© 2013 ALLIED RELIABILITY, INC. 1 A DIVISION OF ALLIED RELIABILITY GROUP
Multi-Technology Fault Identification
Industry: Food and Beverage Technology: On-line MCA (Initially)
Component: Motor Part: Electrical Connections
Time Context
Tuesday, April 16, 2013
Process Information
This asset is a pump used to pump water for the milling process and cannot be shut down for more than 3
hours during the milling process. Shutting down the pump causes operations to have to switch tanks for
that period of time and requires constant monitoring to prevent product overflows.
Summary of Action
During routine on-line (energized) motor circuit data collection, test results indicated a 26.5% current
imbalance, along with a 35.36% impedance imbalance. Looking at Figure 1, the Power Phase shows the
current imbalance indicated by the shorter current 1 and current 3 lines. Figure 2 shows the imbalance in
the current section of the power test results page. Figure 3 is the Current Time Domain showing current 2
higher than currents 1 and 3. Voltage was checked and found to be balanced across the motor starter at
283 VAC phase-to-neutral and 490 VAC phase-to-phase.
Vibration data was collected and found the motor was in alarm for a 2x line electrical frequency,
indicating there was a possible electrical issue (Figure 4). An infrared scan was conducted on the
electrical enclosures containing the fuses and motor starter. The B phase fuse and connections on the
motor starter were operating with an above alarm level temperature differential. A thermographic scan of
the motor revealed that the housing was operating hotter than normal, indicating a possible issue within
the circuit. Figure 5 is an infrared image taken of the motor soon after the current imbalance was
discovered by the on-line test. It shows the motor temperature was running above normal at 215°F,
caused by the current imbalance. Figures 6 & 7 are infrared images taken of the motor starter and fuses.
The temperature differential of the B phase circuit is caused by the imbalance in the circuit due to the
high resistance connection. A work order was written to perform an off-line (de-energized) motor test to
isolate the cause of the imbalances.
An off-line test was conducted from the Motor Control Center (MCC) and found a 44.65% phase-to-
phase resistive imbalance, along with an 11.65% inductive imbalance. Figure 8 shows the phase-to-phase
resistive imbalance and inductive imbalance from the off-line test conducted from the MCC indicating a
high resistive connection in the circuit. It was decided that further testing should be done by going to the
motor and disconnecting the motor from the circuit to further isolate the cause of the imbalances. Upon
opening the motor junction box, a bad connection was discovered (Figure 9). All connections were
repaired and another off-line test was conducted from the MCC, which indicated that the repairs had
corrected the issue.
© 2013 ALLIED RELIABILITY, INC. 2 A DIVISION OF ALLIED RELIABILITY GROUP
Post Notification
Department reliability coordinators and maintenance supervision were notified as soon as it was
confirmed that there was an issue and made aware of the motor running hot, creating a potential burn
hazard for employees.
Supporting Data
Figure 1: Power Phasor Shows Both Current 1 and Current 3 Lower Than Current 2
© 2013 ALLIED RELIABILITY, INC. 3 A DIVISION OF ALLIED RELIABILITY GROUP
Figure 2: Power Test Results Showing the Current and Impedance Imbalances
Figure 3: Current Time Domain Showing Current Imbalance
© 2013 ALLIED RELIABILITY, INC. 4 A DIVISION OF ALLIED RELIABILITY GROUP
Figure 4: Vibration Spectrum Showing 2x Line Electrical Frequency
Figure 5: Infrared Image of Motor Indicating a Maximum Temperature of 215°F
© 2013 ALLIED RELIABILITY, INC. 5 A DIVISION OF ALLIED RELIABILITY GROUP
Figure 6: Infrared Image of Motor Starter Showing B Phase Connection at 147°F
Figure 7: Infrared Image of Fuses Showing the B Phase Fuse at 127°F
© 2013 ALLIED RELIABILITY, INC. 6 A DIVISION OF ALLIED RELIABILITY GROUP
Figure 8: MCA AC Standard Test Showing the Phase-to-Phase Resistive and Inductive Imbalances
Figure 9: Image of Bad Connections Found After Opening the Motor Junction Box Cover
© 2013 ALLIED RELIABILITY, INC. 7 A DIVISION OF ALLIED RELIABILITY GROUP
Plan of Action
Monitoring with MCA both on-line and off-line will help to identify this type of issue before it can
damage equipment or injure personnel.
Conclusion
Not only is this type of condition shortening the life of the motor, but is also a potential hazard to
personnel in the form of a shock hazard or burn hazard. If the connections were touching any part of the
motor frame and the motor was not properly grounded, an individual who happened to touch the motor
would become the least path of resistance to ground and could be seriously injured, suffering burns from
the motor running hot, or worse, loss of life.
By using the multi-technology approach to reliability – on-line/off-line motor circuit analysis, vibration
analysis, infrared analysis, and other reliability technologies including oil analysis and ultrasonic analysis
– this type of anomaly, as well as others, can be detected early and help reduce unexpected downtimes,
production losses, and most importantly, safety concerns for a facility’s personnel.

