SlideShare uma empresa Scribd logo
1 de 108
Baixar para ler offline
High Performance
Chilled Water
Systems


       Mick Schwedler, PE, LEED® AP
       Manager
       Applications Engineering
       Trane
             © 2011 Ingersoll Rand
Normal Performance
Chilled Water Systems
 ASHRAE/IESNA 90.1 (LEED Prerequisite)

 System configuration

 Design parameters

 System control
ASHRAE Standard
90.1-2007 Purpose
        “… Provide minimum
        requirements for the energy-
        efficient design of buildings
        except low-rise residential
        buildings”
Purpose of
ANSI/ASHRAE/IESNA
Standard 90.1-2010
  To establish minimum energy
  efficiency requirements of buildings,
  other than low-rise residential
  buildings for:

1. design, construction, and a plan for
   operation and maintenance, and

2. Utilization of on-site renewable
   energy resources.
Publication and Final
Savings Estimates
 Performed by Pacific Northwest National
 Laboratory (PNNL)
   Savingsof 90.1-2010 compared to
    90.1-2004
   Savings shared are modeled as of
    January 2011
   Includeventilation changes in ASHRAE 62.1
    between 1999 and 2007 versions
90.1 Progress Indicator
 Including receptacle loads in modeling

 Including receptacle load in % savings
  calculation
                            Energy cost savings %   Energy savings
                                                          %
 Ventilation rate changes
   between 62.1-1999               24.0                 25.5
     and 62.1-2007
90.1 Progress Indicator
Excluding receptacle loads in % savings
calculation only

 Including receptacle loads in modeling

 Excluding receptacle load in % savings
  calculation               Energy cost savings %   Energy savings
                                                          %
 Ventilation rate changes
   between 62.1-1999               30.1                 32.6
     and 62.1-2007
LEED Energy and
Atmosphere
 LEED 2009
   10% energy cost savings beyond 90.1-2007

 LEED 2012
   Public Review 2: September 2011
     EA Prerequisite: 10% average energy cost and source
      energy savings beyond 90.1-2010 (new construction)
     EA Credit: Credit for reductions beyond 10%
90.1-2010
Chiller Efficiencies
Paths A & B                                     Before 1/1/2010            As of 1/1/2010c          Test
                                                                                                    Procedureb
  Equipment Type Size CategoryUnits                                   Path A           Path Bd
                                                Full              Full               Full
                                                Load     IPLV     Load     IPLV      Load IPLV ARI 550/590
                      <150 tons         EER     ≥9.562 ≥10.416 ≥9.562      ≥12.50     NA     NA
     Air-cooled
                      ≥150 tons         EER     ≥9.562 ≥10.416 ≥9.562      ≥12.75     NA     NA

                      <75 tons         kW/ton                     ≤0.780   ≤0.630   ≤0.800 ≤0.600
                       ≥75 tons and <           ≤0.790 ≤0.676
    Water Cooled                      kW/ton                      ≤0.775   ≤0.615   ≤0.790 ≤0.586
                       150 tons
Electrically Operated,
                       ≥150 tons and
Positive Displacement                 kW/ton    ≤0.717 ≤0.627 ≤0.680       ≤0.580   ≤0.718 ≤0.540
                       < 300 tons
                      ≥300 tons        kW/ton   ≤0.639 ≤0.571 ≤0.620       ≤0.540   ≤0.639 ≤0.490

                      <150 tons        kW/ton   ≤0.703 ≤0.669
                       ≥150 tons and                              ≤0.634   ≤0.596   ≤0.639 ≤0.450
    Water Cooled                       kW/ton   ≤0.634 ≤0.596
                       < 300 tons
Electrically Operated,
                       ≥300 tons and
     Centrifugal                       kW/ton                     ≤0.576   ≤0.549   ≤0.600 ≤0.400
                       < 600 tons               ≤0.576 ≤0.549
                      ≥600 tons        kW/ton                     ≤0.570   ≤0.539   ≤0.590 ≤0.400


                  Must meet both full and part load requirements
Heat rejection equipment
 Fan speed control 7.5 and
  greater
   Capability to operate at 2/3
    fan speed or less

 Exceptions
   Climates > 7200 CDD50
    (e.g. Miami)
   1/3 of fans on multiple fan
    application
Hydronic system
design and control
 Pump isolation

 Chilled and hot water reset if >300,000
  Btuh
   Exception: Variable flow systems that
    reduce pumping energy
90.1-2007
Hydronic System
Design & Control
These provisions apply if pump system
power > 10 hp:
   Must    be variable flow unless …
     Pump power ≤ 75 hp
     ≤ 3 Control valves

   Limit demand of individual variable-flow
    pumps to 30% of design wattage at 50%
    flow (e.g., use VSD)
     Pump head > 100 ft
     Motor > 50 hp
Waterside
Energy Recovery required
 Service Water Heating
   24 hrs per day and
   Heat rejection > 6 MMBtuh and
   SWH load 1 MMBtuh

 Recover smaller of
   60% of heat rejection
   Preheat water to 85°F
Configuration
  Normal Performance
  Chilled Water

         production
            pumps

                                      distribution
                                      pump
production
     loop


distribution
        loop
                      two-way valve
Design Parameters
Normal Performance
Chilled Water Plant
 ARI 550/590 Standard Conditions
   44°F chilled water
   2.4 gpm/ton chilled water (10°F T)
   3.0 gpm/ton condenser water
    (10°F [9.3] T)
Control
Normal Performance
Chilled Water Plant
 Chilled water distribution pump
  P at most remote load

 Cooling tower fans
   55°F (as cold as possible)

 Constant speed condenser water pumps



  All these “normal” assumptions will be examined
High Performance
Chilled Water Plants
 Standard high performance
     Reduced flow rates, increased ∆Ts
     Variable primary flow

 Advanced high performance
     Equipment capabilities
     System configurations
     System control
a history of
Chiller Performance
                          8.0                                                 centrifugal
                                                                              >600 tons
chiller efficiency, COP




                                                                              screw
                          6.0                                                 150-300 tons
                                                                              scroll
                                                                              <100 tons
                          4.0
                                                                              reciprocating
                                                                              <150 tons

                          2.0


                          0.0
                                    ASHRAE Standard 90            NBI    “best”
                                 90-75    90-75 90.1-89 90.1-99         available
                                (1977)   (1980)
chilled water plant design …
Provocation
Are our “rules of thumb” …

 44 F chilled water supply

 10 F T for chilled water system

 3 gpm/ton condenser water flow


  … in need of repair?
High Performance
Design Parameters
 ASHRAE GreenGuide and CoolTools™
   Chilled water T: 12°F to 20 °F
   Condenser water T:
    12°F to 18 °F (multi-stage)

 Kelly and Chan
   Chilled water T: 18°F
   Condenser water T: 14.2°F
    (3.6 - 8.3% energy savings in various
    climates)
chilled water plant …humid climate
Base Design: 450 Tons
 0.5% design             Coil, valve and chilled
  wet bulb: 78 F           water piping pressure
                           drop: 80 ft
 Entering condenser
  water temperature       Condenser water piping
  (ECWT): 85 F             pressure drop: 30 ft

 Evaporator and          Pump efficiency: 75%
  condenser               Pump motor
  temperature              efficiency: 93%
  differences: 10 F
traditional design …humid climate
System Energy
Consumption
                         350
Energy Consumption, kW




                         300

                         250

                         200

                         150                                              Tower
                                                                          Condenser Water Pump
                         100                                              Chilled Water Pump
                                                                          Chiller (100% Load)
                         50

                          0
                                                2.4/3.0

                               Chilled / Condenser Water Flows, gpm/ton
traditional vs. low-flow design …
System Summary At
Full Load
                         350
Energy Consumption, kW




                         300

                         250

                         200

                         150                                              Tower
                                                                          Condenser Water Pump
                         100                                              Chilled Water Pump
                                                                          Chiller (100% Load)
                         50

                          0
                                     2.4/3.0               1.5/2.0

                               Chilled / Condenser Water Flows, gpm/ton
comparison …humid climate
System Summary At
75% Load
                         350
Energy Consumption, kW




                         300

                         250

                         200

                         150                                              Tower
                                                                          Condenser Water Pump
                         100                                              Chilled Water Pump
                                                                          Chiller (75% Load)
                         50

                          0
                                     2.4/3.0               1.5/2.0

                               Chilled / Condenser Water Flows, gpm/ton
comparison …humid climate
System Summary At
50% Load
                         350
Energy Consumption, kW




                         300

                         250

                         200

                         150                                              Tower
                                                                          Condenser Water Pump
                         100                                              Chilled Water Pump
                                                                          Chiller (50% Load)
                         50

                          0
                                     2.4/3.0               1.5/2.0

                               Chilled / Condenser Water Flows, gpm/ton
comparison …humid climate
System Summary At
25% Load
                         350
Energy Consumption, kW




                         300

                         250

                         200

                         150                                              Tower
                                                                          Condenser Water Pump
                         100                                              Chilled Water Pump
                                                                          Chiller (25% Load)
                         50

                          0
                                     2.4/3.0               1.5/2.0

                               Chilled / Condenser Water Flows, gpm/ton
traditional vs. low-flow design
…humid climate
Savings Summary
                                20.0
    Operating Cost Savings, %



                                       16.5%



                                               10.3%
                                10.0

                                                              6.7%
                                                                     3.8%


                                   0
                                        25%     50%           75%    100%

                                                       Load
High Performance
Design Parameters
 kWh/ton/year


                600
                                                Chilled water
                400                             pump
                200                             Chiller

                 0
                      41/16 42/14 43/12 44/10
                      Chilled water supply
                      temperature/DeltaT
Pipe Size Example
90.1-2010 Table 6.5.4.5
 800 ton system

 3,000 hours of operation

 Chilled water, variable flow

 Condenser water, constant flow

                  Past Design      ASHRAE GreenGuide
                   Practice
              ∆T     Flow   Pipe    ∆T     Flow   Pipe
             (°F)   (gpm)   Size   (°F)   (gpm)   Size
 Chilled     10      1920    10     16    1200     8
 Water
 Condenser   9.4     2400    14     14    1600    12
 Water
High Performance
Design Options
Either …

 Take full energy (operating
 cost) savings

Or …

 Reduce piping size and cost
  Experienced designers use pump,
  piping and tower savings to select an
  even more efficient chiller
Reduced flow works for
all chiller manufacturers
 Logan Airport - Boston:
    $426,000 Construction cost savings
    7.3% operating cost savings

 Large Chemical Manufacturer -Greenville
    $45,000 Excavation and concrete savings
    6.5% Operating cost savings

 Computer Manufacturer - San Francisco
    Existing tower, pipe savings
    2% Operating cost savings (tower not changed)
Low flow works for
retrofit applications
 Chilled water side
    Coil
       It’s a simple heat transfer device
       Reacts to colder entering water
        by returning it warmer




    Ideal for system expansion
Low flow works for
retrofit applications
        Condenser side retrofit opportunity
    Chiller needs to be
     replaced
    Cooling needs have
     increased by 50%
    Cooling tower was
     replaced two years ago
    Condenser pump and
     pipes are in good shape
Condenser side
retrofit opportunity

                                Existing   Retrofit
     Capacity (tons)              500        750
     Flow rate (gpm)             1500       1500
     Condenser Entering Water     85         88
     Temperature (F)
     Condenser Leaving Water      95         103
     Temperature (F)
     Design Wet Bulb (F)         78         78
Humid climates
Low flow works for
short piping runs too
  Condenser Water Side Only - original
                              350.0


                              300.0
   Energy Consumption (kWh)




                              250.0


                              200.0
                                                                     3.0 gpm/ton
                                                                     2.0 gpm/ton
                              150.0


                              100.0


                               50.0


                                0.0
                                      25%   50%         75%   100%
                                              System Load
Humid climates
Low flow works for
short piping runs too
                                      Condenser Water Side Only
                                      ZERO piping pressure drop
                              350.0


                              300.0
   Energy Consumption (kWh)




                              250.0


                              200.0
                                                                       3.0 gpm/ton
                                                                       2.0 gpm/ton
                              150.0


                              100.0


                               50.0


                                0.0
                                        25%   50%         75%   100%
                                                System Load
High Performance
Design Parameters
 Low flow benefits systems - no
  matter whose chiller is being
  used

 Low flow works extremely
  well on existing systems

 Low flow works on short
  piping runs
always, always,
Always Remember …
Oh, by the way...

