ELECTRIC POWER SUBSTATION

An assembly of equipment in an electric power system through which electric energy is
passed for transmission, transformation, distribution, or switching. Also known as
substation.


Electric power substation

An assembly of equipment in an electric power system through which electrical energy is
passed for transmission, distribution, interconnection, transformation, conversion, or
switching. See also Electric power systems.

Specifically, substations are used for some or all of the following purposes: connection of
generators, transmission or distribution lines, and loads to each other; transformation of
power from one voltage level to another; interconnection of alternate sources of power;
switching for alternate connections and isolation of failed or overloaded lines and
equipment; controlling system voltage and power flow; reactive power compensation;
suppression of overvoltage; and detection of faults, monitoring, recording of information,
power measurements, and remote communications. Minor distribution or transmission
equipment installation is not referred to as a substation.

Substations are referred to by the main duty they perform. Broadly speaking, they are
classified as: transmission substations, which are associated with high voltage levels; and
distribution substations, associated with low voltage levels. See also Electric distribution
systems.

Substations are also referred to in a variety of other ways:

   1. Transformer substations are substations whose equipment includes transformers.
   2. Switching substations are substations whose equipment is mainly for various
      connections and interconnections, and does not include transformers.

   3. Customer substations are usually distribution substations on the premises of a
      larger customer, such as a shopping center, large office or commercial building,
      or industrial plant.

   4. Converter stations are complex substations required for high-voltage direct-
      current (HVDC) transmission or interconnection of two ac systems which, for a
      variety of reasons, cannot be connected by an ac connection. The main function of
      converter stations is the conversion of power from ac to dc and vice versa. The
      main equipment includes converter valves usually located inside a large hall,
      transformers, filters, reactors, and capacitors.

   5. Most substations are installed as air-insulated substations, implying that the bus-
      bars and equipment terminations are generally open to the air, and utilize
insulation properties of ambient air for insulation to ground. Modern substations
       in urban areas are esthetically designed with low profiles and often within walls,
       or even indoors.

   6. Metal-clad substations are also air-insulated, but for low voltage levels; they are
      housed in metal cabinets and may be indoors or outdoors.

   7. Acquiring a substation site in an urban area is very difficult because land is either
      unavailable or very expensive. Therefore, there has been a trend toward
      increasing use of gas-insulated substations, which occupy only 5–20% of the
      space occupied by the air-insulated substations. In gas-insulated substations, all
      live equipment and bus-bars are housed in grounded metal enclosures, which are
      sealed and filled with sulfur hexafluoride (SF6) gas, which has excellent insulation
      properties.

   8. For emergency replacement or maintenance of substation transformers, mobile
      substations are used by some utilities.

An appropriate switching arrangement for “connections” of generators, transformers,
lines, and other major equipment is basic to any substation design. There are seven
switching arrangements commonly used: single bus; double bus, single breaker; double
bus, double breaker; main and transfer bus; ring bus; breaker-and-a-half; and breaker-
and-a-third. Each breaker is usually accompanied by two disconnect switches, one on
each side, for maintenance purposes. Selecting the switching arrangement involves
considerations of cost, reliability, maintenance, and flexibility for expansion.

A substation includes a variety of equipment. The principal items are transformers, circuit
breakers, disconnect switches, bus-bars, shunt reactors, shunt capacitors, current and
potential transformers, and control and protection equipment. See also Bus-bar; Circuit
breaker; Electric protective devices; Electric switch; Relay; Transformer; Voltage
regulator.

Good substation grounding is very important for effective relaying and insulation of
equipment; but the safety of the personnel is the governing criterion in the design of
substation grounding. It usually consists of a bare wire grid, laid in the ground; all
equipment grounding points, tanks, support structures, fences, shielding wires and poles,
and so forth, are securely connected to it. The grounding resistance is reduced enough
that a fault from high voltage to ground does not create such high potential gradients on
the ground, and from the structures to ground, to present a safety hazard. Good overhead
shielding is also essential for outdoor substations, so as to virtually eliminate the
possibility of lightning directly striking the equipment. Shielding is provided by overhead
ground wires stretched across the substation or tall grounded poles. See also Grounding;
Lightning and surge protection.

INTERCONNECTION
A link between power systems enabling them to draw on one another's reserves in time of
need and to take advantage of energy cost differentials resulting from such factors as load
diversity, seasonal conditions, time-zone differences, and shared investment in larger
generating units.

OVERVOLTAGE

A voltage greater than that at which a device or circuit is designed to operate. Also
known as overpotential.




   •   What is a substation transformer?
   •   What is the difference between current transformer and voltage transformer?
   •   Why substation is called so?
   •   What is the difference between a power station and a substation?
   •   What is the difference between isolation transformer and step up or step down
       transformer?
   •   Can you use a step down transformer as step up transformer by reversing the
       primary voltage as a secondary voltage?
   •   What is pulse transformer?
   •   What is a booster transformer?
   •   What is isolation transformer?
   •   How transformer works?
   •   What is the uses of core transformer?
   •   What is transformer turns ratio?
   •   What happens when DC supply is given to transformer?
   •   How do you identify a liquid transformer?
   •   How did the Transformer franchise begin?
   •   Operation of an isolation transformer?
   •   What is the difference between amplifier and transformer?
   •   How do you measure core loss in a transformer?
   •   What is the input side of a transformer called?
   •   How many bushing do you get on delta to star transformer?
   •   What is the differnce of a two winding transformer and autotransformer?
   •   What is the difference between electronic and magnetic transformer?
   •   What is the name of the company that makes all of the Transformer toys ?
   •   Explain center-tapped transformer?
   •   What is the disadvantage of using dry type transformer?
   •   How do you work out the volt-amp in a transformer?
   •   Will a transformer within a light make a buzzing sound?
   •   Does Megatron have weapons in the 2007 Transformer movie?
   •   How do you calculate the length of the wire conductor in a transformer?
   •   Turns ratio of a single phase transformer?
   •   How do you figure out maximum current of a 240V transformer circuit?
•   Can you use a 120V to 240V step up transformer for an electric range?
•   How to determine the right transformer in three phase system say it should be
    delta or wye?
•   Why do a Voltage transformer give me a CLIPPED output signal?
•   What is the best transformer to purchase to operate a sewing machine purchased
    in the US in the UK?
•   How do you calculate transformer turns ratio given primary and secondary
    winding voltage?
•   Is it possible to use a 120-240V step up transformer with an electric range when a
    house is only wired for 120V and if so how?
•   Can you use the NTSC selectable option on the European television and a step up
    transformer to make it work in the US?
•   Do you have parts for a wall furnance Transformer part no AT30 Model s7035st
    wr62?
•   Will a 240V water heater operate normally with a 120V 208V service coming off
    a three phase transformer?
•   How do you wire a boost transformer for 240v with 32v boostwhat is x1 x4 h1
    h4?
•   If you live in Israel can you use a transformer to step down the 240V power to
    120V and then use an American appliance or do you also have a cycle problem
    and if so can it be cured?
•   Does varying the resistance in the secondary circuit cause a change in both the
    input and output currents to keep the power on both sides equal on a transformer?
•   Can a transformer autobot or decepticon survive falling throught the Earths
    atmosphere or would the heat and friction instantly kill them?
•   Could you run your in-house electricity on a 12V system since all your appliances
    and radios and tvs mostly have a built-in transformer to reduce the current to a
    much lower voltage?
•   How do you produce 120V lines from 240V lines without using a transformer?
•   Is it safe to run a 220volt ac- 12volt dc step down transformer in a 110v outlet-
    will it transform it to 6v or will it run fine?
•   If you have a 120V Sony stereo amplifier that you plugged into a wall transformer
    to step down from 240V in Denmark and it worked fine then zapped can you
    replace the fried component to accept 240V?
•   How many turns do you need on a ferrite core transformer with a 1cm by 1cm
    square center leg at 14 volts and 100Khz switching speed to maintain a Tesla
    equal to or less than 0.15?
•   What is the difference between a step up and a step down transformer?

1. It is a large encased group of metal plates about the size of a small house with 2
     sets of insulated copper wires wrapped around the plates -an input and output - to
     convert a very high supply line voltage - maybe 44 thousand volts to a lower
     voltage of 2200 volts that runs down the power line poles in your neighborhood.
     Look at your street's power poles and you will see a mini substation that converts
     he 2200 volt to 220 volts and may supply several homes.
2. Actually...NONE. A transformer is a device that steps up, or steps down voltage.
       During this process current is also stepped up or down, however, voltage and
       current are inversely proportional ( meaning an increase in voltage results in a
       decrease in current and vice versa ) As an example: A step up transformer of 10:1
       ratio with 12 volts and 10 ampere of current applied to the primary will have ten
       times the voltage ( 120 volts ) and ten times less current ( 1 ampere ) at the
       secondary...and a step down transformer with the same turns ratio with 120 volts
       and 1 ampere applied to the primary will have 12 volts and ten ampere available
       at the secondary. The electricity supplied into homes and business uses wires
       carrying very high voltage and low current over long distances, then uses step
       down transformers to step down the voltage and step up the current.

   3. The noun substation has one meaning - a subsidiary station where electricity is
       transformed for distribution by a low-network.

   4. Power station is where they actually generate the electricity on an industrial scale.
       Substation is a subsidiary of a power station typically used to step down the
       voltage for more local use of electricity.

   5. Isolation transformer: is a transformer with two separate windings, the primary and
       the secondary. There is an electrical isolation between the primary and the
       secondary. There are also transformers with one winding and connections for
       input and output.
       If the input is low and the output high you can say STEP Up.
       If the input is high and the output low you can say STEP DOWN.
       This transformers can not by used where safety necessary.

6. If the transformer has two separate windings, then, YES a step-down can be used as a
step-up, and vice-versa.

It is more correct to say you are reversing the high and low sides.

By definition Primary is the "IN" side and Secondary is the "OUT" side.

The Primary could be the high voltage side if it is a step-down,
or it could be the low voltage side, if it is a step-up.

Design Considerations

Care must be taken when reversing the operation of a step-down transformer to insure
that it does not exceed the ratings of the transformer. For example, let's say we have a 12
VA step-down transformer that takes 120Vac in and is rated to provide 12V at 1 amp at
the secondary. If we were to reverse it and apply 12Vac to the new primary (the old
secondary), we would have 120Vac at the new secondary, but to keep within the original
ratings it could only be loaded to 0.1A @ 120Vac.
As long as you treat the output rating of the step-down transformer as the input rating as a
step-up transformer, and don't try to draw current beyond what would normally have
been applied to the high voltage primary, you should be fine. Potentially one could push
up the voltage on such a transformer beyond what its stated application specified, while
making sure not to exceed the power rating of the transformer and not exceeding the
breakdown voltage of the transformer's insulation, for example driving the above
transformer at 24V to get 0.05A @ 240Vac. It is important to realize though that the rated
input voltage for a step-down transformer will likely not be a safe input voltage if you use
it as a step-up transformer - for example, applying 120V to the above transformer with
the windings reversed would generate 1.2KV!

   7. A transformer not intended for power conversion, but for galvanically isolating
       electrical signals - usually digital, therefore "pulse".

   8. Normally used in public address systems, where the audio have to travel long
       distances and have to drive more than one speaker then a booster transformer is
       inserted in the audio line, also called audio transformer

9. An isolation transformer does not have a direct electrical path from the power input
side to the power output side. The term is also used to define how much electrical
isolation exists between the input and output windings. For example when using line-
voltage input transformers to power low volatge device handled by humans, a high
degree of isolation is required for safety.

Isolated transformers often use separate bobbins for the primary and secondary coil
windings, but usually the windings are just wound on top of each other with insulation in
between.

Non-Isolated transformers are becoming rare. A common example is the "Variac" which
is a non-isolated variable transformer. Usually the term "auto-transformer" is used to
describe non-isolated transformers. They are rarely found in consumer products.

10. #1...Wire produces a magnetic field when current is passed through it. If you wrap the
wire around something (a core) to make a coil, it concentrates that field. The core isn't
actually necessary but it helps concentrate the field and make the transformer more
effecient.

#2...If you pass a magnetic field through a wire, it produces electron flow.

If you make a coil with 100 wraps and pass current through it, it will produce the
magnetic field. If you have another coil close enough to be IN that magnetic field, and it
has 10 turns, you will get about 1/10 the voltage from the second coil that you put into
the first one.

It gets a lot more complicated than that with formulas and all kinds of mathematics, but
that is the basics of a "step down" transformer.
13. Nothing noticeable. DC power is not transmitted between the coils of a
    transformer. There would be no current on the other side of the transformer,
    unless the power of the source was constantly modulated.