Mais conteúdo relacionado

Destaque (9)

Fault Tree Analysis
 Fault Tree Analysis Fault Tree Analysis
Fault Tree Analysis
 
Fault Tree Analysis
Fault Tree AnalysisFault Tree Analysis
Fault Tree Analysis
 
Fault tree analysis
Fault tree analysisFault tree analysis
Fault tree analysis
 
fault tree analysis
fault tree analysisfault tree analysis
fault tree analysis
 
Pengenalan kepada latihan pemanduan modul perubatan & etika dan profesionalisma
Pengenalan kepada  latihan pemanduan modul perubatan & etika dan profesionalismaPengenalan kepada  latihan pemanduan modul perubatan & etika dan profesionalisma
Pengenalan kepada latihan pemanduan modul perubatan & etika dan profesionalisma
 
Fault tree and event tree in risk analysis
Fault tree and event tree in risk analysisFault tree and event tree in risk analysis
Fault tree and event tree in risk analysis
 
Fault tree analysis
Fault tree analysisFault tree analysis
Fault tree analysis
 
Manper06 fta
Manper06 ftaManper06 fta
Manper06 fta
 
FAULT & EVENT TREE ANALYSIS
FAULT & EVENT TREE ANALYSISFAULT & EVENT TREE ANALYSIS
FAULT & EVENT TREE ANALYSIS
 

Mais de Ricky Smith CMRP, CMRT

Mais de Ricky Smith CMRP, CMRT (20)

Skills of a Proactive Maintenance Technician
Skills of a Proactive Maintenance TechnicianSkills of a Proactive Maintenance Technician
Skills of a Proactive Maintenance Technician
 
Day in the Life (DILO) of a Proactive Maintenance Manager
Day in the Life (DILO) of a Proactive Maintenance ManagerDay in the Life (DILO) of a Proactive Maintenance Manager
Day in the Life (DILO) of a Proactive Maintenance Manager
 
Day in the Life of a Proactive Maintenance Planner
Day in the Life of a Proactive Maintenance PlannerDay in the Life of a Proactive Maintenance Planner
Day in the Life of a Proactive Maintenance Planner
 
Day in the life of a Proactive Maintenance Supervisor
Day in the life of a Proactive Maintenance SupervisorDay in the life of a Proactive Maintenance Supervisor
Day in the life of a Proactive Maintenance Supervisor
 
How to know if your maintenance planning and scheduling is not effective
How to know if your maintenance planning and scheduling is not effectiveHow to know if your maintenance planning and scheduling is not effective
How to know if your maintenance planning and scheduling is not effective
 
Day in the life of a Proactive Maintenance Supervisor
Day in the life of a Proactive Maintenance SupervisorDay in the life of a Proactive Maintenance Supervisor
Day in the life of a Proactive Maintenance Supervisor
 
Day in the Life of a Proactive Maintenance Technician Article
Day in the Life of a Proactive Maintenance Technician  ArticleDay in the Life of a Proactive Maintenance Technician  Article
Day in the Life of a Proactive Maintenance Technician Article
 
Best Maintenance Repair Practices Article
Best Maintenance Repair Practices ArticleBest Maintenance Repair Practices Article
Best Maintenance Repair Practices Article
 
Tool Box Talk - Maintenance Parts Checkout
Tool Box Talk - Maintenance Parts CheckoutTool Box Talk - Maintenance Parts Checkout
Tool Box Talk - Maintenance Parts Checkout
 
