[object Object],Session 12: Motor protection
Protection & Coordination Standards: NEMA & NEC
Protection & Coordination
Protection & Coordination
Protection & Coordination
Protection & Coordination
Protection & Coordination Conductors for a single motor must have an ampacity of not less than 125% of the motor full-load current rating. Conductors that supply several motors must have an ampacity of not less than: (1) 125% of the highest rated motor FLC , plus (2) The sum of the FLCs of the other motors (on the same line). . The highest rated motor is the motor with the highest FLC from the standard. Determine the “other motors in the group” value by balancing the motor FLCs on the feeder being sized, then select the line that has the highest rated motor on it  The motor branch-circuit short-circuit and ground-fault protective device must be capable of carrying the motor’s starting current. A branch-circuit short-circuit and ground-fault protective device protects the motor, the motor control apparatus, and the conductors against short circuits or ground faults Size overload protection devices based on the motor nameplate rating (this protects locked-rotor current damage to motor windings) . Branch-circuit conductors are protected against overloads by the overload device.
Protection & Coordination Motor nameplates:  To define the basic performance and mounting parameters of a motor, the National Electrical Manufacturers Association (NEMA) defines some basic design and dimensional parameters in NEMA Standard MG 1. These parameters are then coded onto the motor nameplate to give you a basic definition of what you have received. Manufacturers often include additional information to further define some key motor features. Section MG 1-10.40, "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors," of the NEMA standard requires that "The following minimum amount of information shall be given on all nameplates of single-phase and polyphase induction motors. For abbreviations, see MG 1-1.80." * Manufacturer's type and frame designation * Horsepower output.
Protection & Coordination * Time rating. (intermitent, for how long or continuous.) * Maximum ambient temperature for which motor is designed.  * Insulation system designation. * RPM at rated load. * Frequency. * Number of phases. * Rated load current. * Voltage. * Code letter for locked rotor kVA.  * Design letter for medium motors.  * NEMA nominal efficiency when required by MG 1- 12.55 * Service factor if other than 1.0. * For motors equipped with thermal protectors, the words "thermally protected" if the motor provides all the protection described in MG 1-12.52.  * For motors rated above 1 hp equipped with over-temperature devices or systems, the words OVER TEMP. PROT.-." A type number as described in MG 1- 12.53 inserted in the blank would identify the protection type. The information on a motor nameplate can be arranged in categories. They are electrical inour, mechanical output, performance, safety and reliability
Protection & Coordination Motor control centers: They come in various configurations. Their main purposes are to control (turn On & Off) the motors and provide protection to motors & connecting cables.  The basic construction consists of an enclosure 90" high with widths & depths varying to accommodate the different components & devices packed into the enclosure. Such enclosures have: the 3-phase horizontal main bus, the risers, the barriers, the main incoming compartment (that would accommodate the lugs, the main switch or the main breaker), the different compartments complete with the back-plates & front compartment doors.  The number of compartments per cubicle varies with the size of starters installed, the maximum is 6 or 7 (function of the design) & the minimum is 1. Motor control centers (MCCs) can be built back to
Protection & Coordination back. The starters included in the MCCs may be wired according to any of the following standard designations:  1)EEMAC class I type A (no terminal blocks). 2)Class I type B (control wiring are brought to terminals in the starter unit).  3)Class I type C (no starter inter-wiring with the control & load wiring brought out to terminals at top or bottom of each section - cubicle- or to a master control section). 4)Class II type B (the control wires from each starter are brought to terminals in each unit with interlocking & inter-wiring between line-up units connected).  5)Class II type C (all wiring is brought to a master terminals section as class I type C but with interlocking & starters inter-wiring connected). The motor type, application and location affect the selection of the starters complete with their associated overload and short circuit protective devices. The full load current of a motor is the current required to produce the full load torque at rated speed. The locked-rotor current (inrush or starting) is the current drawn (from the power source) when the motor is first connected to the line (energized). It lasts over the acceleration period & it magnitude varies from 4 to 10 times the full load current.
Protection & Coordination The speed of the SCIM depends on the number of poles of the motor & the frequency of the power supply. The output torque of the motor (which is the turning force) in lb-ft is equal (motor horsepower/motor revolution per minute) times 5252. The currents passing through the stator as well as the rotor windings of the motor cause an increase in the motor temperature (temperature rise over & above the ambient temperature). In general, the temperature rise produced at full load is not harmful, provided that the motor ambient temperature does not exceed 40oC. For each increase of 10oC above the rated (allowable) temperature of the motor (function of the insulation used for the windings & the iron laminations), the motor’s life is halved. Most motors have a continuous duty rating. Intermittent duty ratings are based on a fixed operating duration (5, 15, 30 or 60 minutes), after which the motor has to be stopped & left (allowed) to cool. If the motor is given a service factor, the motor is allowed to develop more than its rated HP. This increase in the output horsepower is equal the service factor (eg. 1.25, 1.15) minus 1 times the rated HP. Under such condition, no damage or deterioration of the insulation will occur. Jogging describes the repeated starting & stopping of the motor at frequent intervals (for short periods of time).  Plugging of a motor means when a motor running in one direction is momentarily disconnected & reconnected to the source (in such a manner as to reverse its direction of rotation). This action will cause the motor to come to rest faster (than if one tries to brake it while running in the forward direction). The 3 common types of enclosures that a motor might have are the open drip proof (O.D.P.), the totally enclosed fan cooled (T.E.F.C.) and the explosion proof ones.
Protection & Coordination A contactor is a 2-state device for repeatedly establishing & interrupting an electric power circuit. A magnetic contactor is a contactor activated by electromagnetic means (applied in ac circuits). The basic components of a contactor are: contact system, arc extinction devices, mechanical linkages between the contacts & the drive unit, the drive unit, the conductor connections & the frame. The electromagnet (for electromagnetic contactors) consists of, basically, a coil of wire placed on an iron core. The armature is mechanically connected to the contacts. When a contactor's armature is sealed-in, it means that it is held closely against the magnet yoke. When the coil is de-energized, thanks to the small air gap in the iron circuit, the armature drops out (opening the contacts). The contacts pressure corresponds to the rated current of the contactors.
Protection & Coordination In order to reduce the heating produced by the changing of the magnetic flux, the magnets are built up of thin iron laminations. The hum is reduced through the use of shading ring (lag coil) in the pole; it is made of copper. The contacts make, break & carry the rated currents corresponding to the rating of the contactor. As mentioned previously, the most widely used industrial drives are the ac poly-phase induction motors having an average starting currents of 6 times their full load currents. In general, the starting motors currents have hardly any effect on the life of the contactor. The interrupting medium of low voltage contactor is air. The quality of contacts depends on the contact pressure as well as the properties of the contact material. An example for contact material is silver with additives like cadmium oxide. The rating structure of low voltage contactors (used in motor starters) is per EEMAC, the common sizes are 00 to 6 at 575 V, 3-phase supply, 2 HP to 400 HP motors. An example for a contactor continuous current rating for size 00 is 10 amperes (open) & 9 amperes (enclosed). Another example would be for size 6, where the continuous current rating would be 600 A (open) & 540 A (enclosed). The most common types of conrol diagrams used with motor control & protection circuits are the wiring (or connection) diagrams and the schematic (or the elementary) diagrams. In a 3-phase, 3-wire system, the motor circuit consists of 3 power lines (L1, L2 & L3). The motor terminals are identified as T1, T2 & T3. A manual starter consists primarily of a set of manually operated contacts & a motor overload-ensing device (melting alloy, bi-metallic or electronic type). Electro-magnetically operated ones are basically manual ones plus a solenoid for closing the power contacts. The magnet frame & armature assembly of the low voltage contactors are 1 of the following: clapper, plunger (vertical action) or bell crank.
Protection & Coordination The combination motor controller consists of an externally operable circuit disconnecting means (a switch in series with Form II fuse for only short circuit protection or a circuit breaker with magnetic element protection only) in series with a magnetic motor controller (contactor plus overload or a relay that matches the motor heating curve), refer to sketch on page 50.  The methods of starting a squirrel cage induction motor are: across the line (full voltage starting that provides the highest starting torque as well as the highest starting current & accelerates the load to full speed in the shortest possible time), auto- transformer, primary resistor, wye-delta starting & part winding.
Protection & Coordination
