in varied transformation ratios, in many cases
it becomes extremely diļ¬ƒcult to get suitable load impedance.

Further, the temperature rise of the transformer is due to the losses that take place
ā€˜insideā€™ the transformer. The eļ¬ƒciency of the transformer is above 99% even in modest sizes
which means 1 percent of power handled by the transformer actually goes to heat up the
machine. The remaining 99% of the power has to be dissipated in a load impedance external
to the machine. This is very wasteful in terms of energy also. ( If the load is of unity power
factor) Thus the actual loading of the transformer is seldom resorted to. Equivalent loss
methods of loading and ā€˜Phantomā€™ loading are commonly used in the case of transformers.
The load is applied and held constant till the temperature rise of transformer reaches a
steady value. If the ļ¬nal steady temperature rise is lower than the maximum permissible
value, then load can be increased else it is decreased. That load current which gives the
maximum permissible temperature rise is declared as the nominal or rated load current and
the volt amperes are computed using the same.

51

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

In the equivalent loss method a short circuit test is done on the transformer. The
short circuit current is so chosen that the resulting loss taking place inside the transformer
is equivalent to the sum of the iron losses, full load copper losses and assumed stray load
losses. By this method even though one can pump in equivalent loss inside the transformer,
the actual distribution of this loss vastly diļ¬€ers from that taking place in reality. Therefore
this test comes close to a load test but does not replace one.

W

1

A
Io

Io

2Io
V1
V
Iā€™
2

I2

W
A
Vs

I2

Iā€™
2

2

V

Figure 22: Back to Back Test - Phantom Loading

In Phantom loading method two identical transformers are needed. The windings
are connected back to back as shown in Fig. 22. Suitable voltage is injected into the loop
formed by the two secondaries such that full load current passes through them. An equiv52

Indian Institute of Technology Madras
Electrical Machines I

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

alent current then passes through the primary also. The voltage source V1 supplies the
magnetizing current and core losses for the two transformers. The second source supplies
the load component of the current and losses due to the same. There is no power wasted
in a load ( as a matter of fact there is no real load at all) and hence the name Phantom
or virtual loading. The power absorbed by the second transformer which acts as a load is
pushed back in to the mains. The two sources put together meet the core and copper losses
of the two transformers. The transformers work with full ļ¬‚ux drawing full load currents and
hence are closest to the actual loading condition with a physical load.

53

Indian Institute of Technology Madras

More Related Content

What's hot

269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaical269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaicalsampathkumar Mtech Chemical Engg
Ā 
EMI Unit 5 Bridges and Measurement of Physical Parameters
EMI Unit 5 Bridges and  Measurement of Physical ParametersEMI Unit 5 Bridges and  Measurement of Physical Parameters
EMI Unit 5 Bridges and Measurement of Physical ParametersGVNSK Sravya
Ā 
Current Transformer Concepts
Current Transformer ConceptsCurrent Transformer Concepts
Current Transformer ConceptsVijay Badireddi
Ā 
Sharing of the Output Current of A Voltage Source Inverter between Controlled...
Sharing of the Output Current of A Voltage Source Inverter between Controlled...Sharing of the Output Current of A Voltage Source Inverter between Controlled...
Sharing of the Output Current of A Voltage Source Inverter between Controlled...IDES Editor
Ā 
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...IDES Editor
Ā 
Av335 instrumentation lab report
Av335 instrumentation lab reportAv335 instrumentation lab report
Av335 instrumentation lab reportGaurav Vaibhav
Ā 
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...Jobin Abraham
Ā 
AST 406 Ammeter and Voltmeter
AST 406 Ammeter and VoltmeterAST 406 Ammeter and Voltmeter
AST 406 Ammeter and VoltmeterNeil MacIntosh
Ā 
Sinusoidal Response of RC & RL Circuits
Sinusoidal Response of RC & RL CircuitsSinusoidal Response of RC & RL Circuits
Sinusoidal Response of RC & RL CircuitsSachin Mehta
Ā 
Electrical power ecx3232 lab report
Electrical power ecx3232 lab reportElectrical power ecx3232 lab report
Electrical power ecx3232 lab reportSandun Perera
Ā 
Testing of Transformer (AREVA)
Testing of Transformer (AREVA)Testing of Transformer (AREVA)
Testing of Transformer (AREVA)AHMED MOHAMED HEGAB
Ā 
Electrical machines 2 lab manual
Electrical machines 2 lab manualElectrical machines 2 lab manual
Electrical machines 2 lab manualNaga Sai Chaitanya
Ā 
RGPV BE 104 Unit II
RGPV BE 104 Unit IIRGPV BE 104 Unit II
RGPV BE 104 Unit IIMani Deep Dutt
Ā 
Electronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q MeterElectronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q MeterBurdwan University
Ā 
1st year basic electronics
1st year basic electronics1st year basic electronics
1st year basic electronicssaifam
Ā 
Ee 791 drives lab maual
Ee 791 drives lab maualEe 791 drives lab maual
Ee 791 drives lab maualDivya15121983
Ā 
Electrical engg material
Electrical engg material Electrical engg material
Electrical engg material Ramesh Meti
Ā 