14. An amplifier is what increases a rock band's speaker sound output into a ear
    splitting experience and small radio signals in a radio until it makes it out to the
    speaker. A transformer converts AC electricity up or down to a desired level for a
    required project. Example: A battery charger plugged into a wall socket will
    transformed to about 18 volts to do the charging

15. Core loss is also called “No-Load” loss. To measure the core lose simply you
    need variable AC supply, Wattmeters, Ampere meters and Voltmeters. The basic
    principle to perform this measurement is to supply the transformer with its
    nominal voltage and then record the Watt or Kilo watt values. You will need
    precision current and voltage transformers to supply your wattmeters, voltmeters
    and ampere meters. There is a term called “Form Factor” which should be
    measured in order to identify how sinusoidal is your supply voltage and based on
    the value of this Form Factor you need to apply relevant corrections to the
    measured values. For power transformers normally we record no load values
    between 90% and 110% of rated voltage. Based on the test circuit configuration
    you may use “2 or 3 wattmeter” arrangements for 3 phase transformers. For
    further information you can check out my website at www.eonce.com and if you
    need more information you can simply fill the form in “Contact” page on the
    website. Hope this helps. B.M. Mirzaei, P.Eng.
Electricity distribution is the penultimate stage in the delivery (before retail) of
electricity to end users. It is generally considered to include medium-voltage (less than 50
kV) power lines, electrical substations and pole-mounted transformers, low-voltage (less
than 1000 V) distribution wiring and sometimes electricity meters.

Description

History

In the early days of electricity generation to about 1900, direct current DC generators
were connected to loads at the same voltage. The generation, transmission and loads had
to be of the same voltage because there was no way of changing DC voltage levels, other
than inefficient motor-generator sets. Low DC voltages were used (on the order of 100
volts) since that was a practical voltage for incandescent lamps, which were then the
primary electrical load. The low voltage also required less insulation to be safely
distributed within buildings.
The losses in a cable are proportional to the square of the current, the length of the cable,
and the resistivity of the material, and are inversely proportional to cross-sectional area.
Early transmission networks were already using copper, which is one of the best
economically feasible conductors for this application. To reduce the current and copper
required for a given quantity of power transmitted would require a higher transmission
voltage, but no convenient efficient method existed to change the voltage level of DC
power circuits. To keep losses to an economically practical level the Edison DC system
needed thick cables and local generators. Early DC generating plants needed to be within
about 1.5 miles of the farthest customer to avoid the need for excessively large and
expensive conductors.

Introduction of alternating current

The adoption of alternating current (AC) for electricity generation following the War of
Currents dramatically changed the situation. Power transformers, installed at substations,
could be used to raise the voltage from the generators and reduce it to supply loads.
Increasing the voltage reduced the current in the transmission and distribution lines and
hence the size of conductors required and distribution losses incurred. This made it more
economical to distribute power over long distances. Generators (such as hydroelectric
sites) could be located far from the loads.

In North America, early distribution systems used a voltage of 2200 volts corner-
grounded delta. Over time, this was gradually increased to 2400 volts. As cities grew,
most 2400 volt systems were upgraded to 4160/2400 volt, three-phase systems. Some city
and suburban distribution systems continue to use this range of voltages, but most have
been converted to 7200/12470Y, 7620/13200Y, 14400/24940Y, and 19920/34500Y.

European systems used 3300 volts to ground, in support of the 220/380Y volt power
systems used in those countries. In the UK, urban systems progressed to 6.6 kV and then
11 kV (phase to phase), the most common distribution voltage.

North American and European power distribution systems also differ in that North
American systems tend to have a greater number of low-voltage, step-down transformers
located close to customers' premises. For example, in the US a pole-mounted transformer
in a suburban setting may supply 1-3 houses, whereas in the UK a typical urban or
suburban low-voltage substation might be rated at 2 MW and supply a whole
neighbourhood. This is because the higher voltage used in Europe (380 V vs 230 V) may
be carried over a greater distance with acceptable power loss. An advantage of the North
American setup is that failure or maintenance on a single transformer will only affect a
few customers. Advantages of the UK setup are that the transformers may be fewer,
larger and more efficient, and due to diversity there need be less spare capacity in the
transformers, reducing power wastage. In North American city areas with many
customers per unit area, network distribution will be used, with multiple transformers and
low-voltage busses interconnected over several city blocks.

Rural Electrification systems, in contrast to urban systems, tend to use higher voltages
because of the longer distances covered by those distribution lines (see Rural
Electrification Administration). 7200, 12470 and 25000 volt distribution is common in
the United States; 11 kV and 33 kV are common in the UK, New Zealand and Australia;
11 kV and 22 kV are common in South Africa. Other voltages are occasionally used.

In New Zealand, Australia, Saskatchewan, Canada, and South Africa, single wire earth
return systems (SWER) are used to electrify remote rural areas.

While power electronics now allow for conversion between DC voltage levels, AC is still
used in distribution due to the economy, efficiency and reliabilty of transformers. High-
voltage DC is used for transmission of large blocks of power over long distances, or for
interconnecting adjacent AC networks, but not for distribution to customers.

Distribution network configurations

Distribution networks are typically of two types, radial or interconnected (see Spot
Network Substations). A radial network leaves the station and passes through the network
area with no normal connection to any other supply. This is typical of long rural lines
with isolated load areas. An interconnected network is generally found in more urban
areas and will have multiple connections to other points of supply.

These points of connection are normally open but allow various configurations by the
operating utility linemen carefully closing and opening switches. The benefit of the
interconnected model is that in the event of a fault or required maintenance a small area
of network can be isolated and the remainder kept on supply.

Within these networks there may be a mix of overhead line construction utilizing
traditional utility poles and wires and, increasingly, underground construction with cables
and indoor or cabinet substations. However, underground distribution can cost as much as
11 times as much as overhead construction. In part to reduce this cost, underground
power lines are sometimes colocated with other utility lines in what are called Common
utility ducts. Distribution feeders emanating from a substation are generally controlled by
a circuit breaker or fuse which will open when a fault is detected. Automatic Circuit
Reclosers may be installed to further segregate the feeder thus minimising the impact of
faults.

Long feeders experience voltage drop requiring capacitors or voltage regulators to be
installed, and the phase physical relationship to be interchanged.

Characteristics of the supply given to customers are generally mandated by contract
between the supplier and customer. Deviations from the normal usage pattern usually
invoke monthly surcharges. Variables include:

   •   AC or DC - Virtually all public electricity supplies are AC today. Users of large
       amounts of DC power such as some electric railways, telephone exchanges and
       industrial processes such as aluminium smelting either operate their own or have
       adjacent dedicated generating equipment, or use rectifiers to derive DC from the
       public AC supply
   •   Voltage, including tolerance (usually +10 or -15 percentage)
   •   Frequency, commonly 50 & 60 Hz, 16-2/3 Hz for some railways and, in a few
       older industrial and mining locations, 25 Hz
   •   Phase configuration (single phase, polyphase including two phase and three
       phase)
   •   Maximum demand (usually measured as the largest amount of power delivered
       within a 15 or 30 minute period during a billing period)
   •   Load Factor, expressed as a ratio of average load to peak load over a period of
       time. Load factor indicates the degree of effective utilization of equipment (and
       capital investment) of distribution line or system.
   •   Power factor of connected load
   •   Earthing arrangements - TT, TN-S, TN-C-S or TN-C
   •   Maximum prospective short circuit current
   •   Maximum level and frequency of occurrence of transients

See List of countries with mains power plugs, voltages and frequencies.

Modern Distribution Systems

The modern distribution system begins as the primary circuit leaves the sub-station and
ends as the secondary service enters the customers meter socket. A variety of methods,
materials, and equipment are used among the various utility companies across the U.S.,
but the end result is similar. First, the energy leaves the sub-station in a primary circuit,
usually with all three phases.

The most common type of primary is known as a wye configuration (so named because
of the shape of a "Y".) The wye configuration includes 3 phases (represented by the three
outer parts of the "Y") and a neutral (represented by the center of the "Y".) The neutral is
grounded both at the substation and at every power pole. In a typical 12470Y/7200 volt
system, the pole mount transformer's primary winding is rated for 7200 volts and is
connected across one phase of power and the neutral. The primary and secondary (low
voltage) neutrals are bonded (connected) together to provide a path to blow the primary
fuse if any fault occurs that allows primary voltage to enter the secondary lines. An
example of this type of fault would be a primary phase falling across the secondary lines.
Another example would be some type of fault in the transformer itself.




Electric distribution substations transform power from transmission voltage to the lower
voltage used for local distribution to homes and businesses.

The other type of primary configuration is known as delta, this method is older and less
common. Delta is so named because of the shape of the Greek letter delta, a triangle.
Delta has only 3 phases and no neutral. In delta there is only a single voltage, between
two phases (phase to phase), while in wye there are two voltages, between two phases
and between a phase and neutral (phase to neutral). Wye primary is safer because if one
phase becomes grounded, that is makes connection to the ground through a person, tree,
or other object, it should trip out the fused cutout similer to a household circuit breaker
tripping. In delta, if a phase makes connection to ground it will continue to function
normally. It takes two or three phases to make connection to ground before the fused
cutouts will open the circuit. The voltage for this configuration is usually 4800 volts.
Transformers are sometimes used to step down from 7200 or 7600 volts to 4800 volts or
to step up from 4800 volts to 7200 or 7600 volts. When the voltage is stepped up, a
neutral is created by bonding one leg of the 7200/7600 side to ground. This is commonly
used to power single phase underground services or whole housing developments that are
built in 4800 volt delta distribution areas. Step downs are used in areas that have been
upgraded to a 7200/12500Y or 7600/13200Y and the power company chooses to leave a
section as a 4800 volt setup. Sometimes power companies choose to leave sections of a
distribution grid as 4800 volts because this setup is less likely to trip fuses or reclosers in
heavily wooded areas where trees come into contact with lines.

Economic and Political

In the United States, Electric industry "deregulation" reform, started in the mid-1990s,
has led to the creation of electricity markets through the elimination of the former natural
monopoly of generation, transmission, and distribution. As a consequence, electricity has
become more of a commodity. The separation has also led to the development of new
terminology to describe the business units, e.g. line company, wires business and network
company.

Electric Power Distribution




A distribution system originates at a distribution substation and includes the lines, poles,
transformers and other equipment needed to deliver electric power to the customer at
the required voltages. Customers are classed as:
    • Industrial Customer
    • Commercial Customer
    • Residential Customer
    • Transportation Customer



Distribution Systems                                                                      TOP


A distribution system consists of all the facilities and equipment connecting a transmission
system to the customer's equipment.

A typical distribution system can consist of:
    • Substations
    • Distribution Feeder Circuits
    • Switches
    • Protective Equipment
    • Primary Circuits
•   Distribution Transformers
   •   Secondaries, and
   •   Services




                      Figure 1. Energy flow through a typical substation

The following are examples of distribution systems components. Collectively they
constitute a typical distribution system. These typically deliver voltages as high as 34,000
volts (34 kV) and as low as 120 volts.




   Figure 2. Typical residential service drop       Figure 3. Substation pull-off structure
Figure 5. Substation underground distribution
                                                                   bus
    Figure 4. Substation pull-off structure
 (connects substation busswork to overhead
                    lines)




     Figure 6. Distribution primaries and
                 secondaries                        Figure 7. Distribution underbuild
          on subtransmission pole


Additional information:
   • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth
       Edition 2002, McGraw-Hill.



  Industrial Customer                                                                   TOP
Most industries need 2,400 to 4,160 volts to run heavy machinery and usually their
  own substation or substations to reduce the voltage from the transmission line to the
  desired level for distribution throughout the plant area. They usually require 3-phase
  lines to power 3-phase motors.




                      Figure 8. Industrial facility distribution transformer


  Additional information:
     • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E.,
         Tenth Edition 2002, McGraw-Hill.



Commercial Customer                                                                         TOP


Commercial customers are usually served at distribution voltages, ranging from 14.4 kV
to 7.2 kV through a service drop line which leads from a transformer on or near the
distribution pole to the customer's end use structure. They may require 3-phase lines to
power 3-phase motors.




                                                       Figure 10. Commercial service drop




     Figure 9. Distribution transformer to
     3-phase service - commercial facility
Residential Customer                                                                       TOP


 The distribution electricity is reduced to the end use voltage (120/240 volts single phase)
 via a pole mounted or pad-mounted transformer. Power is delivered to the residential
 customer through a service drop line which leads from the distribution pole transformer to
 the customer's structure, for overhead lines, or underground.




  Figure 11. Residential distribution transformer
                                                  Figure 12. Pad-mounted residential distribution
                 and service drop
                                                                  transformer




Transportation Customer                                                                       TOP

Currently the only electric transportation systems are light rail and subway systems. A small
distribution substation reduces the local distribution voltage to the transportation system
requirements. The overhead lines supply electric power to the transportation system motors
and the return current lines are connected to the train tracks.