You may also do this with air
Variable-Primary-Flow
    Systems
variable-flow
      pumps



     check
     valves
                control
                valve
VPF Savings
 First cost: 4-8%

 Annual energy: 3-8%

 Life-cycle cost: 3-5%




      http://www.arti-21cr.org/ARI/util/showdoc.aspx?doc=1085
Flow requirements
VPF System
 Limits (consult manufacturer)
    Absolute flows - Minimum and maximum
    Flow rate changes
      2% of design flow per minute
       not good enough
      10% of design flow per minute borderline
      30% of design flow per minute
       many comfort cooling applications
      50% of design flow per minute
       best

 Always need a way to ensure minimum
  flow (bypass)
Chiller Control
                                                               V a ria b le W a te r F lo w

                    130                                                                                                       1500


                    120                                                                                                       1300


                    110                                                                                                       1100


                    100                                                                                                       900
Water Temp [degF]




                     90                                                                                                       700
                                                                                    E vaporator W ater F low




                                                                                                                                     Flow [gpm]
                     80                                                                                                       500


                     70                                                                                                       300


                     60                                                                                                       100


                     50        E vap E ntering W ater T em p                                                                  -100


                     40                                                                                                       -300
                               E vap Leaving W ater T em p

                     30                                                                                                       -500
                     3:50:00              3:55:00                           4:00:00                            4:05:00   4:10:00
                                                                   T im e (h o u r:m in :s e c )
More information
VPF System
 Http:/trane.com/commercial
  /library/newsletters.asp (1999 and 2002)

 “Primary-Only vs. Primary-Secondary Variable Flow
  Systems,” Taylor, ASHRAE Journal, February 2002

 “Don’t Ignore Variable Flow,” Waltz, Contracting
  Business, July 1997

 “Comparative Analysis of Variable and Constant
  Primary-Flow Chilled-Water-Plant Performance,”
  Bahnfleth and Peyer, HPAC Engineering, April 2001

 “Campus Cooling: Retrofitting Systems,”
  Kreutzmann, HPAC Engineering, July 2002
High Performance
Chilled Water Plants
 Standard high performance
     Reduced flow rates, increased ∆Ts
     Variable primary flow

 Advanced
     Equipment capabilities
     System configurations
     System control
Equipment Capabilities
High Performance
Chilled Water Plant
 Constant speed
   0.570 FL / 0.479 IPLV

 Higher efficiency “same price” options
   Variable speed (spend money on drive)
   Constant speed (spend money on copper)

 Purchase both a drive and more heat
  exchange surface

 Down to 0.45 kW/ton FL available (22%
  reduction)
Same-price Chiller:
Example Performance
      Option      Full Load  IPLV
                  (kW/ton) (kW/ton)
VSD                0.572    0.357
High Efficiency    0.501    0.430
Same-price Chiller:
Example Performance
                 600-ton Replacement Chiller Performance

      400
      350
      300
                                                     High_efficiency_85°F
      250                                            VSD_85°F
                                                     High_efficiency_75°F
 kW




      200
                                                     VSD_75°F
      150                                            High_efficiency_65°F
                                                     VSD_65°F
      100
      50
        0
            0%    20%    40%    60%    80%   100%
                           % Load
Example
 Office building

 Two 400-ton chillers

 Comparisons
   Base system - constant speed
   AFD on both chillers
   High efficiency for both chillers
   AFD on one chiller
   High efficiency for one chiller
What is the actual
utility rate?
 Utility costs
   ‘Combined’ utility rates ($0.10 / kWh)
   Actual utility rates ($12 / kW and $0.06 /
    kWh)
Utility rate comparison
    Simple paybacks, humid climate

                                     Combined rate   Actual rate


     on one      AFD                      6.1          10.8
     chiller
                 High efficiency          6.3            7.7

      on both AFD                         7.2          12.7
      chillers
               High efficiency            7.1            8.3



          Using incorrect “combined” rate
            leads to incorrect decisions
Rule 1
 Use actual utility rates
Temperate climate
with economizer
  Annual operating cost                                                           Simple payback

  $100,000                                                                                      30

   $80,000                                                                                      25
                                                                                                20
   $60,000
                                                                                                15
   $40,000
                                                                                                10
   $20,000                                                                                      5

                                                                                                0
                Base case         AFD on      High efficiency    AFD on       High efficiency
                                both chillers  both chillers    one chiller     one chiller


                   Chiller plant operating cost
                   Simple payback
Temperate climate,
no economizer
  Annual operating cost                                                           Simple payback

  $100,000                                                                                      12

   $80,000                                                                                      10
                                                                                                8
   $60,000
                                                                                                6
   $40,000
                                                                                                4
   $20,000                                                                                      2

                                                                                                0
                Base case         AFD on      High efficiency    AFD on       High efficiency
                                both chillers  both chillers    one chiller     one chiller


                   Chiller plant operating cost
                   Simple payback
Humid climate,
no economizer
  Annual operating cost                                                           Simple payback

  $100,000                                                                                      14

   $80,000                                                                                      12
                                                                                                10
   $60,000
                                                                                                8
   $40,000
                                                                                                6
   $20,000                                                                                      4

                                                                                                2
                Base case         AFD on      High efficiency    AFD on       High efficiency
                                both chillers  both chillers    one chiller     one chiller


                   Chiller plant operating cost
                   Simple payback
Dry climate with
economizer
  Annual operating cost                                                           Simple payback
  $100,000                                                                                      18
                                                                                                16
   $80,000                                                                                      14
                                                                                                12
   $60,000                                                                                      10
                                                                                                8
   $40,000
                                                                                                6
                                                                                                4
   $20,000
                                                                                                2
                                                                                                0
                Base case         AFD on      High efficiency    AFD on       High efficiency
                                both chillers  both chillers    one chiller     one chiller


                   Chiller plant operating cost
                   Simple payback
Rule 2
      Model ROI of
     each investment
Guidance:
VSD or High Efficiency?
 High efficiency                  VSD
      Significant demand              Many hours at low
       charges, especially              condenser water
       ratchet charges                  temperature – and low
                                        load
      Climates where the
       wet bulb doesn’t vary           Perhaps only on one
       substantially                    chiller
      Multiple chillers in the        Factor replacement
       plant                            cost of VSD when
                                        performing life cycle
      Economizer that                  assessment
       reduces low load/low
       lift operating hours
High Performance
Chilled Water Plants
 Standard high performance
     Reduced flow rates, increased ∆Ts
     Variable primary flow

 Advanced
     Equipment capabilities
     System configurations
     System control
VPF System
Minimum flow and bypass control

                         Single chiller

                         Retrofit


     Controller




                                      P
                                       P
What may not be a
good VPF application?
 Two packaged chillers
    Limited evaporator configurations
    Assume minimum flow is about 1.2 gpm/ton

 In parallel

 Wide ∆T (low flow)
    e.g 18°F ∆T is 1.33 gpm/ton

 Why isn’t it a good application?
    Flow can only be turned down 10%
Variable-Volume Pumping System
     (series chillers)
                                       48.4°F
Upstream chiller operating at higher
   temperature is more efficient




                                                41°F
  57°F



              Bypass alternatives
Series Chillers
           Manual service bypass
Series Chiller
Advantages
 Simplifies pumping and  Simple preferential
  sequencing               loading of chillers
    No flow rate transitions    Adjust upstream
                                  chiller’s setpoint
    Makes VPF simple
                                    Upward to unload
                                    Downward to load
 Upstream chiller
  operates at elevated
  temperature
    Efficiency increases
    Capacity increases
       10% or more for
        absorption
High Performance
Chilled Water Plants
 Standard high performance
     Reduced flow rates, increased ∆Ts
     Variable primary flow

 Advanced
     Equipment capabilities
     System configurations
     System control
Control
Normal Performance
Chilled Water Plant
 Chilled water distribution pump
  P at most remote sensor

 Cooling tower fans
   55°F (as cold as possible)
   Somewhere else

 Constant volume condenser water pumps
High Performance
  Chilled Water Pump
  Control




Communicating
    BAS                                       Pump
                Pump Speed   Valve position
                                              Pressure
                                              Sensor
pump-pressure optimization
Control Logic
90.1-2007 Addendum ak


                           Increase pump static pressure setpoint
                     75%

Position (% open)
 of critical valve           No action

                     65%

                           Reduce pump static pressure setpoint
High Performance
Chiller-Tower Control
                                                                       Plant Power vs CWS
                                                                                                                  Chillers cannot meet load
                1,200.0
                               Lowest condenser water                                                             above this condenser water
                               temperature available from                                                         temperature
                               tower at this load and wet-bulb
                               temperature
                1,000.0
                                                                                1,550 tons, 65°F Wet-bulb
                                                                                T        t

                 800.0


                                               1,160 tons, 59°F Wet-bulb
   Power (kW)




                                               T
                 600.0


                                 730 tons, 54°F Wet-bulb Temperature

                 400.0                                                                           Optimal operation



                 200.0




                    0.0
                          60


                                   62


                                          64


                                                    66


                                                           68


                                                                  70


                                                                           72


                                                                                     74


                                                                                            76


                                                                                                    78


                                                                                                            80


                                                                                                                 82


                                                                                                                       84


                                                                                                                             86


                                                                                                                                    88
                                                                       Condenser Water Setpoint (°F)



                                     Hydeman, et. al. Pacific Gas and Electric. Used with permission.
Cooling tower basics
Fan energy consumption
% Full load power
            100


             80


             60



             40


             20


              0
                  0           20   40   60   80   100
                  % Airflow
cooling tower performance factors
Approach and Wet Bulb
                         16.0
   tower approach, deg




                         12.0


                          8.0
                                                        100% load
approach = 9
                          4.0                           50% load

                                                   approach = 4
                          0.0
                                50    60      70       80
                                ambient wet bulb, °F
simple case: constant water flow
Operating Dependencies




