This document provides an overview and discussion of system survivability, data communication links, fault isolators, and performance nomenclature in fire alarm systems. The key points are:
1) Data communication links are critical for system reliability and survivability during fires. Lessons from failed systems show life safety systems can fail early in fires.
2) Fault isolators are used to isolate short circuits and ensure normal operation of devices is not affected if a fault occurs within a floor area.
3) NFPA 72 has updated its performance designations, replacing circuit styles with classes (A, B, C, etc.) based on their fault tolerance and annunciation capabilities.
3. Agenda
1- System Survivability
2- Lessons Learned from Failed System Survivability
3 - Understanding Data Communication Links
4 – Fault Isolator Applications
5 - Networked Data Communications Links
6 – NFPA Updated Performance Nomenclature
4. 1- System Survivability & CAN/ULC-S524
• There is an expectation that life safety systems should
continue to provide some level of performance in a
fire or a disaster
• Survivability of the fire alarm system during a fire is a
relatively new paradigm
• Data Communications Links (DCLs) in new fire alarm
systems are at the heart of the issue of the reliability
and survivability
5. 2- Lessons Learned from Failed System Survivability
• 2 Fore2st Laneway
2 Forest Laneway
North York
6. 2- Lessons Learned from Failed System Survivability
Fatal fire in a Toronto high-rise
Six people died, the issue of the early failure of
life safety systems during the fire was examined
• Failure of the exit lighting
• Failure of the emergency lighting
• Failure of the fire alarm annunciation
• Failure of the fire alarm signaling
• Failure of the voice communication system
7. 3 - Understanding Data Communication Links
DATA COMMUMICATIONS LINK
• The data channel between control units and/or
transponders and annunciators
The fire alarm network
____________________________________
• Active field devices
Addressable fire alarm devices
9. 3 - Understanding Data Communication Links
2006
Data Communication Link Table 3
Addressable fire alarm devices
10. 3 - Understanding Data Communication Links
Capacity of addressable devices
DCLA
300 Device Limit per loop
2 loops shown
Zone 1
ADDRESSABLE MANUAL STATION
ADDRESSABLE SMOKE DETECTOR
ADDRESSABLE HEAT DETECTOR
Data Communication Link Table 3
Addressable Devices
11. 3 - What is a Data Communication Link
Capacity of addressable devices
DCLB
200 Device Limit per loop
2 loops shown
Zone 1
ADDRESSABLE MANUAL STATION
ADDRESSABLE SMOKE DETECTOR
ADDRESSABLE HEAT DETECTOR
Data Communication Link Table 3
Addressable Devices
12. 3 - Understanding Data Communication Links
Capacity of addressable devices
DCLC
300 Device Limit per loop
Isolators used
2 loops shown Multiple
Zones
ADDRESSABLE MANUAL STATION
ADDRESSABLE SMOKE DETECTOR
ADDRESSABLE HEAT DETECTOR
Data Communication Link Table 3
Addressable Devices
13. 4 – Fault Isolator Applications
The Alpha isolator, part no. MIX-100X, is designed to sense and isolate short-circuits
on loops. It is a stand-alone device which is fitted into its own base.
14. 4 – Fault Isolator Applications
Clause 4.2.7 of CAN/ULC-S524
When a data link serves more than one floor area,
a fault within one floor area cannot affect normal
operation of devices in another floor area.
15. 4 – Fault Isolator Applications
Addressable devices
300 Device Limit FOURTH FLOOR
THIRD FLOOR
Fault isolation SECOND FLOOR
module pairs
ADDRESSABLE MANUAL STATION
FIRST FLOOR
ADDRESSABLE SMOKE DETECTOR
ADDRESSABLE HEAT DETECTOR
FIRE ALARM
CONTROL PANEL
FAULT ISOLATION MODULE OR TRANSPONDER
DATA COMMUNICATION
LINK
16. 4 – Fault Isolator Applications
Clause 5.14.6 of CAN/ULC-S524
Do not install the fault isolation modules back to back
17. 4 – Fault Isolator Applications
5.14.6 of CAN/ULC-S524
400mm
Offset the fault isolation modules
18. 4 – Fault Isolator Applications
5.14.8 of CAN/ULC-S524
ZONE 2
ZONE 1 STAIR
Fault isolation modules serving a single device in an exit
19. 4 – Fault Isolator Applications
• Class A Wiring Circuit, DCL Style A, DCL Style C
• Defines the distance between the primary and alternate wiring circuit paths
20. 4 – Fault Isolator Applications
• Class A Wiring Circuit, DCL Style A, DCL Style C
• Defines the distance between the primary and alternate wiring circuit paths
Separation of
Wiring
21. 4 – Fault Isolator Applications
Class A Wiring Circuit, DCL Style A, DCL Style C
Defines the distance between the primary and alternate wiring circuit paths
Separation of
Wiring
22. 4 – Fault Isolator Applications
• Class A Wiring Circuit, DCL Style A, DCL Style C
Separation of
Wiring
23. 4 – Fault Isolator Applications
• Class A Wiring Circuit, DCL Style A, DCL Style C
Separation of
Wiring
24. 4 – Fault Isolator Applications
Separation of
Wiring
25. 5 - Networked Data Communications Links
Only DCLC permitted
1000 Addressable device limit for entire system
Fire Alarm
Control Unit Fire Alarm
Control Unit
One fault
does not disable the system
Data communications
Fire Alarm
Control Unit
Fire Alarm
Fire Alarm Annunciator
Control Unit
DCLA or DLCB
Data communication
Permitted here
26. 5 - Networked Data Communications Links
More than 1000 Addressable device limit for entire system
Must meet Large Scale Network and only DCL-C permitted
Fire Alarm
Control Unit Fire Alarm
Control Unit
Data communications
Fire Alarm
Control Unit
Fire Alarm
Fire Alarm Annunciator
Control Unit
DCLA or DLCB
Data communication
Permitted here
27. 5 - Networked Data Communications Links
NBCC 2010 Division B 3.2.7.9 Emergency Power For
Building Services & 3.2.7.10.(2) & (4) Protection of
Electrical Conductors MECHANICAL PENTHOUSE
Power and/or data Wiring between fire alarm control unit, or
transponder, and primary annunciator(s) one hour fire rated
cable or construction methods for data only.
