NetSure™
ITM with eSure™
Technology
Row-based, Scalable 48V DC UPS
DC Power
For Business-Critical Continuity™
2
Without
Energy Optimization
With
Energy Optimization
SystemEfficiency
Improvement
10%
84%
86%
88%
92%
90%
94%
98%
96%
20% 30% 40% 50% 60% 70% 80% 90% 100%
SystemEfficiency*
Load
*System efficiency includes AC to DC power conversion and internal distribution losses.
Rising power density, rapid and unpredictable growth,
escalating energy consumption and cost, plus a myriad of
other power-related challenges are making it increasingly
complicated and expensive to protect critical network
and computing equipment. The NetSure™
ITM integrates
DC UPS components into a compact, highly reliable
power protection system, offering the answer to your
current and future 48V power needs. This three-phase
480V AC input, 48V DC output UPS provides highly
available power to a wide variety of IT applications and
delivers advanced operating features combined with
reduced total cost of ownership.
The NetSure™
ITM is designed for deployment directly on
the server room floor, and provides protected 48V power to nearby equipment racks. This
preserves the efficiency and reliability benefits of DC power, while minimizing the amount
of copper required and enabling modular growth.
The NetSure™
ITM lowers the cost of
data center design, operation and
management. This 48V direct current
solution is a row-based DC UPS that
delivers simple, scalable and highly
efficient power protection.
A Complete Power Protection SolutionFeatures & Benefits
	 High system efficiency: Reduced power
conversion stages combined with 96%
efficient eSure™
power conversion units
(PCUs) and an advanced energy
optimization mode enable significant
energy savings even at low loads.
	 Scalability and ease of deployment:
Minimize your initial investment and avoid
stranded power by adding expansion DC
UPS modules without interruption in the
field as power needs increase.
	 DC architecture simplicity: Fewer
components,conversionstagesand
distributionbreakersthroughoutthepower
chainensurehighavailability;eliminationof
complexsynchronizationcircuitsandthe
needtode-ratecapacityforphasebalancing
orharmonicsmakesiteasytoengineer.
	 High reliability and exceptional resiliency:
Uninterrupted operation in the unlikely
event of multiple component failures.
	 Ease of maintenance: Field replaceable,
hot swappable PCUs allow rapid replace-
ment without critical bus disruption; low
voltage allows maintenance without
bypass or shutdown.
	 Compact footprint: Row-based, integrated
design saves considerable facility space by
eliminating the need for a dedicated power
room and separate PDU distribution.
	 Flexible deployment options: Top or
bottom cable entry allows for raised or
non-raised floor installations.
	 Advanced control and monitoring: Real
time input and output monitoring,
including power quality and consumption
data, enables facility planning for the
system and each branch circuit; state-of-
the-art battery monitoring with Albér
technology to assure optimal backup
performance.
	 One-year warranty: Provides full system
coverage for one year.
NetSure™
ITM DC UPS Module
Top-Cabled Configuration
Figure 1: NetSure™
ITM System Efficiency
Efficiency Without Compromise™
provides a path to optimize data center infrastructure
around design, operating and management efficiencies –
while maintaining or improving availability. This is
achieved through the proper selection and utilization of
cooling, power and monitoring technologies, supported
by key services and local expertise.
3
Lower Total Cost of Ownership
DC power is often associated with
telecommunications where it has
delivered extremely high reliability for
decades. Since DC power is both
provided by backup power sources
and consumed by electronic
equipment, a DC power architecture
minimizes conversion stages from grid
to chip, thus enabling higher overall
efficiency with increased availability.
	 Factory integrated system for fast and
easy site installation
	 Service or expansion can be performed
while the DC UPS is in operation,
reducing maintenance costs
	 Compact footprint with built-in
batteries and distribution, minimizes
required floor space
	 Designed for scalable growth to
postpone additional capex until
capacity is needed
	 Energy Optimization Mode
Intelligent Power Matching [Figure 1]
•	 Achieves near-peak UPS
efficiency down to 5% system
load by optimizing individual
PCU performance, greatly
reducing energy costs over
time in real world conditions
•	 Matches delivered power
from the UPS to real-time
demand, keeping a minimum
of PCUs active and putting
the rest on standby
•	 Balances the run time of each
PCU by rotating the active and
standby units
•	 Maintains the ability to
respond quickly to changing
load conditions
Unmatched Availability
Resilient design
	 System bus charges batteries and
distributes power directly to the server
rack without additional switching or
conversions
	 65k AIC withstand rating on AC
input breaker(s)
	 Controller outage does not interrupt
power delivery to the critical load and is
field replaceable without system outage
Battery monitoring technology from Albér
	 Detects failing battery cells before
they affect the critical load
	 Checks each cell and associated
connections via a proactive, patented
resistance test to reliably predict
battery performance
	 Provides early warning of cell
problems without frequent discharge
tests or battery degradation; mini-
mum technician visits with maximum
run time protection
	 Systemcontrollerstoresrawdata
accessibleviawebpageorexternal
monitoringsystem
Central to a data center’s strength is its overall uptime. To maintain business continuity,
power systems must exhibit high availability and easily scale for increasing capacity.
NetSure™
rectifiers or power conversion units (PCUs) are the heart of the NetSure™
ITM DC
UPS. Each DC UPS module includes twelve independent 5.8kW PCUs. These PCUs are globally
renowned with over 2 million units deployed, offering unmatched reliability with less than
0.5% return rate (200 years MTBF). The NetSure™
ITM provides many robust features to create
a highly redundant package that minimizes single points of failure. 
Proven power conversion topology
	 Each PCU delivers conditioned,
isolated power to a common
distribution bus
	 PCUs function in parallel for seamless
redundancy without switching
	 Units are hot swappable in the field
without system adjustment;
minimum field repair time (MTTR)
increases overall uptime
Redundant configuration
	 Redundancy can be achieved both
within a DC UPS module by PCU (N+x),
and by complete system (2N)
	 Internal power distribution through
(22) branch circuit breakers allows
redundant A+B power paths to each
rack
	 Battery backup via three parallel
battery strings
	 Optional dual AC inputs allow
upstream switchgear maintenance
without system outage
NetSure™
ITM delivers Efficiency Without Compromise™
INFRASTRUCTURE
MANAGEMENT
Improving performance
of the IT infrastructure
and environment
ECO AVAILABILITY
Balancing high levels of
availability and efficiency
FLEX CAPACITY
Adapting to IT changes for
continuous optimization
and design flexibility
HIGH DENSITY
Delivering architectures
from 10–60 kW/Rack to
minimize space and cost
The NetSure™
ITM solution is a modular system in 70 kW increments,
expandable up to 280 kW (4 DC UPS modules) with one controller.
Flexibility to Meet the Needs of Any Data Center
Flexible Capacity
	 Each integrated DC UPS module occupies
only 24 (W) x 41 (D) of floor space,
including batteries and primary distribution
	 Delivered fully configured for quick and
easy field installation
	 Typically installed in either the middle or at
the end of a row of server racks
	 Deploy only the capacity that is initially
needed; DC UPS modules can be added at
any time to row configurations on the data
center floor
	 Choose from top and bottom cabled
variants for installation in either concrete
or raised floor environments
As Figure 2 illustrates, the NetSure™
ITM
solution starts with a primary DC UPS
module rated for 70kW. As your power
needs increase, you can add up to three
expansion DC UPS modules, for a maximum
capacity of 280kW that may be configured