What's hot (17)

269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaical269010454 electrical-machines-lab-manual-for-petrochemaical
269010454 electrical-machines-lab-manual-for-petrochemaical
Ā 
EMI Unit 5 Bridges and Measurement of Physical Parameters
EMI Unit 5 Bridges and  Measurement of Physical ParametersEMI Unit 5 Bridges and  Measurement of Physical Parameters
EMI Unit 5 Bridges and Measurement of Physical Parameters
Ā 
Current Transformer Concepts
Current Transformer ConceptsCurrent Transformer Concepts
Current Transformer Concepts
Ā 
Sharing of the Output Current of A Voltage Source Inverter between Controlled...
Sharing of the Output Current of A Voltage Source Inverter between Controlled...Sharing of the Output Current of A Voltage Source Inverter between Controlled...
Sharing of the Output Current of A Voltage Source Inverter between Controlled...
Ā 
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
An Algorithm to Detect Point on Wave Initiation of Voltage Sag by Fundamental...
Ā 
Av335 instrumentation lab report
Av335 instrumentation lab reportAv335 instrumentation lab report
Av335 instrumentation lab report
Ā 
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
Ā 
AST 406 Ammeter and Voltmeter
AST 406 Ammeter and VoltmeterAST 406 Ammeter and Voltmeter
AST 406 Ammeter and Voltmeter
Ā 
Sinusoidal Response of RC & RL Circuits
Sinusoidal Response of RC & RL CircuitsSinusoidal Response of RC & RL Circuits
Sinusoidal Response of RC & RL Circuits
Ā 
Electrical power ecx3232 lab report
Electrical power ecx3232 lab reportElectrical power ecx3232 lab report
Electrical power ecx3232 lab report
Ā 
Testing of Transformer (AREVA)
Testing of Transformer (AREVA)Testing of Transformer (AREVA)
Testing of Transformer (AREVA)
Ā 
Electrical machines 2 lab manual
Electrical machines 2 lab manualElectrical machines 2 lab manual
Electrical machines 2 lab manual
Ā 
RGPV BE 104 Unit II
RGPV BE 104 Unit IIRGPV BE 104 Unit II
RGPV BE 104 Unit II
Ā 
Electronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q MeterElectronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q Meter
Ā 
1st year basic electronics
1st year basic electronics1st year basic electronics
1st year basic electronics
Ā 
Ee 791 drives lab maual
Ee 791 drives lab maualEe 791 drives lab maual
Ee 791 drives lab maual
Ā 
Electrical engg material
Electrical engg material Electrical engg material
Electrical engg material
Ā 