Protection & Coordination The second to the fifth methods, inclusive are termed reduced voltage motor starting methods. The selection of the reduced voltage method involves a co-ordination between the required starting torque & allowable starting current (this current overloads the circuit & may reduce the voltage - causing a sag - to other loads in the power distribution system). Certain starting methods necessitate that the motors would be built in certain ways. The starting torque varies with the square of the starting current (when reduced voltage methods - applying less than full line voltage to the motor during starting - are used, the starting current & torque will be lower).  Contactors have to undergo certain tests to be qualified or approved by the bodies having jurisdiction like UL, CSA, IEC. The principle tests are: spacing between live parts & ground, temperature rise of coils, contacts & terminals, operating voltage range, overload capability, mechanical/electrical endurance & dielectric strength tests.  The power (source connected) to the control circuit can be classified into: common control, separate control or control circuit transformer. It can come directly from the power feeding the (power) terminals of the motor, from an external source (d.c.- battery or a.c. station service transformer) or from a step-down control potential transformer connected to the supply line of the motor.
Protection & Coordination
Protection & Coordination Control panels can be built in different constructions depending on the environment and may include any or all of the following devices: contactors, breakers, switches, relays, push-buttons, selector switches, meters, pilot lights (filament or LED). These panels incorporate the logic (decision making), input & output devices. Motors are too sensitive to negative sequence currents generated when the voltage supplied to the motor is unbalanced or when a single-phase condition occurs. A sequence relay is used and is installed in the control panel. This relay can be of the negative sequence voltage sensing or the current sensing type. The type of the relay sensing technique dictates the location of the relay i.e. upstream or downstream the fault (to be sensed) for current sensing relays and downstream the fault for voltage sensing ones. The fused switch, the moulded case current limiting circuit breaker or the mccb plus the current limiter is used whenever the available short circuit current in the system is beyond the circuit breaker interrupting capacity. When it is required to limit the short circuit current (downstream) to a lower level than the available in the system, a switch/fuse combination is used with class J fuses (high rupture capacity current limiting fuses, 200 KA interrupting rating). Other fuse classes found in MCC line-ups are C & R.  Programmable logic controllers (PLC) are used often to control motors and make decisions regarding starting, running & stopping the motors. They are usually in stalled in the MCC line-up.
Protection & Coordination Protection of medium voltage motors:
Protection & Coordination Medium voltage controllers: They consist of one or more contactors, each with 3 current limiting fuses, the draw-out mechanism, instrument transformers, meters, protective low voltage devices (relays), bus bars, barriers, shutters, operating coils, control transformers, auxiliary switches, activating levers & springs, the frame and the steel enclosure housing all these components. The enclosures may be front access (to be built back to back or to be installed against the wall) only or front & back access. Typical applications would include controlling & protecting the following equipment: squirrel cage induction motors (SCIM), including non-reversing, reversing & multi-speed, reduced voltage starters including autotransformer & reactor starting types, synchronous motors including brush-less & brush types, wound rotor motors, transformer & capacitor banks.  For decades, medium-voltage motors were switched exclusively by air-break contactors. The design of air-break contactors has to allow for the large contact gap required (approximately 1.5 ") & for the arc chutes (as the arc has to be drawn & forced into the chutes to get elongated, cooled, having its resistance increased & extinguished). The arc is, generally, maintained for several 1/2 cycles, it restrikes after a current zero because the dielectric strength of the break (gap) recovers relatively slowly. As the arc is driven into the chute, its voltage rises sharply & the current amplitude decreases. At the instant of arc extinction, the phase angle between the current & voltage becomes zero and the voltage stressing the break becomes less severe. The second type of interrupting medium, used in motor controllers contactors, is vacuum. With vacuum contactors, the arc is confined to the
Protection & Coordination contact gap (which is only a few millimeters as vacuum has a dielectric strength of 30 KV/mm). Arcs in vacuum can be classified into diffused (for currents less than 10 KA ) & constricted (for higher currents). When the short circuit current exceeds 10 KA, a transition occurs from the diffused to the constricted form of arc in vacuum. Overheating (which is one of the side effects of constricted arcs) can lead to restrikes.  The two most commonly used contact shapes, of vacuum interrupters, are the disc & the hollow cylindrical ones. The latter would have inclined slits (to divert the current flowing away from the axial direction). The arc is driven along the circular end (contact end faces). The contact rings are beveled to push the arc outwards (toward the rim or edge of the
Protection & Coordination circular contact).  After contact separation, the metal vapour plasma fills the entire contact gap. Short recombination time of the charge carriers (in the contact gap zone) is one important property of the plasma. As the current decreases (on the short circuit current cycle heading toward zero), the carriers’ number decreases. After arc extinction, the remaining charge carriers recombine on the metal surface (contacts) and the gap (contacts break) de-ionizes pretty fast. After current zero, restriking is eliminated. The current carrying contacts experience minimum erosion. High number of operations (2 million) with up to 300 amperes motor load is possible. The arc energy is low as well as the arcing time (1/2 cycle). The heat dissipation is reasonable as the arc duration is short & the amount of heat generated is small i.e. no possibility of contact welding. Contact surface oxidization and contamination is not possible as the interior of the vacuum bottle is isolated from its surroundings (environment). Filler material (for the contact) is used in order to achieve lo current chopping levels (in the range of 0.3 ampere). To calculate the superimposed peak overvoltage due to current (arc chopping), use the following formula overvoltage = surge impedance times chopped current magnitude (where surge impedance = (Inductance / Capacitance) .5  ohms). The use of motor starters to control medium voltage motors, placed an emphasis on the ability of the series fuse to withstand current pulses (due to motor starting, inrush, currents). A fuse used in protection of electrical motors must fulfill the following requirements:  1)It should have a good a good withstand ability, in the 10 to 60 seconds zone, and it should act fast in the.1 to .01 seconds zone.  2)It should possess minimum values for the cut-off currents as well as for the current let through (I2t).
Protection & Coordination 1)It should have the ability to interrupt all fault currents beyond the capability of the associated devices (the contactor) up to the maximum fault level of the system.  2)It should have the highest possible current rating (for a given fuse size) to allow for maximum utilization of space within associated equipment. The use of contactor/fuse combination may lead to smaller size cables (than with circuit breakers due to the fact of the limiting capability for the let through energy of the fuses). The fuse elements (used in motor protection fuses) have a straight through element with stress relief points (rather than a spirally wound filament on a core). In general, surge arresters are not required with vacuum contactors due to the fact that the cable distance between the contactor & the terminal box of the motor is quite short and shot cable lengths are used. Though, if multiple-reignition is expected, then surge arresters must be used and located close to the motors. Vacuum contactors are not suitable for use on direct current systems. De-rating of the motor controller units may be deemed necessary under abnormal operating conditions like altitude, frequency of power supply, temperature, exposure to fumes, dirt, humidity, etc. The table defining a medium voltage controller (contactor and fuse) will have the following data as a minimum: the contactor maximum continuous current, the interrupting capacity (at the specified KV), the designation, the voltage rating and range, the interrupting capacity of the fuse (in KA and MVA @ the rated voltage), the maximum HP motor rating (for the motor design, power factor, voltage, controller current rating), the dielectric withstand voltage (including BIL), the controller-type (full
Protection & Coordination voltage, reversing vs. non-reversing or reduced voltage, auto transformer vs. reactor type). The medium voltage fuses for controllers can be defined when the following values are given: the motor locked rotor current, motor full load current & service factor, the maximum continuous current rating of the fuse inside the compartment, the fuse size, the peak current let through characteristics. The standard ratings for the medium voltage open (i.e. not installed in an enclosure) contactors are 400 & 800 amperes. The contactor rating is derated when installed in its compartment in the cubicle. For example, with one-high controller cubicle, the current ratings for the 800 & 400 amperes would be 720 & 360 amperes.
Protection & Coordination
Protection & Coordination