for N+1 redundancy by subtracting one 6kW
PCU from the rating. Each DC UPS module
also includes 48V primary power distribution
with 22 circuit breakers (6 fuses optional).
Various server rack densities are supported
with 5-10 minutes of battery backup time
across three parallel 48V battery strings.
70kW (64kW N+1)
140kW (134kW N+1)
210kW (204kW N+1)
280kW (274kW N+1)
Figure 2: System Scalability
Figure 2: Primary DC UPS module with 3 expansion modules (top-cabled configuration shown)
Install only the capacity required; link up to four DC UPS modules to one controller 
Figure 3 depicts two top-cable installation
scenarios. Depending on your site and
budget requirements, the NetSure™
ITM
solution can either be installed as a single
deployment [Figure 3a], or incrementally by
row [Figure 3b] as power requirements grow.
In either scenario, DC distribution cabling to
each rack is reduced by placing the NetSure™
ITM in-the-row.
Both AC and DC loads can be accommodated
at the same site. AC loads can either be
protected by an AC UPS or via a rack-mount
DC to AC inverter fed from the DC UPS, both
available from your local Emerson Network
Power representative.
4
Whatever the physical layout of your data center, 
the NetSure™
ITM minimizes required floor space. With DC UPS
building block modules, you can mix and match configurations
and standard layouts to fit your available space.
Figure 3a: 140kW initial deployment
Two DC UPS modules power blade server racks
Figure 3b: 70kW initial deployment (front row) 
Add DC UPS and server capacity as needed (back row)
Figure 3: NetSure™
ITM Row-Based Installation Examples Ideal Applications for Reliable,
Scalable 48V DC Power:
	 New and expanding small to medium
data centers
	 High-density, scalable blade deployments
	 Predesigned pods and clusters
	 Facilities with constrained power and limited
power room space
	 Facilities without a dedicated power room
	 New deployments with unpredictable
growth and limited initial investment
	 Applications combining servers and
networking equipment (VoIP, PoE, etc.)
	 Network testing labs
5
The NetSure™
ITM easily compliments existing AC power systems, whether
you are planning a new facility or expanding an existing data center.
Components of the NetSure™
ITM DC  Power System
Each NetSure™
ITM DC UPS module consists of twelve 5.8 kW power conversion units (PCUs),
an advanced controller, three strings of 6V long-life VRLA battery cells, and 48V DC branch
distribution to feed each server rack. In addition to comprehensive efficiency and power
metrics, the advanced controller provides complete system and battery monitoring. Further-
more, power to each output circuit is individually monitored. Batteries and your choice of
output distribution are integrated into the system prior to shipment from the factory for
simplified site installation.
Excellence EB4 VRLA BatteryNetSure™
System Controller ACU+eSure™
High-Efficiency Power Conversion Unit
6
Energy Optimization and
Comprehensive Monitoring
All NetSure™
ITM DC UPS modules are
controlled and monitored by the Advanced
Control Unit (ACU+). Critical system
functions and operational conditions as well
as alarms can be viewed both locally via LCD
display and remotely via a secure web
interface, Liebert®
SiteScan™
or
EnergyMaster™
Remote Supervision.
Essential system metrics and alarms are
continuously monitored:
	 System input and output details
	 Battery state of health
	 DC output branch distribution circuits
VRLA Batteries
The system features three strings of 6V
VRLA batteries from Emerson. The
Excellence series battery is a top-of-the-
line front terminal battery that is designed
for reliable and efficient operation with a
long life expectancy. High energy density
combined with superior endurance ensures
long-term, trouble-free performance.
Designed for small areas, the Excellence
series consumes less rack space and
facilitates easy installation and handling.
This battery is rated for 10 years at 25°C and
includes a 3 year full warranty.
Power Conversion
Units (PCUs)
Designed for best-in-class efficiency
(96%) and high power density, the
foundation of the NetSure™
ITM
is the modular 3-phase input PCUs.
Installation and maintenance is easy
with plug-and-play functionality and a
weight of only 17.6 lbs (8 kg). The PCU
also features a low THD level (5%).
SiteWeb™
BRC
AC
DC
AC
DC
A B A B A B A B
AC
DC
AC
DC
48VDC
Output
48VDC
Output
48VDC
Output
48VDC
Output
AC
DC
AC
DC
AC
DC
AC
DC
1
12
13
24
25
36
37
48
1 22 23 44 45 66 67
(3strings)(3strings)(3strings)(3strings)
88
One-line diagram for a four DC UPS module system shown with
circuit breaker output and dual AC input.
Figure 4: NetSure™
ITM Internal Schematic
7
SiteWeb™
BRC
with Albér®
Technology
Industry leading battery monitoring technology from
Albér provides detailed information and alarms regarding
the battery backup condition that will minimize site visits
and maintenance. The functionality of the SiteWeb™
BRC
is integrated with the system controller to continuously
monitor and test the battery backup system at the cell or
block level without affecting battery performance. It
measures cell internal resistance, intercell resistance, cell
voltages, battery current and temperature. The informa-
tion and alarms can be viewed via a web browser or
connected to Liebert SiteScan™
or EnergyMaster™
Remote Supervision for long term trending and analysis.
1	 AC input wiring
(top or bottom)
2	 Power Conversion Unit
(12 x 5833W)
3	 ACU+ controller
4	 480V AC input breaker
5	 AC connection point
	 6	 Battery fuses
	 7	 48V DC output distribution –
22x100-200A breakers (shown);
2x500A + 4x200A fuses (optional)
	 8	 Battery cooling fans
	 9	 Integrated battery compartment;
(3) strings VRLA batteries
2
3
4
7
7
5
1
1
6
NetSure™
ITM Front View
(bottom-cabled version shown
with front covers removed)
NetSure™
ITM Rear View
(rear cover removed)
9
8
Rack-Mount Server Applications Blade Server or High Capacity
Switch Applications
8
Easy Zero Rack Unit Power Distribution
Featuring plug-and-play connectors for simple field connections, NetSure™
RDB
48V Rack Distribution Units are designed to complete your NetSure™
ITM Solution.
Space Saving Design
When it’s time to deploy DC power
in your rack, a zero U, rear mount
configuration keeps the most rack
space available for your revenue
generating equipment.
Robust, tool-less, easy to use
The NetSure™
RDB Series of rack PDUs
is designed to handle up to an 8.6 kW
load and provisioned to optimize the
wire size required to each device.
The result is a system that is easy to
pre-configure and manage long term.
Because of the plug-and-play connec-
tivity, no special tools or expertise
are needed to maintain or move your
IT equipment.
	 Quick input connectors facilitate
easy installation and allow for
tool-less field adjustments as layouts
or requirements change
	 Each outlet is individually
protected by a circuit breaker
	 Breaker trip notification
for added convenience when
troubleshooting outages
	 Versatile PDU mounting options
permit installation in any orientation
NetSure™
RDB Series Models
High Power Distribution
(50-80A output breakers)
2  3 outlet configurations
Medium Power Distribution
(25-35A output breakers)
6 outlet configuration
Low Power Distribution
(10-20A output breakers)
6  15 outlet configurations 
NetSure™
RDB M6
NetSure™
RDB H2
NetSure™
RDB H3
NetSure™
RDB L15
NetSure™
RDB L6
9
Trust the service and support of your
NetSure™
ITM system to the experts at
Emerson Network Power. Our services are
offered by technical professionals who
have, on average, more than a decade of
field experience with DC and network
equipment. On the rare occasion that
service is required, our technicians can be
at your site within hours and are backed by
an entire organization ready to help
resolve any issues.
We offer a complete suite of services to
optimize and maintain the operation of
your NetSure™
ITM solution throughout
its life cycle.
Startup
We know the risks that improper system
configuration can pose to your equipment
and business. That’s why, even if a third-party
has installed your system, you can depend on
us to perform site testing and verification. We