  Wet bulb                Load
  Condenser water         Condenser water
   temperature             temperature
  Load                    Chiller design
  Tower design
condenser water control
“Normal” Setpoint
            Hot?
             e.g., 85°F, minimizes tower
             energy consumption

            Cold?
             e.g., 55°F, minimizes chiller
             energy consumption

            Optimized?
optimal condenser water control
Chiller–Tower Interaction
                         400
                                total
energy consumption, kW




                         300

                                chiller
                                                     optimal
                         200                       control point


                         100
                                tower


                           0
                               72       74   76     78      80     82     84
                                        condenser water temperature, °F
High Performance
Chiller-Tower Control
 Braun, Diderrich

 Hydeman, Gillespie,
  Kammerud

 Schwedler,
  ASHRAE Journal

 Cascia

 Crowther and
  Furlong
chiller–tower optimization
An Example …
                720,000 ft² hotel

                2 chillers, 2 tower cells

                Control strategies
                   Make leaving-tower water cold
                    as possible (55F)
                   Optimize system operation
                   Entering-condenser setpoint
                    equals design …
                     85°F for humid climates
                     80°F for dry climates
chiller–tower control strategies
    North America
                               350K
                                                                control strategy:
annual operating cost, $ USD




                               300K                                55°F lvg tower
                                                                   optimal control
                               250K
                                                                   design ECWT

                               200K

                               150K

                               100K

                               50K

                                  0
                                      Mexico City   Orlando   San Diego    Toronto
chiller–tower control strategies
    Global Locations
                               500K
                                              control strategy:
annual operating cost, $ USD




                                                 55°F lvg tower
                                                 optimal control
                               400K
                                                 design ECWT


                               300K


                               200K


                               100K


                                  0
                                      Dubai   Paris     Sao Paulo Singapore
operating cost savings, %




     0
             2
                   4
                         6
                             8
                                 10
                                      12
           Dubai                           14



           Paris



           Sao Paulo



           Singapore



           Mexico City


location
                                                                   chiller–tower optimization




           Orlando



           San Diego
                                                Operating Cost Savings




           Toronto
chiller–tower optimization
Perspective on Savings
For centrifugal chillers ≥ 300 tons, ASHRAE
90.1 requires …
     0.576 kW/ton at full load
     0.549 kW/ton at IPLV

… using ARI standard rating conditions
chiller–tower optimization
    Perspective on Savings
             Equivalent
Savings, %   chiller efficiency

   0.0       0.576

   2.8       0.560

   4.5       0.550

   6.2       0.540

 14.0        0.495
Where’s the Meter?
           On the
           BUILDING
chiller–tower optimization
Finding “Near Optimal”
 Tower design
  (flow rate, range, approach)

 Chiller design
    Refrigeration cycle
     (vapor compression vs. absorption)
    Compressor type
    Capacity control (variable-speed drive)

 Changing conditions
  (chiller load, ambient wet bulb)
chiller–tower optimization
Necessities
                      System-level
                       controls

                      Variable-frequency
                       drive
                       on tower fans

                      High-quality
                       dewpoint sensor
Number of chillers
operating
 Operate one at nearly full load or two at
  part load?

 Examine IPLV assumptions
VSDs and centrifugal chillers
A Closer Look at IPLV
Load        Weighting            ECWT         kW/Ton

100%            0.01              85°F          0.572

 75%            0.42              75°F          0.420

 50%            0.45              65°F          0.308

 25%            0.12              65°F          0.372
VSDs improve part-lift performance, so running two chillers
with VSDs at part load seems more efficient than one chiller at
double the same load, but …is dependent on condenser water
temperature
Chiller power only
             45% Plant load
                   Operate 1 or 2 Chillers?
                   Chiller kW Only
             350
                       1@90% Load
             300
                       2@45% Load
             250
Chiller kW




             200

             150

             100

              50

               0
                       55            60     65       70       75      80      85
                                     Available Tower Water Temperature (ºF)
Chillers plus pumps
  45% Plant load
                             Operate 1 or 2 Chillers?
                             Chiller Plus Pump kW
                       400
                                 1@90% Load
                       350
Chiller Plus Pump kW




                                 2@45% Load
                       300
                       250
                       200
                       150
                       100
                        50
                         0
                                55        60        65     70      75       80      85
                                           Available Tower Water Temperature (ºF)
Operate 1 or 2 chillers?
                                   Run 1 or 2 VSD Chillers?
                             400
                                                                                                           1@90% Load
                             350                                                                           2@45% Load
                                                                                                           1@80% Load
                                        Operate multiple chillers here,
                             300                                                                           2@40% Load
Total Chiller Plus Pump kW




                                        otherwise single chiller
                                                                                                           1@70% Load
                             250                                                                           2@35% Load
                                                                                                           1@60% Load
                             200
                                                                                                           2@30% Load
                                                                                                           1@50% Load
                             150
                                                                                                           2@25% Load
                             100

                              50

                               0
                                   60              65            70              75              80   85
                                                        Available Tower Water Temperature (ºF)
Operate 1 or 2 chillers?
 45% plant load: One chiller until tower
 temperature is < 65°F

 40% plant load: One chiller until tower
 temperature is < 60°F

 35% plant load and below: One chiller
High Performance
Condenser Water Pump
Control – Variable?
 Pump speed limits
   Tower static lift
   Tower nozzles (minimum flow)
   Condenser minimum flow

 Pump speed reductions result in
   Increased leaving condenser water
    temperature
   Decreased cooling tower effectiveness
   Possible chiller surge
High Performance
Condenser Water Pump
Control – Variable?
 The condenser water pump is the hardest
  place to properly utilize a variable frequency
  drive during operation

 There are successful installations
variable-flow condenser water
Pump Speed
 Determining minimum speed

 Variable flow affects:
   Pump
   Cooling tower
   Chiller
condenser water pump
Minimum Speed
Determinants:

 Minimum condenser flow
 Tower static lift
 Minimum tower flow
   Nozzle selection
   Performance
reducing flow & fan speed
   Effect on System
                         fan speed
                   300


                   250
system power, kW




                   200


                   150

                                     conditions:
                   100
                                     • 70% load
                                     • 50°F WB
                    50


                     0
                      50       60    70      80     90   100
                               condenser water flow, %
Varying fan and pump
speed together
variable condenser water flow
Guidance
 Can provide savings …
   Finding proper operating
    points requires more time,
    more fine-tuning

 Two-step process:
  1 Reduce design pump power
  2 Is variable condenser-water
    flow still warranted?
ROI
High Performance
Chilled Water Plants

 EnergyPlus

 Non-bin

 Schematic
 tools that
 analyze in 30-
 45 minutes
 are available
High Performance
Chilled Water Plants
 Standard high performance
     Reduced flow rates, increased ∆Ts
     Variable primary flow

 Advanced high performance
     Equipment capabilities
     System configurations
     System control
High performance chilled water plant
Winchester Medical
Center
Medical Center
Winchester, Virginia
 Five 750-ton chillers        VFD’s on
    0.571 kW/ton full load       Chilled water pumps
    Chilled water                Cooling tower fans
     58 to 42°F
                                  Condenser water
    Condenser water               pumps
     84 to 95°F
     (missed opportunity)      Sophisticated control
                                system with lots of
    VFD’s
                                  Programming
 Variable primary flow
                                  Commissioning
 Owner
                                                                                                                                                                                                                                                        Center


                                                                                                                                                                                                            Operators




                              Service provider
                                                                                                                                                                                                                                    Working together




                                                   Controls provider
                                                                                                               Equipment provider
                                                                                                                                                                                    Consulting engineer


                                                                                                                              Load (tons)
                                                               8/
                                                                  8/
                                                                     2
                                                               8/ 00 3
                                                                  8/2 1
                                                                            4
                                                                                     0.0
                                                                                              200.0
                                                                                                             400.0
                                                                                                                            600.0
                                                                                                                                                    800.0
                                                                                                                                                                   1000.0
                                                                                                                                                                                    1200.0
                                                                                                                                                                                               1400.0




                                                               8/8 00 3 :30
                                                                   /2 1 3
                                                               8/ 00 3 :30
                                                                  8/
                                                                     2 12
                                                               8/ 00 3 :30
                                                                  8/2 1
                                                                       0 1:3




 Applications engineering
                                                                8/8 0 3 1 0
                                                                     /2 0:3
                                                                8/ 00 3 0
                                                                   8/
                                                                       20 9 :3
                                                                8/ 0 3 0
                                                                   8/2 8
                                                                              :3
                                                                8/8 00 3 0
                                                                     /2 7 :3
                                                                8/ 00 3 0
                                                                   8/
                                                                       2 6 :3
                                                                8/8 00 3 0
                                                                     /2 5 :3
                                                                8/8 00 3 0
                                                                     /2 4 :3
                                                                8/ 00 3 0
                                                                   8/
                                                                       2 3 :3
                                                                8/8 00 3 0
                                                                     /2 2 :3
                                                                8/8 00 3 0
                                                                     /      1
                                                               8/ 200 :3 0
                                                   Time/Date




                                                                  7/2 3
                                                                            0
                                                               8/7 00 3 :3 0
                                                                   /2 2 3
                                                               8/ 00 3 :30
                                                                  7/
                                                                     20 2 2
                                                               8/       0 3 :30
                                                                  7/2 2
                                                                            1
                                                               8/7 00 3 :30
                                                                   /2 2 0
                                                                       0
                                                               8/ 0 3 :30
                                                                  7/
                                                                     2 19
                                                               8/7 00 3 :30
                                                                   /2 1 8
                                                               8/7 00 3 :30
                                                                   /2 17
                                                                                                                                                                                                                                                        Winchester Medical




                                                               8/ 00 3 :30
                                                                  7/
                                                                     20 1 6
                                                                        0 3 :30
                                                                           15
                                                                              :3
                                                                                 0
                                                                                     0.00
                                                                                            0.10
                                                                                                      0.20
                                                                                                                     0.30
                                                                                                                                         0.40
                                                                                                                                                            0.50
                                                                                                                                                                            0.60
                                                                                                                                                                                        0.70
                                                                                                                                                                                               0.80




                                                                                                                       Efficiency (kW/ton)
                                                                                                                                             tons
                                                                                                                                    kW/ton
Load (tons)
            8/
               8/
                  2
            8/ 00 3
               8/
                  2 14




                                 0.0
                                          200.0
                                                         400.0
                                                                        600.0
                                                                                                800.0
                                                                                                               1000.0
                                                                                                                               1200.0
            8/ 00 3 :30
               8/                                                                                                                         1400.0
                  2 13
            8/ 00 3 :30
               8/
                  2 12
            8/ 00 3 :30
               8/
                  20 1 1
                    0 :
             8/ 3 1 30
                8/
                   2 0:
             8/ 00 3 30
                8/
                   20 9 :3
             8/ 0 3 0
                8/
                   2 8 :3
             8/ 00 3 0
                8/
                   2 7 :3
             8/ 00 3 0
                8/
                   2 6 :3
             8/ 00 3 0
                8/
                   2 5 :3
             8/ 00 3 0
                8/
                   2 4 :3
             8/ 00 3 0
                8/
                   2 3 :3
                                                                                                                                                   Chiller plant