Protection & Coordination Motor protection relays: A relay offering comprehensive protection may have but not limited to the following set of features: a. thermal protection (49) b. extended start protection /monitoring (accelerating time) (48) c. stalling protection (mechanical jam) d. number of starts limitation (66) e. short circuit protection (50P) f. ground (earth) fault protection (50/51G) g. winding RTD measurement/trip (38) h. negative sequence current detection (46) i. undervoltage protection (27) j. loss-of-load protection or under current (37) k. out-of-step protection (for synchronous motors only) (40) l. loss of supply protection (for synchronous motors only) (56) m. auxiliary supply supervision (59K) Motor thermal protection (protection against overload conditions/overheating): The majority of winding failures are either indirectly or directly caused by overloading (either prolonged or intermittent/cyclic), operation on unbalanced supply voltage (causing negative sequence current through the motor negative resistance), or single phasing (has the same effect as unbalance source), which all lead through excessive heating to the deterioration of the winding insulation until an electrical fault occurs.
Protection & Coordination The generally accepted rule is that insulation life is halved for each 10° C rise in temperature above the rated value, modified by the length of time spent at the higher temperature. As an electrical machine has a relatively large heat storage capacity, it follows that infrequent overloads of short duration may not adversely affect the machine. However, sustained overloads of only a few percent may result in premature ageing and insulation failure. Furthermore, the thermal withstand capability of the motor is affected by heating in the winding (which function of the motor loading) prior to a fault. It is therefore important that the relay characteristic takes into account the extremes of zero and full-load pre-fault current known respectively as the 'Cold' and 'Hot' conditions. The relays, in general, offer the following choices to the user: • Thermal limit curves per NEMA standard, voltage dependent and customized • IEC 60255-8 Thermal overload curves • Current unbalance biasing (including the effect of negative sequence current in heating the motor) • Independent running and stopped exponential cooling curves • Optional RTD biasing of the Thermal Model to adapt to real-time temperature measurements • Compensation for Hot (when the motor is restarting and its temperature is higher than under cold starting condition)/cold motor conditions. In general, the relay thermal model integrates both stator and rotor heating and cooling into a single model. Extended start time protection:
Protection & Coordination The relay function protects the motor from overheating in cases of abnormal loading during motor starts. The motor can be tripped if the motor does not reach a running condition within the programmable Motor Acceleration time. Stalling protection (mechanical jam): This function senses increased loading associated with process or load related faults causing the motor to jam or stall. A programmable delay setting can be used to allow the process to attempt clear itself before issuing a trip. Number of starts limitation (start inhibit): This function prevents starting of a motor when the motor is too hot and does not have a sufficient amount thermal capacity available to allow a start without being re-tripped. Short Circuit Protection: Motor short-circuit protection is often provided to cater for major stator winding faults and terminal flashovers. Short Circuit Overcurrent protection protects damage to the motor during a locked rotor condition. The  relay provide for instantaneous overcurrent protection, the elements can be configured for protection, alarming, and control during locked rotor conditions. For motors fed by circuit breakers, a single definite time overcurrent relay element is all that is required for this purpose, set to about 125% of motor starting current. The time delay is required to prevent spurious operation due to CT spill currents, and is typically set at 100ms.  Ground fault protection: One of the most common faults to occur on a motor is a stator winding fault. Whatever the initial form of the fault (phase-phase, etc.) or the cause (cyclic overheating, etc.),
Protection & Coordination the presence of the surrounding metallic frame and casing will ensure that it rapidly develops into a fault involving earth. Therefore, provision of earth fault protection is very important. The type and sensitivity of protection provided depends largely on the system earthing. It is common, however, to provide both instantaneous and time-delayed relay elements to cater for major and slowly developing faults. Overtemperature protection: The crelay ould support RTD inputs that allow for configuring the Alarming and Tripping Temperature of each RTD, detecting RTD shorting conditions, and selecting RTD voting that requires more than one RTD to detect an over-temperature condition before it will issue a Trip command.  The programmable RTD inputs can be used in monitoring the Stator, Bearing and the ambient temperatures. Each RTD input has 2 operational levels: alarm and trip. The relay could support RTD trip voting and provide open RTD failure alarming Negative sequence current detection: Unbalanced currents give rise to a negative sequence component in the stator current. The negative sequence current produces an additional flux which rotates at synchronous speed in the opposite direction of the rotor. The eddy currents which are induced in the rotor parts will have the double network frequency. During such sustained conditions, the temperature of the rotor may reaches high levels which accelerate the ageing of the insulation and cause mechanical stress on the rotating components. The relay calculates negative sequence current
Protection & Coordination and compared it with the set operate value for the alarm and the trip function. Undervoltage protection: Motors may overheat or even stall when subjected to prolonged undervoltage conditions. Transient undervoltages will generally allow a motor to recover when the voltage is restored, unless the supply is weak. Motors fed by contactors have inherent undervoltage protection, unless a latched contactor is used. Where a specific undervoltage trip is required, a definite time undervoltage element is used. If two elements are provided, alarm and trip settings can be used. An interlock with the motor starter is required to block relay operation when the starting device is open, otherwise a start will never be permitted. The voltage and time delay settings will be system and motor dependent. They must allow for all voltage dips likely to occur on the system during transient faults, starting of motors, etc. to avoid spurious trips. As motor starting can result in a voltage depression to 80% of nominal, the voltage setting is likely to be below this value. Re-acceleration is normally possible for voltage dips lasting between 0.5-2 seconds, depending on system, motor and drive characteristics, and therefore the time delay will be set bearing these factors in mind. Loss-of-load protection or under current: The Undercurrent Protection element provides the ability of tripping the motor due to external conditions that can cause the load being pulled by the motor to drop below a pre-set level. This element is useful when the loss of the load results in a loss of cooling which will cause the asset to overheat. Loss-of-load protection has a number of possible functions. It can be used to protect a pump against becoming unprimed, or to stop a motor in case of a failure in a mechanical transmission (e.g. conveyor belt)/
Protection & Coordination Out-of-step protection (for synchronous motors only): A synchronous motor may decelerate and lose synchronism (fall out-of-step) if a mechanical overload exceeding the peak motor torque occurs. Other conditions that may cause this condition are a fall in the applied voltage to stator or field windings. Such a fall may not need to be prolonged, a voltage dip of a few seconds may be all that is required. An out-of-step condition causes the motor to draw excessive current and generate a pulsating torque. Even if the cause is removed promptly, the motor will probably not recover synchronism, but eventually stall. Hence, it must be disconnected from the supply. The current drawn during an out-of-step condition is at a very low power factor. Hence a relay element that responds to low power factor can be used to provide protection. The element must be inhibited during starting, when a similar low power factor condition occurs. This can conveniently be achieved by use of a definite time delay, set to a value slightly in excess of the motor start time. The power factor setting will vary depending on the rated power factor of the motor. It would typically be 0.1 less than the motor rated power factor i.e. for a motor rated at 0.85 power factor, the setting would be 0.75. Loss of supply protection (for synchronous motors only): If the supply to a synchronous motor is interrupted, it is essential that the motor breaker be tripped as quickly as possible if there is any possibility of the supply being restored automatically or without the machine operator’s knowledge. This is necessary in order to prevent the supply being restored out of phase with the motor generated voltage.
Protection & Coordination Two methods are generally used to detect this condition, in order to cover different operating modes of the motor. Auxiliary supply supervision (59K): This supervision may include any or all of the following: • Integrity of coils (monitoring continuously their resistance). In case coils are in a good condition, the output COIL OK will be activated. • Control voltage (supervision of low voltage). If voltage is correct, the output BREAKER VOLTAGE OK will be activated. • Checks the breaker control circuit. If both control voltage AND coils integrity are correct, then the output BREAKER CIRCUIT OK will be activated. Other protection functions that may be found in motor protection circuits : Stator Differential This relay provides Stator Differential Protection for fast clearing of stator phase faults. Advanced CT saturation detection algorithms as well as dual slope characteristic are incorporated for increased security during heavy faults. Underfrequency function: The underfrequency relay element will operate in the case of the supply failing when the motor is on load, which causes the motor to decelerate quickly. Typically, two elements are provided, for alarm and trip indications. The underfrequency setting value needs to consider the power system characteristics. In some power systems, lengthy periods of operation at frequencies substantially below normal occur, and should not result in a motor trip. The minimum safe operating frequency of the motor under load conditions must therefore be determined, along with minimum system frequency.