                Figure 13. Public transit train powered by overhead electric lines
Figure 14. Substation where electricity is conditioned for powering commuter trains




  Figure 15. Power runs from the substation      Figure 16. Electric cables carry electricity to
  underground to the poles where power is                 power the train's motors
  delivered to the power lines. The circuit is
completed through the train tracks, with lines
         returning to the substation.
Illustrated Glossary: Substations

A substation is a high-voltage electric system facility. It is used to switch generators, equipment, and circuits or
lines in and out of a system. It also is used to change AC voltages from one level to another, and/or change
alternating current to direct current or direct current to alternating current. Some substations are small with little
more than a transformer and associated switches. Others are very large with several transformers and dozens of
switches and other equipment. There are three aspects to substations:




                                             Figure 1. Typical substation
   •   Substation Types: Although, there are generally four types of substations there are substations that are a
       combination of two or more types.
           Step-up Transmission Substation
           Step-down Transmission Substation
           Distribution Substation
           Underground Distribution Substation
           Substation Functions
           Substation Equipment

  Step-up Transmission Substation                                                                             TOP


  A step-up transmission substation receives electric power from a nearby generating facility and uses a large
  power transformer to increase the voltage for transmission to distant locations. A transmission bus is used
  to distribute electric power to one or more transmission lines. There can also be a tap on the incoming
  power feed from the generation plant to provide electric power to operate equipment in the generation
  plant.

  A substation can have circuit breakers that are used to switch generation and transmission circuits in and
  out of service as needed or for emergencies requiring shut-down of power to a circuit or redirection of
  power.
The specific voltages leaving a step-up transmission substation are determined by the customer needs of
the utility supplying power and to the requirements of any connections to regional grids. Typical voltages
are:

          High voltage (HV) ac:                        69 kV, 115 kV, 138 kV, 161 kV, 230 kV
          Extra-high voltage (EHV) ac:                 345 kV, 500 kV, 765 kV
          Ultra-high voltage (UHV) ac:                 1100 kV, 1500 kV
          Direct-current high voltage (dc HV):         ±250 kV, ±400 kV, ±500 kV

Direct current voltage is either positive or negative polarity. A DC line has two conductors, so one would be
positive and the other negative.




        Figure 2. Step-up AC transmission substation       Figure 3. Step-up transmission substation to
                                                                       AC transmission lines




Step-down Transmission Substation                                                                         TOP

Step-down transmission substations are located at switching points in an electrical grid. They connect
different parts of a grid and are a source for subtransmission lines or distribution lines. The step-down
substation can change the transmission voltage to a subtransmission voltage, usually 69 kV. The
subtransmission voltage lines can then serve as a source to distribution substations. Sometimes, power is
tapped from the subtransmission line for use in an industrial facility along the way. Otherwise, the power
goes to a distribution substation.
Figure 4. Step-down transmission substation




                                     Figure 5. Step-down power transformer




Distribution Substation                                                                                TOP

Distribution substations are located near to the end-users. Distribution substation transformers change the
transmission or subtransmission voltage to lower levels for use by end-users. Typical distribution voltages
vary from 34,500Y/19,920 volts to 4,160Y/2400 volts.

34,500Y/19,920 volts is interpreted as a three-phase circuit with a grounded neutral source. This would
have three high-voltage conductors or wires and one grounded neutral conductor, a total of four wires. The
voltage between the three phase conductors or wires would be 34,500 volts and the voltage between one
phase conductor and the neutral ground would be 19,920 volts.

From here the power is distributed to industrial, commercial, and residential customers.




               Figure 6. Distribution substation                Figure 8. Distribution substation
Figure 9. Distribution substation



               Figure 7. Distribution substation




Underground Distribution Substation                                                                    TOP




                                                             Figure 10. Underground Distribution Substation

Underground distribution substations are also located near to the end-users. Distribution substation
transformers change the subtransmission voltage to lower levels for use by end-users. Typical distribution
voltages vary from 34,500Y/19,920 volts to 4,160Y/2400 volts.

An underground system may consist of these parts:
   • Conduits

   •   Duct Runs

   •   Manholes

   •   High-Voltage Underground Cables

   •   Transformer Vault

   •   Riser

   •   Transformers
From here the power is distributed to industrial, commercial, and residential customers.




Substation Functions                                                                                     TOP


Substations are designed to accomplish the following functions, although not all substations have all these
functions:
    • Change voltage from one level to another

   •   Regulate voltage to compensate for system voltage changes

   •   Switch transmission and distribution circuits into and out of the grid system

   •   Measure electric power qualities flowing in the circuits

   •   Connect communication signals to the circuits

   •   Eliminate lightning and other electrical surges from the system

   •   Connect electric generation plants to the system

   •   Make interconnections between the electric systems of more than one utility

   •   Control reactive kilovolt-amperes supplied to and the flow of reactive kilovolt-amperes in the circuits

Additional information:
   • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth Edition 2002,
       McGraw-Hill.
Substation Equipment                                                                                TOP

The major components of a typical substation are:

Air Circuit Breaker                Distribution Bus                       Potheads
Batteries                          Duct Runs                              Power-line Carrier
Bus Support Insulators             Frequency Changers                     Power Transformers
Capacitor Bank                     Grounding Resistors                    Rectifiers
Circuit Switchers                  Grounding Transformers                 Relays
Concrete Foundation                High-Voltage Underground Cables        SF6 Circuit Breakers
Conduits                           High-Voltage Fuses                     Shunt Reactors
Control House                      Lightning Arresters                    Steel Superstructures
Control Panels                     Manholes                               Supervisory Control
Control Wires                      Metal-clad Switchgear                  Suspension Insulators
Converter Stations                 Meters                                 Synchronous Condensers
Coupling Capacitors                Microwave                              Transmission Bus
Current Transformers               Oil Circuit Breakers                   Vacuum Circuit Breakers
Disconnect Switches                Potential Transformers


Additional information:
   • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth Edition 2002,
       McGraw-Hill.




        Air Circuit Breakers


        Air circuit breakers are used to interrupt circuits while current flows through them.
        Compressed air is used to quench the arc when the connection is broken.




                                          Figure 1. Air circuit breaker
Batteries


Batteries are used in the substation control house as a backup to power the control systems
in case of a power blackout.




                         Figure 1. Backup batteries in the control house




Bus Support Insulators


Bus support insulators are porcelain or fiberglass insulators that serve to isolate the bus bar
switches and other support structures and to prevent leakage current from flowing through
the structure or to ground. These insulators are similar in function to other insulators used in
substations and transmission poles and towers.




                                Figure 1. Bus support insulators
Capacitor Bank


Capacitors are used to control the level of the voltage supplied to the customer by reducing
or eliminating the voltage drop in the system caused by inductive reactive loads.




      Figure 1. Capacitor bank, end view             Figure 2. Capacitor bank, side view




Circuit Switchers


Circuit switchers provide equipment protection for transformers, lines, cables, and capacitor banks.
They also are used to energize and deenergize capacitor banks and other circuits.
Figure 1. Circuit switchers                             Figure 2. Circuit switcher




Control House


The substation control house contains switchboard panels, batteries, battery chargers, supervisory
control, power-line carrier, meters, and relays. The control house provides all weather protection
and security for the control equipment. It is also called a doghouse.




                                        Figure 1. Control house
Figure 2. Substation control house                      Figure 3. Control house




Control Panels


Control panels contain meters, control switches and recorders located in the control building,
also called a doghouse. These are used to control the substation equipment, to send power
from one circuit to another or to open or to to shut down circuits when needed.




     Figure 1. Substation control panel
                                                Figure 2. Substation control panel, detail




Converter Stations


Converter stations are located at the terminals of a DC transmission line. Converter stations
can change alternating current into direct current or change direct current to alternating
current. Sometimes converter stations are located at a generation power plant or at
transmission substations. Two unsynchronized AC transmission systems can be connected
together with converter stations.

Converter stations are also found in most substations for converting the emergency battery
back-up system to AC power for use in an emergency.




                           Figure 1. Converter station in battery room




Coupling Capacitors


Coupling capacitors are used to transmit communication signals to transmission lines. Some
are used to measure the voltage in transmission lines. In signal transmission the coupling
capacitor is part of a power line carrier circuit as shown in the schematic below. A coupling
capacitor is used in this circuit in conjunction with a line trap. Line traps can be installed at
the substation or on a transmission line tower.




             Figure 1. Power line carrier schematic showing use of coupling capacitors
Figure 3. Substation line traps




              Figure 2. Primary coupling capacitor




Current Transformers


Current transformers can be used to supply information for measuring power flows and the
electrical inputs for the operation of protective relays associated with the transmission and
distribution circuits or for power transformers. These current transformers have the primary
winding connected in series with the conductor carrying the current to be measured or
controlled. The secondary winding is thus insulated from the high voltage and can then be
connected to low-voltage metering circuits.

Current transformers are also used for street lighting circuits. Street lighting requires a
constant current to prevent flickering lights and a current transformer is used to provide that
constant current. In this case the current transformer utilizes a moving secondary coil to
vary the output so that a constant current is obtained.




                                                               Figure 2. Pole type
                                                                    constant
                Figure 1. Metering current transformers
current transformer




                             Figure 3. 400 kV current transformer




Disconnect Switches


Disconnect switches or circuit breakers are used to isolate equipment or to redirect current in a
substation. Many different types of disconnect switches are shown below.




   Figure 1. Disconnect switches on an outgoing     Figure 2. Motorized disconnect switch (circuit
                 distribution circuit                                 breaker)
Figure 3. Motorized circuit breaker – control box   Figure 4. Motorized circuit breaker - switch detail




                        Figure 5. Substation motorized grounding switches
Distribution Bus


A distribution bus is a steel structure array of switches used to route power out of a
substation.




                                                        Figure 2. Distribution bus




       Figure 1. Distribution bus




Frequency Changers


A frequency changer is a motor-generator set that changes power of an alternating current
system from one frequency to one or more different frequencies, with or without a change in
the number of phases, or in voltage. Sometimes a converter is used to accomplish this.




                   Figure 1. Frequency changers at a transportation substation
Grounding Resistors


Grounding Resistors are designed to provide added safety to industrial distribution systems
by limiting ground fault current to reasonable levels. They are usually connected between
earth ground and the neutral of power transformers, power generators or artificial neutral
transformers. Their main purpose is to limit the maximum fault current to a value which will
not damage generating, distribution or other associated equipment in the power system, yet
allow sufficient flow of fault current to operate protective relays to clear the fault.




                                 Figure 1. Grounding resistor




Grounding Transformers


A grounding transformer is intended primarily to provide a neutral point for grounding
purposes. It may be provided with a delta winding in which resistors or reactors are
connected.
Figure 1. Grounding transformer - front view   Figure 2. Grounding transformer - back view




High-Voltage Underground Cables


High-Voltage underground cables are constructed in many different ways, but are usually shielded
cables. They are made with a conductor, conductor-strand shielding, insulation, semi-conducting
insulation shielding, metallic insulation shielding, and a sheath. The sheath can be metallic and may
then serve as the metallic insulation shielding and be covered with a nonmetallic jacket to protect
the sheath. This sheath helps to reduce or eliminate inductive reactance. Such cables are commonly
used in circuits operating at 2400 volts or higher.
Figure 1. High-voltage underground cables            Figure 2. High-voltage underground cables




High Voltage Fuses


High voltage fuses are used to protect the electrical system in a substation from power
transformer faults. They are switched for maintenance and safety.




  Figure 1. High voltage fuses in a switch box   Figure 2. External switch for high voltage fuses




Lightning Arresters


Lightning arresters are protective devices for limiting surge voltages due to lightning strikes or
equipment faults or other events, to prevent damage to equipment and disruption of service. Also
called surge arresters.

Lightning arresters are installed on many different pieces of equipment such as power poles and
towers, power transformers, circuit breakers, bus structures, and steel superstructures in
substations.
Figure 2. Lightning arrester on distribution pole
  Figure 1. Lightning arresters on bus structures
                                                                      transformer




           Figure 3. Lightning arresters




                                                    Figure 4. Lightning arrester on substation power
                                                                      transformer




Manholes
A manhole is the opening in the underground duct system which houses cables splices and which
cablemen enter to pull in cable and to make splices and tests. Also called a splicing chamber or
cable vault.




               Figure 1. Manholes




                                                               Figure 2. Manhole cover




Meters


Various types of meters are found in substation control houses. They all are measuring
devices and can be an indicating meter or a recording meter. An indicating meter shows on a
dial the quantity being measured. A recording meter makes a permanent record of the
quantity being measured, usually by tracing a line on a chart or graph. Newer recording
meters store the information electronically. The photo below left is an indicating amperage
meter. On the right is a recording meter.
Figure 2. Recording power meter
  Figure 1. An indicating AC amperes meter




Microwave


Substations commonly use microwave communication equipment for communication with
local and regional electric power system control centers. This system allows for rapid
communication and signaling for controlling the routing of power.

Electric power for microwave transmission comes from special transformers that reduce
incoming transmission voltage to that required for the microwave system.




    Figure 1. Substation microwave communication
                         tower
Figure 2. Microwave power
                                                                     transformers




Oil Circuit Breakers


Oil circuit breakers are used to switch circuits and equipment in and out of a system in a
substation. They are oil filled to provide cooling and to prevent arcing when the switch is
activated.