If the fire alarm emergency communication control units or
transponders are provided with sufficient batteries then fire
rated cables for the 120 volt power supply is not required.
2 hour rated MI or CI
cable or construction
method
Data Communication
Link Fire Alarm
Emergency
Communication System
Network Backbone
Ground Floor
PARKING GARAGE P1-P4
28. 5 - Networked Data Communications Links
2010 NBCC Division B 3.2.7.8
Emergency Power For Fire Alarm
MECHANICAL PENTHOUSE
All emergency power feed wiring
from the generator to the individual
fire alarm emergency
communication control units must
be installed to survive two hours.
If the fire alarm emergency
communication control units or
transponders are provided with
sufficient batteries then cables do
not require fire rating.
Low rise buildings do not require
fire rated cables
2 hour rated MI or CI
cable or construction
method
Emergency
Transfer Power
Distribution
Generator switch
Panel
Ground Floor
PARKING GARAGE P1-P4
29. 5 - Networked Data Communications Links
• Refer to Table 3 of CAN/ULC-S524
• More than 1000 Addressable device limit
for entire system
• Must meet Large Scale Network
• Only DCL-C permitted
30. 5 - Networked Data Communications Links
• Each transponder has STAND ALONE capability
• Degraded mode capability
• Each transponder must have:
• Signal silence
• Reset
• Trouble silence
• Stand alone indicator
• In high buildings per Quebec Construction Code
• At least one ADDITIONAL transponder with
• Full annunciation per QCC
• Means to transmit voice communication with “ ALL CALL” capability
• Transponders must be in an electrical room with a 1 hour
fire separation
31. 6 – NFPA Updated Performance Nomenclature
The new NFPA 72 NFPA 72: National Fire Alarm and
Signaling Code Handbook (2010) has eliminated the
circuit styles.
Instead, NFPA now designates circuits and pathways as
Class A, Class B, Class C, Class D, Class E or Class
X, depending on their performance.
32. 6 – NFPA Updated Performance Nomenclature
12.3.1* Class A. A pathway shall be designated as Class A when it
performs as follows:
(1) It includes a redundant path.
(2) Operational capability continues past a single open.
(3) Conditions that affect the intended operation of the path are
annunciated.
The Class A Style 7 performance is now defined as Class X.
FOURTH FLOOR
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
FIRE ALARM
CONTROL PANEL
33. 6 –NFPA Updated Performance Nomenclature
12.3.3* Class C. A pathway shall be designated as Class C when it performs as follows:
(1) It includes one or more pathways where operational capability is verified via end to-
end communication, but the integrity of individual paths is not monitored.
(2) A loss of end-to-end communication is annunciated.
A.12.3.3 The Class C reference is new and is intended to describe technologies that
supervise the communication pathway by polling or continuous communication
“handshaking” such as the following:
(1) Fire control unit or supervisory station connections to a wired LAN, WAN, or Internet
(2) Fire control unit or supervisory station connections to a wireless LAN,WAN, and
Internet
(3) Fire control unit or supervisory station connections to a wireless (proprietary
communications)
(4) Fire control unit digital alarm communication transmitter or supervisory station digital
alarm communication receiver connections to the public switched telephone network
34. 6 – NFPA Updated Performance Nomenclature
NFPA 72 Signal Line Circuit Performance
NFPA 72- 2007 Style 4 Style 6 Class A Style 7
NFPA 72 - 2010 Class B Class A Class X
Type of Fault
Single Open Trouble Alarm, Trouble Alarm, Trouble
Single Ground , Alarm, Trouble Alarm, Trouble
Trouble (ground) (ground) Alarm, Trouble (ground)
Short Trouble Trouble Alarm, Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm, Trouble
Open and ground Trouble Alarm, Trouble Alarm, Trouble
Communications loss Trouble Trouble Trouble
• Alarm - The control panel must be able to process an alarm input signal in the
presence of this type of fault.
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Class E does not require supervision