Similar to 1 7

Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Milton Sarker
Ā 
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...IRJET Journal
Ā 
Ac machines-lab-manual
Ac machines-lab-manualAc machines-lab-manual
Ac machines-lab-manualRao Umar
Ā 
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...IRJET Journal
Ā 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-enSuresh Patil
Ā 
Measurement of resistance
Measurement of resistanceMeasurement of resistance
Measurement of resistanceANKUR GHEEWALA
Ā 
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET Journal
Ā 
Vinay report
Vinay reportVinay report
Vinay reportVinay Singh
Ā 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)irjes
Ā 
L-25(TB)(ET) ((EE)NPTEL).pdf
L-25(TB)(ET) ((EE)NPTEL).pdfL-25(TB)(ET) ((EE)NPTEL).pdf
L-25(TB)(ET) ((EE)NPTEL).pdfasprilla mangombe
Ā 
Best-transformer-test-procedures-en
  Best-transformer-test-procedures-en  Best-transformer-test-procedures-en
Best-transformer-test-procedures-enbala12984
Ā 
Eet3082 binod kumar sahu lecturer_10
Eet3082 binod kumar sahu lecturer_10Eet3082 binod kumar sahu lecturer_10
Eet3082 binod kumar sahu lecturer_10BinodKumarSahu5
Ā 
A study of 220V AC-5V DC Converter
A study of 220V AC-5V DC ConverterA study of 220V AC-5V DC Converter
A study of 220V AC-5V DC ConverterSabrina Chowdhury
Ā 
Electronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. KawareElectronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. KawareProf. Swapnil V. Kaware
Ā 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2koperundeviG
Ā 
Superposition and norton Theorem
Superposition and norton TheoremSuperposition and norton Theorem
Superposition and norton TheoremMahmudul Alam
Ā 

Similar to 1 7 (20)

1 7
1 71 7
1 7
Ā 
Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.Lightning Characteristics and Impulse Voltage.
Lightning Characteristics and Impulse Voltage.
Ā 
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Design and Simulation of Generation of High DC Voltage using Cockcroft Walton...
Ā 
Ac machines-lab-manual
Ac machines-lab-manualAc machines-lab-manual
Ac machines-lab-manual
Ā 
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
IRJET-Comparative Analysis of Rectangular and Square Column for Axial loading...
Ā 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
Ā 
Measurement of resistance
Measurement of resistanceMeasurement of resistance
Measurement of resistance
Ā 
1 6
1 61 6
1 6
Ā 
1 6
1 61 6
1 6
Ā 
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
IRJET- Integrated Variable Resistor using Switched Capacitor Circuit and Volt...
Ā 
Vinay report
Vinay reportVinay report
Vinay report
Ā 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)
Ā 
L-25(TB)(ET) ((EE)NPTEL).pdf
L-25(TB)(ET) ((EE)NPTEL).pdfL-25(TB)(ET) ((EE)NPTEL).pdf
L-25(TB)(ET) ((EE)NPTEL).pdf
Ā 
Best-transformer-test-procedures-en
  Best-transformer-test-procedures-en  Best-transformer-test-procedures-en
Best-transformer-test-procedures-en
Ā 
Eet3082 binod kumar sahu lecturer_10
Eet3082 binod kumar sahu lecturer_10Eet3082 binod kumar sahu lecturer_10
Eet3082 binod kumar sahu lecturer_10
Ā 
report of power electronics
report of power electronicsreport of power electronics
report of power electronics
Ā 
A study of 220V AC-5V DC Converter
A study of 220V AC-5V DC ConverterA study of 220V AC-5V DC Converter
A study of 220V AC-5V DC Converter
Ā 
Electronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. KawareElectronics Lab Manual by Er. Swapnil V. Kaware
Electronics Lab Manual by Er. Swapnil V. Kaware
Ā 
Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2Testing of power_transformers_kt_80_gb_2
Testing of power_transformers_kt_80_gb_2
Ā 
Superposition and norton Theorem
Superposition and norton TheoremSuperposition and norton Theorem
Superposition and norton Theorem
Ā 

