UPS A
BYPASS LINE INPUT. (MAINTENANCE BYPASS)
BYPASS LINE INPUT. (STATIC SWITCH)
RECTIFIER INVERTER
INPUT
MAINS
STATIC SWITCH
TO
EXTENSION
BATTERY
Mains CABINET CRITCAL
Supply LOAD
UPS B
BYPASS LINE INPUT. (MAINTENANCE BYPASS)
BYPASS LINE INPUT. (STATIC SWITCH)
RECTIFIER INVERTER
INPUT
MAINS
STATIC SWITCH
TO
EXTENSION
BATTERY
CABINET
Bypass
Switch.
200kVA Parallel 2 x100kVA with External Bypass
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
34. ٜاى٘صو اىتفشػٜ اإلدتٞبغ
UPS A
BYPASS LINE INPUT. (MAINTENANCE BYPASS)
BYPASS LINE INPUT. (STATIC SWITCH)
RECTIFIER INVERTER
INPUT
MAINS
STATIC SWITCH
TO
EXTENSION
BATTERY
Mains CABINET
CRITCAL
Supply
LOAD
UPS B
BYPASS LINE INPUT. (MAINTENANCE BYPASS)
BYPASS LINE INPUT. (STATIC SWITCH)
RECTIFIER INVERTER
INPUT
MAINS
STATIC SWITCH
TO
EXTENSION
BATTERY
CABINET
200kVA Parallel Redundant (2 x200kVA) UPS
(No Bypass Required)
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
35. دو ٍشبمو اىقذسح
Power Problem Standby Power TVSS Automatic UPS
Power Conditioner Voltage (online) Dual
System Stabiliser Conversion
Generator (AVS)
Mains Failures
Sags / Brownouts
Surges
Spikes / Transients
High Frequency Noise
Frequency Variation
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
36. اىَختيفخUPS إٍنبّٞبد
On-Line
Power Problem Off-Line Line Interactive
Double Conversion
Mains Failures
Sags / Brownouts
Surges
Spikes / Transients
High Frequency Noise
Harmonic Distortion
Frequency Variation
No Break Change-over
ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
37. StandbyUPS اى٘دذح اإلدتٞبغٞخ
Design and Operation
¥ The simple off-line static UPS has the same configuration as the on-line version, but it only
switches in when it senses a fluctuation or interruption in the power supply. In other words, the
system operates on "bypass" during normal operation.
¥ Lower cost units may not include a voltage regulator in the design.
¥ The simple off-line static system is the least expensive and the least sophisticated UPS on the
market.
¥ It is quiet and relatively compact.
Uses
¥ Most small (<3 kVA) systems currently sold to protect against power interruptions are standby
systems since they are relatively inexpensive. However, great care should be taken to ensure that a
product of this type will provide adequate protection for the given application.
¥ This product is generally used for microcomputer installations, and cash register (point of sale)
applications.
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
¥ It is not often employed on main-frame computers. munthear@gmail.com
38. اىذَبٝبد
Power failures High voltage spikes
Power sags Frequency variations
Power surges Switching transients
Brownouts Harmonic distortion
Line noise
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
39. Each series is designed to fit a different level of power
protection needs and allows you to match your needs
precisely with the appropriate level of power protection.
Series 3
Series 5
Series 9
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
40. COMMUNICATIONS ٗسبئو اإلتصبه
• Remote Indication – LEDs, LCD, mimics
• Modem – Remote interrogation by phone
• FCT (fixed cell terminals) for remote locations.
• 24/7 Monitoring – Service Centre
• Controlled Shutdown & Monitoring Software
• RS 232 – Direct connection to server/PC
• SNMP – Presence on LAN – WWW
• Keep critical servers running longer (load shedding)
• Real time monitoring
• 24/7 Monitoring - email alert, SMS, WAP
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
51. اىَؼبٝٞش
BS EN 62040: UPS Industry standard
• BS EN 62040-1-1:2003 Uninterruptible power systems
(UPS). General and safety requirements for UPS used in
operator access areas
• BS EN 62040-1-2:2003 Uninterruptible power systems
(UPS). General and safety requirements for UPS used in
restricted access locations
• BS EN 62040-3:2001 Uninterruptible power systems (UPS).