                                               Figure 2. Oil circuit breakers in a distribution
                                                                    circuit



   Figure 1. Oil circuit breakers in a 41 kV
                     circuit




Potential Transformers


Potential transformers are required to provide accurate voltages for meters used for billing
industrial customers or utility companies.
Figure 1. Potential transformers                Figure 2. Potential transformer




Potheads


A type of insulator with a bell or pot-like shape used to connect underground electrical cables
to overhead lines. It serves to separate the bunched-up conductors from one another in the
cable to the much wider separation in the overhead line. It also seals the cable end from the
weather. Potheads are mounted on a distribution pole and the assembly is called a riser
pole.
Figure 1. Three conductor potheads on pole




      Figure 2. Three conductor pothead                 Figure 3. Potheads on pole




Power-line Carrier


A power line carrier is communication equipment that operates at radio-frequencies,
generally below 600 kilohertz, to transmit information over electric power transmission
lines. A high frequency signal is superimposed on the normal voltage on a power circuit. The
power line carrier is usually coupled to the power line by means of a coupling capacitor in
conjunction with a line trap.

A device for producing radio-frequency power for transmission on power lines.
Figure 1. Power-line carrier schematic




                                                      Figure 2. Power-line carrier device in
                                                                  control house




Power Transformers


Power transformers raise or lower the voltage as needed to serve the transmission or distribution
circuits.




                                                        Figure 3. Power Transformer, front view




      Figure 1. Power transformer, back view
Figure 2. Large power transformers




                                                           Figure 4. Step-up transformer diagram




Rectifiers


A rectifier is a device used to convert alternating current to direct current.




      Figure 1. Full wave rectifier circuit diagram
                                                                   Figure 2. Rectifier
Relays


A relay is a low-powered device used to activate a high-powered device. Relays are used to
trigger circuit breakers and other switches in substations and transmission and distribution
systems.




     Figure 1. Substation control panel relays




                                                       Figure 2. Relay and control panel




SF6 Circuit Breakers


SF6 circuit breakers operate to switch electric circuits and equipment in and out of the
system. These circuit breakers are filled with compressed sulfur-hexafluoride gas which acts
to open and close the switch contacts. The gas also interrupts the current flow when the
contacts are open.
Figure 1. SF6 gas power circuit breaker




                                                       Figure 2. SF6 gas power circuit breaker




Shunt Reactors


Shunt reactors are used in an extra high-voltage substation to neutralize inductive reactance
in long EHV transmission lines. The photo shows an installation of both an older version and
a newer version of the reactor.




                            Figure 1. Shunt reactors in a substation




Steel Superstructures

Steel superstructures are used to support equipment, lines, and switches in substations as
well as transmission and distribution line towers and poles.




                       Figure 1. Steel superstructure for circuit breakers




   Figure 2. Substation with many steel superstructures for equipment and connection supports




Supervisory Control


Supervisory control refers to equipment that allows for remote control of a substation's
functions from a system control center or other point of control. Supervisory control can be
used to:
    operate circuit breakers,
       operate tap changers on power transformers,
       supervise the position and condition of equipment, and
       telemeter the quantity of energy in a circuit or in substation equipment.




       Figure 1. Supervisory control room



                                                      Figure 2. Supervisory control panel




Suspension Insulators


An insulator type usually made of porcelain that can be stacked in a string and hangs from a
cross arm on a tower or pole and supports the line conductor. Suspension insulators are
used for very high voltage systems when it is not practical or safe to use other types of
insulators. They have an advantage in that one or more of the insulators in a string can be
changed out without replacing the entire string.




                                 Figure 1. Suspension insulators
Figure 2. Suspension insulators               Figure 3. Suspension insulators




Synchronous Condensers


A synchronous condenser is a synchronous machine running without mechanical load and
supplying or absorbing reactive power to or from a power system. Also called a synchronous
capacitor, synchronous compensator or rotating machinery.

In November 1995, the first static synchronous compensator began operating at a TVA
substation in Knoxville, Tennessee. This compensator can regulate voltage without expensive
external capacitors or reactors.




                               Figure 1. Synchronous condenser




Transmission Bus
Transmission buses are steel structure arrays of switches used to route power into a
substation.




             Figure 1. Transmission bus




                                                       Figure 2. Transmission bus from inside




Vacuum Circuit Breakers


A circuit breaker is a device used to complete, maintain, and interrupt currents flowing in a
circuit under normal or faulted conditions. A vacuum circuit breaker utilizes a vacuum to
extinguish arcing when the circuit breaker is opened and to act as a dielectric to insulate the
contacts after the arc is interrupted. One type of circuit breaker is called a recloser. A
vacuum recloser is designed to interrupt and reclose an AC current circuit automatically, and
can be designed to cycle a set number of times before it must be reset manually.
Figure 1. Vacuum circuit breaker, inside       Figure 2. Vacuum circuit breaker, outside




Transformer Vault


A transformer vault is a structure or room in which power transformers, network protectors,
voltage regulators, circuit breakers, meters, etc. are housed.




                           Figure 1. An underground transformer vault




Transformer - Underground


An underground transformer is essentially the same as an aboveground transformer, but is
constructed for the particular needs of underground installation. Vault type, pad-mounted,
submersible, and direct-buried transformers are used in underground systems. Pad-mounted
transformers are installed on a concrete pad on the surface near the end-user.
Figure 1. Pad-mounted transformer for
                underground system
                                                        Figure 2. Transformer in underground vault



 DISTRIBUTION

Distribution Feeder Circuits


Distribution feeder circuits are the connections between the output terminals of a distribution
substation and the input terminals of primary circuits. The distribution feeder circuit
conductors leave the substation from a circuit breaker or circuit recloser via underground
cables, called substation exit cables. The underground cables connect to a nearby overhead
primary circuit outside the substation. This eliminates multiple circuits on the poles adjacent
to the substations thereby improving the overall appearance of the substation.

Several distribution feeder circuits can leave a substation extending in different directions to
serve customers. The underground cables are connected to the primary circuit via a nearby
riser pole.

The distribution feeder bay routes power from the substation to the distribution primary
feeder circuits.

In the photo of the distribution main feeder the primary circuit is fed underground to a
nearby distribution system overhead line. The yellow cables are the primary feeder lines
going underground.
Figure 1. 3-phase distribution feeder bay




                                                        Figure 3. Distribution feeder recloser




          Figure 2. Distribution main feeder




Distribution Transformers


Distribution transformers reduce the voltage of the primary circuit to the voltage required by
customers. This voltage varies and is usually:
     120/240 volts single phase for residential customers,

      480Y/277 or 208Y/120 for commercial or light industry customers.

Three-phase pad mounted transformers are used with an underground primary circuit and three
single-phase pole type transformers for overhead service.

Network service can be provided for areas with large concentrations of businesses. These are
usually transformers installed in an underground vault. Power is then sent via underground cables
to the separate customers.
Figure 3. Residential distribution transformer
      Figure 1. Air Distribution transformer -
                commercial facility




      Figure 2. Industrial facility distribution     Figure 4. Pad-mounted residential distribution
                   transformer                                       transformer




Primary Circuits


Primary circuits are the distribution circuits that carry power from substations to local load areas.
They are also called express feeders or distribution main feeders. The distribution feeder bay routes
power from the substation to the distribution primary feeder circuits.

In the photo of the distribution main feeder the primary circuit is fed underground to a nearby
distribution system overhead line. The yellow cables are the primary feeder lines going
underground.
Figure 1. 3phase distribution feeder bay
                                                            Figure 2. Distribution main feeder




        Figure 3. Overhead primary feeder            Figure 4. Distribution primary feeder underbuild




Protective Equipment


Protective equipment in a distribution system consists of protective relays, cutout switches,
disconnect switches, lightning arresters, and fuses. These work individually or may work in
concert to open circuits whenever a short circuit, lightning strikes or other disruptive event
occurs.

When a circuit breakers opens, the entire distribution circuit is deenergized. Since this can
disrupt power to many customers, the distribution system is often designed with many
layers of redundancy. Through redundancy, power can be shut off in portions of the system
only, but not the entire system, or can be redirected to continue to serve customers. Only in
extreme events, or failure of redundant systems, does an entire system become
deenergized, shutting off power to large numbers of customers.

The redundancy consists of the many fuses and fused cutouts throughout the system that
can disable parts of the system but not the entire system. Lightning arresters also act locally
to drain off electrical energy from a lightning strike so that the larger circuit breakers are not
actuated.




   Figure 1. Substation bus lightning arresters   Figure 4. Pole mounted type - lightning arrester




                                                         Figure 5. Air-break isolator switch




             Figure 2. Fused cut-out
Figure 6. Non load-break fuse




     Figure 3. Substation disconnect switch




                                                            Figure 7. Load-break fuse




Secondaries


Secondaries are the conductors originating at the low-voltage secondary winding of a distribution transformer
for residential service are three-wire single-phase circuits. They extend along the rear lot lines, alleys, or stre
customer's premises. The secondaries can be overhead lines or underground lines.

Overhead secondary lines are usually strung below the primary lines and typically in a vertical plane. When se
strung in a vertical plane, they are directly attached to the support pole one above the other. This is in contra
primary lines which are often strung on a cross bar or other attachment in a horizontal or "V" shaped plane.
Figure 2. Secondaries in a vertical plane




   Figure 1. Cabled secondaries                                                            Figure 3. Cabled seconda
                                                                                                        in a "V" plan




Services


The wires extending from the secondaries or distribution transformer to a customer's location are
called a service. A service can be above or below ground. Underground services have a riser
connection at the distribution pole. Commercial and residential services are much the same and
can be either 120 or 220 or both.




                                                             Figure 2. Service line to residence
 Figure 1. Distribution system lines and associated
                     equipment
Figure 3. Commercial service




                                                    Figure 4. Secondary to underground service via a
                                                                          riser




Switches


Distribution systems have switches installed at strategic locations to redirect or cut-off power flows
for load balancing or sectionalizing. Also, this permits repairing of damaged lines or equipment or
upgrading work on the system. The many types of switches include:
      circuit-breaker switches
      single-pole disconnect switches
      three-pole group-operated switches
      pad-mounted switchgear




                                                           Figure 2. Air-break isolator switch

      Figure 1. Air circuit-breaker switches
Figure 4. Single-pole disconnect switch combined
Figure 3. Circuit switchers
                                     with a fuse is called a fused cutout




                                     Figure 6. Pad mounted switchgear




Figure 5. Circuit breakers
Figure 7. Group-operated three-pole air break switch

Mais conteúdo relacionado

Mais procurados

Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substationsvishalgohel12195
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Substations
SubstationsSubstations
Substationsitfakash
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesPower System Operation
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Simple Current Transformer (CT) Testing for Switchyard Equipment.
Simple Current Transformer (CT) Testing for Switchyard Equipment.Simple Current Transformer (CT) Testing for Switchyard Equipment.
Simple Current Transformer (CT) Testing for Switchyard Equipment.SARAVANAN A
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenancekarikalan123
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 

Mais procurados (20)

Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Presentation on substations
Presentation on substationsPresentation on substations
Presentation on substations
 
ISOLATORS.pptx
ISOLATORS.pptxISOLATORS.pptx
ISOLATORS.pptx
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
220kv substation
220kv substation220kv substation
220kv substation
 
Substations
SubstationsSubstations
Substations
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Lightning Arrester Working Principle & Types
Lightning Arrester Working Principle & TypesLightning Arrester Working Principle & Types
Lightning Arrester Working Principle & Types
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
 
Simple Current Transformer (CT) Testing for Switchyard Equipment.
Simple Current Transformer (CT) Testing for Switchyard Equipment.Simple Current Transformer (CT) Testing for Switchyard Equipment.
Simple Current Transformer (CT) Testing for Switchyard Equipment.
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Electrical SUBSTATION ppt
Electrical SUBSTATION pptElectrical SUBSTATION ppt
Electrical SUBSTATION ppt
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 

Destaque

33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)Prateek Agarwal
 
Typical layout of a Sub-Station
Typical layout of a Sub-StationTypical layout of a Sub-Station
Typical layout of a Sub-StationTowfiqur Rahman
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substationssapna186
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV Girish Gupta
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substationIshank Ranjan
 
Training from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, JaipurTraining from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, JaipurR-One Power
 
132kv Substation
132kv Substation132kv Substation
132kv Substationguestecdd58
 
Distribution systems
Distribution systemsDistribution systems
Distribution systemsSURAJ PRASAD
 
Anatomy of brain sulcus and gyrus - Dr.Sajith MD RD
Anatomy of brain sulcus and gyrus - Dr.Sajith MD RDAnatomy of brain sulcus and gyrus - Dr.Sajith MD RD
Anatomy of brain sulcus and gyrus - Dr.Sajith MD RDSajith Selvaganesan
 
Rainforest powerpoint[1]
Rainforest powerpoint[1]Rainforest powerpoint[1]
Rainforest powerpoint[1]eswift12
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system Ankush Bharti
 
Practical oral histology ii
Practical oral histology iiPractical oral histology ii
Practical oral histology iiTitey
 
MULLER AO CLASSIFICATION
MULLER AO CLASSIFICATIONMULLER AO CLASSIFICATION
MULLER AO CLASSIFICATIONinks76
 
Drug excretion
Drug  excretionDrug  excretion
Drug excretionsuniu
 

Destaque (20)

Substation overview
Substation overviewSubstation overview
Substation overview
 
33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)33/11 kV substation (u.p.p.c.l.)
33/11 kV substation (u.p.p.c.l.)
 