Recently uploaded

Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
Ā 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyEthan lee
Ā 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
Ā 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
Ā 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
Ā 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsMichael W. Hawkins
Ā 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 DelhiCall Girls in Delhi
Ā 
Event mailer assignment progress report .pdf
Event mailer assignment progress report .pdfEvent mailer assignment progress report .pdf
Event mailer assignment progress report .pdftbatkhuu1
Ā 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
Ā 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
Ā 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsApsara Of India
Ā 
VIP Call Girls In Saharaganj ( Lucknow ) šŸ” 8923113531 šŸ” Cash Payment (COD) šŸ‘’
VIP Call Girls In Saharaganj ( Lucknow  ) šŸ” 8923113531 šŸ”  Cash Payment (COD) šŸ‘’VIP Call Girls In Saharaganj ( Lucknow  ) šŸ” 8923113531 šŸ”  Cash Payment (COD) šŸ‘’
VIP Call Girls In Saharaganj ( Lucknow ) šŸ” 8923113531 šŸ” Cash Payment (COD) šŸ‘’anilsa9823
Ā 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurSuhani Kapoor
Ā 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in managementchhavia330
Ā 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
Ā 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
Ā 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageMatteo Carbone
Ā 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insightsseribangash
Ā 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...Any kyc Account
Ā 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth MarketingShawn Pang
Ā 

Recently uploaded (20)

Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
Ā 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
Ā 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Ā 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
Ā 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Ā 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael Hawkins
Ā 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
Ā 
Event mailer assignment progress report .pdf
Event mailer assignment progress report .pdfEvent mailer assignment progress report .pdf
Event mailer assignment progress report .pdf
Ā 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Ā 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Ā 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Ā 
VIP Call Girls In Saharaganj ( Lucknow ) šŸ” 8923113531 šŸ” Cash Payment (COD) šŸ‘’
VIP Call Girls In Saharaganj ( Lucknow  ) šŸ” 8923113531 šŸ”  Cash Payment (COD) šŸ‘’VIP Call Girls In Saharaganj ( Lucknow  ) šŸ” 8923113531 šŸ”  Cash Payment (COD) šŸ‘’
VIP Call Girls In Saharaganj ( Lucknow ) šŸ” 8923113531 šŸ” Cash Payment (COD) šŸ‘’
Ā 
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service JamshedpurVIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
VIP Call Girl Jamshedpur Aashi 8250192130 Independent Escort Service Jamshedpur
Ā 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in management
Ā 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
Ā 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
Ā 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
Ā 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Ā 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
Ā 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Ā 