Mais conteúdo relacionado

Mais procurados

Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformerssiddharam kantoli
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protectionNischal Popat
 
Alternator protection
Alternator protectionAlternator protection
Alternator protectionjawaharramaya
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Loss of excitation
Loss of excitationLoss of excitation
Loss of excitationNTPC
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsPower System Operation
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
 
Static excitation-system
Static excitation-systemStatic excitation-system
Static excitation-systemDeepak Jha
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear johny renoald
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 

Mais procurados (20)

Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Electrical HT/LT Motor protection
Electrical HT/LT Motor protectionElectrical HT/LT Motor protection
Electrical HT/LT Motor protection
 
Alternator protection
Alternator protectionAlternator protection
Alternator protection
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Loss of excitation
Loss of excitationLoss of excitation
Loss of excitation
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Reactors
ReactorsReactors
Reactors
 
Out of step
Out of stepOut of step
Out of step
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
 
Static excitation-system
Static excitation-systemStatic excitation-system
Static excitation-system
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 

Semelhante a Motor protection

Speed Control of Induction Motor Using Hysteresis Method
Speed Control of Induction Motor Using Hysteresis MethodSpeed Control of Induction Motor Using Hysteresis Method
Speed Control of Induction Motor Using Hysteresis MethodIRJET Journal
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centresalehkhan
 
Factors to be considered for motor selection
Factors  to be considered for motor selectionFactors  to be considered for motor selection
Factors to be considered for motor selectionshanmu m
 
Electric motor-controls-tutorial
Electric motor-controls-tutorialElectric motor-controls-tutorial
Electric motor-controls-tutorialElmer Salazar
 
star delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protectionstar delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protectionBHUPATI PRADHAN
 
Motor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.orgMotor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.orgDien Ha The
 
1694355611974.pdf
1694355611974.pdf1694355611974.pdf
1694355611974.pdfNafir Anas
 
TC-MODULE – 2.pdf
TC-MODULE – 2.pdfTC-MODULE – 2.pdf
TC-MODULE – 2.pdfNayan351985
 
MCC Motor Control Center 1
MCC Motor Control Center 1MCC Motor Control Center 1
MCC Motor Control Center 1Sakshi Vashist
 
Starting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motorsStarting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motorsmorin moli
 
Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applicationselprocus
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power Systemvkmalik
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxshivendra68
 
So Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co DienSo Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co DienMan_Ebook
 
Abb technical guide_no_7_revc
Abb technical guide_no_7_revcAbb technical guide_no_7_revc
Abb technical guide_no_7_revcShashank Pathak
 

Semelhante a Motor protection (20)

Speed Control of Induction Motor Using Hysteresis Method
Speed Control of Induction Motor Using Hysteresis MethodSpeed Control of Induction Motor Using Hysteresis Method
Speed Control of Induction Motor Using Hysteresis Method
 
Motor Control Centre
Motor Control CentreMotor Control Centre
Motor Control Centre
 
Factors to be considered for motor selection
Factors  to be considered for motor selectionFactors  to be considered for motor selection
Factors to be considered for motor selection
 
Electric motor-controls-tutorial
Electric motor-controls-tutorialElectric motor-controls-tutorial
Electric motor-controls-tutorial
 
star delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protectionstar delta auto starter with forward reverse and motor protection
star delta auto starter with forward reverse and motor protection
 
WIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUESWIRING MOTOR EMERSON EDUARDO RODRIGUES
WIRING MOTOR EMERSON EDUARDO RODRIGUES
 
Motor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.orgMotor circuit breakers mmp t series dienhathe.org
Motor circuit breakers mmp t series dienhathe.org
 
1694355611974.pdf
1694355611974.pdf1694355611974.pdf
1694355611974.pdf
 
TC-MODULE – 2.pdf
TC-MODULE – 2.pdfTC-MODULE – 2.pdf
TC-MODULE – 2.pdf
 
MCC Motor Control Center 1
MCC Motor Control Center 1MCC Motor Control Center 1
MCC Motor Control Center 1
 
Starting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motorsStarting and control of three-phase asynchronous motors
Starting and control of three-phase asynchronous motors
 
Motor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its ApplicationsMotor StarterTypes and Technology of Motor Starter And Its Applications
Motor StarterTypes and Technology of Motor Starter And Its Applications
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
 
LV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptxLV SWITCHGEAR -Final PPT.pptx
LV SWITCHGEAR -Final PPT.pptx
 
So Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co DienSo Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co Dien
 
C2000 m en_20120201
C2000 m en_20120201C2000 m en_20120201
C2000 m en_20120201
 
Chapter 4 electrical-auxiliary_systems
Chapter 4 electrical-auxiliary_systemsChapter 4 electrical-auxiliary_systems
Chapter 4 electrical-auxiliary_systems
 
Motor.ppt
Motor.pptMotor.ppt
Motor.ppt
 
Abb technical guide_no_7_revc
Abb technical guide_no_7_revcAbb technical guide_no_7_revc
Abb technical guide_no_7_revc
 
Abb technical guide no.07 revc
Abb technical guide no.07 revcAbb technical guide no.07 revc
Abb technical guide no.07 revc
 

Mais de H. Kheir

Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settingsH. Kheir
 
تعليم الاسيانيه بدون معلم المستوي المتوسط
تعليم الاسيانيه بدون معلم المستوي المتوسطتعليم الاسيانيه بدون معلم المستوي المتوسط
تعليم الاسيانيه بدون معلم المستوي المتوسطH. Kheir
 
تعليم الاسيانيه بدون معلم الاساسيات
تعليم الاسيانيه بدون معلم الاساسياتتعليم الاسيانيه بدون معلم الاساسيات
تعليم الاسيانيه بدون معلم الاساسياتH. Kheir
 
تعليم الاسيانيه بدون معلم المستوي: المبادىء
تعليم الاسيانيه بدون معلم المستوي: المبادىء  تعليم الاسيانيه بدون معلم المستوي: المبادىء
تعليم الاسيانيه بدون معلم المستوي: المبادىء H. Kheir
 
تعليم الايطاليه بدون معلم المستوى المتوسط
تعليم الايطاليه بدون معلم  المستوى المتوسطتعليم الايطاليه بدون معلم  المستوى المتوسط
تعليم الايطاليه بدون معلم المستوى المتوسطH. Kheir
 
تعليم الانجليزية بدون معلم المستوي المتوسط
تعليم الانجليزية بدون معلم المستوي المتوسطتعليم الانجليزية بدون معلم المستوي المتوسط
تعليم الانجليزية بدون معلم المستوي المتوسطH. Kheir
 
تعليم الإنجليزية بدون معلم الاساسيات
تعليم الإنجليزية بدون معلم الاساسياتتعليم الإنجليزية بدون معلم الاساسيات
تعليم الإنجليزية بدون معلم الاساسياتH. Kheir
 
تعليم الإنجليزية بدون معلم المستوي: المبادىء
تعليم الإنجليزية بدون معلم المستوي: المبادىءتعليم الإنجليزية بدون معلم المستوي: المبادىء
تعليم الإنجليزية بدون معلم المستوي: المبادىءH. Kheir
 
تعليم الفرنسية بدون معلم
تعليم الفرنسية بدون معلم  تعليم الفرنسية بدون معلم
تعليم الفرنسية بدون معلم H. Kheir
 
Learn french language
Learn french languageLearn french language
Learn french languageH. Kheir
 