Typical layout of a Sub-Station
Typical layout of a Sub-StationTypical layout of a Sub-Station
Typical layout of a Sub-Station
 
Types Of Substations
Types Of SubstationsTypes Of Substations
Types Of Substations
 
Substation
Substation Substation
Substation
 
Electrical substations: 132 KV
Electrical substations: 132 KV Electrical substations: 132 KV
Electrical substations: 132 KV
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
 
Training from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, JaipurTraining from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
Training from 220kv GSS Sanganer, which is located on Muhana Road, Jaipur
 
132kv Substation
132kv Substation132kv Substation
132kv Substation
 
Distribution systems
Distribution systemsDistribution systems
Distribution systems
 
Anatomy of brain sulcus and gyrus - Dr.Sajith MD RD
Anatomy of brain sulcus and gyrus - Dr.Sajith MD RDAnatomy of brain sulcus and gyrus - Dr.Sajith MD RD
Anatomy of brain sulcus and gyrus - Dr.Sajith MD RD
 
Rainforest powerpoint[1]
Rainforest powerpoint[1]Rainforest powerpoint[1]
Rainforest powerpoint[1]
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system
 
Practical oral histology ii
Practical oral histology iiPractical oral histology ii
Practical oral histology ii
 
MULLER AO CLASSIFICATION
MULLER AO CLASSIFICATIONMULLER AO CLASSIFICATION
MULLER AO CLASSIFICATION
 
Ppt cyst lung
Ppt cyst lungPpt cyst lung
Ppt cyst lung
 
Stored Grain Insect Pests
Stored Grain Insect PestsStored Grain Insect Pests
Stored Grain Insect Pests
 
Drug excretion
Drug  excretionDrug  excretion
Drug excretion
 
Carcinoma rectum (Rectal Cancer)
Carcinoma rectum (Rectal Cancer)Carcinoma rectum (Rectal Cancer)
Carcinoma rectum (Rectal Cancer)
 
Fracture healing
Fracture  healingFracture  healing
Fracture healing
 

Semelhante a Electric power substation

High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Punebizproto26
 
MINI INVERTER PROJECT.pptx
MINI INVERTER PROJECT.pptxMINI INVERTER PROJECT.pptx
MINI INVERTER PROJECT.pptxshamlaK
 
Electrical_substation_general_equipments.ppt
Electrical_substation_general_equipments.pptElectrical_substation_general_equipments.ppt
Electrical_substation_general_equipments.pptBrijeshKumar33410
 
Electrical substation general_equipments
Electrical substation general_equipmentsElectrical substation general_equipments
Electrical substation general_equipmentsEman Dacanay
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE Lalit Kumar
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at JassureShuvam Pathania
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)Ameh Messiah Edache
 
10 different equipment used in Distribution Substation
10 different equipment used in Distribution Substation10 different equipment used in Distribution Substation
10 different equipment used in Distribution SubstationDevanshVarma1
 
Design of substation (with Transformer Design)
Design of substation (with Transformer Design) Design of substation (with Transformer Design)
Design of substation (with Transformer Design) SayanSarkar55
 
Substation presentation by ram
Substation presentation by ramSubstation presentation by ram
Substation presentation by ramGRBabu Naidu
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf Ishan Khandelwal
 
Load Distribution
Load DistributionLoad Distribution
Load DistributionArpit Gupta
 
ALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxsfQyoom
 
220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)Pankaj Rawal
 

Semelhante a Electric power substation (20)

G1-Distri-Transformer.pptx
G1-Distri-Transformer.pptxG1-Distri-Transformer.pptx
G1-Distri-Transformer.pptx
 
High Tension Current Transformer in Pune
High Tension Current Transformer in PuneHigh Tension Current Transformer in Pune
High Tension Current Transformer in Pune
 
UNIT-5 TD_Study Notes.pptx
UNIT-5 TD_Study Notes.pptxUNIT-5 TD_Study Notes.pptx
UNIT-5 TD_Study Notes.pptx
 
MINI INVERTER PROJECT.pptx
MINI INVERTER PROJECT.pptxMINI INVERTER PROJECT.pptx
MINI INVERTER PROJECT.pptx
 
Electrical_substation_general_equipments.ppt
Electrical_substation_general_equipments.pptElectrical_substation_general_equipments.ppt
Electrical_substation_general_equipments.ppt
 
Electrical substation general_equipments
Electrical substation general_equipmentsElectrical substation general_equipments
Electrical substation general_equipments
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
ntpc ppt
ntpc pptntpc ppt
ntpc ppt
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
 
10 different equipment used in Distribution Substation
10 different equipment used in Distribution Substation10 different equipment used in Distribution Substation
10 different equipment used in Distribution Substation
 
T&D_Unit V.pdf
T&D_Unit V.pdfT&D_Unit V.pdf
T&D_Unit V.pdf
 
Design of substation (with Transformer Design)
Design of substation (with Transformer Design) Design of substation (with Transformer Design)
Design of substation (with Transformer Design)
 
Substation presentation by ram
Substation presentation by ramSubstation presentation by ram
Substation presentation by ram
 
400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf 400 kv Heerapura gss ppt by ishan pdf
400 kv Heerapura gss ppt by ishan pdf
 
Load Distribution
Load DistributionLoad Distribution
Load Distribution
 
Study tour to optcl
Study tour to optclStudy tour to optcl
Study tour to optcl
 
various types of transformers.
various types of transformers.various types of transformers.
various types of transformers.
 
ALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptxALBA MANUFACTURING OF TRANSFORMERS.pptx
ALBA MANUFACTURING OF TRANSFORMERS.pptx
 
220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)220kv gss pindwara(sirohi)
220kv gss pindwara(sirohi)
 