will provide testing and verification of the DC
UPS, including PCUs, batteries and control
points, to ensure problems are identified
before they occur.
Technical Support
Remote support provides an immediate
interface with experienced technical experts
24hours a day to help resolve unexpected
systemincidents and support you in operating
andmanaging your DC UPS.
Preventive Maintenance
Our preventive maintenance programs
will ensure your NetSure™
ITM runs at
peak system availability and establishes a
predictable maintenance budget protect-
ed from costly emergency repairs. Periodic
inspections identify problems before they
occur and maintain maximum operating
efficiency. This DC UPS service plan
provides a clear picture of system status
and recommendations for corrective
steps to prevent future problems. Various
scopes of work that cover PCUs, batteries
(including capacity testing), and DC
distribution are available.
Available exclusively to Emerson Network
Power preventive maintenance customers,
our secure customer website, Freedom-
Care, gives you the capability to view
and download service and maintenance
visit reports.
EnergyMaster™
Remote Supervision
EnergyMaster™
assessment and remote
supervision solutions provide an integrated
approach to managing the energy and
health of network infrastructures.
Emerson experts optimize power consum-
ing equipment for maximum energy
savings and provide consistent network
reliability through remote supervision
routines that reduce maintenance costs.
Field Service
On-site field engineers are available for
scheduled equipment replacement,
emergency on-site technical trouble-
shooting or system field upgrades.
Training
Courses, offered on-site or in our
training center, provide knowledge in
the operation, control, troubleshooting
and maintenance of the NetSure™
ITM.
Design and Installation
We offer industry-leading experience and
resources to expertly design your DC UPS
and 48V DC distribution system. Our field
installation team is available throughout
North America to provide local knowledge
and quick response to project require-
ments. Installation services offer a variety
of options to ensure the project is
completed and tested as per agreed
upon engineering specifications.
A Life Cycle of Expert Service and Support
DEPL
OYMENT
DESIG
N
Critical
Infrastructure
Lifecycle
O
PTIMIZATION
10
NetSure™
ITM – Technical Specifications
DC UPS Primary Module 1 Expansion Module 2 Expansion Module 3 Expansion Module 4
Power Rating (full) – kW 70 70 70 70
Power Rating (N +1) – kW 64 70 70 70
AC Input Specifications
Phase 3
Power Factor 0.99 at full load, 0.97 at 50% load
Frequency – Hz 45-65
Input Voltage – Nominal 400 / 480V, 3 wire + ground
Input Voltage – Range 304-530 VAC; shall withstand up to 600 VAC input without damage.
Input Breaker Rating / AIC Rating – A 150 / 65,000
Max Input Current / DC UPS Module 480V: 111A @ 384V; 89A @ 480V
400V: 133A @ 320V; 107A @ 400V
380V: 140A @ 304V; 112A @ 380V
Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value
Total Harmonic Distortion 5% from 50-100% of load
DC Output Specifications
Voltage Nominal: -48VDC; normal operation: -54.5 VDC (battery float)
Range: -42 to -58 VDC
System Efficiency 96% peak; 95.5% from 40-100% load (system level including branch distribution losses)
Energy Optimization Mode: Intelligent Power Matching Allows operation at near-peak efficiency down to 5% overall load
Branch Distribution Options 22 circuit breakers, 100-200A each; optional: 6 fuses, 2x500A + 4x200A
Battery Specification
Type VRLA, Emerson Excellence EB4, 200 Ah
Arrangement 3 strings; eight 6V blocks per string
Backup Time See backup time table at various loads
Design Life 15 years @ 20 °C ; 10 years @ 25 °C
Recharge Time (to 97% of nominal capacity) Less than 3 hours for  35% load; Less than 4 hours  15% load
Physical Data
Form Factor Rack
Installed Dimensions (H x W x D) – in. (mm) 85 x 24 x 41 (2150 x 600 x 1050)
Installed Weight – lb. (kg) 2925 (1325)
Environmental Specifications
System Operating Temp. – °F (°C) -5 °C to +35 °C; recommended operation with battery: 20 °C to 25 °C air inlet
System Storage Temp. – °F (°C) -40 to 158 °F (-40 °C to +70 °C)
Relative Humidity 0 to 95%, non condensing
Operating Elevation – ft. (m) 6562 (2000) at full power
Audible Noise  62dB
Heat Rejection at Full Load – BTU/hr. (kW) 9,554 (2.8) per DC UPS module
EMI FCC class A
Safety Certifications
Agency Approved CE Marked to EN 60 950-1:2006
UL Listed to 60 950-1 + UL 1801; CSA certified
Monitoring Capability
Standard Web-based monitoring, alarm reporting via SNMP, and integration with SiteScan via SiteLink-E module
Optional Energy Master Remote Supervision
11
eSure™
PCU (R48-6000Ne) – Technical Specifications
DC Output
Output Power 5833W maximum
Regulation Steady state output voltage remains within +/-0.25% for any combination of input voltage from 5% to 100% load
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 100 mv rms per Telcordia GR-947-CORE
Psophometric Noise Does not exceed 1 mv from 10% to 100% load
Protection
Current Limiting The output current is limited to 110 amps
Over Current Internal fuse
Physical Characteristics
Mounting Plug-in installation, hot swappable
Dimensions (H x W x D) – in. (mm) 3.36 x 8.83 x 14.62 (85.5 x 224.5 x 371.5)
Weight – lb. (kg) 22 (10)
Peace of mind. It’s confidence you’ve done everything possible to assure system
uptime. It’s confidence the DC UPS you rely on is operating at peak performance.
It’s confidence you’ve selected the best partner available to sustain your critical
network infrastructure. That is Emerson Network Power.
Battery Back-up Time (minutes)
DC UPS
Load
Single module
70kW
Two modules
140kW
Three modules
210kW
Four modules
280kW
10kW 130 300 480 630
20kW 55 130 210 300
30kW 28 90 130 180
40kW 17 55 90 130
50kW 12 41 70 100
64kW 7 24 50 75
70kW 3 21 43 69
80kW 17 34 55
90kW 14 27 47
100kW 12 22 40
110kW 10 19 34
120kW 8 17 28
134kW 6 16 25
140kW 3 14 22
150kW 12 19
160kW 10 17
170kW 9 15
180kW 8 14
190kW 7 13
204kW 4 11
210kW 2 10
220kW 9
230kW 9
240kW 8
250kW 7
260kW 6
274kW 3
280kW 1
© 2012 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.
Emerson Network Power
Energy Systems, North America
4350 Weaver Parkway, Warrenville, IL 60555
Toll Free: +1 800 800 1280 (USA and Canada)
Telephone: +1 440 246 6999 Fax: +1 440 246 4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: EmersonEnergy.com
Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering
together to provide innovative solutions for customers in industrial, commercial, and consumer markets through its
network power, process management, industrial automation, climate technologies, and tools and storage businesses.
For more information, visit: Emerson.com.
Emerson Network Power, a business of Emerson (NYSE:EMR), maximizes reliability, deployment speed and operational
efficiency for communications networks. A trusted industry leader in smart infrastructure technologies, Emerson
Network Power provides innovative, rapidly deployable solutions that deliver efficiency and uncompromised reliability
regardless of network demands. Our solutions are supported globally by local Emerson Network Power service techni-
cians. Learn more about Emerson Network Power products and services at:
EmersonNetworkPower.com/EnergySystems.
Learn more about the NetSure™
ITM DC UPS from Emerson at: EmersonNetworkPower.com/NetSureITM.
This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing) may not be
used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or services concerned. Emerson
Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or conditions of supply of any product or service.
Emerson®
, Emerson Network Power™
, Business-Critical Continuity™
, Efficiency Without Compromise™
, Albér®
, EnergyMaster™
, eSure™
, Liebert®
, NetSure™
, SiteScan™
and
SiteWeb™
are trademarks of Emerson Electric Co. and/or one of its subsidiaries.
Code: 100B-NSITM / 0212
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
.
AC Power
Connectivity
Infrastructure Management  Monitoring Precision Cooling
Racks  Integrated CabinetsOutside Plant
ServicesDC Power Power Switching  Controls
Embedded Computing
Embedded Power
Industrial Power
EmersonNetworkPower.com