Learn italian language
Learn italian languageLearn italian language
Learn italian languageH. Kheir
 
Protection and control, part 1
Protection and control, part 1Protection and control, part 1
Protection and control, part 1H. Kheir
 
Switchyards (outdoor substations), part 1
Switchyards (outdoor substations), part 1Switchyards (outdoor substations), part 1
Switchyards (outdoor substations), part 1H. Kheir
 
Computer Programming For Power Systems Analysts.
Computer Programming For Power Systems Analysts.Computer Programming For Power Systems Analysts.
Computer Programming For Power Systems Analysts.H. Kheir
 
How-to use off-the-shelf software packages to perform power systems analysis
How-to use off-the-shelf software packages to perform power systems analysisHow-to use off-the-shelf software packages to perform power systems analysis
How-to use off-the-shelf software packages to perform power systems analysisH. Kheir
 
Learning spanish language
Learning spanish languageLearning spanish language
Learning spanish languageH. Kheir
 
Linux tips
Linux tipsLinux tips
Linux tipsH. Kheir
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
A step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsA step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsH. Kheir
 
Indoor & outdoor substations, an overview
Indoor & outdoor substations, an overviewIndoor & outdoor substations, an overview
Indoor & outdoor substations, an overviewH. Kheir
 

Mais de H. Kheir (20)

Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settings
 
تعليم الاسيانيه بدون معلم المستوي المتوسط
تعليم الاسيانيه بدون معلم المستوي المتوسطتعليم الاسيانيه بدون معلم المستوي المتوسط
تعليم الاسيانيه بدون معلم المستوي المتوسط
 
تعليم الاسيانيه بدون معلم الاساسيات
تعليم الاسيانيه بدون معلم الاساسياتتعليم الاسيانيه بدون معلم الاساسيات
تعليم الاسيانيه بدون معلم الاساسيات
 
تعليم الاسيانيه بدون معلم المستوي: المبادىء
تعليم الاسيانيه بدون معلم المستوي: المبادىء  تعليم الاسيانيه بدون معلم المستوي: المبادىء
تعليم الاسيانيه بدون معلم المستوي: المبادىء
 
تعليم الايطاليه بدون معلم المستوى المتوسط
تعليم الايطاليه بدون معلم  المستوى المتوسطتعليم الايطاليه بدون معلم  المستوى المتوسط
تعليم الايطاليه بدون معلم المستوى المتوسط
 
تعليم الانجليزية بدون معلم المستوي المتوسط
تعليم الانجليزية بدون معلم المستوي المتوسطتعليم الانجليزية بدون معلم المستوي المتوسط
تعليم الانجليزية بدون معلم المستوي المتوسط
 
تعليم الإنجليزية بدون معلم الاساسيات
تعليم الإنجليزية بدون معلم الاساسياتتعليم الإنجليزية بدون معلم الاساسيات
تعليم الإنجليزية بدون معلم الاساسيات
 
تعليم الإنجليزية بدون معلم المستوي: المبادىء
تعليم الإنجليزية بدون معلم المستوي: المبادىءتعليم الإنجليزية بدون معلم المستوي: المبادىء
تعليم الإنجليزية بدون معلم المستوي: المبادىء
 
تعليم الفرنسية بدون معلم
تعليم الفرنسية بدون معلم  تعليم الفرنسية بدون معلم
تعليم الفرنسية بدون معلم
 
Learn french language
Learn french languageLearn french language
Learn french language
 
Learn italian language
Learn italian languageLearn italian language
Learn italian language
 
Protection and control, part 1
Protection and control, part 1Protection and control, part 1
Protection and control, part 1
 
Switchyards (outdoor substations), part 1
Switchyards (outdoor substations), part 1Switchyards (outdoor substations), part 1
Switchyards (outdoor substations), part 1
 
Computer Programming For Power Systems Analysts.
Computer Programming For Power Systems Analysts.Computer Programming For Power Systems Analysts.
Computer Programming For Power Systems Analysts.
 
How-to use off-the-shelf software packages to perform power systems analysis
How-to use off-the-shelf software packages to perform power systems analysisHow-to use off-the-shelf software packages to perform power systems analysis
How-to use off-the-shelf software packages to perform power systems analysis
 
Learning spanish language
Learning spanish languageLearning spanish language
Learning spanish language
 
Linux tips
Linux tipsLinux tips
Linux tips
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
A step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsA step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systems
 
Indoor & outdoor substations, an overview
Indoor & outdoor substations, an overviewIndoor & outdoor substations, an overview
Indoor & outdoor substations, an overview
 

Último

THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONTHEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONHumphrey A Beña
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceSamikshaHamane
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Celine George
 
Grade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptxGrade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptxChelloAnnAsuncion2
 
Earth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice greatEarth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice greatYousafMalik24
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxthorishapillay1
 
ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...
ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...
ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...JhezDiaz1
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptxmary850239
 
Barangay Council for the Protection of Children (BCPC) Orientation.pptx
Barangay Council for the Protection of Children (BCPC) Orientation.pptxBarangay Council for the Protection of Children (BCPC) Orientation.pptx
Barangay Council for the Protection of Children (BCPC) Orientation.pptxCarlos105
 
Judging the Relevance and worth of ideas part 2.pptx
Judging the Relevance  and worth of ideas part 2.pptxJudging the Relevance  and worth of ideas part 2.pptx
Judging the Relevance and worth of ideas part 2.pptxSherlyMaeNeri
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomnelietumpap1
 
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdfInclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdfTechSoup
 
How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17Celine George
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...Nguyen Thanh Tu Collection
 
Gas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxGas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxDr.Ibrahim Hassaan
 
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Celine George
 

Último (20)

THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATIONTHEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
THEORIES OF ORGANIZATION-PUBLIC ADMINISTRATION
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in Pharmacovigilance
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17
 
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptxYOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
YOUVE GOT EMAIL_FINALS_EL_DORADO_2024.pptx
 
Grade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptxGrade 9 Q4-MELC1-Active and Passive Voice.pptx
Grade 9 Q4-MELC1-Active and Passive Voice.pptx
 
Earth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice greatEarth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice great
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptx
 
ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...
ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...
ENGLISH 7_Q4_LESSON 2_ Employing a Variety of Strategies for Effective Interp...
 
4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx4.18.24 Movement Legacies, Reflection, and Review.pptx
4.18.24 Movement Legacies, Reflection, and Review.pptx
 
Barangay Council for the Protection of Children (BCPC) Orientation.pptx
Barangay Council for the Protection of Children (BCPC) Orientation.pptxBarangay Council for the Protection of Children (BCPC) Orientation.pptx
Barangay Council for the Protection of Children (BCPC) Orientation.pptx
 
Judging the Relevance and worth of ideas part 2.pptx
Judging the Relevance  and worth of ideas part 2.pptxJudging the Relevance  and worth of ideas part 2.pptx
Judging the Relevance and worth of ideas part 2.pptx
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choom
 
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
 
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptxLEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
 
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdfInclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
Inclusivity Essentials_ Creating Accessible Websites for Nonprofits .pdf
 
How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17How to Add Barcode on PDF Report in Odoo 17
How to Add Barcode on PDF Report in Odoo 17
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
 
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptxYOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
 
Gas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxGas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptx
 
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
Incoming and Outgoing Shipments in 3 STEPS Using Odoo 17
 