             8/ 00 3 0
                8/
                   2 2 :3
             8/ 00 3 0
                8/       1
            8/ 200 :3 0




Time/Date
               7/
                  2    3
                         0
            8/ 00 3 :3 0
               7/
                  2 23
            8/ 00 3 :30
               7/
                  2 22
            8/ 00 3 :30
               7/
                  2 21
            8/ 00 3 :30
               7/
                                                                                                                                                   WMC - August 12




                  2 20
            8/ 00 3 :30
               7/
                  2 19
            8/ 00 3 :30
               7/
                  2 18
            8/ 00 3 :30
               7/
                  2 17
            8/ 00 3 :30
               7/
                  20 1 6
                    0 3 :30
                       15
                           :3
                             0
                                 0.00
                                        0.10
                                                  0.20
                                                                 0.30
                                                                                     0.40
                                                                                                        0.50
                                                                                                                        0.60
                                                                                                                                   0.70
                                                                                                                                          0.80




                                                                   Efficiency (kW/ton)
                                                                                         tons
                                                                                kW/ton
Tons




                        0.0
                               200.0
                                       400.0
                                               600.0
                                                         800.0
                                                                 1000.0
                                                                          1200.0
                                                                                   1400.0
                                                                                            1600.0
        1/0/1900 0:00
        1/0/1900 0:00
        1/0/1900 0:00
        1/0/1900 0:00
        1/0/1900 0:00
       9/1/2003 14:00
       9/1/2003 19:30
        9/2/2003 1:00
        9/2/2003 6:30
       9/2/2003 12:00
       9/2/2003 17:30
       9/2/2003 23:00
        9/3/2003 4:30
                                                                                                     Chiller plant




       9/3/2003 10:00
       9/3/2003 15:30
       9/3/2003 21:00




Time
        9/4/2003 2:30
        9/4/2003 8:00
                                                                                                     WMC - Sept 1-7




       9/4/2003 13:30
       9/4/2003 19:00
                                                                                                      Weekly-Summary




        9/5/2003 0:30
        9/5/2003 6:00
       9/5/2003 11:30
       9/5/2003 17:00
       9/5/2003 22:30
        9/6/2003 4:00
        9/6/2003 9:30
       9/6/2003 15:00
       9/6/2003 20:30
        9/7/2003 2:00
        9/7/2003 7:30
                        0.00
                               0.10
                                       0.20
                                               0.30
                                                         0.40
                                                                 0.50
                                                                          0.60
                                                                                   0.70
                                                                                            0.80




                                                       kW/ton
                                                       tons
                                                       kW/ton
Winchester Medical
Center - Mark Baker
    “Please use our data,
     names, etc. We're
     proud of our facility!”
    “By the way, we're
     now operating @
     -0.20 kW/ton. The
     power company just
     sent us our 1st check.
     Ha..Ha…”
Remember...

     Without controls,
     it’s not a system.
The meter is on the
building!
It’s a great time to
be in this business!

Mais conteúdo relacionado

Mais procurados

Mais procurados (20)

Trane design chiller.pdf
Trane design chiller.pdfTrane design chiller.pdf
Trane design chiller.pdf
 
Refrigeration and Air conditioning
Refrigeration and Air conditioningRefrigeration and Air conditioning
Refrigeration and Air conditioning
 
Steam Condenser performance and loss diagnostic
Steam Condenser performance and loss diagnosticSteam Condenser performance and loss diagnostic
Steam Condenser performance and loss diagnostic
 
REFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONINGREFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONING
 
Steam turbine
Steam turbineSteam turbine
Steam turbine
 
Air refrigeration systems
Air refrigeration systemsAir refrigeration systems
Air refrigeration systems
 
cooling tower
cooling towercooling tower
cooling tower
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginers
 
Fbc boilers
Fbc boilersFbc boilers
Fbc boilers
 
Compressor and Types
Compressor and TypesCompressor and Types
Compressor and Types
 
Multi pressure system in VCRS
Multi pressure system in VCRSMulti pressure system in VCRS
Multi pressure system in VCRS
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
Cooling tower
Cooling towerCooling tower
Cooling tower
 
Boilers ppt (energy conversion)
Boilers ppt (energy conversion)Boilers ppt (energy conversion)
Boilers ppt (energy conversion)
 
Refrigerant condenser and its types
Refrigerant condenser and its typesRefrigerant condenser and its types
Refrigerant condenser and its types
 
Efficient Steam Systems -
Efficient Steam Systems -Efficient Steam Systems -
Efficient Steam Systems -
 
Air Conditioning & Hvac Systems
Air Conditioning & Hvac SystemsAir Conditioning & Hvac Systems
Air Conditioning & Hvac Systems
 
Vapor Compression Refrigeration System
Vapor Compression Refrigeration System Vapor Compression Refrigeration System
Vapor Compression Refrigeration System
 
Construction of 500 MW Steam Boiler
Construction of 500 MW Steam BoilerConstruction of 500 MW Steam Boiler
Construction of 500 MW Steam Boiler
 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
 

Destaque

Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled AirconditioningAljon Altiche
 
Hvac chilled water distribution schemes
Hvac chilled water distribution schemesHvac chilled water distribution schemes
Hvac chilled water distribution schemesMazhar Sheikh
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air ConditioningSaurabh Jain
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234KRISHAN KUMAR
 
Hvac Presentation
Hvac PresentationHvac Presentation
Hvac PresentationChoong KW
 
Illinois ASHRAE 2011 Technology Awards
Illinois ASHRAE 2011 Technology AwardsIllinois ASHRAE 2011 Technology Awards
Illinois ASHRAE 2011 Technology AwardsIllinois ASHRAE
 
YEA ASHRAE Kick-Off Meeting 2011
YEA ASHRAE Kick-Off Meeting 2011YEA ASHRAE Kick-Off Meeting 2011
YEA ASHRAE Kick-Off Meeting 2011Illinois ASHRAE
 
Illinois ASHRAE Research Promotion
Illinois ASHRAE Research PromotionIllinois ASHRAE Research Promotion
Illinois ASHRAE Research PromotionIllinois ASHRAE
 
Nicor Gas Non-Residential Energy Efficiency Programs
Nicor Gas Non-Residential Energy Efficiency ProgramsNicor Gas Non-Residential Energy Efficiency Programs
Nicor Gas Non-Residential Energy Efficiency ProgramsIllinois ASHRAE
 
Chicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Welcome AddressChicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Welcome AddressIllinois ASHRAE
 
Chicago Energy Modeling Conference Key Note
Chicago Energy Modeling Conference Key NoteChicago Energy Modeling Conference Key Note
Chicago Energy Modeling Conference Key NoteIllinois ASHRAE
 
Waterside energy-recovery hourlong-chicago_ashrae
Waterside energy-recovery hourlong-chicago_ashraeWaterside energy-recovery hourlong-chicago_ashrae
Waterside energy-recovery hourlong-chicago_ashraeIllinois ASHRAE
 
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
Preliminary Modeling & Life Cycle Costing:  Underpinnings of Integrated Design.Preliminary Modeling & Life Cycle Costing:  Underpinnings of Integrated Design.
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.Illinois ASHRAE
 
Chilled Water Plant Optimization
Chilled Water Plant OptimizationChilled Water Plant Optimization
Chilled Water Plant OptimizationJoePessa
 
Measurement & Verification
Measurement & VerificationMeasurement & Verification
Measurement & VerificationIllinois ASHRAE
 
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs:  Benefits of Energy Modeling to OwnersAssessing Your Building Energy Costs:  Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs: Benefits of Energy Modeling to OwnersIllinois ASHRAE
 
Modeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and EnergyModeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and EnergyIllinois ASHRAE
 
Active Chilled Beam Technology
Active Chilled Beam TechnologyActive Chilled Beam Technology
Active Chilled Beam TechnologyIllinois ASHRAE
 

Destaque (20)

Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled Airconditioning
 
Hvac chilled water distribution schemes
Hvac chilled water distribution schemesHvac chilled water distribution schemes
Hvac chilled water distribution schemes
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air Conditioning
 
HVAC Sysems & AHU
HVAC Sysems & AHUHVAC Sysems & AHU
HVAC Sysems & AHU
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234
 
Hvac Presentation
Hvac PresentationHvac Presentation
Hvac Presentation
 
Illinois ASHRAE 2011 Technology Awards
Illinois ASHRAE 2011 Technology AwardsIllinois ASHRAE 2011 Technology Awards
Illinois ASHRAE 2011 Technology Awards
 
YEA ASHRAE Kick-Off Meeting 2011
YEA ASHRAE Kick-Off Meeting 2011YEA ASHRAE Kick-Off Meeting 2011
YEA ASHRAE Kick-Off Meeting 2011
 
Illinois ASHRAE Research Promotion
Illinois ASHRAE Research PromotionIllinois ASHRAE Research Promotion
Illinois ASHRAE Research Promotion
 
Nicor Gas Non-Residential Energy Efficiency Programs
Nicor Gas Non-Residential Energy Efficiency ProgramsNicor Gas Non-Residential Energy Efficiency Programs
Nicor Gas Non-Residential Energy Efficiency Programs
 
Chicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Welcome AddressChicago Energy Modeling Conference Welcome Address
Chicago Energy Modeling Conference Welcome Address
 
Chicago Energy Modeling Conference Key Note
Chicago Energy Modeling Conference Key NoteChicago Energy Modeling Conference Key Note
Chicago Energy Modeling Conference Key Note
 
Waterside energy-recovery hourlong-chicago_ashrae
Waterside energy-recovery hourlong-chicago_ashraeWaterside energy-recovery hourlong-chicago_ashrae
Waterside energy-recovery hourlong-chicago_ashrae
 
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
Preliminary Modeling & Life Cycle Costing:  Underpinnings of Integrated Design.Preliminary Modeling & Life Cycle Costing:  Underpinnings of Integrated Design.
Preliminary Modeling & Life Cycle Costing: Underpinnings of Integrated Design.
 