Tool Box Talk - Lubrication of Bearings
Tool Box Talk - Lubrication of BearingsTool Box Talk - Lubrication of Bearings
Tool Box Talk - Lubrication of Bearings
 
Tool Box Talk - Maintenance Planning and Scheduling
Tool Box Talk - Maintenance Planning and SchedulingTool Box Talk - Maintenance Planning and Scheduling
Tool Box Talk - Maintenance Planning and Scheduling
 
Top 7 Reasons why Maintenance Work Orders are Closed Out Accurately
Top 7 Reasons why Maintenance Work Orders are Closed Out AccuratelyTop 7 Reasons why Maintenance Work Orders are Closed Out Accurately
Top 7 Reasons why Maintenance Work Orders are Closed Out Accurately
 
Tool Box Talk - How to Stop Hydraulic Leaks and Why
Tool Box Talk - How to Stop Hydraulic Leaks and WhyTool Box Talk - How to Stop Hydraulic Leaks and Why
Tool Box Talk - How to Stop Hydraulic Leaks and Why
 
Maintenance of Hydraulic Systems
Maintenance of Hydraulic SystemsMaintenance of Hydraulic Systems
Maintenance of Hydraulic Systems
 
PM Tool Box Talk 101 - Fundamentals of Preventive Maintenance
PM Tool Box Talk 101 - Fundamentals of Preventive MaintenancePM Tool Box Talk 101 - Fundamentals of Preventive Maintenance
PM Tool Box Talk 101 - Fundamentals of Preventive Maintenance
 
How to Develop an Effective Maintenance Skills Training Program
How to Develop an Effective Maintenance Skills Training ProgramHow to Develop an Effective Maintenance Skills Training Program
How to Develop an Effective Maintenance Skills Training Program
 
What is Lean Maintenance
What is Lean MaintenanceWhat is Lean Maintenance
What is Lean Maintenance
 
Best Maintenance Repair Practices
Best Maintenance Repair PracticesBest Maintenance Repair Practices
Best Maintenance Repair Practices
 
PM Tool Box Talk 101 - Fundamentals of Preventive Maintenance
PM Tool Box Talk 101 -  Fundamentals of Preventive MaintenancePM Tool Box Talk 101 -  Fundamentals of Preventive Maintenance
PM Tool Box Talk 101 - Fundamentals of Preventive Maintenance
 
Day in the Life of (DILO) of a Proactive Maintenance Technician
Day in the Life of (DILO) of a Proactive Maintenance TechnicianDay in the Life of (DILO) of a Proactive Maintenance Technician
Day in the Life of (DILO) of a Proactive Maintenance Technician
 

Último

Último (20)

AWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of TerraformAWS Community Day CPH - Three problems of Terraform
AWS Community Day CPH - Three problems of Terraform
 
Developing An App To Navigate The Roads of Brazil
Developing An App To Navigate The Roads of BrazilDeveloping An App To Navigate The Roads of Brazil
Developing An App To Navigate The Roads of Brazil
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CV
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...Apidays New York 2024 - The value of a flexible API Management solution for O...
Apidays New York 2024 - The value of a flexible API Management solution for O...
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)Powerful Google developer tools for immediate impact! (2023-24 C)
Powerful Google developer tools for immediate impact! (2023-24 C)
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Tech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfTech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdf
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 