Method of specifying the performance and test requirements
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
52. اىَؼبٝٞش
BS EN 62040 replaces the EN50091 standard.
EN50091-1: Uninterruptible Power supply systems; general provisions of safety
EN50091-1-1: Uninterruptible Power supply systems; general provisions of safety used in
areas accessible to operators
EN60950 : ITE Information technology equipment safety
EN50091-2: Uninterruptible Power supply systems (UPS) electromagnetic compatibility
provisions
EN50081-2: Electromagnetic compatibility (immunity)
EN61000-4-2: Immunity: Electro Static Discharge (ESD)
EN61000-4-3: Immunity: Electromagnetic Fields
EN61000-4-4: Immunity: Transient over voltages (BURST)
EN61000-4-5: Immunity: Current surges (Surges)
EN61000-4-11: Low frequency Disturbances
EN50141: Induced radio interference
EN55022: Radio frequency disturbance
ENV50091-3: UPS performance and test provisions
IEC146 : semiconductor electronic converters
IEC529 : degree of protection of casings
European directives
73/23: Low Voltage Directive enforcing CE marking
89/336: electromagnetic compatibility directive enforcing CE marking
53. ت٘صٞبد
Engineering Recommendation G5/4
Planning levels for Harmonic Voltage Distortion and the connection of non-linear
equipment to transmission systems and distribution networks in the United Kingdom
UPS will put Harmonics back on to the mains
6 Pulse Rectifier typical THD of 20-30%
12 Pulse rectifier typical THD less than 8%.
Filters are required to give a THD less than 5%.
Active or Passive.
G5/4 States-
If load draws more than 16A / phase an assessment should be made.
If in Doubt - Ask the UPS Manufacturer.
Remember the Building should comply with the standard not just the UPS
- ٛاىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدس
munthear@gmail.com
54. الشروط الفنية لنظام تغذية كهربائية عدمية االنقطاع
UPS
• استطاعة النظام KVA
يعمل النظام بطريقة TRUE ON-LINEبدون أى زمن انقطاع . •
وثوقية عالية،جيب ذكر . MTBF •
املطابقة مع املقاييس والعايري ..…,ISO,DIN,VDE,IEC •
توفر امكانية الربط التفرعى احلقيقي لوحدات ال ٍ UPSغ ثؼعٖب. •
العمل عند درجات حرارة من 0 حىت 04 دسجخ ٍئ٘ٝخ ػْذ اىذَو اىنبٍو ٗ ىضٍِ •
غٞش ٍذذٗد .
العمل عند درجة رطوبة %59 غري متكاثف وحتديد املدة . •
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
55. مستوى الضجيج ال يزيد عن 60 dBAػيٚ ثؼذ ٍتش ٗادذ. •
الحجم و الوزن اقل ما يمكن . •
يتعهد العارض بتقدم كافة كات التشغيل والخدمة و الصيانة و االصالح.
كتالو •
يتعهد العارض بتقديم وثائق رسمية تبين مكان الصنع و شهادات جودة لل ٗ UPS •
ىيَذخشاد .
أعمال كيب والتوصيل بالشكل النظامي, بحيث تكون األحمال موزعة و متوازنة
التر •
بشكل صحيح.
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
56. يجب على العارض القيام بأعمال التأريض الصحيح ( قياس •
التأريض على عاتق المتعهد) و كل ما يلزم للحصول على أداء
ممتاز لوحدات التغذية المعنية .
ضرورة التعرف على طبيعة األحمال ونظام التوزيع الكهربائية •
الموجود .
الضمانة المجانية لمدة سنة على األقل ،تبدأ بعد وضع النظام •
بالخدمة الفعلية
يوضح العارض إمكانية الصيانة عن بعد عن طريق خط الهاتف . •
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
57. • يقدم العارض عرض فنى يوضح فيو خدمات الصيانة وعرض مالي
كنسبة من العرض المالى االجمالى لصيانة النظام لمدة خمسة
سنوات.