Building EQ
Building EQBuilding EQ
Building EQ
 
Chilled Water Plant Optimization
Chilled Water Plant OptimizationChilled Water Plant Optimization
Chilled Water Plant Optimization
 
Measurement & Verification
Measurement & VerificationMeasurement & Verification
Measurement & Verification
 
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs:  Benefits of Energy Modeling to OwnersAssessing Your Building Energy Costs:  Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
 
Modeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and EnergyModeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and Energy
 
Active Chilled Beam Technology
Active Chilled Beam TechnologyActive Chilled Beam Technology
Active Chilled Beam Technology
 

Semelhante a High Performance Chilled Water Systems Optimization

Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~iNtpc (national thermal power corporation) sipat boiler haxxo24 i~i
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~ihaxxo24
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boilerAshvani Shukla
 
Energy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration SystemsEnergy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration Systemseecfncci
 
Refrigeration and air conditioning system
Refrigeration and air conditioning systemRefrigeration and air conditioning system
Refrigeration and air conditioning systembikramstalion
 
hvac and refrigeration system
hvac and refrigeration systemhvac and refrigeration system
hvac and refrigeration systemSRINIVASGILLALA
 
Chilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.pptChilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.pptEstevanhuertas
 
Solar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaionSolar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaionSulaiman Dawood Barry
 
Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) SYED KHURSHID ALAM ARZOO
 
Ice Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet CoolingIce Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet Coolingss383
 
AERMEC 2013 Presentation
AERMEC 2013 PresentationAERMEC 2013 Presentation
AERMEC 2013 PresentationBritton Wallace
 
SUPER CRITICAL BOILER.pdf
SUPER CRITICAL BOILER.pdfSUPER CRITICAL BOILER.pdf
SUPER CRITICAL BOILER.pdfVivaanRavi
 
Energy-Saving Designs for Existing Buildings
Energy-Saving Designs for Existing BuildingsEnergy-Saving Designs for Existing Buildings
Energy-Saving Designs for Existing BuildingsIllinois ASHRAE
 
Super-Critical Boiler.ppt
Super-Critical Boiler.pptSuper-Critical Boiler.ppt
Super-Critical Boiler.pptMarcWorld
 
2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidlmichaeljmack
 

Semelhante a High Performance Chilled Water Systems Optimization (20)

Super critical boiler
Super critical boilerSuper critical boiler
Super critical boiler
 
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~iNtpc (national thermal power corporation) sipat boiler haxxo24 i~i
Ntpc (national thermal power corporation) sipat boiler haxxo24 i~i
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boiler
 
Energy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration SystemsEnergy efficiency in Refrigeration Systems
Energy efficiency in Refrigeration Systems
 
Refrigeration and air conditioning system
Refrigeration and air conditioning systemRefrigeration and air conditioning system
Refrigeration and air conditioning system
 
hvac and refrigeration system
hvac and refrigeration systemhvac and refrigeration system
hvac and refrigeration system
 
Chilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.pptChilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.ppt
 
Solar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaionSolar Thermal Power Plant 2nd presentaion
Solar Thermal Power Plant 2nd presentaion
 
ppt on kstps 2016
ppt on kstps 2016ppt on kstps 2016
ppt on kstps 2016
 
Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation) Hvac - presentation (Air conditioning presentation)
Hvac - presentation (Air conditioning presentation)
 
Ice Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet CoolingIce Slurry TES for Turbine Inlet Cooling
Ice Slurry TES for Turbine Inlet Cooling
 
2015 emc broadusa
2015 emc broadusa2015 emc broadusa
2015 emc broadusa
 
Steam Engineering basics
Steam Engineering basicsSteam Engineering basics
Steam Engineering basics
 
AERMEC 2013 Presentation
AERMEC 2013 PresentationAERMEC 2013 Presentation
AERMEC 2013 Presentation
 
SUPER CRITICAL BOILER.pdf
SUPER CRITICAL BOILER.pdfSUPER CRITICAL BOILER.pdf
SUPER CRITICAL BOILER.pdf
 
O&amp;m of boiler
O&amp;m of boilerO&amp;m of boiler
O&amp;m of boiler
 
Energy-Saving Designs for Existing Buildings
Energy-Saving Designs for Existing BuildingsEnergy-Saving Designs for Existing Buildings
Energy-Saving Designs for Existing Buildings
 
Adm apn045-en 0912
Adm apn045-en 0912Adm apn045-en 0912
Adm apn045-en 0912
 
Super-Critical Boiler.ppt
Super-Critical Boiler.pptSuper-Critical Boiler.ppt
Super-Critical Boiler.ppt
 
2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl
 

Mais de Illinois ASHRAE

Net Zero Energy Buildings
Net Zero Energy BuildingsNet Zero Energy Buildings
Net Zero Energy BuildingsIllinois ASHRAE
 
Standard 90.1-2010 Update
Standard 90.1-2010 UpdateStandard 90.1-2010 Update
Standard 90.1-2010 UpdateIllinois ASHRAE
 
Illinois ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011Illinois ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011Illinois ASHRAE
 
ComEd Retro-Commissioning Program
ComEd Retro-Commissioning ProgramComEd Retro-Commissioning Program
ComEd Retro-Commissioning ProgramIllinois ASHRAE
 
Smart Ideas for Your Business
Smart Ideas for Your BusinessSmart Ideas for Your Business
Smart Ideas for Your BusinessIllinois ASHRAE
 
Solar Project Risk from the Developer’s Point of View
Solar Project Risk from the Developer’s Point of ViewSolar Project Risk from the Developer’s Point of View
Solar Project Risk from the Developer’s Point of ViewIllinois ASHRAE
 
Illinois Chapter of ASHRAE April 2011 Student Night
Illinois Chapter of ASHRAE April 2011 Student NightIllinois Chapter of ASHRAE April 2011 Student Night
Illinois Chapter of ASHRAE April 2011 Student NightIllinois ASHRAE
 
Smoke Control in Buildings
Smoke Control in BuildingsSmoke Control in Buildings
Smoke Control in BuildingsIllinois ASHRAE
 
Rock Valley College - Chilled Beams Lesson Learned
Rock Valley College - Chilled Beams Lesson LearnedRock Valley College - Chilled Beams Lesson Learned
Rock Valley College - Chilled Beams Lesson LearnedIllinois ASHRAE
 
Enhancing the Healing Environment with Geothermal Energy - Sherman Hospital
Enhancing the Healing Environment with Geothermal Energy - Sherman HospitalEnhancing the Healing Environment with Geothermal Energy - Sherman Hospital
Enhancing the Healing Environment with Geothermal Energy - Sherman HospitalIllinois ASHRAE
 
Natural Gas Rebate Programs
Natural Gas Rebate ProgramsNatural Gas Rebate Programs
Natural Gas Rebate ProgramsIllinois ASHRAE
 

Mais de Illinois ASHRAE (16)

Net Zero Energy Buildings
Net Zero Energy BuildingsNet Zero Energy Buildings
Net Zero Energy Buildings
 
Standard 90.1-2010 Update
Standard 90.1-2010 UpdateStandard 90.1-2010 Update
Standard 90.1-2010 Update
 
Illinois ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011Illinois ASHRAE Kick-Off Meeting 2011
Illinois ASHRAE Kick-Off Meeting 2011
 
ASHRAE Standard 189.1
ASHRAE Standard 189.1ASHRAE Standard 189.1
ASHRAE Standard 189.1
 
ComEd Retro-Commissioning Program
ComEd Retro-Commissioning ProgramComEd Retro-Commissioning Program
ComEd Retro-Commissioning Program
 
Smart Ideas for Your Business
Smart Ideas for Your BusinessSmart Ideas for Your Business
Smart Ideas for Your Business
 
ASHRAE Standard 100
ASHRAE Standard 100ASHRAE Standard 100
ASHRAE Standard 100
 
Solar Project Risk from the Developer’s Point of View
Solar Project Risk from the Developer’s Point of ViewSolar Project Risk from the Developer’s Point of View
Solar Project Risk from the Developer’s Point of View
 
Illinois Chapter of ASHRAE April 2011 Student Night
Illinois Chapter of ASHRAE April 2011 Student NightIllinois Chapter of ASHRAE April 2011 Student Night
Illinois Chapter of ASHRAE April 2011 Student Night
 
Solar Thermal Cooling
Solar Thermal CoolingSolar Thermal Cooling
Solar Thermal Cooling
 
Life Safety Products
Life Safety ProductsLife Safety Products
Life Safety Products
 
Smoke Control in Buildings
Smoke Control in BuildingsSmoke Control in Buildings
Smoke Control in Buildings
 
Control Dampers
Control DampersControl Dampers
Control Dampers
 
Rock Valley College - Chilled Beams Lesson Learned
Rock Valley College - Chilled Beams Lesson LearnedRock Valley College - Chilled Beams Lesson Learned
Rock Valley College - Chilled Beams Lesson Learned
 
Enhancing the Healing Environment with Geothermal Energy - Sherman Hospital
Enhancing the Healing Environment with Geothermal Energy - Sherman HospitalEnhancing the Healing Environment with Geothermal Energy - Sherman Hospital
Enhancing the Healing Environment with Geothermal Energy - Sherman Hospital
 
Natural Gas Rebate Programs
Natural Gas Rebate ProgramsNatural Gas Rebate Programs
Natural Gas Rebate Programs
 

Último

BIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptx
BIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptxBIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptx
BIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptxSayali Powar
 
Mental Health Awareness - a toolkit for supporting young minds
Mental Health Awareness - a toolkit for supporting young mindsMental Health Awareness - a toolkit for supporting young minds
Mental Health Awareness - a toolkit for supporting young mindsPooky Knightsmith
 
Q-Factor HISPOL Quiz-6th April 2024, Quiz Club NITW
Q-Factor HISPOL Quiz-6th April 2024, Quiz Club NITWQ-Factor HISPOL Quiz-6th April 2024, Quiz Club NITW
Q-Factor HISPOL Quiz-6th April 2024, Quiz Club NITWQuiz Club NITW
 
Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...
Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...
Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...DhatriParmar
 
Man or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptx
Man or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptxMan or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptx
Man or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptxDhatriParmar
 
Q-Factor General Quiz-7th April 2024, Quiz Club NITW
Q-Factor General Quiz-7th April 2024, Quiz Club NITWQ-Factor General Quiz-7th April 2024, Quiz Club NITW
Q-Factor General Quiz-7th April 2024, Quiz Club NITWQuiz Club NITW
 
DIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptx
DIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptxDIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptx
DIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptxMichelleTuguinay1
 
Reading and Writing Skills 11 quarter 4 melc 1
Reading and Writing Skills 11 quarter 4 melc 1Reading and Writing Skills 11 quarter 4 melc 1
Reading and Writing Skills 11 quarter 4 melc 1GloryAnnCastre1
 
Congestive Cardiac Failure..presentation
Congestive Cardiac Failure..presentationCongestive Cardiac Failure..presentation
Congestive Cardiac Failure..presentationdeepaannamalai16
 
Narcotic and Non Narcotic Analgesic..pdf
Narcotic and Non Narcotic Analgesic..pdfNarcotic and Non Narcotic Analgesic..pdf
Narcotic and Non Narcotic Analgesic..pdfPrerana Jadhav
 
ICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdfICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdfVanessa Camilleri
 
Textual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHSTextual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHSMae Pangan
 
Oppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmOppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmStan Meyer
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxHumphrey A Beña
 
4.11.24 Mass Incarceration and the New Jim Crow.pptx
4.11.24 Mass Incarceration and the New Jim Crow.pptx4.11.24 Mass Incarceration and the New Jim Crow.pptx
4.11.24 Mass Incarceration and the New Jim Crow.pptxmary850239
 
MS4 level being good citizen -imperative- (1) (1).pdf
MS4 level   being good citizen -imperative- (1) (1).pdfMS4 level   being good citizen -imperative- (1) (1).pdf
MS4 level being good citizen -imperative- (1) (1).pdfMr Bounab Samir
 
How to Make a Duplicate of Your Odoo 17 Database
How to Make a Duplicate of Your Odoo 17 DatabaseHow to Make a Duplicate of Your Odoo 17 Database
How to Make a Duplicate of Your Odoo 17 DatabaseCeline George
 
ESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnv
ESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnvESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnv
ESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnvRicaMaeCastro1
 
Multi Domain Alias In the Odoo 17 ERP Module
Multi Domain Alias In the Odoo 17 ERP ModuleMulti Domain Alias In the Odoo 17 ERP Module
Multi Domain Alias In the Odoo 17 ERP ModuleCeline George
 
Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)
Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)
Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)lakshayb543
 

Último (20)

BIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptx
BIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptxBIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptx
BIOCHEMISTRY-CARBOHYDRATE METABOLISM CHAPTER 2.pptx
 
Mental Health Awareness - a toolkit for supporting young minds
Mental Health Awareness - a toolkit for supporting young mindsMental Health Awareness - a toolkit for supporting young minds
Mental Health Awareness - a toolkit for supporting young minds
 
Q-Factor HISPOL Quiz-6th April 2024, Quiz Club NITW
Q-Factor HISPOL Quiz-6th April 2024, Quiz Club NITWQ-Factor HISPOL Quiz-6th April 2024, Quiz Club NITW
Q-Factor HISPOL Quiz-6th April 2024, Quiz Club NITW
 
Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...
Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...
Blowin' in the Wind of Caste_ Bob Dylan's Song as a Catalyst for Social Justi...
 