Electric power substation

  • 1. ELECTRIC POWER SUBSTATION An assembly of equipment in an electric power system through which electric energy is passed for transmission, transformation, distribution, or switching. Also known as substation. Electric power substation An assembly of equipment in an electric power system through which electrical energy is passed for transmission, distribution, interconnection, transformation, conversion, or switching. See also Electric power systems. Specifically, substations are used for some or all of the following purposes: connection of generators, transmission or distribution lines, and loads to each other; transformation of power from one voltage level to another; interconnection of alternate sources of power; switching for alternate connections and isolation of failed or overloaded lines and equipment; controlling system voltage and power flow; reactive power compensation; suppression of overvoltage; and detection of faults, monitoring, recording of information, power measurements, and remote communications. Minor distribution or transmission equipment installation is not referred to as a substation. Substations are referred to by the main duty they perform. Broadly speaking, they are classified as: transmission substations, which are associated with high voltage levels; and distribution substations, associated with low voltage levels. See also Electric distribution systems. Substations are also referred to in a variety of other ways: 1. Transformer substations are substations whose equipment includes transformers. 2. Switching substations are substations whose equipment is mainly for various connections and interconnections, and does not include transformers. 3. Customer substations are usually distribution substations on the premises of a larger customer, such as a shopping center, large office or commercial building, or industrial plant. 4. Converter stations are complex substations required for high-voltage direct- current (HVDC) transmission or interconnection of two ac systems which, for a variety of reasons, cannot be connected by an ac connection. The main function of converter stations is the conversion of power from ac to dc and vice versa. The main equipment includes converter valves usually located inside a large hall, transformers, filters, reactors, and capacitors. 5. Most substations are installed as air-insulated substations, implying that the bus- bars and equipment terminations are generally open to the air, and utilize
  • 2. insulation properties of ambient air for insulation to ground. Modern substations in urban areas are esthetically designed with low profiles and often within walls, or even indoors. 6. Metal-clad substations are also air-insulated, but for low voltage levels; they are housed in metal cabinets and may be indoors or outdoors. 7. Acquiring a substation site in an urban area is very difficult because land is either unavailable or very expensive. Therefore, there has been a trend toward increasing use of gas-insulated substations, which occupy only 5–20% of the space occupied by the air-insulated substations. In gas-insulated substations, all live equipment and bus-bars are housed in grounded metal enclosures, which are sealed and filled with sulfur hexafluoride (SF6) gas, which has excellent insulation properties. 8. For emergency replacement or maintenance of substation transformers, mobile substations are used by some utilities. An appropriate switching arrangement for “connections” of generators, transformers, lines, and other major equipment is basic to any substation design. There are seven switching arrangements commonly used: single bus; double bus, single breaker; double bus, double breaker; main and transfer bus; ring bus; breaker-and-a-half; and breaker- and-a-third. Each breaker is usually accompanied by two disconnect switches, one on each side, for maintenance purposes. Selecting the switching arrangement involves considerations of cost, reliability, maintenance, and flexibility for expansion. A substation includes a variety of equipment. The principal items are transformers, circuit breakers, disconnect switches, bus-bars, shunt reactors, shunt capacitors, current and potential transformers, and control and protection equipment. See also Bus-bar; Circuit breaker; Electric protective devices; Electric switch; Relay; Transformer; Voltage regulator. Good substation grounding is very important for effective relaying and insulation of equipment; but the safety of the personnel is the governing criterion in the design of substation grounding. It usually consists of a bare wire grid, laid in the ground; all equipment grounding points, tanks, support structures, fences, shielding wires and poles, and so forth, are securely connected to it. The grounding resistance is reduced enough that a fault from high voltage to ground does not create such high potential gradients on the ground, and from the structures to ground, to present a safety hazard. Good overhead shielding is also essential for outdoor substations, so as to virtually eliminate the possibility of lightning directly striking the equipment. Shielding is provided by overhead ground wires stretched across the substation or tall grounded poles. See also Grounding; Lightning and surge protection. INTERCONNECTION
  • 3. A link between power systems enabling them to draw on one another's reserves in time of need and to take advantage of energy cost differentials resulting from such factors as load diversity, seasonal conditions, time-zone differences, and shared investment in larger generating units. OVERVOLTAGE A voltage greater than that at which a device or circuit is designed to operate. Also known as overpotential. • What is a substation transformer? • What is the difference between current transformer and voltage transformer? • Why substation is called so? • What is the difference between a power station and a substation? • What is the difference between isolation transformer and step up or step down transformer? • Can you use a step down transformer as step up transformer by reversing the primary voltage as a secondary voltage? • What is pulse transformer? • What is a booster transformer? • What is isolation transformer? • How transformer works? • What is the uses of core transformer? • What is transformer turns ratio? • What happens when DC supply is given to transformer? • How do you identify a liquid transformer? • How did the Transformer franchise begin? • Operation of an isolation transformer? • What is the difference between amplifier and transformer? • How do you measure core loss in a transformer? • What is the input side of a transformer called? • How many bushing do you get on delta to star transformer? • What is the differnce of a two winding transformer and autotransformer? • What is the difference between electronic and magnetic transformer? • What is the name of the company that makes all of the Transformer toys ? • Explain center-tapped transformer? • What is the disadvantage of using dry type transformer? • How do you work out the volt-amp in a transformer? • Will a transformer within a light make a buzzing sound? • Does Megatron have weapons in the 2007 Transformer movie? • How do you calculate the length of the wire conductor in a transformer? • Turns ratio of a single phase transformer? • How do you figure out maximum current of a 240V transformer circuit?
  • 4. Can you use a 120V to 240V step up transformer for an electric range? • How to determine the right transformer in three phase system say it should be delta or wye? • Why do a Voltage transformer give me a CLIPPED output signal? • What is the best transformer to purchase to operate a sewing machine purchased in the US in the UK? • How do you calculate transformer turns ratio given primary and secondary winding voltage? • Is it possible to use a 120-240V step up transformer with an electric range when a house is only wired for 120V and if so how? • Can you use the NTSC selectable option on the European television and a step up transformer to make it work in the US? • Do you have parts for a wall furnance Transformer part no AT30 Model s7035st wr62? • Will a 240V water heater operate normally with a 120V 208V service coming off a three phase transformer? • How do you wire a boost transformer for 240v with 32v boostwhat is x1 x4 h1 h4? • If you live in Israel can you use a transformer to step down the 240V power to 120V and then use an American appliance or do you also have a cycle problem and if so can it be cured? • Does varying the resistance in the secondary circuit cause a change in both the input and output currents to keep the power on both sides equal on a transformer? • Can a transformer autobot or decepticon survive falling throught the Earths atmosphere or would the heat and friction instantly kill them? • Could you run your in-house electricity on a 12V system since all your appliances and radios and tvs mostly have a built-in transformer to reduce the current to a much lower voltage? • How do you produce 120V lines from 240V lines without using a transformer? • Is it safe to run a 220volt ac- 12volt dc step down transformer in a 110v outlet- will it transform it to 6v or will it run fine? • If you have a 120V Sony stereo amplifier that you plugged into a wall transformer to step down from 240V in Denmark and it worked fine then zapped can you replace the fried component to accept 240V? • How many turns do you need on a ferrite core transformer with a 1cm by 1cm square center leg at 14 volts and 100Khz switching speed to maintain a Tesla equal to or less than 0.15? • What is the difference between a step up and a step down transformer? 1. It is a large encased group of metal plates about the size of a small house with 2 sets of insulated copper wires wrapped around the plates -an input and output - to convert a very high supply line voltage - maybe 44 thousand volts to a lower voltage of 2200 volts that runs down the power line poles in your neighborhood. Look at your street's power poles and you will see a mini substation that converts he 2200 volt to 220 volts and may supply several homes.
  • 5. 2. Actually...NONE. A transformer is a device that steps up, or steps down voltage. During this process current is also stepped up or down, however, voltage and current are inversely proportional ( meaning an increase in voltage results in a decrease in current and vice versa ) As an example: A step up transformer of 10:1 ratio with 12 volts and 10 ampere of current applied to the primary will have ten times the voltage ( 120 volts ) and ten times less current ( 1 ampere ) at the secondary...and a step down transformer with the same turns ratio with 120 volts and 1 ampere applied to the primary will have 12 volts and ten ampere available at the secondary. The electricity supplied into homes and business uses wires carrying very high voltage and low current over long distances, then uses step down transformers to step down the voltage and step up the current. 3. The noun substation has one meaning - a subsidiary station where electricity is transformed for distribution by a low-network. 4. Power station is where they actually generate the electricity on an industrial scale. Substation is a subsidiary of a power station typically used to step down the voltage for more local use of electricity. 5. Isolation transformer: is a transformer with two separate windings, the primary and the secondary. There is an electrical isolation between the primary and the secondary. There are also transformers with one winding and connections for input and output. If the input is low and the output high you can say STEP Up. If the input is high and the output low you can say STEP DOWN. This transformers can not by used where safety necessary. 6. If the transformer has two separate windings, then, YES a step-down can be used as a step-up, and vice-versa. It is more correct to say you are reversing the high and low sides. By definition Primary is the "IN" side and Secondary is the "OUT" side. The Primary could be the high voltage side if it is a step-down, or it could be the low voltage side, if it is a step-up. Design Considerations Care must be taken when reversing the operation of a step-down transformer to insure that it does not exceed the ratings of the transformer. For example, let's say we have a 12 VA step-down transformer that takes 120Vac in and is rated to provide 12V at 1 amp at the secondary. If we were to reverse it and apply 12Vac to the new primary (the old secondary), we would have 120Vac at the new secondary, but to keep within the original ratings it could only be loaded to 0.1A @ 120Vac.
  • 6. As long as you treat the output rating of the step-down transformer as the input rating as a step-up transformer, and don't try to draw current beyond what would normally have been applied to the high voltage primary, you should be fine. Potentially one could push up the voltage on such a transformer beyond what its stated application specified, while making sure not to exceed the power rating of the transformer and not exceeding the breakdown voltage of the transformer's insulation, for example driving the above transformer at 24V to get 0.05A @ 240Vac. It is important to realize though that the rated input voltage for a step-down transformer will likely not be a safe input voltage if you use it as a step-up transformer - for example, applying 120V to the above transformer with the windings reversed would generate 1.2KV! 7. A transformer not intended for power conversion, but for galvanically isolating electrical signals - usually digital, therefore "pulse". 8. Normally used in public address systems, where the audio have to travel long distances and have to drive more than one speaker then a booster transformer is inserted in the audio line, also called audio transformer 9. An isolation transformer does not have a direct electrical path from the power input side to the power output side. The term is also used to define how much electrical isolation exists between the input and output windings. For example when using line- voltage input transformers to power low volatge device handled by humans, a high degree of isolation is required for safety. Isolated transformers often use separate bobbins for the primary and secondary coil windings, but usually the windings are just wound on top of each other with insulation in between. Non-Isolated transformers are becoming rare. A common example is the "Variac" which is a non-isolated variable transformer. Usually the term "auto-transformer" is used to describe non-isolated transformers. They are rarely found in consumer products. 10. #1...Wire produces a magnetic field when current is passed through it. If you wrap the wire around something (a core) to make a coil, it concentrates that field. The core isn't actually necessary but it helps concentrate the field and make the transformer more effecient. #2...If you pass a magnetic field through a wire, it produces electron flow. If you make a coil with 100 wraps and pass current through it, it will produce the magnetic field. If you have another coil close enough to be IN that magnetic field, and it has 10 turns, you will get about 1/10 the voltage from the second coil that you put into the first one. It gets a lot more complicated than that with formulas and all kinds of mathematics, but that is the basics of a "step down" transformer.
  • 7. 13. Nothing noticeable. DC power is not transmitted between the coils of a transformer. There would be no current on the other side of the transformer, unless the power of the source was constantly modulated. 14. An amplifier is what increases a rock band's speaker sound output into a ear splitting experience and small radio signals in a radio until it makes it out to the speaker. A transformer converts AC electricity up or down to a desired level for a required project. Example: A battery charger plugged into a wall socket will transformed to about 18 volts to do the charging 15. Core loss is also called “No-Load” loss. To measure the core lose simply you need variable AC supply, Wattmeters, Ampere meters and Voltmeters. The basic principle to perform this measurement is to supply the transformer with its nominal voltage and then record the Watt or Kilo watt values. You will need precision current and voltage transformers to supply your wattmeters, voltmeters and ampere meters. There is a term called “Form Factor” which should be measured in order to identify how sinusoidal is your supply voltage and based on the value of this Form Factor you need to apply relevant corrections to the measured values. For power transformers normally we record no load values between 90% and 110% of rated voltage. Based on the test circuit configuration you may use “2 or 3 wattmeter” arrangements for 3 phase transformers. For further information you can check out my website at www.eonce.com and if you need more information you can simply fill the form in “Contact” page on the website. Hope this helps. B.M. Mirzaei, P.Eng.
  • 8. Electricity distribution is the penultimate stage in the delivery (before retail) of electricity to end users. It is generally considered to include medium-voltage (less than 50 kV) power lines, electrical substations and pole-mounted transformers, low-voltage (less than 1000 V) distribution wiring and sometimes electricity meters. Description History In the early days of electricity generation to about 1900, direct current DC generators were connected to loads at the same voltage. The generation, transmission and loads had to be of the same voltage because there was no way of changing DC voltage levels, other than inefficient motor-generator sets. Low DC voltages were used (on the order of 100 volts) since that was a practical voltage for incandescent lamps, which were then the primary electrical load. The low voltage also required less insulation to be safely distributed within buildings.
  • 9. The losses in a cable are proportional to the square of the current, the length of the cable, and the resistivity of the material, and are inversely proportional to cross-sectional area. Early transmission networks were already using copper, which is one of the best economically feasible conductors for this application. To reduce the current and copper required for a given quantity of power transmitted would require a higher transmission voltage, but no convenient efficient method existed to change the voltage level of DC power circuits. To keep losses to an economically practical level the Edison DC system needed thick cables and local generators. Early DC generating plants needed to be within about 1.5 miles of the farthest customer to avoid the need for excessively large and expensive conductors. Introduction of alternating current The adoption of alternating current (AC) for electricity generation following the War of Currents dramatically changed the situation. Power transformers, installed at substations, could be used to raise the voltage from the generators and reduce it to supply loads. Increasing the voltage reduced the current in the transmission and distribution lines and hence the size of conductors required and distribution losses incurred. This made it more economical to distribute power over long distances. Generators (such as hydroelectric sites) could be located far from the loads. In North America, early distribution systems used a voltage of 2200 volts corner- grounded delta. Over time, this was gradually increased to 2400 volts. As cities grew, most 2400 volt systems were upgraded to 4160/2400 volt, three-phase systems. Some city