1 7

  • 1. Electrical Machines I 7 Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao Testing of Transformers The structure of the circuit equivalent of a practical transformer is developed earlier. The performance parameters of interest can be obtained by solving that circuit for any load conditions. The equivalent circuit parameters are available to the designer of the transformers from the various expressions that he uses for designing the transformers. But for a user these are not available most of the times. Also when a transformer is rewound with diļ¬€erent primary and secondary windings the equivalent circuit also changes. In order to get the equivalent circuit parameters test methods are heavily depended upon. From the analysis of the equivalent circuit one can determine the electrical parameters. But if the temperature rise of the transformer is required, then test method is the most dependable one. There are several tests that can be done on the transformer; however a few common ones are discussed here. 7.1 Winding resistance test This is nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the winding resistance, more commonly feasible with high voltage windings. For low voltage windings a resistance-bridge method can be used. From the d.c resistance one can get the a.c. resistance by applying skin eļ¬€ect corrections. 44 Indian Institute of Technology Madras
  • 2. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao V3 S A2 Vs ~ a2 a2 V1 + A2 + V2 V - A1 a1 A1 (a)A.C.test a1 (b)D.C.test Figure 18: Polarity Test 7.2 Polarity Test This is needed for identifying the primary and secondary phasor polarities. It is a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer is connected to a low voltage a.c. source with the connections made as shown in the ļ¬g. 18(a). A supply voltage Vs is applied to the primary and the readings of the voltmeters V1 , V2 and V3 are noted. V1 : V2 gives the turns ratio. If V3 reads V1 āˆ’V2 then assumed dot locations are correct (for the connection shown). The beginning and end of the primary and secondary may then be marked by A1 āˆ’ A2 and a1 āˆ’ a2 respectively. If the voltage rises from A1 to A2 in the primary, at any instant it does so from a1 to a2 in the secondary. If more secondary terminals are present due to taps taken from the windings they can be labeled as a3 , a4 , a5 , a6 . It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. 45 Indian Institute of Technology Madras
  • 3. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao Fig. 18(b) shows the d.c. method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong. 7.3 Open Circuit Test W A V1 Io V2 V Im V1 jXm Ic Rc (a)Physical Arrangement (b)Equivalent Circuit Figure 19: No Load Test As the name suggests, the secondary is kept open circuited and nominal value of the input voltage is applied to the primary winding and the input current and power are measured. In Fig. 19(a) V, A, W are the voltmeter, ammeter and wattmeter respectively. Let these meters read V1 , I0 and W0 respectively.Fig. 19(b) shows the equivalent circuit of the transformer under this test. The no load current at rated voltage is less than 1 percent of nominal current and hence the loss and drop that take place in primary impedance r1 + jxl1 due to the no load current I0 is negligible. The active component Ic of the no load current I0 46 Indian Institute of Technology Madras
  • 4. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao represents the core losses and reactive current Im is the current needed for the magnetization. Thus the watt meter reading W0 = V1 Ic = Pcore (38) W0 V1 (39) āˆ“ Ic = āˆ“ Im = Rc = 2 2 I0 āˆ’ Ic V1 Ic or andXm = (40) V1 Im (41) V1 Io Figure 20: Open Circuit Characteristics The parameters measured already are in terms of the primary. Sometimes the primary voltage required may be in kilo-Volts and it may not be feasible to apply nominal voltage to primary from the point of safety to personnel and equipment. If the secondary voltage is low, one can perform the test with LV side energized keeping the HV side open circuited. In this case the parameters that are obtained are in terms of LV . These have to be referred to HV side if we need the equivalent circuit referred to HV side. 47 Indian Institute of Technology Madras
  • 5. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao Sometimes the nominal value of high voltage itself may not be known, or in doubt, especially in a rewound transformer. In such cases an open circuit characteristics is ļ¬rst obtained, which is a graph showing the applied voltage as a function of the no load current. This is a non linear curve as shown in Fig. 20. This graph is obtained by noting the current drawn by transformer at diļ¬€erent applied voltage, keeping the secondary open circuited. The usual operating point selected for operation lies at some standard voltage around the knee point of the characteristic. After this value is chosen as the nominal value the parameters are calculated as mentioned above. 7.4 Short Circuit Test The purpose of this test is to determine the series branch parameters of the equiv- alent circuit of Fig. 21(b). As the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. Let these values be Vsc , Isc and Wsc respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation current which is only 1 percent or less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch ā€² is thus assumed to be absent. Also I1 = I2 as I0 ā‰ƒ 0. Therefore Wsc is the sum of the copper losses in primary and secondary put together. The reactive power consumed is that absorbed by the leakage reactance of the two windings. ā€² 2 Wsc = Isc (r1 + r2 ) Zsc = Vsc Isc ā€² (43) ā€² (xl1 + xl2 ) = 2 Zsc āˆ’ (r1 + r2 )2 48 Indian Institute of Technology Madras (42) (44)