• يقدم العارض الئحة مسعرة بقطع التبديل التى يراىا ضرورية من
خالل خبرتو في الصيانة .
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
58. RECTEFIERاملقوم
يحول الشاحن التيار المتناوب القادم من الشبكة إلى تيار مستمر الذي بدوره يقوم بتغذية •
المعرج والمدخرات معا" .
جهد الدخل :ثالثي الطور 083(-02%,+01%) فولت . •
تردد الدخل :05 ىرتز -+01% •
يعمل بطريقة الشحن العائم . FLOAT CHARGE •
يجب أن يكون الجهاز محمي من حاالت ارتفاع الجهد العابرة و التي قد تصل إلى 6 •
كيلو فولت.
الحماية السابقة متوفرة على جميع الخطوط (الفازات والنتر واالرضي) . •
مزود بمرشح RFو EMIفي المدخل . •
يفضل وجود عزل غلفاني للشبكة الكهربائية . •
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
59. INVERTERج
املعر
جهد الخرج :ثالثي الطور + حيادي + أرضي ,083 فولت بخطأ ال يتجاوز 1 % في •
الحالة المستقرة و%3 في الحالة الديناميكية.
تردد الخرج : 05 هرتس +- 100.0 هرتس (, )FREE RUNNING •
شكل موجة الخرج : جيبية نقية . •
يفضل أن ال يتجاوز التشوه االجمالي 2% بالنسبة للحمل الخطي و 4% بالنسبة •
للحمل الالخطي .
زمن عمل البطاريات : 01 دقيقة عند الحمل االعظمي . •
المردود(الكفاءة) : يجب ان ال يقل عن 39 % . •
CREST FACTORهعاهل التحويل النبضي :يجب أن ال يقل عن 3 . •
قابلية تجاوز الحمل : زيادة الحمل بمقدار 051 % لمدة دقيقة واحدة على األقل و •
521% لمدة عشرة دقائق على األقل. زيادة بمقدار 0002% على األقل بالنسبة
للممر اآللي .
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
60. املمر االيل
AUTOMATIC BYPASS
• يستخدم لتغذية الحمل مباشرة وبشكل الي من الشبكة الكهربائية
من دون حدوث انقطاع في التغذية . وذلك في حاالت زيادة
الحمل OVER LOA Dأو حدوث خلل في نظام ال . UPS
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ -
munthear@gmail.com
61. املمر اليدوي
MANUAL BYPASS
• يعمل يدويا.
• يستخدم لتغذية االحمال أثناء فترات الصيانة .
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ
ٍْmunthear@gmail.comزس اىقبدسٛ -
62. املدخرات BATTERY
المدخرات من النوع الحمضي LEAD-ACIDالجافة المغلقة التي ال تحتاج صيانة . •
ذات عمر طويل ال يقل عن 5 سنوات . •
سعة المدخرات كافية لعمل الجهاز لمدة عشرة دقائق عند الحمل االسمي . •
يجب على العارض ذكر نوع المدخرة واسم كة المصنعة ومكان الصنع وتاريخ االنتاج باالضافة الى
الشر •
عددىا وسعتها .
اىَشمض اىؼشثٜ ىيتذسٝت - اىذمت٘س اىَْٖذط ٍذَذ ٍْزس اىقبدسٛ
-munthear@gmail.com
63. وحدات االظهار والمراقبة
DISPLAY AND MONITORING
• يزود النظام بمنبهات سمعية و مرئية لبيان عمل الجهاز اضافة الى التنبيو عن االعطال
مثل زيادة الحمولة وارتفاع درجة الحرارة وانخفاض جهد المدخرات
• يزود الجهاز بلوحة الكترونية للتحكم لشاشة اظهار تسمح بمراقبة ما يلي :
حالة عمل الجهاز.
زمن عمل المدخرات
توتر الخرج
توتر الدخل
تردد الدخل
تردد الخرج
جهد المدخرات
سجل االعطال .