  • 10. and suburban distribution systems continue to use this range of voltages, but most have been converted to 7200/12470Y, 7620/13200Y, 14400/24940Y, and 19920/34500Y. European systems used 3300 volts to ground, in support of the 220/380Y volt power systems used in those countries. In the UK, urban systems progressed to 6.6 kV and then 11 kV (phase to phase), the most common distribution voltage. North American and European power distribution systems also differ in that North American systems tend to have a greater number of low-voltage, step-down transformers located close to customers' premises. For example, in the US a pole-mounted transformer in a suburban setting may supply 1-3 houses, whereas in the UK a typical urban or suburban low-voltage substation might be rated at 2 MW and supply a whole neighbourhood. This is because the higher voltage used in Europe (380 V vs 230 V) may be carried over a greater distance with acceptable power loss. An advantage of the North American setup is that failure or maintenance on a single transformer will only affect a few customers. Advantages of the UK setup are that the transformers may be fewer, larger and more efficient, and due to diversity there need be less spare capacity in the transformers, reducing power wastage. In North American city areas with many customers per unit area, network distribution will be used, with multiple transformers and low-voltage busses interconnected over several city blocks. Rural Electrification systems, in contrast to urban systems, tend to use higher voltages because of the longer distances covered by those distribution lines (see Rural Electrification Administration). 7200, 12470 and 25000 volt distribution is common in the United States; 11 kV and 33 kV are common in the UK, New Zealand and Australia; 11 kV and 22 kV are common in South Africa. Other voltages are occasionally used. In New Zealand, Australia, Saskatchewan, Canada, and South Africa, single wire earth return systems (SWER) are used to electrify remote rural areas. While power electronics now allow for conversion between DC voltage levels, AC is still used in distribution due to the economy, efficiency and reliabilty of transformers. High- voltage DC is used for transmission of large blocks of power over long distances, or for interconnecting adjacent AC networks, but not for distribution to customers. Distribution network configurations Distribution networks are typically of two types, radial or interconnected (see Spot Network Substations). A radial network leaves the station and passes through the network area with no normal connection to any other supply. This is typical of long rural lines with isolated load areas. An interconnected network is generally found in more urban areas and will have multiple connections to other points of supply. These points of connection are normally open but allow various configurations by the operating utility linemen carefully closing and opening switches. The benefit of the
  • 11. interconnected model is that in the event of a fault or required maintenance a small area of network can be isolated and the remainder kept on supply. Within these networks there may be a mix of overhead line construction utilizing traditional utility poles and wires and, increasingly, underground construction with cables and indoor or cabinet substations. However, underground distribution can cost as much as 11 times as much as overhead construction. In part to reduce this cost, underground power lines are sometimes colocated with other utility lines in what are called Common utility ducts. Distribution feeders emanating from a substation are generally controlled by a circuit breaker or fuse which will open when a fault is detected. Automatic Circuit Reclosers may be installed to further segregate the feeder thus minimising the impact of faults. Long feeders experience voltage drop requiring capacitors or voltage regulators to be installed, and the phase physical relationship to be interchanged. Characteristics of the supply given to customers are generally mandated by contract between the supplier and customer. Deviations from the normal usage pattern usually invoke monthly surcharges. Variables include: • AC or DC - Virtually all public electricity supplies are AC today. Users of large amounts of DC power such as some electric railways, telephone exchanges and industrial processes such as aluminium smelting either operate their own or have adjacent dedicated generating equipment, or use rectifiers to derive DC from the public AC supply • Voltage, including tolerance (usually +10 or -15 percentage) • Frequency, commonly 50 & 60 Hz, 16-2/3 Hz for some railways and, in a few older industrial and mining locations, 25 Hz • Phase configuration (single phase, polyphase including two phase and three phase) • Maximum demand (usually measured as the largest amount of power delivered within a 15 or 30 minute period during a billing period) • Load Factor, expressed as a ratio of average load to peak load over a period of time. Load factor indicates the degree of effective utilization of equipment (and capital investment) of distribution line or system. • Power factor of connected load • Earthing arrangements - TT, TN-S, TN-C-S or TN-C • Maximum prospective short circuit current • Maximum level and frequency of occurrence of transients See List of countries with mains power plugs, voltages and frequencies. Modern Distribution Systems The modern distribution system begins as the primary circuit leaves the sub-station and ends as the secondary service enters the customers meter socket. A variety of methods,
  • 12. materials, and equipment are used among the various utility companies across the U.S., but the end result is similar. First, the energy leaves the sub-station in a primary circuit, usually with all three phases. The most common type of primary is known as a wye configuration (so named because of the shape of a "Y".) The wye configuration includes 3 phases (represented by the three outer parts of the "Y") and a neutral (represented by the center of the "Y".) The neutral is grounded both at the substation and at every power pole. In a typical 12470Y/7200 volt system, the pole mount transformer's primary winding is rated for 7200 volts and is connected across one phase of power and the neutral. The primary and secondary (low voltage) neutrals are bonded (connected) together to provide a path to blow the primary fuse if any fault occurs that allows primary voltage to enter the secondary lines. An example of this type of fault would be a primary phase falling across the secondary lines. Another example would be some type of fault in the transformer itself. Electric distribution substations transform power from transmission voltage to the lower voltage used for local distribution to homes and businesses. The other type of primary configuration is known as delta, this method is older and less common. Delta is so named because of the shape of the Greek letter delta, a triangle. Delta has only 3 phases and no neutral. In delta there is only a single voltage, between two phases (phase to phase), while in wye there are two voltages, between two phases and between a phase and neutral (phase to neutral). Wye primary is safer because if one phase becomes grounded, that is makes connection to the ground through a person, tree, or other object, it should trip out the fused cutout similer to a household circuit breaker tripping. In delta, if a phase makes connection to ground it will continue to function normally. It takes two or three phases to make connection to ground before the fused cutouts will open the circuit. The voltage for this configuration is usually 4800 volts. Transformers are sometimes used to step down from 7200 or 7600 volts to 4800 volts or to step up from 4800 volts to 7200 or 7600 volts. When the voltage is stepped up, a neutral is created by bonding one leg of the 7200/7600 side to ground. This is commonly used to power single phase underground services or whole housing developments that are
  • 13. built in 4800 volt delta distribution areas. Step downs are used in areas that have been upgraded to a 7200/12500Y or 7600/13200Y and the power company chooses to leave a section as a 4800 volt setup. Sometimes power companies choose to leave sections of a distribution grid as 4800 volts because this setup is less likely to trip fuses or reclosers in heavily wooded areas where trees come into contact with lines. Economic and Political In the United States, Electric industry "deregulation" reform, started in the mid-1990s, has led to the creation of electricity markets through the elimination of the former natural monopoly of generation, transmission, and distribution. As a consequence, electricity has become more of a commodity. The separation has also led to the development of new terminology to describe the business units, e.g. line company, wires business and network company. Electric Power Distribution A distribution system originates at a distribution substation and includes the lines, poles, transformers and other equipment needed to deliver electric power to the customer at the required voltages. Customers are classed as: • Industrial Customer • Commercial Customer • Residential Customer • Transportation Customer Distribution Systems TOP A distribution system consists of all the facilities and equipment connecting a transmission system to the customer's equipment. A typical distribution system can consist of: • Substations • Distribution Feeder Circuits • Switches • Protective Equipment • Primary Circuits
  • 14. Distribution Transformers • Secondaries, and • Services Figure 1. Energy flow through a typical substation The following are examples of distribution systems components. Collectively they constitute a typical distribution system. These typically deliver voltages as high as 34,000 volts (34 kV) and as low as 120 volts. Figure 2. Typical residential service drop Figure 3. Substation pull-off structure
  • 15. Figure 5. Substation underground distribution bus Figure 4. Substation pull-off structure (connects substation busswork to overhead lines) Figure 6. Distribution primaries and secondaries Figure 7. Distribution underbuild on subtransmission pole Additional information: • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth Edition 2002, McGraw-Hill. Industrial Customer TOP
  • 16. Most industries need 2,400 to 4,160 volts to run heavy machinery and usually their own substation or substations to reduce the voltage from the transmission line to the desired level for distribution throughout the plant area. They usually require 3-phase lines to power 3-phase motors. Figure 8. Industrial facility distribution transformer Additional information: • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth Edition 2002, McGraw-Hill. Commercial Customer TOP Commercial customers are usually served at distribution voltages, ranging from 14.4 kV to 7.2 kV through a service drop line which leads from a transformer on or near the distribution pole to the customer's end use structure. They may require 3-phase lines to power 3-phase motors. Figure 10. Commercial service drop Figure 9. Distribution transformer to 3-phase service - commercial facility
  • 17. Residential Customer TOP The distribution electricity is reduced to the end use voltage (120/240 volts single phase) via a pole mounted or pad-mounted transformer. Power is delivered to the residential customer through a service drop line which leads from the distribution pole transformer to the customer's structure, for overhead lines, or underground. Figure 11. Residential distribution transformer Figure 12. Pad-mounted residential distribution and service drop transformer Transportation Customer TOP Currently the only electric transportation systems are light rail and subway systems. A small distribution substation reduces the local distribution voltage to the transportation system requirements. The overhead lines supply electric power to the transportation system motors and the return current lines are connected to the train tracks. Figure 13. Public transit train powered by overhead electric lines
  • 18. Figure 14. Substation where electricity is conditioned for powering commuter trains Figure 15. Power runs from the substation Figure 16. Electric cables carry electricity to underground to the poles where power is power the train's motors delivered to the power lines. The circuit is completed through the train tracks, with lines returning to the substation.
  • 19. Illustrated Glossary: Substations A substation is a high-voltage electric system facility. It is used to switch generators, equipment, and circuits or lines in and out of a system. It also is used to change AC voltages from one level to another, and/or change alternating current to direct current or direct current to alternating current. Some substations are small with little more than a transformer and associated switches. Others are very large with several transformers and dozens of switches and other equipment. There are three aspects to substations: Figure 1. Typical substation • Substation Types: Although, there are generally four types of substations there are substations that are a combination of two or more types.  Step-up Transmission Substation  Step-down Transmission Substation  Distribution Substation  Underground Distribution Substation  Substation Functions  Substation Equipment Step-up Transmission Substation TOP A step-up transmission substation receives electric power from a nearby generating facility and uses a large power transformer to increase the voltage for transmission to distant locations. A transmission bus is used to distribute electric power to one or more transmission lines. There can also be a tap on the incoming power feed from the generation plant to provide electric power to operate equipment in the generation plant. A substation can have circuit breakers that are used to switch generation and transmission circuits in and out of service as needed or for emergencies requiring shut-down of power to a circuit or redirection of power.
  • 20. The specific voltages leaving a step-up transmission substation are determined by the customer needs of the utility supplying power and to the requirements of any connections to regional grids. Typical voltages are: High voltage (HV) ac: 69 kV, 115 kV, 138 kV, 161 kV, 230 kV Extra-high voltage (EHV) ac: 345 kV, 500 kV, 765 kV Ultra-high voltage (UHV) ac: 1100 kV, 1500 kV Direct-current high voltage (dc HV): ±250 kV, ±400 kV, ±500 kV Direct current voltage is either positive or negative polarity. A DC line has two conductors, so one would be positive and the other negative. Figure 2. Step-up AC transmission substation Figure 3. Step-up transmission substation to AC transmission lines Step-down Transmission Substation TOP Step-down transmission substations are located at switching points in an electrical grid. They connect different parts of a grid and are a source for subtransmission lines or distribution lines. The step-down substation can change the transmission voltage to a subtransmission voltage, usually 69 kV. The subtransmission voltage lines can then serve as a source to distribution substations. Sometimes, power is tapped from the subtransmission line for use in an industrial facility along the way. Otherwise, the power goes to a distribution substation.
  • 21. Figure 4. Step-down transmission substation Figure 5. Step-down power transformer Distribution Substation TOP Distribution substations are located near to the end-users. Distribution substation transformers change the transmission or subtransmission voltage to lower levels for use by end-users. Typical distribution voltages vary from 34,500Y/19,920 volts to 4,160Y/2400 volts. 34,500Y/19,920 volts is interpreted as a three-phase circuit with a grounded neutral source. This would have three high-voltage conductors or wires and one grounded neutral conductor, a total of four wires. The voltage between the three phase conductors or wires would be 34,500 volts and the voltage between one phase conductor and the neutral ground would be 19,920 volts. From here the power is distributed to industrial, commercial, and residential customers. Figure 6. Distribution substation Figure 8. Distribution substation
  • 22. Figure 9. Distribution substation Figure 7. Distribution substation Underground Distribution Substation TOP Figure 10. Underground Distribution Substation Underground distribution substations are also located near to the end-users. Distribution substation transformers change the subtransmission voltage to lower levels for use by end-users. Typical distribution voltages vary from 34,500Y/19,920 volts to 4,160Y/2400 volts. An underground system may consist of these parts: • Conduits • Duct Runs • Manholes • High-Voltage Underground Cables • Transformer Vault • Riser • Transformers
  • 23. From here the power is distributed to industrial, commercial, and residential customers. Substation Functions TOP Substations are designed to accomplish the following functions, although not all substations have all these functions: • Change voltage from one level to another • Regulate voltage to compensate for system voltage changes • Switch transmission and distribution circuits into and out of the grid system • Measure electric power qualities flowing in the circuits • Connect communication signals to the circuits • Eliminate lightning and other electrical surges from the system • Connect electric generation plants to the system • Make interconnections between the electric systems of more than one utility • Control reactive kilovolt-amperes supplied to and the flow of reactive kilovolt-amperes in the circuits Additional information: • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth Edition 2002, McGraw-Hill.
  • 24. Substation Equipment TOP The major components of a typical substation are: Air Circuit Breaker Distribution Bus Potheads Batteries Duct Runs Power-line Carrier Bus Support Insulators Frequency Changers Power Transformers Capacitor Bank Grounding Resistors Rectifiers Circuit Switchers Grounding Transformers Relays Concrete Foundation High-Voltage Underground Cables SF6 Circuit Breakers Conduits High-Voltage Fuses Shunt Reactors Control House Lightning Arresters Steel Superstructures Control Panels Manholes Supervisory Control Control Wires Metal-clad Switchgear Suspension Insulators Converter Stations Meters Synchronous Condensers Coupling Capacitors Microwave Transmission Bus Current Transformers Oil Circuit Breakers Vacuum Circuit Breakers Disconnect Switches Potential Transformers Additional information: • The Lineman's and Cableman's Handbook, Shoemaker, T. M., Mack, J. E., Tenth Edition 2002, McGraw-Hill. Air Circuit Breakers Air circuit breakers are used to interrupt circuits while current flows through them. Compressed air is used to quench the arc when the connection is broken. Figure 1. Air circuit breaker
  • 25. Batteries Batteries are used in the substation control house as a backup to power the control systems in case of a power blackout. Figure 1. Backup batteries in the control house Bus Support Insulators Bus support insulators are porcelain or fiberglass insulators that serve to isolate the bus bar switches and other support structures and to prevent leakage current from flowing through the structure or to ground. These insulators are similar in function to other insulators used in substations and transmission poles and towers. Figure 1. Bus support insulators
  • 26. Capacitor Bank Capacitors are used to control the level of the voltage supplied to the customer by reducing or eliminating the voltage drop in the system caused by inductive reactive loads. Figure 1. Capacitor bank, end view Figure 2. Capacitor bank, side view Circuit Switchers Circuit switchers provide equipment protection for transformers, lines, cables, and capacitor banks. They also are used to energize and deenergize capacitor banks and other circuits.
  • 27. Figure 1. Circuit switchers Figure 2. Circuit switcher Control House The substation control house contains switchboard panels, batteries, battery chargers, supervisory control, power-line carrier, meters, and relays. The control house provides all weather protection and security for the control equipment. It is also called a doghouse. Figure 1. Control house