Mais conteúdo relacionado

Mais procurados

Hacking the Conventional Data Center Infrastructure
Hacking the Conventional  Data Center InfrastructureHacking the Conventional  Data Center Infrastructure
Hacking the Conventional Data Center InfrastructureSchneider Electric
 
A New Language for Specifying Modular Data Centers
A New Language for Specifying Modular Data CentersA New Language for Specifying Modular Data Centers
A New Language for Specifying Modular Data CentersSchneider Electric
 
Wireless monitoring and control for smart grid and home appliances
Wireless monitoring and control for smart grid and home appliancesWireless monitoring and control for smart grid and home appliances
Wireless monitoring and control for smart grid and home appliancesUmayal Saravana Selvan
 
What is a data center
What is a data centerWhat is a data center
What is a data centerLivin Jose
 
Ni project presentation version 3
Ni project presentation version 3Ni project presentation version 3
Ni project presentation version 3Ahmed Zahid
 
Smart Power Grid Monitoring System
Smart Power Grid Monitoring SystemSmart Power Grid Monitoring System
Smart Power Grid Monitoring SystemImane Haf
 
Analysis optimization and monitoring system
Analysis optimization and monitoring system Analysis optimization and monitoring system
Analysis optimization and monitoring system slmnsvn
 
Eco-mode: Benefits and Risks of Energy-saving Modes of UPS Operation
Eco-mode: Benefits and Risks of Energy-saving Modes of UPS OperationEco-mode: Benefits and Risks of Energy-saving Modes of UPS Operation
Eco-mode: Benefits and Risks of Energy-saving Modes of UPS OperationSchneider Electric India
 
Multi string PV array
Multi string PV arrayMulti string PV array
Multi string PV arrayNIT MEGHALAYA
 
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...Schneider Electric
 
WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)Vikram Purohit
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET Journal
 
Load Shedding Management
Load Shedding ManagementLoad Shedding Management
Load Shedding Managementijtsrd
 
DISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRID
DISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRIDDISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRID
DISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRIDNIT MEGHALAYA
 

Mais procurados (20)

Hacking the Conventional Data Center Infrastructure
Hacking the Conventional  Data Center InfrastructureHacking the Conventional  Data Center Infrastructure
Hacking the Conventional Data Center Infrastructure
 
Related standards and specifications for the smart grid Class-20
Related standards and specifications for the smart grid Class-20Related standards and specifications for the smart grid Class-20
Related standards and specifications for the smart grid Class-20
 
A New Language for Specifying Modular Data Centers
A New Language for Specifying Modular Data CentersA New Language for Specifying Modular Data Centers
A New Language for Specifying Modular Data Centers
 
Wireless monitoring and control for smart grid and home appliances
Wireless monitoring and control for smart grid and home appliancesWireless monitoring and control for smart grid and home appliances
Wireless monitoring and control for smart grid and home appliances
 
Gemini_3__3008_web
Gemini_3__3008_webGemini_3__3008_web
Gemini_3__3008_web
 
What is a data center
What is a data centerWhat is a data center
What is a data center
 
Ni project presentation version 3
Ni project presentation version 3Ni project presentation version 3
Ni project presentation version 3
 
Smart Power Grid Monitoring System
Smart Power Grid Monitoring SystemSmart Power Grid Monitoring System
Smart Power Grid Monitoring System
 
Tactical Solar
Tactical SolarTactical Solar
Tactical Solar
 
Analysis optimization and monitoring system
Analysis optimization and monitoring system Analysis optimization and monitoring system
Analysis optimization and monitoring system
 
Energy storage systems control methods in micro grids Class-30, Subject: Di...
Energy storage systems control methods in micro grids Class-30,  Subject:  Di...Energy storage systems control methods in micro grids Class-30,  Subject:  Di...
Energy storage systems control methods in micro grids Class-30, Subject: Di...
 
Eco-mode: Benefits and Risks of Energy-saving Modes of UPS Operation
Eco-mode: Benefits and Risks of Energy-saving Modes of UPS OperationEco-mode: Benefits and Risks of Energy-saving Modes of UPS Operation
Eco-mode: Benefits and Risks of Energy-saving Modes of UPS Operation
 
Ppt2
Ppt2Ppt2
Ppt2
 
Multi string PV array
Multi string PV arrayMulti string PV array
Multi string PV array
 
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
Operational Cost Avoidance through Harmonic Mitigation in Industrial Environm...
 
WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)WIDE AREA MONITORING SYSTEMS(WAMS)
WIDE AREA MONITORING SYSTEMS(WAMS)
 
2014 PV Distribution System Modeling Workshop: CA Rule 21 Update: Tom Bialek,...
2014 PV Distribution System Modeling Workshop: CA Rule 21 Update: Tom Bialek,...2014 PV Distribution System Modeling Workshop: CA Rule 21 Update: Tom Bialek,...
2014 PV Distribution System Modeling Workshop: CA Rule 21 Update: Tom Bialek,...
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
 
Load Shedding Management
Load Shedding ManagementLoad Shedding Management
Load Shedding Management
 
DISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRID
DISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRIDDISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRID
DISTRIBUTED GENERATION ENVIRONMENT WITH SMART GRID
 

Semelhante a NetSure ITM 48V DC UPS

UPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen42U Data Center Solutions
 
Raritan BCM Data Sheet
Raritan BCM Data SheetRaritan BCM Data Sheet
Raritan BCM Data SheetMike Hogan
 
3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf
3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf
3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdfEnertech UPS
 
Dph series product presentation (1)
Dph series product presentation (1)Dph series product presentation (1)
Dph series product presentation (1)currentautomation
 
Delta UPS – Modulon Family
Delta UPS – Modulon FamilyDelta UPS – Modulon Family
Delta UPS – Modulon Familycurrentautomation
 
Riello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheetRiello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheetRobin Koffler MBA CDCEP
 
6dec2011 - Power Back-up_1
6dec2011 - Power Back-up_16dec2011 - Power Back-up_1
6dec2011 - Power Back-up_1Agora Group
 
Data center power infrastructure
Data center power infrastructureData center power infrastructure
Data center power infrastructureLivin Jose
 
SICAM FCM – Feeder Condition Monitor
SICAM FCM – Feeder Condition MonitorSICAM FCM – Feeder Condition Monitor
SICAM FCM – Feeder Condition Monitorashwini reliserv
 
Power Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited ApcPower Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited Apccharles1010
 
Lasting+ +centre+de+date+-++12mai2010
Lasting+ +centre+de+date+-++12mai2010Lasting+ +centre+de+date+-++12mai2010
Lasting+ +centre+de+date+-++12mai2010Agora Group
 
9395-UPS-Brochure
9395-UPS-Brochure9395-UPS-Brochure
9395-UPS-BrochureEhab Saleh
 
7 kt 7km pac measuring devices
7 kt 7km pac measuring devices7 kt 7km pac measuring devices
7 kt 7km pac measuring deviceslogenatech
 
Eaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptxEaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptxmancangkul1
 

Semelhante a NetSure ITM 48V DC UPS (20)

UPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with JenUPS Solutions for the Next Generation Data Center with Jen
UPS Solutions for the Next Generation Data Center with Jen
 
Hitec Brochure QPS English_LR
Hitec Brochure QPS English_LRHitec Brochure QPS English_LR
Hitec Brochure QPS English_LR
 
Raritan BCM Data Sheet
Raritan BCM Data SheetRaritan BCM Data Sheet
Raritan BCM Data Sheet
 
3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf
3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf
3 Phase Hybrid Solar Inverters Hybrid Inverter Bidirectional PCU.pdf
 
Dph series product presentation (1)
Dph series product presentation (1)Dph series product presentation (1)
Dph series product presentation (1)
 
Delta UPS – Modulon Family
Delta UPS – Modulon FamilyDelta UPS – Modulon Family
Delta UPS – Modulon Family
 
NetSure-502-Brochure
NetSure-502-BrochureNetSure-502-Brochure
NetSure-502-Brochure
 
Riello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheetRiello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheet
 
10027042_USV_Argument_gb
10027042_USV_Argument_gb10027042_USV_Argument_gb
10027042_USV_Argument_gb
 
6dec2011 - Power Back-up_1
6dec2011 - Power Back-up_16dec2011 - Power Back-up_1
6dec2011 - Power Back-up_1
 
C04832838
C04832838C04832838
C04832838
 
Data center power infrastructure
Data center power infrastructureData center power infrastructure
Data center power infrastructure
 
Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
  Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK  Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
 
SICAM FCM – Feeder Condition Monitor
SICAM FCM – Feeder Condition MonitorSICAM FCM – Feeder Condition Monitor
SICAM FCM – Feeder Condition Monitor
 
Power Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited ApcPower Point Data Centre Uk Limited Apc
Power Point Data Centre Uk Limited Apc
 
Lasting+ +centre+de+date+-++12mai2010
Lasting+ +centre+de+date+-++12mai2010Lasting+ +centre+de+date+-++12mai2010
Lasting+ +centre+de+date+-++12mai2010
 
A comprehensive review of distributed power system architecture for telecom a...
A comprehensive review of distributed power system architecture for telecom a...A comprehensive review of distributed power system architecture for telecom a...
A comprehensive review of distributed power system architecture for telecom a...
 
9395-UPS-Brochure
9395-UPS-Brochure9395-UPS-Brochure
9395-UPS-Brochure
 
7 kt 7km pac measuring devices
7 kt 7km pac measuring devices7 kt 7km pac measuring devices
7 kt 7km pac measuring devices
 
Eaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptxEaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptx
 

Último

04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptxHampshireHUG
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century educationjfdjdjcjdnsjd
 
Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slidevu2urc
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEarley Information Science
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processorsdebabhi2
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherRemote DBA Services
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Scriptwesley chun
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoffsammart93
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking MenDelhi Call girls
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfsudhanshuwaghmare1
 
Tech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfTech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfhans926745
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationRadu Cotescu
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...Neo4j
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsMaria Levchenko
 

Último (20)

04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
presentation ICT roal in 21st century education
presentation ICT roal in 21st century educationpresentation ICT roal in 21st century education
presentation ICT roal in 21st century education
 
Histor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slideHistor y of HAM Radio presentation slide
Histor y of HAM Radio presentation slide
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Script
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot TakeoffStrategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
Strategize a Smooth Tenant-to-tenant Migration and Copilot Takeoff
 
08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men08448380779 Call Girls In Friends Colony Women Seeking Men
08448380779 Call Girls In Friends Colony Women Seeking Men
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Tech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfTech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdf
 
Scaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organizationScaling API-first – The story of a global engineering organization
Scaling API-first – The story of a global engineering organization
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 