Man or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptx
Man or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptxMan or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptx
Man or Manufactured_ Redefining Humanity Through Biopunk Narratives.pptx
 
Q-Factor General Quiz-7th April 2024, Quiz Club NITW
Q-Factor General Quiz-7th April 2024, Quiz Club NITWQ-Factor General Quiz-7th April 2024, Quiz Club NITW
Q-Factor General Quiz-7th April 2024, Quiz Club NITW
 
DIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptx
DIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptxDIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptx
DIFFERENT BASKETRY IN THE PHILIPPINES PPT.pptx
 
Reading and Writing Skills 11 quarter 4 melc 1
Reading and Writing Skills 11 quarter 4 melc 1Reading and Writing Skills 11 quarter 4 melc 1
Reading and Writing Skills 11 quarter 4 melc 1
 
Congestive Cardiac Failure..presentation
Congestive Cardiac Failure..presentationCongestive Cardiac Failure..presentation
Congestive Cardiac Failure..presentation
 
Narcotic and Non Narcotic Analgesic..pdf
Narcotic and Non Narcotic Analgesic..pdfNarcotic and Non Narcotic Analgesic..pdf
Narcotic and Non Narcotic Analgesic..pdf
 
ICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdfICS2208 Lecture6 Notes for SL spaces.pdf
ICS2208 Lecture6 Notes for SL spaces.pdf
 
Textual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHSTextual Evidence in Reading and Writing of SHS
Textual Evidence in Reading and Writing of SHS
 
Oppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and FilmOppenheimer Film Discussion for Philosophy and Film
Oppenheimer Film Discussion for Philosophy and Film
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
 
4.11.24 Mass Incarceration and the New Jim Crow.pptx
4.11.24 Mass Incarceration and the New Jim Crow.pptx4.11.24 Mass Incarceration and the New Jim Crow.pptx
4.11.24 Mass Incarceration and the New Jim Crow.pptx
 
MS4 level being good citizen -imperative- (1) (1).pdf
MS4 level   being good citizen -imperative- (1) (1).pdfMS4 level   being good citizen -imperative- (1) (1).pdf
MS4 level being good citizen -imperative- (1) (1).pdf
 
How to Make a Duplicate of Your Odoo 17 Database
How to Make a Duplicate of Your Odoo 17 DatabaseHow to Make a Duplicate of Your Odoo 17 Database
How to Make a Duplicate of Your Odoo 17 Database
 
ESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnv
ESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnvESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnv
ESP 4-EDITED.pdfmmcncncncmcmmnmnmncnmncmnnjvnnv
 
Multi Domain Alias In the Odoo 17 ERP Module
Multi Domain Alias In the Odoo 17 ERP ModuleMulti Domain Alias In the Odoo 17 ERP Module
Multi Domain Alias In the Odoo 17 ERP Module
 
Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)
Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)
Visit to a blind student's school🧑‍🦯🧑‍🦯(community medicine)
 