Motor protection

  • 1.
  • 2. Protection & Coordination Standards: NEMA & NEC
  • 7. Protection & Coordination Conductors for a single motor must have an ampacity of not less than 125% of the motor full-load current rating. Conductors that supply several motors must have an ampacity of not less than: (1) 125% of the highest rated motor FLC , plus (2) The sum of the FLCs of the other motors (on the same line). . The highest rated motor is the motor with the highest FLC from the standard. Determine the “other motors in the group” value by balancing the motor FLCs on the feeder being sized, then select the line that has the highest rated motor on it The motor branch-circuit short-circuit and ground-fault protective device must be capable of carrying the motor’s starting current. A branch-circuit short-circuit and ground-fault protective device protects the motor, the motor control apparatus, and the conductors against short circuits or ground faults Size overload protection devices based on the motor nameplate rating (this protects locked-rotor current damage to motor windings) . Branch-circuit conductors are protected against overloads by the overload device.
  • 8. Protection & Coordination Motor nameplates: To define the basic performance and mounting parameters of a motor, the National Electrical Manufacturers Association (NEMA) defines some basic design and dimensional parameters in NEMA Standard MG 1. These parameters are then coded onto the motor nameplate to give you a basic definition of what you have received. Manufacturers often include additional information to further define some key motor features. Section MG 1-10.40, "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors," of the NEMA standard requires that "The following minimum amount of information shall be given on all nameplates of single-phase and polyphase induction motors. For abbreviations, see MG 1-1.80." * Manufacturer's type and frame designation * Horsepower output.
  • 9. Protection & Coordination * Time rating. (intermitent, for how long or continuous.) * Maximum ambient temperature for which motor is designed. * Insulation system designation. * RPM at rated load. * Frequency. * Number of phases. * Rated load current. * Voltage. * Code letter for locked rotor kVA. * Design letter for medium motors. * NEMA nominal efficiency when required by MG 1- 12.55 * Service factor if other than 1.0. * For motors equipped with thermal protectors, the words "thermally protected" if the motor provides all the protection described in MG 1-12.52. * For motors rated above 1 hp equipped with over-temperature devices or systems, the words OVER TEMP. PROT.-." A type number as described in MG 1- 12.53 inserted in the blank would identify the protection type. The information on a motor nameplate can be arranged in categories. They are electrical inour, mechanical output, performance, safety and reliability
  • 10. Protection & Coordination Motor control centers: They come in various configurations. Their main purposes are to control (turn On & Off) the motors and provide protection to motors & connecting cables. The basic construction consists of an enclosure 90" high with widths & depths varying to accommodate the different components & devices packed into the enclosure. Such enclosures have: the 3-phase horizontal main bus, the risers, the barriers, the main incoming compartment (that would accommodate the lugs, the main switch or the main breaker), the different compartments complete with the back-plates & front compartment doors. The number of compartments per cubicle varies with the size of starters installed, the maximum is 6 or 7 (function of the design) & the minimum is 1. Motor control centers (MCCs) can be built back to
  • 11. Protection & Coordination back. The starters included in the MCCs may be wired according to any of the following standard designations: 1)EEMAC class I type A (no terminal blocks). 2)Class I type B (control wiring are brought to terminals in the starter unit). 3)Class I type C (no starter inter-wiring with the control & load wiring brought out to terminals at top or bottom of each section - cubicle- or to a master control section). 4)Class II type B (the control wires from each starter are brought to terminals in each unit with interlocking & inter-wiring between line-up units connected). 5)Class II type C (all wiring is brought to a master terminals section as class I type C but with interlocking & starters inter-wiring connected). The motor type, application and location affect the selection of the starters complete with their associated overload and short circuit protective devices. The full load current of a motor is the current required to produce the full load torque at rated speed. The locked-rotor current (inrush or starting) is the current drawn (from the power source) when the motor is first connected to the line (energized). It lasts over the acceleration period & it magnitude varies from 4 to 10 times the full load current.
  • 12. Protection & Coordination The speed of the SCIM depends on the number of poles of the motor & the frequency of the power supply. The output torque of the motor (which is the turning force) in lb-ft is equal (motor horsepower/motor revolution per minute) times 5252. The currents passing through the stator as well as the rotor windings of the motor cause an increase in the motor temperature (temperature rise over & above the ambient temperature). In general, the temperature rise produced at full load is not harmful, provided that the motor ambient temperature does not exceed 40oC. For each increase of 10oC above the rated (allowable) temperature of the motor (function of the insulation used for the windings & the iron laminations), the motor’s life is halved. Most motors have a continuous duty rating. Intermittent duty ratings are based on a fixed operating duration (5, 15, 30 or 60 minutes), after which the motor has to be stopped & left (allowed) to cool. If the motor is given a service factor, the motor is allowed to develop more than its rated HP. This increase in the output horsepower is equal the service factor (eg. 1.25, 1.15) minus 1 times the rated HP. Under such condition, no damage or deterioration of the insulation will occur. Jogging describes the repeated starting & stopping of the motor at frequent intervals (for short periods of time). Plugging of a motor means when a motor running in one direction is momentarily disconnected & reconnected to the source (in such a manner as to reverse its direction of rotation). This action will cause the motor to come to rest faster (than if one tries to brake it while running in the forward direction). The 3 common types of enclosures that a motor might have are the open drip proof (O.D.P.), the totally enclosed fan cooled (T.E.F.C.) and the explosion proof ones.
  • 13. Protection & Coordination A contactor is a 2-state device for repeatedly establishing & interrupting an electric power circuit. A magnetic contactor is a contactor activated by electromagnetic means (applied in ac circuits). The basic components of a contactor are: contact system, arc extinction devices, mechanical linkages between the contacts & the drive unit, the drive unit, the conductor connections & the frame. The electromagnet (for electromagnetic contactors) consists of, basically, a coil of wire placed on an iron core. The armature is mechanically connected to the contacts. When a contactor's armature is sealed-in, it means that it is held closely against the magnet yoke. When the coil is de-energized, thanks to the small air gap in the iron circuit, the armature drops out (opening the contacts). The contacts pressure corresponds to the rated current of the contactors.
  • 14. Protection & Coordination In order to reduce the heating produced by the changing of the magnetic flux, the magnets are built up of thin iron laminations. The hum is reduced through the use of shading ring (lag coil) in the pole; it is made of copper. The contacts make, break & carry the rated currents corresponding to the rating of the contactor. As mentioned previously, the most widely used industrial drives are the ac poly-phase induction motors having an average starting currents of 6 times their full load currents. In general, the starting motors currents have hardly any effect on the life of the contactor. The interrupting medium of low voltage contactor is air. The quality of contacts depends on the contact pressure as well as the properties of the contact material. An example for contact material is silver with additives like cadmium oxide. The rating structure of low voltage contactors (used in motor starters) is per EEMAC, the common sizes are 00 to 6 at 575 V, 3-phase supply, 2 HP to 400 HP motors. An example for a contactor continuous current rating for size 00 is 10 amperes (open) & 9 amperes (enclosed). Another example would be for size 6, where the continuous current rating would be 600 A (open) & 540 A (enclosed). The most common types of conrol diagrams used with motor control & protection circuits are the wiring (or connection) diagrams and the schematic (or the elementary) diagrams. In a 3-phase, 3-wire system, the motor circuit consists of 3 power lines (L1, L2 & L3). The motor terminals are identified as T1, T2 & T3. A manual starter consists primarily of a set of manually operated contacts & a motor overload-ensing device (melting alloy, bi-metallic or electronic type). Electro-magnetically operated ones are basically manual ones plus a solenoid for closing the power contacts. The magnet frame & armature assembly of the low voltage contactors are 1 of the following: clapper, plunger (vertical action) or bell crank.
  • 15. Protection & Coordination The combination motor controller consists of an externally operable circuit disconnecting means (a switch in series with Form II fuse for only short circuit protection or a circuit breaker with magnetic element protection only) in series with a magnetic motor controller (contactor plus overload or a relay that matches the motor heating curve), refer to sketch on page 50. The methods of starting a squirrel cage induction motor are: across the line (full voltage starting that provides the highest starting torque as well as the highest starting current & accelerates the load to full speed in the shortest possible time), auto- transformer, primary resistor, wye-delta starting & part winding.