NetSure ITM 48V DC UPS

  • 1. NetSure™ ITM with eSure™ Technology Row-based, Scalable 48V DC UPS DC Power For Business-Critical Continuity™
  • 2. 2 Without Energy Optimization With Energy Optimization SystemEfficiency Improvement 10% 84% 86% 88% 92% 90% 94% 98% 96% 20% 30% 40% 50% 60% 70% 80% 90% 100% SystemEfficiency* Load *System efficiency includes AC to DC power conversion and internal distribution losses. Rising power density, rapid and unpredictable growth, escalating energy consumption and cost, plus a myriad of other power-related challenges are making it increasingly complicated and expensive to protect critical network and computing equipment. The NetSure™ ITM integrates DC UPS components into a compact, highly reliable power protection system, offering the answer to your current and future 48V power needs. This three-phase 480V AC input, 48V DC output UPS provides highly available power to a wide variety of IT applications and delivers advanced operating features combined with reduced total cost of ownership. The NetSure™ ITM is designed for deployment directly on the server room floor, and provides protected 48V power to nearby equipment racks. This preserves the efficiency and reliability benefits of DC power, while minimizing the amount of copper required and enabling modular growth. The NetSure™ ITM lowers the cost of data center design, operation and management. This 48V direct current solution is a row-based DC UPS that delivers simple, scalable and highly efficient power protection. A Complete Power Protection SolutionFeatures & Benefits High system efficiency: Reduced power conversion stages combined with 96% efficient eSure™ power conversion units (PCUs) and an advanced energy optimization mode enable significant energy savings even at low loads. Scalability and ease of deployment: Minimize your initial investment and avoid stranded power by adding expansion DC UPS modules without interruption in the field as power needs increase. DC architecture simplicity: Fewer components,conversionstagesand distributionbreakersthroughoutthepower chainensurehighavailability;eliminationof complexsynchronizationcircuitsandthe needtode-ratecapacityforphasebalancing orharmonicsmakesiteasytoengineer. High reliability and exceptional resiliency: Uninterrupted operation in the unlikely event of multiple component failures. Ease of maintenance: Field replaceable, hot swappable PCUs allow rapid replace- ment without critical bus disruption; low voltage allows maintenance without bypass or shutdown. Compact footprint: Row-based, integrated design saves considerable facility space by eliminating the need for a dedicated power room and separate PDU distribution. Flexible deployment options: Top or bottom cable entry allows for raised or non-raised floor installations. Advanced control and monitoring: Real time input and output monitoring, including power quality and consumption data, enables facility planning for the system and each branch circuit; state-of- the-art battery monitoring with Albér technology to assure optimal backup performance. One-year warranty: Provides full system coverage for one year. NetSure™ ITM DC UPS Module Top-Cabled Configuration Figure 1: NetSure™ ITM System Efficiency Efficiency Without Compromise™ provides a path to optimize data center infrastructure around design, operating and management efficiencies – while maintaining or improving availability. This is achieved through the proper selection and utilization of cooling, power and monitoring technologies, supported by key services and local expertise.
  • 3. 3 Lower Total Cost of Ownership DC power is often associated with telecommunications where it has delivered extremely high reliability for decades. Since DC power is both provided by backup power sources and consumed by electronic equipment, a DC power architecture minimizes conversion stages from grid to chip, thus enabling higher overall efficiency with increased availability. Factory integrated system for fast and easy site installation Service or expansion can be performed while the DC UPS is in operation, reducing maintenance costs Compact footprint with built-in batteries and distribution, minimizes required floor space Designed for scalable growth to postpone additional capex until capacity is needed Energy Optimization Mode Intelligent Power Matching [Figure 1] • Achieves near-peak UPS efficiency down to 5% system load by optimizing individual PCU performance, greatly reducing energy costs over time in real world conditions • Matches delivered power from the UPS to real-time demand, keeping a minimum of PCUs active and putting the rest on standby • Balances the run time of each PCU by rotating the active and standby units • Maintains the ability to respond quickly to changing load conditions Unmatched Availability Resilient design System bus charges batteries and distributes power directly to the server rack without additional switching or conversions 65k AIC withstand rating on AC input breaker(s) Controller outage does not interrupt power delivery to the critical load and is field replaceable without system outage Battery monitoring technology from Albér Detects failing battery cells before they affect the critical load Checks each cell and associated connections via a proactive, patented resistance test to reliably predict battery performance Provides early warning of cell problems without frequent discharge tests or battery degradation; mini- mum technician visits with maximum run time protection Systemcontrollerstoresrawdata accessibleviawebpageorexternal monitoringsystem Central to a data center’s strength is its overall uptime. To maintain business continuity, power systems must exhibit high availability and easily scale for increasing capacity. NetSure™ rectifiers or power conversion units (PCUs) are the heart of the NetSure™ ITM DC UPS. Each DC UPS module includes twelve independent 5.8kW PCUs. These PCUs are globally renowned with over 2 million units deployed, offering unmatched reliability with less than 0.5% return rate (200 years MTBF). The NetSure™ ITM provides many robust features to create a highly redundant package that minimizes single points of failure.  Proven power conversion topology Each PCU delivers conditioned, isolated power to a common distribution bus PCUs function in parallel for seamless redundancy without switching Units are hot swappable in the field without system adjustment; minimum field repair time (MTTR) increases overall uptime Redundant configuration Redundancy can be achieved both within a DC UPS module by PCU (N+x), and by complete system (2N) Internal power distribution through (22) branch circuit breakers allows redundant A+B power paths to each rack Battery backup via three parallel battery strings Optional dual AC inputs allow upstream switchgear maintenance without system outage NetSure™ ITM delivers Efficiency Without Compromise™ INFRASTRUCTURE MANAGEMENT Improving performance of the IT infrastructure and environment ECO AVAILABILITY Balancing high levels of availability and efficiency FLEX CAPACITY Adapting to IT changes for continuous optimization and design flexibility HIGH DENSITY Delivering architectures from 10–60 kW/Rack to minimize space and cost