High Performance Chilled Water Systems Optimization

  • 1. High Performance Chilled Water Systems Mick Schwedler, PE, LEED® AP Manager Applications Engineering Trane © 2011 Ingersoll Rand
  • 2. Normal Performance Chilled Water Systems  ASHRAE/IESNA 90.1 (LEED Prerequisite)  System configuration  Design parameters  System control
  • 3. ASHRAE Standard 90.1-2007 Purpose “… Provide minimum requirements for the energy- efficient design of buildings except low-rise residential buildings”
  • 4. Purpose of ANSI/ASHRAE/IESNA Standard 90.1-2010 To establish minimum energy efficiency requirements of buildings, other than low-rise residential buildings for: 1. design, construction, and a plan for operation and maintenance, and 2. Utilization of on-site renewable energy resources.
  • 5. Publication and Final Savings Estimates  Performed by Pacific Northwest National Laboratory (PNNL)  Savingsof 90.1-2010 compared to 90.1-2004  Savings shared are modeled as of January 2011  Includeventilation changes in ASHRAE 62.1 between 1999 and 2007 versions
  • 6. 90.1 Progress Indicator  Including receptacle loads in modeling  Including receptacle load in % savings calculation Energy cost savings % Energy savings % Ventilation rate changes between 62.1-1999 24.0 25.5 and 62.1-2007
  • 7. 90.1 Progress Indicator Excluding receptacle loads in % savings calculation only  Including receptacle loads in modeling  Excluding receptacle load in % savings calculation Energy cost savings % Energy savings % Ventilation rate changes between 62.1-1999 30.1 32.6 and 62.1-2007
  • 8. LEED Energy and Atmosphere  LEED 2009  10% energy cost savings beyond 90.1-2007  LEED 2012  Public Review 2: September 2011  EA Prerequisite: 10% average energy cost and source energy savings beyond 90.1-2010 (new construction)  EA Credit: Credit for reductions beyond 10%
  • 9. 90.1-2010 Chiller Efficiencies Paths A & B Before 1/1/2010 As of 1/1/2010c Test Procedureb Equipment Type Size CategoryUnits Path A Path Bd Full Full Full Load IPLV Load IPLV Load IPLV ARI 550/590 <150 tons EER ≥9.562 ≥10.416 ≥9.562 ≥12.50 NA NA Air-cooled ≥150 tons EER ≥9.562 ≥10.416 ≥9.562 ≥12.75 NA NA <75 tons kW/ton ≤0.780 ≤0.630 ≤0.800 ≤0.600 ≥75 tons and < ≤0.790 ≤0.676 Water Cooled kW/ton ≤0.775 ≤0.615 ≤0.790 ≤0.586 150 tons Electrically Operated, ≥150 tons and Positive Displacement kW/ton ≤0.717 ≤0.627 ≤0.680 ≤0.580 ≤0.718 ≤0.540 < 300 tons ≥300 tons kW/ton ≤0.639 ≤0.571 ≤0.620 ≤0.540 ≤0.639 ≤0.490 <150 tons kW/ton ≤0.703 ≤0.669 ≥150 tons and ≤0.634 ≤0.596 ≤0.639 ≤0.450 Water Cooled kW/ton ≤0.634 ≤0.596 < 300 tons Electrically Operated, ≥300 tons and Centrifugal kW/ton ≤0.576 ≤0.549 ≤0.600 ≤0.400 < 600 tons ≤0.576 ≤0.549 ≥600 tons kW/ton ≤0.570 ≤0.539 ≤0.590 ≤0.400 Must meet both full and part load requirements
  • 10. Heat rejection equipment  Fan speed control 7.5 and greater  Capability to operate at 2/3 fan speed or less  Exceptions  Climates > 7200 CDD50 (e.g. Miami)  1/3 of fans on multiple fan application
  • 11. Hydronic system design and control  Pump isolation  Chilled and hot water reset if >300,000 Btuh  Exception: Variable flow systems that reduce pumping energy
  • 12. 90.1-2007 Hydronic System Design & Control These provisions apply if pump system power > 10 hp:  Must be variable flow unless …  Pump power ≤ 75 hp  ≤ 3 Control valves  Limit demand of individual variable-flow pumps to 30% of design wattage at 50% flow (e.g., use VSD)  Pump head > 100 ft  Motor > 50 hp
  • 13. Waterside Energy Recovery required  Service Water Heating  24 hrs per day and  Heat rejection > 6 MMBtuh and  SWH load 1 MMBtuh  Recover smaller of  60% of heat rejection  Preheat water to 85°F
  • 14. Configuration Normal Performance Chilled Water production pumps distribution pump production loop distribution loop two-way valve
  • 15. Design Parameters Normal Performance Chilled Water Plant  ARI 550/590 Standard Conditions  44°F chilled water  2.4 gpm/ton chilled water (10°F T)  3.0 gpm/ton condenser water (10°F [9.3] T)
  • 16. Control Normal Performance Chilled Water Plant  Chilled water distribution pump P at most remote load  Cooling tower fans  55°F (as cold as possible)  Constant speed condenser water pumps All these “normal” assumptions will be examined
  • 17. High Performance Chilled Water Plants  Standard high performance  Reduced flow rates, increased ∆Ts  Variable primary flow  Advanced high performance  Equipment capabilities  System configurations  System control
  • 18. a history of Chiller Performance 8.0 centrifugal >600 tons chiller efficiency, COP screw 6.0 150-300 tons scroll <100 tons 4.0 reciprocating <150 tons 2.0 0.0 ASHRAE Standard 90 NBI “best” 90-75 90-75 90.1-89 90.1-99 available (1977) (1980)
  • 19. chilled water plant design … Provocation Are our “rules of thumb” …  44 F chilled water supply  10 F T for chilled water system  3 gpm/ton condenser water flow … in need of repair?
  • 20. High Performance Design Parameters  ASHRAE GreenGuide and CoolTools™  Chilled water T: 12°F to 20 °F  Condenser water T: 12°F to 18 °F (multi-stage)  Kelly and Chan  Chilled water T: 18°F  Condenser water T: 14.2°F (3.6 - 8.3% energy savings in various climates)
  • 21. chilled water plant …humid climate Base Design: 450 Tons  0.5% design  Coil, valve and chilled wet bulb: 78 F water piping pressure drop: 80 ft  Entering condenser water temperature  Condenser water piping (ECWT): 85 F pressure drop: 30 ft  Evaporator and  Pump efficiency: 75% condenser  Pump motor temperature efficiency: 93% differences: 10 F
  • 22. traditional design …humid climate System Energy Consumption 350 Energy Consumption, kW 300 250 200 150 Tower Condenser Water Pump 100 Chilled Water Pump Chiller (100% Load) 50 0 2.4/3.0 Chilled / Condenser Water Flows, gpm/ton
  • 23. traditional vs. low-flow design … System Summary At Full Load 350 Energy Consumption, kW 300 250 200 150 Tower Condenser Water Pump 100 Chilled Water Pump Chiller (100% Load) 50 0 2.4/3.0 1.5/2.0 Chilled / Condenser Water Flows, gpm/ton
  • 24. comparison …humid climate System Summary At 75% Load 350 Energy Consumption, kW 300 250 200 150 Tower Condenser Water Pump 100 Chilled Water Pump Chiller (75% Load) 50 0 2.4/3.0 1.5/2.0 Chilled / Condenser Water Flows, gpm/ton
  • 25. comparison …humid climate System Summary At 50% Load 350 Energy Consumption, kW 300 250 200 150 Tower Condenser Water Pump 100 Chilled Water Pump Chiller (50% Load) 50 0 2.4/3.0 1.5/2.0 Chilled / Condenser Water Flows, gpm/ton
  • 26. comparison …humid climate System Summary At 25% Load 350 Energy Consumption, kW 300 250 200 150 Tower Condenser Water Pump 100 Chilled Water Pump Chiller (25% Load) 50 0 2.4/3.0 1.5/2.0 Chilled / Condenser Water Flows, gpm/ton
  • 27. traditional vs. low-flow design …humid climate Savings Summary 20.0 Operating Cost Savings, % 16.5% 10.3% 10.0 6.7% 3.8% 0 25% 50% 75% 100% Load
  • 28. High Performance Design Parameters kWh/ton/year 600 Chilled water 400 pump 200 Chiller 0 41/16 42/14 43/12 44/10 Chilled water supply temperature/DeltaT
  • 29. Pipe Size Example 90.1-2010 Table 6.5.4.5  800 ton system  3,000 hours of operation  Chilled water, variable flow  Condenser water, constant flow Past Design ASHRAE GreenGuide Practice ∆T Flow Pipe ∆T Flow Pipe (°F) (gpm) Size (°F) (gpm) Size Chilled 10 1920 10 16 1200 8 Water Condenser 9.4 2400 14 14 1600 12 Water
  • 30. High Performance Design Options Either …  Take full energy (operating cost) savings Or …  Reduce piping size and cost Experienced designers use pump, piping and tower savings to select an even more efficient chiller
  • 31. Reduced flow works for all chiller manufacturers  Logan Airport - Boston:  $426,000 Construction cost savings  7.3% operating cost savings  Large Chemical Manufacturer -Greenville  $45,000 Excavation and concrete savings  6.5% Operating cost savings  Computer Manufacturer - San Francisco  Existing tower, pipe savings  2% Operating cost savings (tower not changed)
  • 32. Low flow works for retrofit applications  Chilled water side  Coil  It’s a simple heat transfer device  Reacts to colder entering water by returning it warmer  Ideal for system expansion
  • 33. Low flow works for retrofit applications Condenser side retrofit opportunity  Chiller needs to be replaced  Cooling needs have increased by 50%  Cooling tower was replaced two years ago  Condenser pump and pipes are in good shape
  • 34. Condenser side retrofit opportunity Existing Retrofit Capacity (tons) 500 750 Flow rate (gpm) 1500 1500 Condenser Entering Water 85 88 Temperature (F) Condenser Leaving Water 95 103 Temperature (F) Design Wet Bulb (F) 78 78
  • 35. Humid climates Low flow works for short piping runs too Condenser Water Side Only - original 350.0 300.0 Energy Consumption (kWh) 250.0 200.0 3.0 gpm/ton 2.0 gpm/ton 150.0 100.0 50.0 0.0 25% 50% 75% 100% System Load
  • 36. Humid climates Low flow works for short piping runs too Condenser Water Side Only ZERO piping pressure drop 350.0 300.0 Energy Consumption (kWh) 250.0 200.0 3.0 gpm/ton 2.0 gpm/ton 150.0 100.0 50.0 0.0 25% 50% 75% 100% System Load
  • 37. High Performance Design Parameters  Low flow benefits systems - no matter whose chiller is being used  Low flow works extremely well on existing systems  Low flow works on short piping runs
  • 39. Oh, by the way... You may also do this with air
  • 40. Variable-Primary-Flow Systems variable-flow pumps check valves control valve
  • 41. VPF Savings  First cost: 4-8%  Annual energy: 3-8%  Life-cycle cost: 3-5% http://www.arti-21cr.org/ARI/util/showdoc.aspx?doc=1085
  • 42. Flow requirements VPF System  Limits (consult manufacturer)  Absolute flows - Minimum and maximum  Flow rate changes  2% of design flow per minute not good enough  10% of design flow per minute borderline  30% of design flow per minute many comfort cooling applications  50% of design flow per minute best  Always need a way to ensure minimum flow (bypass)
  • 43. Chiller Control V a ria b le W a te r F lo w 130 1500 120 1300 110 1100 100 900 Water Temp [degF] 90 700 E vaporator W ater F low Flow [gpm] 80 500 70 300 60 100 50 E vap E ntering W ater T em p -100 40 -300 E vap Leaving W ater T em p 30 -500 3:50:00 3:55:00 4:00:00 4:05:00 4:10:00 T im e (h o u r:m in :s e c )
  • 44. More information VPF System  Http:/trane.com/commercial /library/newsletters.asp (1999 and 2002)  “Primary-Only vs. Primary-Secondary Variable Flow Systems,” Taylor, ASHRAE Journal, February 2002  “Don’t Ignore Variable Flow,” Waltz, Contracting Business, July 1997  “Comparative Analysis of Variable and Constant Primary-Flow Chilled-Water-Plant Performance,” Bahnfleth and Peyer, HPAC Engineering, April 2001  “Campus Cooling: Retrofitting Systems,” Kreutzmann, HPAC Engineering, July 2002
  • 45. High Performance Chilled Water Plants  Standard high performance  Reduced flow rates, increased ∆Ts  Variable primary flow  Advanced  Equipment capabilities  System configurations  System control
  • 46. Equipment Capabilities High Performance Chilled Water Plant  Constant speed  0.570 FL / 0.479 IPLV  Higher efficiency “same price” options  Variable speed (spend money on drive)  Constant speed (spend money on copper)  Purchase both a drive and more heat exchange surface  Down to 0.45 kW/ton FL available (22% reduction)
  • 47. Same-price Chiller: Example Performance Option Full Load IPLV (kW/ton) (kW/ton) VSD 0.572 0.357 High Efficiency 0.501 0.430
  • 48. Same-price Chiller: Example Performance 600-ton Replacement Chiller Performance 400 350 300 High_efficiency_85°F 250 VSD_85°F High_efficiency_75°F kW 200 VSD_75°F 150 High_efficiency_65°F VSD_65°F 100 50 0 0% 20% 40% 60% 80% 100% % Load
  • 49. Example  Office building  Two 400-ton chillers  Comparisons  Base system - constant speed  AFD on both chillers  High efficiency for both chillers  AFD on one chiller  High efficiency for one chiller
  • 50. What is the actual utility rate?  Utility costs  ‘Combined’ utility rates ($0.10 / kWh)  Actual utility rates ($12 / kW and $0.06 / kWh)
  • 51. Utility rate comparison Simple paybacks, humid climate Combined rate Actual rate on one AFD 6.1 10.8 chiller High efficiency 6.3 7.7 on both AFD 7.2 12.7 chillers High efficiency 7.1 8.3 Using incorrect “combined” rate leads to incorrect decisions
  • 52. Rule 1 Use actual utility rates
  • 53. Temperate climate with economizer Annual operating cost Simple payback $100,000 30 $80,000 25 20 $60,000 15 $40,000 10 $20,000 5 0 Base case AFD on High efficiency AFD on High efficiency both chillers both chillers one chiller one chiller Chiller plant operating cost Simple payback