  • 17. Protection & Coordination The second to the fifth methods, inclusive are termed reduced voltage motor starting methods. The selection of the reduced voltage method involves a co-ordination between the required starting torque & allowable starting current (this current overloads the circuit & may reduce the voltage - causing a sag - to other loads in the power distribution system). Certain starting methods necessitate that the motors would be built in certain ways. The starting torque varies with the square of the starting current (when reduced voltage methods - applying less than full line voltage to the motor during starting - are used, the starting current & torque will be lower). Contactors have to undergo certain tests to be qualified or approved by the bodies having jurisdiction like UL, CSA, IEC. The principle tests are: spacing between live parts & ground, temperature rise of coils, contacts & terminals, operating voltage range, overload capability, mechanical/electrical endurance & dielectric strength tests. The power (source connected) to the control circuit can be classified into: common control, separate control or control circuit transformer. It can come directly from the power feeding the (power) terminals of the motor, from an external source (d.c.- battery or a.c. station service transformer) or from a step-down control potential transformer connected to the supply line of the motor.
  • 19. Protection & Coordination Control panels can be built in different constructions depending on the environment and may include any or all of the following devices: contactors, breakers, switches, relays, push-buttons, selector switches, meters, pilot lights (filament or LED). These panels incorporate the logic (decision making), input & output devices. Motors are too sensitive to negative sequence currents generated when the voltage supplied to the motor is unbalanced or when a single-phase condition occurs. A sequence relay is used and is installed in the control panel. This relay can be of the negative sequence voltage sensing or the current sensing type. The type of the relay sensing technique dictates the location of the relay i.e. upstream or downstream the fault (to be sensed) for current sensing relays and downstream the fault for voltage sensing ones. The fused switch, the moulded case current limiting circuit breaker or the mccb plus the current limiter is used whenever the available short circuit current in the system is beyond the circuit breaker interrupting capacity. When it is required to limit the short circuit current (downstream) to a lower level than the available in the system, a switch/fuse combination is used with class J fuses (high rupture capacity current limiting fuses, 200 KA interrupting rating). Other fuse classes found in MCC line-ups are C & R. Programmable logic controllers (PLC) are used often to control motors and make decisions regarding starting, running & stopping the motors. They are usually in stalled in the MCC line-up.
  • 20. Protection & Coordination Protection of medium voltage motors:
  • 21. Protection & Coordination Medium voltage controllers: They consist of one or more contactors, each with 3 current limiting fuses, the draw-out mechanism, instrument transformers, meters, protective low voltage devices (relays), bus bars, barriers, shutters, operating coils, control transformers, auxiliary switches, activating levers & springs, the frame and the steel enclosure housing all these components. The enclosures may be front access (to be built back to back or to be installed against the wall) only or front & back access. Typical applications would include controlling & protecting the following equipment: squirrel cage induction motors (SCIM), including non-reversing, reversing & multi-speed, reduced voltage starters including autotransformer & reactor starting types, synchronous motors including brush-less & brush types, wound rotor motors, transformer & capacitor banks. For decades, medium-voltage motors were switched exclusively by air-break contactors. The design of air-break contactors has to allow for the large contact gap required (approximately 1.5 ") & for the arc chutes (as the arc has to be drawn & forced into the chutes to get elongated, cooled, having its resistance increased & extinguished). The arc is, generally, maintained for several 1/2 cycles, it restrikes after a current zero because the dielectric strength of the break (gap) recovers relatively slowly. As the arc is driven into the chute, its voltage rises sharply & the current amplitude decreases. At the instant of arc extinction, the phase angle between the current & voltage becomes zero and the voltage stressing the break becomes less severe. The second type of interrupting medium, used in motor controllers contactors, is vacuum. With vacuum contactors, the arc is confined to the
  • 22. Protection & Coordination contact gap (which is only a few millimeters as vacuum has a dielectric strength of 30 KV/mm). Arcs in vacuum can be classified into diffused (for currents less than 10 KA ) & constricted (for higher currents). When the short circuit current exceeds 10 KA, a transition occurs from the diffused to the constricted form of arc in vacuum. Overheating (which is one of the side effects of constricted arcs) can lead to restrikes. The two most commonly used contact shapes, of vacuum interrupters, are the disc & the hollow cylindrical ones. The latter would have inclined slits (to divert the current flowing away from the axial direction). The arc is driven along the circular end (contact end faces). The contact rings are beveled to push the arc outwards (toward the rim or edge of the
  • 23. Protection & Coordination circular contact). After contact separation, the metal vapour plasma fills the entire contact gap. Short recombination time of the charge carriers (in the contact gap zone) is one important property of the plasma. As the current decreases (on the short circuit current cycle heading toward zero), the carriers’ number decreases. After arc extinction, the remaining charge carriers recombine on the metal surface (contacts) and the gap (contacts break) de-ionizes pretty fast. After current zero, restriking is eliminated. The current carrying contacts experience minimum erosion. High number of operations (2 million) with up to 300 amperes motor load is possible. The arc energy is low as well as the arcing time (1/2 cycle). The heat dissipation is reasonable as the arc duration is short & the amount of heat generated is small i.e. no possibility of contact welding. Contact surface oxidization and contamination is not possible as the interior of the vacuum bottle is isolated from its surroundings (environment). Filler material (for the contact) is used in order to achieve lo current chopping levels (in the range of 0.3 ampere). To calculate the superimposed peak overvoltage due to current (arc chopping), use the following formula overvoltage = surge impedance times chopped current magnitude (where surge impedance = (Inductance / Capacitance) .5 ohms). The use of motor starters to control medium voltage motors, placed an emphasis on the ability of the series fuse to withstand current pulses (due to motor starting, inrush, currents). A fuse used in protection of electrical motors must fulfill the following requirements: 1)It should have a good a good withstand ability, in the 10 to 60 seconds zone, and it should act fast in the.1 to .01 seconds zone. 2)It should possess minimum values for the cut-off currents as well as for the current let through (I2t).
  • 24. Protection & Coordination 1)It should have the ability to interrupt all fault currents beyond the capability of the associated devices (the contactor) up to the maximum fault level of the system. 2)It should have the highest possible current rating (for a given fuse size) to allow for maximum utilization of space within associated equipment. The use of contactor/fuse combination may lead to smaller size cables (than with circuit breakers due to the fact of the limiting capability for the let through energy of the fuses). The fuse elements (used in motor protection fuses) have a straight through element with stress relief points (rather than a spirally wound filament on a core). In general, surge arresters are not required with vacuum contactors due to the fact that the cable distance between the contactor & the terminal box of the motor is quite short and shot cable lengths are used. Though, if multiple-reignition is expected, then surge arresters must be used and located close to the motors. Vacuum contactors are not suitable for use on direct current systems. De-rating of the motor controller units may be deemed necessary under abnormal operating conditions like altitude, frequency of power supply, temperature, exposure to fumes, dirt, humidity, etc. The table defining a medium voltage controller (contactor and fuse) will have the following data as a minimum: the contactor maximum continuous current, the interrupting capacity (at the specified KV), the designation, the voltage rating and range, the interrupting capacity of the fuse (in KA and MVA @ the rated voltage), the maximum HP motor rating (for the motor design, power factor, voltage, controller current rating), the dielectric withstand voltage (including BIL), the controller-type (full
  • 25. Protection & Coordination voltage, reversing vs. non-reversing or reduced voltage, auto transformer vs. reactor type). The medium voltage fuses for controllers can be defined when the following values are given: the motor locked rotor current, motor full load current & service factor, the maximum continuous current rating of the fuse inside the compartment, the fuse size, the peak current let through characteristics. The standard ratings for the medium voltage open (i.e. not installed in an enclosure) contactors are 400 & 800 amperes. The contactor rating is derated when installed in its compartment in the cubicle. For example, with one-high controller cubicle, the current ratings for the 800 & 400 amperes would be 720 & 360 amperes.