  • 4. The NetSure™ ITM solution is a modular system in 70 kW increments, expandable up to 280 kW (4 DC UPS modules) with one controller. Flexibility to Meet the Needs of Any Data Center Flexible Capacity Each integrated DC UPS module occupies only 24 (W) x 41 (D) of floor space, including batteries and primary distribution Delivered fully configured for quick and easy field installation Typically installed in either the middle or at the end of a row of server racks Deploy only the capacity that is initially needed; DC UPS modules can be added at any time to row configurations on the data center floor Choose from top and bottom cabled variants for installation in either concrete or raised floor environments As Figure 2 illustrates, the NetSure™ ITM solution starts with a primary DC UPS module rated for 70kW. As your power needs increase, you can add up to three expansion DC UPS modules, for a maximum capacity of 280kW that may be configured for N+1 redundancy by subtracting one 6kW PCU from the rating. Each DC UPS module also includes 48V primary power distribution with 22 circuit breakers (6 fuses optional). Various server rack densities are supported with 5-10 minutes of battery backup time across three parallel 48V battery strings. 70kW (64kW N+1) 140kW (134kW N+1) 210kW (204kW N+1) 280kW (274kW N+1) Figure 2: System Scalability Figure 2: Primary DC UPS module with 3 expansion modules (top-cabled configuration shown) Install only the capacity required; link up to four DC UPS modules to one controller Figure 3 depicts two top-cable installation scenarios. Depending on your site and budget requirements, the NetSure™ ITM solution can either be installed as a single deployment [Figure 3a], or incrementally by row [Figure 3b] as power requirements grow. In either scenario, DC distribution cabling to each rack is reduced by placing the NetSure™ ITM in-the-row. Both AC and DC loads can be accommodated at the same site. AC loads can either be protected by an AC UPS or via a rack-mount DC to AC inverter fed from the DC UPS, both available from your local Emerson Network Power representative. 4 Whatever the physical layout of your data center, the NetSure™ ITM minimizes required floor space. With DC UPS building block modules, you can mix and match configurations and standard layouts to fit your available space.
  • 5. Figure 3a: 140kW initial deployment Two DC UPS modules power blade server racks Figure 3b: 70kW initial deployment (front row) Add DC UPS and server capacity as needed (back row) Figure 3: NetSure™ ITM Row-Based Installation Examples Ideal Applications for Reliable, Scalable 48V DC Power: New and expanding small to medium data centers High-density, scalable blade deployments Predesigned pods and clusters Facilities with constrained power and limited power room space Facilities without a dedicated power room New deployments with unpredictable growth and limited initial investment Applications combining servers and networking equipment (VoIP, PoE, etc.) Network testing labs 5 The NetSure™ ITM easily compliments existing AC power systems, whether you are planning a new facility or expanding an existing data center.
  • 6. Components of the NetSure™ ITM DC Power System Each NetSure™ ITM DC UPS module consists of twelve 5.8 kW power conversion units (PCUs), an advanced controller, three strings of 6V long-life VRLA battery cells, and 48V DC branch distribution to feed each server rack. In addition to comprehensive efficiency and power metrics, the advanced controller provides complete system and battery monitoring. Further- more, power to each output circuit is individually monitored. Batteries and your choice of output distribution are integrated into the system prior to shipment from the factory for simplified site installation. Excellence EB4 VRLA BatteryNetSure™ System Controller ACU+eSure™ High-Efficiency Power Conversion Unit 6 Energy Optimization and Comprehensive Monitoring All NetSure™ ITM DC UPS modules are controlled and monitored by the Advanced Control Unit (ACU+). Critical system functions and operational conditions as well as alarms can be viewed both locally via LCD display and remotely via a secure web interface, Liebert® SiteScan™ or EnergyMaster™ Remote Supervision. Essential system metrics and alarms are continuously monitored: System input and output details Battery state of health DC output branch distribution circuits VRLA Batteries The system features three strings of 6V VRLA batteries from Emerson. The Excellence series battery is a top-of-the- line front terminal battery that is designed for reliable and efficient operation with a long life expectancy. High energy density combined with superior endurance ensures long-term, trouble-free performance. Designed for small areas, the Excellence series consumes less rack space and facilitates easy installation and handling. This battery is rated for 10 years at 25°C and includes a 3 year full warranty. Power Conversion Units (PCUs) Designed for best-in-class efficiency (96%) and high power density, the foundation of the NetSure™ ITM is the modular 3-phase input PCUs. Installation and maintenance is easy with plug-and-play functionality and a weight of only 17.6 lbs (8 kg). The PCU also features a low THD level (5%).
  • 7. SiteWeb™ BRC AC DC AC DC A B A B A B A B AC DC AC DC 48VDC Output 48VDC Output 48VDC Output 48VDC Output AC DC AC DC AC DC AC DC 1 12 13 24 25 36 37 48 1 22 23 44 45 66 67 (3strings)(3strings)(3strings)(3strings) 88 One-line diagram for a four DC UPS module system shown with circuit breaker output and dual AC input. Figure 4: NetSure™ ITM Internal Schematic 7 SiteWeb™ BRC with Albér® Technology Industry leading battery monitoring technology from Albér provides detailed information and alarms regarding the battery backup condition that will minimize site visits and maintenance. The functionality of the SiteWeb™ BRC is integrated with the system controller to continuously monitor and test the battery backup system at the cell or block level without affecting battery performance. It measures cell internal resistance, intercell resistance, cell voltages, battery current and temperature. The informa- tion and alarms can be viewed via a web browser or connected to Liebert SiteScan™ or EnergyMaster™ Remote Supervision for long term trending and analysis. 1 AC input wiring (top or bottom) 2 Power Conversion Unit (12 x 5833W) 3 ACU+ controller 4 480V AC input breaker 5 AC connection point 6 Battery fuses 7 48V DC output distribution – 22x100-200A breakers (shown); 2x500A + 4x200A fuses (optional) 8 Battery cooling fans 9 Integrated battery compartment; (3) strings VRLA batteries 2 3 4 7 7 5 1 1 6 NetSure™ ITM Front View (bottom-cabled version shown with front covers removed) NetSure™ ITM Rear View (rear cover removed) 9 8
  • 8. Rack-Mount Server Applications Blade Server or High Capacity Switch Applications 8 Easy Zero Rack Unit Power Distribution Featuring plug-and-play connectors for simple field connections, NetSure™ RDB 48V Rack Distribution Units are designed to complete your NetSure™ ITM Solution. Space Saving Design When it’s time to deploy DC power in your rack, a zero U, rear mount configuration keeps the most rack space available for your revenue generating equipment. Robust, tool-less, easy to use The NetSure™ RDB Series of rack PDUs is designed to handle up to an 8.6 kW load and provisioned to optimize the wire size required to each device. The result is a system that is easy to pre-configure and manage long term. Because of the plug-and-play connec- tivity, no special tools or expertise are needed to maintain or move your IT equipment. Quick input connectors facilitate easy installation and allow for tool-less field adjustments as layouts or requirements change Each outlet is individually protected by a circuit breaker Breaker trip notification for added convenience when troubleshooting outages Versatile PDU mounting options permit installation in any orientation NetSure™ RDB Series Models High Power Distribution (50-80A output breakers) 2 3 outlet configurations Medium Power Distribution (25-35A output breakers) 6 outlet configuration Low Power Distribution (10-20A output breakers) 6 15 outlet configurations NetSure™ RDB M6 NetSure™ RDB H2 NetSure™ RDB H3 NetSure™ RDB L15 NetSure™ RDB L6