  • 28. Figure 2. Substation control house Figure 3. Control house Control Panels Control panels contain meters, control switches and recorders located in the control building, also called a doghouse. These are used to control the substation equipment, to send power from one circuit to another or to open or to to shut down circuits when needed. Figure 1. Substation control panel Figure 2. Substation control panel, detail Converter Stations Converter stations are located at the terminals of a DC transmission line. Converter stations can change alternating current into direct current or change direct current to alternating current. Sometimes converter stations are located at a generation power plant or at
  • 29. transmission substations. Two unsynchronized AC transmission systems can be connected together with converter stations. Converter stations are also found in most substations for converting the emergency battery back-up system to AC power for use in an emergency. Figure 1. Converter station in battery room Coupling Capacitors Coupling capacitors are used to transmit communication signals to transmission lines. Some are used to measure the voltage in transmission lines. In signal transmission the coupling capacitor is part of a power line carrier circuit as shown in the schematic below. A coupling capacitor is used in this circuit in conjunction with a line trap. Line traps can be installed at the substation or on a transmission line tower. Figure 1. Power line carrier schematic showing use of coupling capacitors
  • 30. Figure 3. Substation line traps Figure 2. Primary coupling capacitor Current Transformers Current transformers can be used to supply information for measuring power flows and the electrical inputs for the operation of protective relays associated with the transmission and distribution circuits or for power transformers. These current transformers have the primary winding connected in series with the conductor carrying the current to be measured or controlled. The secondary winding is thus insulated from the high voltage and can then be connected to low-voltage metering circuits. Current transformers are also used for street lighting circuits. Street lighting requires a constant current to prevent flickering lights and a current transformer is used to provide that constant current. In this case the current transformer utilizes a moving secondary coil to vary the output so that a constant current is obtained. Figure 2. Pole type constant Figure 1. Metering current transformers
  • 31. current transformer Figure 3. 400 kV current transformer Disconnect Switches Disconnect switches or circuit breakers are used to isolate equipment or to redirect current in a substation. Many different types of disconnect switches are shown below. Figure 1. Disconnect switches on an outgoing Figure 2. Motorized disconnect switch (circuit distribution circuit breaker)
  • 32. Figure 3. Motorized circuit breaker – control box Figure 4. Motorized circuit breaker - switch detail Figure 5. Substation motorized grounding switches
  • 33. Distribution Bus A distribution bus is a steel structure array of switches used to route power out of a substation. Figure 2. Distribution bus Figure 1. Distribution bus Frequency Changers A frequency changer is a motor-generator set that changes power of an alternating current system from one frequency to one or more different frequencies, with or without a change in the number of phases, or in voltage. Sometimes a converter is used to accomplish this. Figure 1. Frequency changers at a transportation substation
  • 34. Grounding Resistors Grounding Resistors are designed to provide added safety to industrial distribution systems by limiting ground fault current to reasonable levels. They are usually connected between earth ground and the neutral of power transformers, power generators or artificial neutral transformers. Their main purpose is to limit the maximum fault current to a value which will not damage generating, distribution or other associated equipment in the power system, yet allow sufficient flow of fault current to operate protective relays to clear the fault. Figure 1. Grounding resistor Grounding Transformers A grounding transformer is intended primarily to provide a neutral point for grounding purposes. It may be provided with a delta winding in which resistors or reactors are connected.
  • 35. Figure 1. Grounding transformer - front view Figure 2. Grounding transformer - back view High-Voltage Underground Cables High-Voltage underground cables are constructed in many different ways, but are usually shielded cables. They are made with a conductor, conductor-strand shielding, insulation, semi-conducting insulation shielding, metallic insulation shielding, and a sheath. The sheath can be metallic and may then serve as the metallic insulation shielding and be covered with a nonmetallic jacket to protect the sheath. This sheath helps to reduce or eliminate inductive reactance. Such cables are commonly used in circuits operating at 2400 volts or higher.
  • 36. Figure 1. High-voltage underground cables Figure 2. High-voltage underground cables High Voltage Fuses High voltage fuses are used to protect the electrical system in a substation from power transformer faults. They are switched for maintenance and safety. Figure 1. High voltage fuses in a switch box Figure 2. External switch for high voltage fuses Lightning Arresters Lightning arresters are protective devices for limiting surge voltages due to lightning strikes or equipment faults or other events, to prevent damage to equipment and disruption of service. Also called surge arresters. Lightning arresters are installed on many different pieces of equipment such as power poles and towers, power transformers, circuit breakers, bus structures, and steel superstructures in substations.
  • 37. Figure 2. Lightning arrester on distribution pole Figure 1. Lightning arresters on bus structures transformer Figure 3. Lightning arresters Figure 4. Lightning arrester on substation power transformer Manholes
  • 38. A manhole is the opening in the underground duct system which houses cables splices and which cablemen enter to pull in cable and to make splices and tests. Also called a splicing chamber or cable vault. Figure 1. Manholes Figure 2. Manhole cover Meters Various types of meters are found in substation control houses. They all are measuring devices and can be an indicating meter or a recording meter. An indicating meter shows on a dial the quantity being measured. A recording meter makes a permanent record of the quantity being measured, usually by tracing a line on a chart or graph. Newer recording meters store the information electronically. The photo below left is an indicating amperage meter. On the right is a recording meter.
  • 39. Figure 2. Recording power meter Figure 1. An indicating AC amperes meter Microwave Substations commonly use microwave communication equipment for communication with local and regional electric power system control centers. This system allows for rapid communication and signaling for controlling the routing of power. Electric power for microwave transmission comes from special transformers that reduce incoming transmission voltage to that required for the microwave system. Figure 1. Substation microwave communication tower
  • 40. Figure 2. Microwave power transformers Oil Circuit Breakers Oil circuit breakers are used to switch circuits and equipment in and out of a system in a substation. They are oil filled to provide cooling and to prevent arcing when the switch is activated. Figure 2. Oil circuit breakers in a distribution circuit Figure 1. Oil circuit breakers in a 41 kV circuit Potential Transformers Potential transformers are required to provide accurate voltages for meters used for billing industrial customers or utility companies.
  • 41. Figure 1. Potential transformers Figure 2. Potential transformer Potheads A type of insulator with a bell or pot-like shape used to connect underground electrical cables to overhead lines. It serves to separate the bunched-up conductors from one another in the cable to the much wider separation in the overhead line. It also seals the cable end from the weather. Potheads are mounted on a distribution pole and the assembly is called a riser pole.
  • 42. Figure 1. Three conductor potheads on pole Figure 2. Three conductor pothead Figure 3. Potheads on pole Power-line Carrier A power line carrier is communication equipment that operates at radio-frequencies, generally below 600 kilohertz, to transmit information over electric power transmission lines. A high frequency signal is superimposed on the normal voltage on a power circuit. The power line carrier is usually coupled to the power line by means of a coupling capacitor in conjunction with a line trap. A device for producing radio-frequency power for transmission on power lines.
  • 43. Figure 1. Power-line carrier schematic Figure 2. Power-line carrier device in control house Power Transformers Power transformers raise or lower the voltage as needed to serve the transmission or distribution circuits. Figure 3. Power Transformer, front view Figure 1. Power transformer, back view
  • 44. Figure 2. Large power transformers Figure 4. Step-up transformer diagram Rectifiers A rectifier is a device used to convert alternating current to direct current. Figure 1. Full wave rectifier circuit diagram Figure 2. Rectifier
  • 45. Relays A relay is a low-powered device used to activate a high-powered device. Relays are used to trigger circuit breakers and other switches in substations and transmission and distribution systems. Figure 1. Substation control panel relays Figure 2. Relay and control panel SF6 Circuit Breakers SF6 circuit breakers operate to switch electric circuits and equipment in and out of the system. These circuit breakers are filled with compressed sulfur-hexafluoride gas which acts to open and close the switch contacts. The gas also interrupts the current flow when the contacts are open.
  • 46. Figure 1. SF6 gas power circuit breaker Figure 2. SF6 gas power circuit breaker Shunt Reactors Shunt reactors are used in an extra high-voltage substation to neutralize inductive reactance in long EHV transmission lines. The photo shows an installation of both an older version and a newer version of the reactor. Figure 1. Shunt reactors in a substation Steel Superstructures Steel superstructures are used to support equipment, lines, and switches in substations as
  • 47. well as transmission and distribution line towers and poles. Figure 1. Steel superstructure for circuit breakers Figure 2. Substation with many steel superstructures for equipment and connection supports Supervisory Control Supervisory control refers to equipment that allows for remote control of a substation's functions from a system control center or other point of control. Supervisory control can be used to:
  • 48. operate circuit breakers,  operate tap changers on power transformers,  supervise the position and condition of equipment, and  telemeter the quantity of energy in a circuit or in substation equipment. Figure 1. Supervisory control room Figure 2. Supervisory control panel Suspension Insulators An insulator type usually made of porcelain that can be stacked in a string and hangs from a cross arm on a tower or pole and supports the line conductor. Suspension insulators are used for very high voltage systems when it is not practical or safe to use other types of insulators. They have an advantage in that one or more of the insulators in a string can be changed out without replacing the entire string. Figure 1. Suspension insulators
  • 49. Figure 2. Suspension insulators Figure 3. Suspension insulators Synchronous Condensers A synchronous condenser is a synchronous machine running without mechanical load and supplying or absorbing reactive power to or from a power system. Also called a synchronous capacitor, synchronous compensator or rotating machinery. In November 1995, the first static synchronous compensator began operating at a TVA substation in Knoxville, Tennessee. This compensator can regulate voltage without expensive external capacitors or reactors. Figure 1. Synchronous condenser Transmission Bus
  • 50. Transmission buses are steel structure arrays of switches used to route power into a substation. Figure 1. Transmission bus Figure 2. Transmission bus from inside Vacuum Circuit Breakers A circuit breaker is a device used to complete, maintain, and interrupt currents flowing in a circuit under normal or faulted conditions. A vacuum circuit breaker utilizes a vacuum to extinguish arcing when the circuit breaker is opened and to act as a dielectric to insulate the contacts after the arc is interrupted. One type of circuit breaker is called a recloser. A vacuum recloser is designed to interrupt and reclose an AC current circuit automatically, and can be designed to cycle a set number of times before it must be reset manually.
  • 51. Figure 1. Vacuum circuit breaker, inside Figure 2. Vacuum circuit breaker, outside Transformer Vault A transformer vault is a structure or room in which power transformers, network protectors, voltage regulators, circuit breakers, meters, etc. are housed. Figure 1. An underground transformer vault Transformer - Underground An underground transformer is essentially the same as an aboveground transformer, but is constructed for the particular needs of underground installation. Vault type, pad-mounted, submersible, and direct-buried transformers are used in underground systems. Pad-mounted transformers are installed on a concrete pad on the surface near the end-user.
  • 52. Figure 1. Pad-mounted transformer for underground system Figure 2. Transformer in underground vault DISTRIBUTION Distribution Feeder Circuits Distribution feeder circuits are the connections between the output terminals of a distribution substation and the input terminals of primary circuits. The distribution feeder circuit conductors leave the substation from a circuit breaker or circuit recloser via underground cables, called substation exit cables. The underground cables connect to a nearby overhead primary circuit outside the substation. This eliminates multiple circuits on the poles adjacent to the substations thereby improving the overall appearance of the substation. Several distribution feeder circuits can leave a substation extending in different directions to serve customers. The underground cables are connected to the primary circuit via a nearby riser pole. The distribution feeder bay routes power from the substation to the distribution primary feeder circuits. In the photo of the distribution main feeder the primary circuit is fed underground to a nearby distribution system overhead line. The yellow cables are the primary feeder lines going underground.
  • 53. Figure 1. 3-phase distribution feeder bay Figure 3. Distribution feeder recloser Figure 2. Distribution main feeder Distribution Transformers Distribution transformers reduce the voltage of the primary circuit to the voltage required by customers. This voltage varies and is usually:  120/240 volts single phase for residential customers,  480Y/277 or 208Y/120 for commercial or light industry customers. Three-phase pad mounted transformers are used with an underground primary circuit and three single-phase pole type transformers for overhead service. Network service can be provided for areas with large concentrations of businesses. These are usually transformers installed in an underground vault. Power is then sent via underground cables to the separate customers.
  • 54. Figure 3. Residential distribution transformer Figure 1. Air Distribution transformer - commercial facility Figure 2. Industrial facility distribution Figure 4. Pad-mounted residential distribution transformer transformer Primary Circuits Primary circuits are the distribution circuits that carry power from substations to local load areas. They are also called express feeders or distribution main feeders. The distribution feeder bay routes power from the substation to the distribution primary feeder circuits. In the photo of the distribution main feeder the primary circuit is fed underground to a nearby distribution system overhead line. The yellow cables are the primary feeder lines going underground.
  • 55. Figure 1. 3phase distribution feeder bay Figure 2. Distribution main feeder Figure 3. Overhead primary feeder Figure 4. Distribution primary feeder underbuild Protective Equipment Protective equipment in a distribution system consists of protective relays, cutout switches, disconnect switches, lightning arresters, and fuses. These work individually or may work in concert to open circuits whenever a short circuit, lightning strikes or other disruptive event occurs. When a circuit breakers opens, the entire distribution circuit is deenergized. Since this can disrupt power to many customers, the distribution system is often designed with many
  • 56. layers of redundancy. Through redundancy, power can be shut off in portions of the system only, but not the entire system, or can be redirected to continue to serve customers. Only in extreme events, or failure of redundant systems, does an entire system become deenergized, shutting off power to large numbers of customers. The redundancy consists of the many fuses and fused cutouts throughout the system that can disable parts of the system but not the entire system. Lightning arresters also act locally to drain off electrical energy from a lightning strike so that the larger circuit breakers are not actuated. Figure 1. Substation bus lightning arresters Figure 4. Pole mounted type - lightning arrester Figure 5. Air-break isolator switch Figure 2. Fused cut-out
  • 57. Figure 6. Non load-break fuse Figure 3. Substation disconnect switch Figure 7. Load-break fuse Secondaries Secondaries are the conductors originating at the low-voltage secondary winding of a distribution transformer for residential service are three-wire single-phase circuits. They extend along the rear lot lines, alleys, or stre customer's premises. The secondaries can be overhead lines or underground lines. Overhead secondary lines are usually strung below the primary lines and typically in a vertical plane. When se strung in a vertical plane, they are directly attached to the support pole one above the other. This is in contra primary lines which are often strung on a cross bar or other attachment in a horizontal or "V" shaped plane.
  • 58. Figure 2. Secondaries in a vertical plane Figure 1. Cabled secondaries Figure 3. Cabled seconda in a "V" plan Services The wires extending from the secondaries or distribution transformer to a customer's location are called a service. A service can be above or below ground. Underground services have a riser connection at the distribution pole. Commercial and residential services are much the same and can be either 120 or 220 or both. Figure 2. Service line to residence Figure 1. Distribution system lines and associated equipment
  • 59. Figure 3. Commercial service Figure 4. Secondary to underground service via a riser Switches Distribution systems have switches installed at strategic locations to redirect or cut-off power flows for load balancing or sectionalizing. Also, this permits repairing of damaged lines or equipment or upgrading work on the system. The many types of switches include:  circuit-breaker switches  single-pole disconnect switches  three-pole group-operated switches  pad-mounted switchgear Figure 2. Air-break isolator switch Figure 1. Air circuit-breaker switches
  • 60. Figure 4. Single-pole disconnect switch combined Figure 3. Circuit switchers with a fuse is called a fused cutout Figure 6. Pad mounted switchgear Figure 5. Circuit breakers
  • 61. Figure 7. Group-operated three-pole air break switch