  • 54. Temperate climate, no economizer Annual operating cost Simple payback $100,000 12 $80,000 10 8 $60,000 6 $40,000 4 $20,000 2 0 Base case AFD on High efficiency AFD on High efficiency both chillers both chillers one chiller one chiller Chiller plant operating cost Simple payback
  • 55. Humid climate, no economizer Annual operating cost Simple payback $100,000 14 $80,000 12 10 $60,000 8 $40,000 6 $20,000 4 2 Base case AFD on High efficiency AFD on High efficiency both chillers both chillers one chiller one chiller Chiller plant operating cost Simple payback
  • 56. Dry climate with economizer Annual operating cost Simple payback $100,000 18 16 $80,000 14 12 $60,000 10 8 $40,000 6 4 $20,000 2 0 Base case AFD on High efficiency AFD on High efficiency both chillers both chillers one chiller one chiller Chiller plant operating cost Simple payback
  • 57. Rule 2 Model ROI of each investment
  • 58. Guidance: VSD or High Efficiency?  High efficiency  VSD  Significant demand  Many hours at low charges, especially condenser water ratchet charges temperature – and low load  Climates where the wet bulb doesn’t vary  Perhaps only on one substantially chiller  Multiple chillers in the  Factor replacement plant cost of VSD when performing life cycle  Economizer that assessment reduces low load/low lift operating hours
  • 59. High Performance Chilled Water Plants  Standard high performance  Reduced flow rates, increased ∆Ts  Variable primary flow  Advanced  Equipment capabilities  System configurations  System control
  • 60. VPF System Minimum flow and bypass control  Single chiller  Retrofit Controller P P
  • 61. What may not be a good VPF application?  Two packaged chillers  Limited evaporator configurations  Assume minimum flow is about 1.2 gpm/ton  In parallel  Wide ∆T (low flow)  e.g 18°F ∆T is 1.33 gpm/ton  Why isn’t it a good application?  Flow can only be turned down 10%
  • 62. Variable-Volume Pumping System (series chillers) 48.4°F Upstream chiller operating at higher temperature is more efficient 41°F 57°F Bypass alternatives
  • 63. Series Chillers Manual service bypass
  • 64. Series Chiller Advantages  Simplifies pumping and  Simple preferential sequencing loading of chillers  No flow rate transitions  Adjust upstream chiller’s setpoint  Makes VPF simple  Upward to unload  Downward to load  Upstream chiller operates at elevated temperature  Efficiency increases  Capacity increases  10% or more for absorption
  • 65. High Performance Chilled Water Plants  Standard high performance  Reduced flow rates, increased ∆Ts  Variable primary flow  Advanced  Equipment capabilities  System configurations  System control
  • 66. Control Normal Performance Chilled Water Plant  Chilled water distribution pump P at most remote sensor  Cooling tower fans  55°F (as cold as possible)  Somewhere else  Constant volume condenser water pumps
  • 67. High Performance Chilled Water Pump Control Communicating BAS Pump Pump Speed Valve position Pressure Sensor
  • 68. pump-pressure optimization Control Logic 90.1-2007 Addendum ak Increase pump static pressure setpoint 75% Position (% open) of critical valve No action 65% Reduce pump static pressure setpoint
  • 69. High Performance Chiller-Tower Control Plant Power vs CWS Chillers cannot meet load 1,200.0 Lowest condenser water above this condenser water temperature available from temperature tower at this load and wet-bulb temperature 1,000.0 1,550 tons, 65°F Wet-bulb T t 800.0 1,160 tons, 59°F Wet-bulb Power (kW) T 600.0 730 tons, 54°F Wet-bulb Temperature 400.0 Optimal operation 200.0 0.0 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 Condenser Water Setpoint (°F) Hydeman, et. al. Pacific Gas and Electric. Used with permission.
  • 70. Cooling tower basics Fan energy consumption % Full load power 100 80 60 40 20 0 0 20 40 60 80 100 % Airflow
  • 71. cooling tower performance factors Approach and Wet Bulb 16.0 tower approach, deg 12.0 8.0 100% load approach = 9 4.0 50% load approach = 4 0.0 50 60 70 80 ambient wet bulb, °F
  • 72. simple case: constant water flow Operating Dependencies  Wet bulb  Load  Condenser water  Condenser water temperature temperature  Load  Chiller design  Tower design
  • 73. condenser water control “Normal” Setpoint  Hot? e.g., 85°F, minimizes tower energy consumption  Cold? e.g., 55°F, minimizes chiller energy consumption  Optimized?
  • 74. optimal condenser water control Chiller–Tower Interaction 400 total energy consumption, kW 300 chiller optimal 200 control point 100 tower 0 72 74 76 78 80 82 84 condenser water temperature, °F
  • 75. High Performance Chiller-Tower Control  Braun, Diderrich  Hydeman, Gillespie, Kammerud  Schwedler, ASHRAE Journal  Cascia  Crowther and Furlong
  • 76. chiller–tower optimization An Example …  720,000 ft² hotel  2 chillers, 2 tower cells  Control strategies  Make leaving-tower water cold as possible (55F)  Optimize system operation  Entering-condenser setpoint equals design … 85°F for humid climates 80°F for dry climates
  • 77. chiller–tower control strategies North America 350K control strategy: annual operating cost, $ USD 300K 55°F lvg tower optimal control 250K design ECWT 200K 150K 100K 50K 0 Mexico City Orlando San Diego Toronto
  • 78. chiller–tower control strategies Global Locations 500K control strategy: annual operating cost, $ USD 55°F lvg tower optimal control 400K design ECWT 300K 200K 100K 0 Dubai Paris Sao Paulo Singapore
  • 79. operating cost savings, % 0 2 4 6 8 10 12 Dubai 14 Paris Sao Paulo Singapore Mexico City location chiller–tower optimization Orlando San Diego Operating Cost Savings Toronto
  • 80. chiller–tower optimization Perspective on Savings For centrifugal chillers ≥ 300 tons, ASHRAE 90.1 requires …  0.576 kW/ton at full load  0.549 kW/ton at IPLV … using ARI standard rating conditions
  • 81. chiller–tower optimization Perspective on Savings Equivalent Savings, % chiller efficiency 0.0 0.576 2.8 0.560 4.5 0.550 6.2 0.540 14.0 0.495
  • 82. Where’s the Meter? On the BUILDING
  • 83. chiller–tower optimization Finding “Near Optimal”  Tower design (flow rate, range, approach)  Chiller design  Refrigeration cycle (vapor compression vs. absorption)  Compressor type  Capacity control (variable-speed drive)  Changing conditions (chiller load, ambient wet bulb)
  • 84. chiller–tower optimization Necessities  System-level controls  Variable-frequency drive on tower fans  High-quality dewpoint sensor
  • 85. Number of chillers operating  Operate one at nearly full load or two at part load?  Examine IPLV assumptions
  • 86. VSDs and centrifugal chillers A Closer Look at IPLV Load Weighting ECWT kW/Ton 100% 0.01 85°F 0.572 75% 0.42 75°F 0.420 50% 0.45 65°F 0.308 25% 0.12 65°F 0.372 VSDs improve part-lift performance, so running two chillers with VSDs at part load seems more efficient than one chiller at double the same load, but …is dependent on condenser water temperature
  • 87. Chiller power only 45% Plant load Operate 1 or 2 Chillers? Chiller kW Only 350 1@90% Load 300 2@45% Load 250 Chiller kW 200 150 100 50 0 55 60 65 70 75 80 85 Available Tower Water Temperature (ºF)
  • 88. Chillers plus pumps 45% Plant load Operate 1 or 2 Chillers? Chiller Plus Pump kW 400 1@90% Load 350 Chiller Plus Pump kW 2@45% Load 300 250 200 150 100 50 0 55 60 65 70 75 80 85 Available Tower Water Temperature (ºF)
  • 89. Operate 1 or 2 chillers? Run 1 or 2 VSD Chillers? 400 1@90% Load 350 2@45% Load 1@80% Load Operate multiple chillers here, 300 2@40% Load Total Chiller Plus Pump kW otherwise single chiller 1@70% Load 250 2@35% Load 1@60% Load 200 2@30% Load 1@50% Load 150 2@25% Load 100 50 0 60 65 70 75 80 85 Available Tower Water Temperature (ºF)
  • 90. Operate 1 or 2 chillers?  45% plant load: One chiller until tower temperature is < 65°F  40% plant load: One chiller until tower temperature is < 60°F  35% plant load and below: One chiller
  • 91. High Performance Condenser Water Pump Control – Variable?  Pump speed limits  Tower static lift  Tower nozzles (minimum flow)  Condenser minimum flow  Pump speed reductions result in  Increased leaving condenser water temperature  Decreased cooling tower effectiveness  Possible chiller surge
  • 92. High Performance Condenser Water Pump Control – Variable?  The condenser water pump is the hardest place to properly utilize a variable frequency drive during operation  There are successful installations
  • 93. variable-flow condenser water Pump Speed  Determining minimum speed  Variable flow affects:  Pump  Cooling tower  Chiller
  • 94. condenser water pump Minimum Speed Determinants:  Minimum condenser flow  Tower static lift  Minimum tower flow  Nozzle selection  Performance
  • 95. reducing flow & fan speed Effect on System fan speed 300 250 system power, kW 200 150 conditions: 100 • 70% load • 50°F WB 50 0 50 60 70 80 90 100 condenser water flow, %
  • 96. Varying fan and pump speed together
  • 97. variable condenser water flow Guidance  Can provide savings …  Finding proper operating points requires more time, more fine-tuning  Two-step process: 1 Reduce design pump power 2 Is variable condenser-water flow still warranted?
  • 98. ROI High Performance Chilled Water Plants  EnergyPlus  Non-bin  Schematic tools that analyze in 30- 45 minutes are available
  • 99. High Performance Chilled Water Plants  Standard high performance  Reduced flow rates, increased ∆Ts  Variable primary flow  Advanced high performance  Equipment capabilities  System configurations  System control
  • 100. High performance chilled water plant Winchester Medical Center
  • 101. Medical Center Winchester, Virginia  Five 750-ton chillers  VFD’s on  0.571 kW/ton full load  Chilled water pumps  Chilled water  Cooling tower fans 58 to 42°F  Condenser water  Condenser water pumps 84 to 95°F (missed opportunity)  Sophisticated control system with lots of  VFD’s  Programming  Variable primary flow  Commissioning
  • 102.  Owner Center  Operators  Service provider  Working together  Controls provider  Equipment provider  Consulting engineer Load (tons) 8/ 8/ 2 8/ 00 3 8/2 1 4 0.0 200.0 400.0 600.0 800.0 1000.0 1200.0 1400.0 8/8 00 3 :30 /2 1 3 8/ 00 3 :30 8/ 2 12 8/ 00 3 :30 8/2 1 0 1:3  Applications engineering 8/8 0 3 1 0 /2 0:3 8/ 00 3 0 8/ 20 9 :3 8/ 0 3 0 8/2 8 :3 8/8 00 3 0 /2 7 :3 8/ 00 3 0 8/ 2 6 :3 8/8 00 3 0 /2 5 :3 8/8 00 3 0 /2 4 :3 8/ 00 3 0 8/ 2 3 :3 8/8 00 3 0 /2 2 :3 8/8 00 3 0 / 1 8/ 200 :3 0 Time/Date 7/2 3 0 8/7 00 3 :3 0 /2 2 3 8/ 00 3 :30 7/ 20 2 2 8/ 0 3 :30 7/2 2 1 8/7 00 3 :30 /2 2 0 0 8/ 0 3 :30 7/ 2 19 8/7 00 3 :30 /2 1 8 8/7 00 3 :30 /2 17 Winchester Medical 8/ 00 3 :30 7/ 20 1 6 0 3 :30 15 :3 0 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 Efficiency (kW/ton) tons kW/ton
  • 103. Load (tons) 8/ 8/ 2 8/ 00 3 8/ 2 14 0.0 200.0 400.0 600.0 800.0 1000.0 1200.0 8/ 00 3 :30 8/ 1400.0 2 13 8/ 00 3 :30 8/ 2 12 8/ 00 3 :30 8/ 20 1 1 0 : 8/ 3 1 30 8/ 2 0: 8/ 00 3 30 8/ 20 9 :3 8/ 0 3 0 8/ 2 8 :3 8/ 00 3 0 8/ 2 7 :3 8/ 00 3 0 8/ 2 6 :3 8/ 00 3 0 8/ 2 5 :3 8/ 00 3 0 8/ 2 4 :3 8/ 00 3 0 8/ 2 3 :3 Chiller plant 8/ 00 3 0 8/ 2 2 :3 8/ 00 3 0 8/ 1 8/ 200 :3 0 Time/Date 7/ 2 3 0 8/ 00 3 :3 0 7/ 2 23 8/ 00 3 :30 7/ 2 22 8/ 00 3 :30 7/ 2 21 8/ 00 3 :30 7/ WMC - August 12 2 20 8/ 00 3 :30 7/ 2 19 8/ 00 3 :30 7/ 2 18 8/ 00 3 :30 7/ 2 17 8/ 00 3 :30 7/ 20 1 6 0 3 :30 15 :3 0 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 Efficiency (kW/ton) tons kW/ton
  • 104. Tons 0.0 200.0 400.0 600.0 800.0 1000.0 1200.0 1400.0 1600.0 1/0/1900 0:00 1/0/1900 0:00 1/0/1900 0:00 1/0/1900 0:00 1/0/1900 0:00 9/1/2003 14:00 9/1/2003 19:30 9/2/2003 1:00 9/2/2003 6:30 9/2/2003 12:00 9/2/2003 17:30 9/2/2003 23:00 9/3/2003 4:30 Chiller plant 9/3/2003 10:00 9/3/2003 15:30 9/3/2003 21:00 Time 9/4/2003 2:30 9/4/2003 8:00 WMC - Sept 1-7 9/4/2003 13:30 9/4/2003 19:00 Weekly-Summary 9/5/2003 0:30 9/5/2003 6:00 9/5/2003 11:30 9/5/2003 17:00 9/5/2003 22:30 9/6/2003 4:00 9/6/2003 9:30 9/6/2003 15:00 9/6/2003 20:30 9/7/2003 2:00 9/7/2003 7:30 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 kW/ton tons kW/ton
  • 105. Winchester Medical Center - Mark Baker  “Please use our data, names, etc. We're proud of our facility!”  “By the way, we're now operating @ -0.20 kW/ton. The power company just sent us our 1st check. Ha..Ha…”
  • 106. Remember... Without controls, it’s not a system.
  • 107. The meter is on the building!
  • 108. It’s a great time to be in this business!