  • 9. 9 Trust the service and support of your NetSure™ ITM system to the experts at Emerson Network Power. Our services are offered by technical professionals who have, on average, more than a decade of field experience with DC and network equipment. On the rare occasion that service is required, our technicians can be at your site within hours and are backed by an entire organization ready to help resolve any issues. We offer a complete suite of services to optimize and maintain the operation of your NetSure™ ITM solution throughout its life cycle. Startup We know the risks that improper system configuration can pose to your equipment and business. That’s why, even if a third-party has installed your system, you can depend on us to perform site testing and verification. We will provide testing and verification of the DC UPS, including PCUs, batteries and control points, to ensure problems are identified before they occur. Technical Support Remote support provides an immediate interface with experienced technical experts 24hours a day to help resolve unexpected systemincidents and support you in operating andmanaging your DC UPS. Preventive Maintenance Our preventive maintenance programs will ensure your NetSure™ ITM runs at peak system availability and establishes a predictable maintenance budget protect- ed from costly emergency repairs. Periodic inspections identify problems before they occur and maintain maximum operating efficiency. This DC UPS service plan provides a clear picture of system status and recommendations for corrective steps to prevent future problems. Various scopes of work that cover PCUs, batteries (including capacity testing), and DC distribution are available. Available exclusively to Emerson Network Power preventive maintenance customers, our secure customer website, Freedom- Care, gives you the capability to view and download service and maintenance visit reports. EnergyMaster™ Remote Supervision EnergyMaster™ assessment and remote supervision solutions provide an integrated approach to managing the energy and health of network infrastructures. Emerson experts optimize power consum- ing equipment for maximum energy savings and provide consistent network reliability through remote supervision routines that reduce maintenance costs. Field Service On-site field engineers are available for scheduled equipment replacement, emergency on-site technical trouble- shooting or system field upgrades. Training Courses, offered on-site or in our training center, provide knowledge in the operation, control, troubleshooting and maintenance of the NetSure™ ITM. Design and Installation We offer industry-leading experience and resources to expertly design your DC UPS and 48V DC distribution system. Our field installation team is available throughout North America to provide local knowledge and quick response to project require- ments. Installation services offer a variety of options to ensure the project is completed and tested as per agreed upon engineering specifications. A Life Cycle of Expert Service and Support DEPL OYMENT DESIG N Critical Infrastructure Lifecycle O PTIMIZATION
  • 10. 10 NetSure™ ITM – Technical Specifications DC UPS Primary Module 1 Expansion Module 2 Expansion Module 3 Expansion Module 4 Power Rating (full) – kW 70 70 70 70 Power Rating (N +1) – kW 64 70 70 70 AC Input Specifications Phase 3 Power Factor 0.99 at full load, 0.97 at 50% load Frequency – Hz 45-65 Input Voltage – Nominal 400 / 480V, 3 wire + ground Input Voltage – Range 304-530 VAC; shall withstand up to 600 VAC input without damage. Input Breaker Rating / AIC Rating – A 150 / 65,000 Max Input Current / DC UPS Module 480V: 111A @ 384V; 89A @ 480V 400V: 133A @ 320V; 107A @ 400V 380V: 140A @ 304V; 112A @ 380V Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value Total Harmonic Distortion 5% from 50-100% of load DC Output Specifications Voltage Nominal: -48VDC; normal operation: -54.5 VDC (battery float) Range: -42 to -58 VDC System Efficiency 96% peak; 95.5% from 40-100% load (system level including branch distribution losses) Energy Optimization Mode: Intelligent Power Matching Allows operation at near-peak efficiency down to 5% overall load Branch Distribution Options 22 circuit breakers, 100-200A each; optional: 6 fuses, 2x500A + 4x200A Battery Specification Type VRLA, Emerson Excellence EB4, 200 Ah Arrangement 3 strings; eight 6V blocks per string Backup Time See backup time table at various loads Design Life 15 years @ 20 °C ; 10 years @ 25 °C Recharge Time (to 97% of nominal capacity) Less than 3 hours for 35% load; Less than 4 hours 15% load Physical Data Form Factor Rack Installed Dimensions (H x W x D) – in. (mm) 85 x 24 x 41 (2150 x 600 x 1050) Installed Weight – lb. (kg) 2925 (1325) Environmental Specifications System Operating Temp. – °F (°C) -5 °C to +35 °C; recommended operation with battery: 20 °C to 25 °C air inlet System Storage Temp. – °F (°C) -40 to 158 °F (-40 °C to +70 °C) Relative Humidity 0 to 95%, non condensing Operating Elevation – ft. (m) 6562 (2000) at full power Audible Noise 62dB Heat Rejection at Full Load – BTU/hr. (kW) 9,554 (2.8) per DC UPS module EMI FCC class A Safety Certifications Agency Approved CE Marked to EN 60 950-1:2006 UL Listed to 60 950-1 + UL 1801; CSA certified Monitoring Capability Standard Web-based monitoring, alarm reporting via SNMP, and integration with SiteScan via SiteLink-E module Optional Energy Master Remote Supervision
  • 11. 11 eSure™ PCU (R48-6000Ne) – Technical Specifications DC Output Output Power 5833W maximum Regulation Steady state output voltage remains within +/-0.25% for any combination of input voltage from 5% to 100% load Wide Band Noise Does not exceed 250 mv peak-to-peak, or 100 mv rms per Telcordia GR-947-CORE Psophometric Noise Does not exceed 1 mv from 10% to 100% load Protection Current Limiting The output current is limited to 110 amps Over Current Internal fuse Physical Characteristics Mounting Plug-in installation, hot swappable Dimensions (H x W x D) – in. (mm) 3.36 x 8.83 x 14.62 (85.5 x 224.5 x 371.5) Weight – lb. (kg) 22 (10) Peace of mind. It’s confidence you’ve done everything possible to assure system uptime. It’s confidence the DC UPS you rely on is operating at peak performance. It’s confidence you’ve selected the best partner available to sustain your critical network infrastructure. That is Emerson Network Power. Battery Back-up Time (minutes) DC UPS Load Single module 70kW Two modules 140kW Three modules 210kW Four modules 280kW 10kW 130 300 480 630 20kW 55 130 210 300 30kW 28 90 130 180 40kW 17 55 90 130 50kW 12 41 70 100 64kW 7 24 50 75 70kW 3 21 43 69 80kW 17 34 55 90kW 14 27 47 100kW 12 22 40 110kW 10 19 34 120kW 8 17 28 134kW 6 16 25 140kW 3 14 22 150kW 12 19 160kW 10 17 170kW 9 15 180kW 8 14 190kW 7 13 204kW 4 11 210kW 2 10 220kW 9 230kW 9 240kW 8 250kW 7 260kW 6 274kW 3 280kW 1
  • 12. © 2012 Emerson Network Power Energy Systems, North America, Inc. All rights reserved. Emerson Network Power Energy Systems, North America 4350 Weaver Parkway, Warrenville, IL 60555 Toll Free: +1 800 800 1280 (USA and Canada) Telephone: +1 440 246 6999 Fax: +1 440 246 4876 Web: EmersonNetworkPower.com/EnergySystems EnergyNet: EmersonEnergy.com Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering together to provide innovative solutions for customers in industrial, commercial, and consumer markets through its network power, process management, industrial automation, climate technologies, and tools and storage businesses. For more information, visit: Emerson.com. Emerson Network Power, a business of Emerson (NYSE:EMR), maximizes reliability, deployment speed and operational efficiency for communications networks. A trusted industry leader in smart infrastructure technologies, Emerson Network Power provides innovative, rapidly deployable solutions that deliver efficiency and uncompromised reliability regardless of network demands. Our solutions are supported globally by local Emerson Network Power service techni- cians. Learn more about Emerson Network Power products and services at: EmersonNetworkPower.com/EnergySystems. Learn more about the NetSure™ ITM DC UPS from Emerson at: EmersonNetworkPower.com/NetSureITM. This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or conditions of supply of any product or service. Emerson® , Emerson Network Power™ , Business-Critical Continuity™ , Efficiency Without Compromise™ , Albér® , EnergyMaster™ , eSure™ , Liebert® , NetSure™ , SiteScan™ and SiteWeb™ are trademarks of Emerson Electric Co. and/or one of its subsidiaries. Code: 100B-NSITM / 0212 Emerson Network Power. The global leader in enabling Business-Critical Continuity™ . AC Power Connectivity Infrastructure Management Monitoring Precision Cooling Racks Integrated CabinetsOutside Plant ServicesDC Power Power Switching Controls Embedded Computing Embedded Power Industrial Power EmersonNetworkPower.com