  • 6. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao W A Vsc V (a)Physical Arrangement Isc r1 jxl1 rā€™2 Vsc (b)Equivalent Circuit Figure 21: Short Circuit Test 49 Indian Institute of Technology Madras jxā€™l2
  • 7. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao If the approximate equivalent circuit is required then there is no need to separate r1 ā€² ā€² and r2 or xl1 and xl2 . However if the exact equivalent circuit is needed then either r1 or ā€² r2 is determined from the resistance measurement and the other separated from the total. ā€² As for the separation of xl1 and xl2 is concerned, they are assumed to be equal. This is a fairly valid assumption for many types of transformer windings as the leakage ļ¬‚ux paths are through air and are similar. 7.5 Load Test Load Test helps to determine the total loss that takes place, when the transformer is loaded. Unlike the tests described previously, in the present case nominal voltage is applied across the primary and rated current is drown from the secondary. Load test is used mainly 1. to determine the rated load of the machine and the temperature rise 2. to determine the voltage regulation and eļ¬ƒciency of the transformer. Rated load is determined by loading the transformer on a continuous basis and observing the steady state temperature rise. The losses that are generated inside the transformer on load appear as heat. This heats the transformer and the temperature of the transformer increases. The insulation of the transformer is the one to get aļ¬€ected by this rise in the temperature. Both paper and oil which are used for insulation in the transformer start getting degenerated and get decomposed. If the ļ¬‚ash point of the oil is reached the transformer goes up in ļ¬‚ames. Hence to have a reasonable life expectancy the loading of the transformer must be limited to that value which gives the maximum temperature rise tolerated by the insulation. This aspect of temperature rise cannot be guessed from the electrical equivalent circuit. Further, the losses like dielectric losses and stray load losses are not modeled in the 50 Indian Institute of Technology Madras
  • 8. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao equivalent circuit and the actual loss under load condition will be in error to that extent. Many external means of removal of heat from the transformer in the form of diļ¬€erent cooling methods give rise to diļ¬€erent values for temperature rise of insulation. Hence these permit diļ¬€erent levels of loading for the same transformer. Hence the only sure way of ascertaining the rating is by conducting a load test. It is rather easy to load a transformer of small ratings. As the rating increases it becomes diļ¬ƒcult to ļ¬nd a load that can absorb the requisite power and a source to feed the necessary current. As the transformers come in varied transformation ratios, in many cases it becomes extremely diļ¬ƒcult to get suitable load impedance. Further, the temperature rise of the transformer is due to the losses that take place ā€˜insideā€™ the transformer. The eļ¬ƒciency of the transformer is above 99% even in modest sizes which means 1 percent of power handled by the transformer actually goes to heat up the machine. The remaining 99% of the power has to be dissipated in a load impedance external to the machine. This is very wasteful in terms of energy also. ( If the load is of unity power factor) Thus the actual loading of the transformer is seldom resorted to. Equivalent loss methods of loading and ā€˜Phantomā€™ loading are commonly used in the case of transformers. The load is applied and held constant till the temperature rise of transformer reaches a steady value. If the ļ¬nal steady temperature rise is lower than the maximum permissible value, then load can be increased else it is decreased. That load current which gives the maximum permissible temperature rise is declared as the nominal or rated load current and the volt amperes are computed using the same. 51 Indian Institute of Technology Madras
  • 9. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao In the equivalent loss method a short circuit test is done on the transformer. The short circuit current is so chosen that the resulting loss taking place inside the transformer is equivalent to the sum of the iron losses, full load copper losses and assumed stray load losses. By this method even though one can pump in equivalent loss inside the transformer, the actual distribution of this loss vastly diļ¬€ers from that taking place in reality. Therefore this test comes close to a load test but does not replace one. W 1 A Io Io 2Io V1 V Iā€™ 2 I2 W A Vs I2 Iā€™ 2 2 V Figure 22: Back to Back Test - Phantom Loading In Phantom loading method two identical transformers are needed. The windings are connected back to back as shown in Fig. 22. Suitable voltage is injected into the loop formed by the two secondaries such that full load current passes through them. An equiv52 Indian Institute of Technology Madras
  • 10. Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao alent current then passes through the primary also. The voltage source V1 supplies the magnetizing current and core losses for the two transformers. The second source supplies the load component of the current and losses due to the same. There is no power wasted in a load ( as a matter of fact there is no real load at all) and hence the name Phantom or virtual loading. The power absorbed by the second transformer which acts as a load is pushed back in to the mains. The two sources put together meet the core and copper losses of the two transformers. The transformers work with full ļ¬‚ux drawing full load currents and hence are closest to the actual loading condition with a physical load. 53 Indian Institute of Technology Madras