Case Study - Multi-technology Fault Identification

  • 1. © 2013 ALLIED RELIABILITY, INC. 1 A DIVISION OF ALLIED RELIABILITY GROUP Multi-Technology Fault Identification Industry: Food and Beverage Technology: On-line MCA (Initially) Component: Motor Part: Electrical Connections Time Context Tuesday, April 16, 2013 Process Information This asset is a pump used to pump water for the milling process and cannot be shut down for more than 3 hours during the milling process. Shutting down the pump causes operations to have to switch tanks for that period of time and requires constant monitoring to prevent product overflows. Summary of Action During routine on-line (energized) motor circuit data collection, test results indicated a 26.5% current imbalance, along with a 35.36% impedance imbalance. Looking at Figure 1, the Power Phase shows the current imbalance indicated by the shorter current 1 and current 3 lines. Figure 2 shows the imbalance in the current section of the power test results page. Figure 3 is the Current Time Domain showing current 2 higher than currents 1 and 3. Voltage was checked and found to be balanced across the motor starter at 283 VAC phase-to-neutral and 490 VAC phase-to-phase. Vibration data was collected and found the motor was in alarm for a 2x line electrical frequency, indicating there was a possible electrical issue (Figure 4). An infrared scan was conducted on the electrical enclosures containing the fuses and motor starter. The B phase fuse and connections on the motor starter were operating with an above alarm level temperature differential. A thermographic scan of the motor revealed that the housing was operating hotter than normal, indicating a possible issue within the circuit. Figure 5 is an infrared image taken of the motor soon after the current imbalance was discovered by the on-line test. It shows the motor temperature was running above normal at 215°F, caused by the current imbalance. Figures 6 & 7 are infrared images taken of the motor starter and fuses. The temperature differential of the B phase circuit is caused by the imbalance in the circuit due to the high resistance connection. A work order was written to perform an off-line (de-energized) motor test to isolate the cause of the imbalances. An off-line test was conducted from the Motor Control Center (MCC) and found a 44.65% phase-to- phase resistive imbalance, along with an 11.65% inductive imbalance. Figure 8 shows the phase-to-phase resistive imbalance and inductive imbalance from the off-line test conducted from the MCC indicating a high resistive connection in the circuit. It was decided that further testing should be done by going to the motor and disconnecting the motor from the circuit to further isolate the cause of the imbalances. Upon opening the motor junction box, a bad connection was discovered (Figure 9). All connections were repaired and another off-line test was conducted from the MCC, which indicated that the repairs had corrected the issue.
  • 2. © 2013 ALLIED RELIABILITY, INC. 2 A DIVISION OF ALLIED RELIABILITY GROUP Post Notification Department reliability coordinators and maintenance supervision were notified as soon as it was confirmed that there was an issue and made aware of the motor running hot, creating a potential burn hazard for employees. Supporting Data Figure 1: Power Phasor Shows Both Current 1 and Current 3 Lower Than Current 2
  • 3. © 2013 ALLIED RELIABILITY, INC. 3 A DIVISION OF ALLIED RELIABILITY GROUP Figure 2: Power Test Results Showing the Current and Impedance Imbalances Figure 3: Current Time Domain Showing Current Imbalance
  • 4. © 2013 ALLIED RELIABILITY, INC. 4 A DIVISION OF ALLIED RELIABILITY GROUP Figure 4: Vibration Spectrum Showing 2x Line Electrical Frequency Figure 5: Infrared Image of Motor Indicating a Maximum Temperature of 215°F
  • 5. © 2013 ALLIED RELIABILITY, INC. 5 A DIVISION OF ALLIED RELIABILITY GROUP Figure 6: Infrared Image of Motor Starter Showing B Phase Connection at 147°F Figure 7: Infrared Image of Fuses Showing the B Phase Fuse at 127°F
  • 6. © 2013 ALLIED RELIABILITY, INC. 6 A DIVISION OF ALLIED RELIABILITY GROUP Figure 8: MCA AC Standard Test Showing the Phase-to-Phase Resistive and Inductive Imbalances Figure 9: Image of Bad Connections Found After Opening the Motor Junction Box Cover
  • 7. © 2013 ALLIED RELIABILITY, INC. 7 A DIVISION OF ALLIED RELIABILITY GROUP Plan of Action Monitoring with MCA both on-line and off-line will help to identify this type of issue before it can damage equipment or injure personnel. Conclusion Not only is this type of condition shortening the life of the motor, but is also a potential hazard to personnel in the form of a shock hazard or burn hazard. If the connections were touching any part of the motor frame and the motor was not properly grounded, an individual who happened to touch the motor would become the least path of resistance to ground and could be seriously injured, suffering burns from the motor running hot, or worse, loss of life. By using the multi-technology approach to reliability – on-line/off-line motor circuit analysis, vibration analysis, infrared analysis, and other reliability technologies including oil analysis and ultrasonic analysis – this type of anomaly, as well as others, can be detected early and help reduce unexpected downtimes, production losses, and most importantly, safety concerns for a facility’s personnel.