  • 28. Protection & Coordination Motor protection relays: A relay offering comprehensive protection may have but not limited to the following set of features: a. thermal protection (49) b. extended start protection /monitoring (accelerating time) (48) c. stalling protection (mechanical jam) d. number of starts limitation (66) e. short circuit protection (50P) f. ground (earth) fault protection (50/51G) g. winding RTD measurement/trip (38) h. negative sequence current detection (46) i. undervoltage protection (27) j. loss-of-load protection or under current (37) k. out-of-step protection (for synchronous motors only) (40) l. loss of supply protection (for synchronous motors only) (56) m. auxiliary supply supervision (59K) Motor thermal protection (protection against overload conditions/overheating): The majority of winding failures are either indirectly or directly caused by overloading (either prolonged or intermittent/cyclic), operation on unbalanced supply voltage (causing negative sequence current through the motor negative resistance), or single phasing (has the same effect as unbalance source), which all lead through excessive heating to the deterioration of the winding insulation until an electrical fault occurs.
  • 29. Protection & Coordination The generally accepted rule is that insulation life is halved for each 10° C rise in temperature above the rated value, modified by the length of time spent at the higher temperature. As an electrical machine has a relatively large heat storage capacity, it follows that infrequent overloads of short duration may not adversely affect the machine. However, sustained overloads of only a few percent may result in premature ageing and insulation failure. Furthermore, the thermal withstand capability of the motor is affected by heating in the winding (which function of the motor loading) prior to a fault. It is therefore important that the relay characteristic takes into account the extremes of zero and full-load pre-fault current known respectively as the 'Cold' and 'Hot' conditions. The relays, in general, offer the following choices to the user: • Thermal limit curves per NEMA standard, voltage dependent and customized • IEC 60255-8 Thermal overload curves • Current unbalance biasing (including the effect of negative sequence current in heating the motor) • Independent running and stopped exponential cooling curves • Optional RTD biasing of the Thermal Model to adapt to real-time temperature measurements • Compensation for Hot (when the motor is restarting and its temperature is higher than under cold starting condition)/cold motor conditions. In general, the relay thermal model integrates both stator and rotor heating and cooling into a single model. Extended start time protection:
  • 30. Protection & Coordination The relay function protects the motor from overheating in cases of abnormal loading during motor starts. The motor can be tripped if the motor does not reach a running condition within the programmable Motor Acceleration time. Stalling protection (mechanical jam): This function senses increased loading associated with process or load related faults causing the motor to jam or stall. A programmable delay setting can be used to allow the process to attempt clear itself before issuing a trip. Number of starts limitation (start inhibit): This function prevents starting of a motor when the motor is too hot and does not have a sufficient amount thermal capacity available to allow a start without being re-tripped. Short Circuit Protection: Motor short-circuit protection is often provided to cater for major stator winding faults and terminal flashovers. Short Circuit Overcurrent protection protects damage to the motor during a locked rotor condition. The relay provide for instantaneous overcurrent protection, the elements can be configured for protection, alarming, and control during locked rotor conditions. For motors fed by circuit breakers, a single definite time overcurrent relay element is all that is required for this purpose, set to about 125% of motor starting current. The time delay is required to prevent spurious operation due to CT spill currents, and is typically set at 100ms. Ground fault protection: One of the most common faults to occur on a motor is a stator winding fault. Whatever the initial form of the fault (phase-phase, etc.) or the cause (cyclic overheating, etc.),
  • 31. Protection & Coordination the presence of the surrounding metallic frame and casing will ensure that it rapidly develops into a fault involving earth. Therefore, provision of earth fault protection is very important. The type and sensitivity of protection provided depends largely on the system earthing. It is common, however, to provide both instantaneous and time-delayed relay elements to cater for major and slowly developing faults. Overtemperature protection: The crelay ould support RTD inputs that allow for configuring the Alarming and Tripping Temperature of each RTD, detecting RTD shorting conditions, and selecting RTD voting that requires more than one RTD to detect an over-temperature condition before it will issue a Trip command. The programmable RTD inputs can be used in monitoring the Stator, Bearing and the ambient temperatures. Each RTD input has 2 operational levels: alarm and trip. The relay could support RTD trip voting and provide open RTD failure alarming Negative sequence current detection: Unbalanced currents give rise to a negative sequence component in the stator current. The negative sequence current produces an additional flux which rotates at synchronous speed in the opposite direction of the rotor. The eddy currents which are induced in the rotor parts will have the double network frequency. During such sustained conditions, the temperature of the rotor may reaches high levels which accelerate the ageing of the insulation and cause mechanical stress on the rotating components. The relay calculates negative sequence current
  • 32. Protection & Coordination and compared it with the set operate value for the alarm and the trip function. Undervoltage protection: Motors may overheat or even stall when subjected to prolonged undervoltage conditions. Transient undervoltages will generally allow a motor to recover when the voltage is restored, unless the supply is weak. Motors fed by contactors have inherent undervoltage protection, unless a latched contactor is used. Where a specific undervoltage trip is required, a definite time undervoltage element is used. If two elements are provided, alarm and trip settings can be used. An interlock with the motor starter is required to block relay operation when the starting device is open, otherwise a start will never be permitted. The voltage and time delay settings will be system and motor dependent. They must allow for all voltage dips likely to occur on the system during transient faults, starting of motors, etc. to avoid spurious trips. As motor starting can result in a voltage depression to 80% of nominal, the voltage setting is likely to be below this value. Re-acceleration is normally possible for voltage dips lasting between 0.5-2 seconds, depending on system, motor and drive characteristics, and therefore the time delay will be set bearing these factors in mind. Loss-of-load protection or under current: The Undercurrent Protection element provides the ability of tripping the motor due to external conditions that can cause the load being pulled by the motor to drop below a pre-set level. This element is useful when the loss of the load results in a loss of cooling which will cause the asset to overheat. Loss-of-load protection has a number of possible functions. It can be used to protect a pump against becoming unprimed, or to stop a motor in case of a failure in a mechanical transmission (e.g. conveyor belt)/
  • 33. Protection & Coordination Out-of-step protection (for synchronous motors only): A synchronous motor may decelerate and lose synchronism (fall out-of-step) if a mechanical overload exceeding the peak motor torque occurs. Other conditions that may cause this condition are a fall in the applied voltage to stator or field windings. Such a fall may not need to be prolonged, a voltage dip of a few seconds may be all that is required. An out-of-step condition causes the motor to draw excessive current and generate a pulsating torque. Even if the cause is removed promptly, the motor will probably not recover synchronism, but eventually stall. Hence, it must be disconnected from the supply. The current drawn during an out-of-step condition is at a very low power factor. Hence a relay element that responds to low power factor can be used to provide protection. The element must be inhibited during starting, when a similar low power factor condition occurs. This can conveniently be achieved by use of a definite time delay, set to a value slightly in excess of the motor start time. The power factor setting will vary depending on the rated power factor of the motor. It would typically be 0.1 less than the motor rated power factor i.e. for a motor rated at 0.85 power factor, the setting would be 0.75. Loss of supply protection (for synchronous motors only): If the supply to a synchronous motor is interrupted, it is essential that the motor breaker be tripped as quickly as possible if there is any possibility of the supply being restored automatically or without the machine operator’s knowledge. This is necessary in order to prevent the supply being restored out of phase with the motor generated voltage.
  • 34. Protection & Coordination Two methods are generally used to detect this condition, in order to cover different operating modes of the motor. Auxiliary supply supervision (59K): This supervision may include any or all of the following: • Integrity of coils (monitoring continuously their resistance). In case coils are in a good condition, the output COIL OK will be activated. • Control voltage (supervision of low voltage). If voltage is correct, the output BREAKER VOLTAGE OK will be activated. • Checks the breaker control circuit. If both control voltage AND coils integrity are correct, then the output BREAKER CIRCUIT OK will be activated. Other protection functions that may be found in motor protection circuits : Stator Differential This relay provides Stator Differential Protection for fast clearing of stator phase faults. Advanced CT saturation detection algorithms as well as dual slope characteristic are incorporated for increased security during heavy faults. Underfrequency function: The underfrequency relay element will operate in the case of the supply failing when the motor is on load, which causes the motor to decelerate quickly. Typically, two elements are provided, for alarm and trip indications. The underfrequency setting value needs to consider the power system characteristics. In some power systems, lengthy periods of operation at frequencies substantially below normal occur, and should not result in a motor trip. The minimum safe operating frequency of the motor under load conditions must therefore be determined, along with minimum system frequency.