S D V S N Rao et al Int. Journal of Engineering Research and Applications

www.ijera.com

ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855

RESEARCH ARTICLE

OPEN ACCESS

Promotion of Seismic Retrofitting For Existing Low
Earthquake Resistant Structures
S D V S N Rao1, J Vikranth2 M.E. (Ph.D.)
1

Assistant Professor, Department of Civil Engineering, PYDAH College of Engineering and Tech.,
Visakhapatnam
2
Associate Professor, Department of Civil Engineering, ANITS, Sangivalasa, Visakhapatnam
ABSTARCT
The aftermath of an earthquake manifests great devastation due to unpredicted seismic motion striking extensive
damage to innumerable buildings of varying degree i.e. either full or partial or slight. This damage to structures
in its turn causes irreparable loss of life with a large number of casualties. As a result frightened occupants may
refuse to enter the building unless assured of the safety of the building from future earthquake. It has been
observed that majority of such earthquake damaged buildings may be safely reused, if they are converted into
seismically resistant structures by employing a few retrofitting measures. This proves to be a better option
catering to the economic considerations and immediate shelter problems rather than replacement of buildings.
Seismic retrofitting of building structures is one of the most important aspects for mitigating seismic hazards
especially in earthquake-prone countries. Various terms are associated to retrofitting with a marginal difference
like repair, strengthening, retrofitting, remolding, rehabilitation, reconstruction etc. but there is no consensus on
them.
The main objective of this thesis work is the measures to be adopted in case of inadequacy without making structural
retrofitting.
Keywords: Earth quake, Retrofitting, Assessment.
mode of failure, structural behavior and weak and
strong design aspects as derived from the earthquake
I.
INTRODUCTION
damage surveys exercise considerable influence on
The need of seismic retrofitting of buildings
selection of retrofitting methods of buildings. Usually
arises under two circumstances:
the retrofitting method is aimed at increasing the
(i) Earthquake damaged buildings and
lateral resistance of the structure.
The lateral
(ii) Earthquake-vulnerable buildings that have not yet
resistance includes the lateral strength or stiffness and
experienced severe earthquake.
lateral displacement or ductility of the structures. The
The problems faced by a structural engineer in
lateral resistance is often provided through
retrofitting earthquake damaged buildings are:
modification or addition of retrofitting elements of an
(a) lack of standards for methods of retrofitting;
existing structure in certain areas only.
(b) effectiveness of retrofitting techniques since there
is a considerable dearth of experience and data on
retrofitted structure;
III.
NEED FOR SEISMIC
(c) absence of consensus on appropriate methods for
RETROFITTING:
the wide range of parameters like type of structures,
An existing structure may need seismic
condition of materials, type of damage, amount of
retrofitting, if the structure was initially not designed
damage, location of damage, significance of damage,
and constructed to resist an earthquake. Further,
condition under which a damaged element can be
retrofitting would be essential if the structure was
retrofitted etc. Therefore, a catalogue of available
initially designed and constructed to resist an
options regarding feasible and practical retrofitting
earthquake but
method is needed by the structural engineer due to
i) The loading/ load carrying parameters have changed
great variability of retrofitting requirements differing
since its construction due to:
from building to building.
 The present structural quality being bad due to
poor maintenance or aging
II.
CONSIDERATION IN
 Loads have increased due to change of mode of
RETROFITTING OF STRUCTURES
use.
The method of retrofitting principally
 Alterations / extensions are carried out or are
depends on the horizontal and vertical load resisting
contemplated.
system of the structure and type of materials used for
ii) The design criteria have changed due to:
parent construction. It also relies on the technology
 Up gradation of the seismic zone, importance
that is feasible and economical. The understanding of
factor etc.
www.ijera.com

1850 | P a g e
S D V S N Rao et al Int. Journal of Engineering Research and Applications

www.ijera.com

ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855


Revisions in the methodology or specifications of
structural design/detailing.

IV.
CLASSIFICATION OF
RETROFITTING TECHNIQUES
There are two ways to enhance the seismic
capacity of existing structures.
The first is a
structural-level approach of retrofitting which involves
global modifications to the structural system. The
second is a member level approach of retrofitting or
local retrofitting which deals with an increase of the
ductility of components with adequate capacities to
satisfy their specific limit states. Based on the above
concept the available techniques of retrofitting of
reinforced concrete buildings may be classified as in
Figure 7.1.1

Fig.1

V.

Retrofitting Techniques

SEISMIC ASSESSMENT

Seismic assessment is a natural prerequisite
to seismic retrofitting. Ideally, the purpose of a
comprehensive assessment should be to “assess the
seismic resistance of the structure for the present
criteria and to check the feasibility of one or more
(alternative) practical schemes of retrofitting keeping
in mind the aspects of economy and convenience to
the owners”. Hence, every task of assessment should
pass through a set of well-defined steps, should refer
to or create useful references and end with a wellstructured report giving recommendations for the
schemes of retrofitting along with their merits,
demerits and limitations.
Primarily, the process of assessment will
consist of:
Fieldwork: This will entail collection of data by
detailed inspection of the structure.
References: References should comprise original
drawings, drawings of extensions, test results etc as
compiled data.
Office work: This would mainly involve structural
analysis to suggest feasible schemes of retrofitting.
6.5.1 STEPS OF ASSESSMENT:
The standard and comprehensive assessment
should involve data collection, compilation of data and
www.ijera.com

assessing the feasibility of retrofitting. The details are
given below.
6.5.2 Data Collection:
Data collection is a primary process in
assessment work. Following are the steps involved in
the data collection for seismic assessment.
 Review of original architectural and structural
drawings (if available) from the angles of
structural design and detailing. This has to be
done by checking whether the structure was
originally designed for earthquake from:
 The loading specifications and provisions for
future extensions.
 The materials specifications.
 The soil properties.
 The seismic design parameters (if the
structure was designed for seismic loads).
 The design methodology.
Even if the original drawings are
available, before using them, it is necessary to
compare them with the existing building and to
confirm that they indeed represent the actual
building.
 If original drawings are not available or if they do
not match the existing building, as
in-built
drawings may be prepared for future use in
modeling for feasibility assessment. While it
would be easy to prepare architectural drawings,
preparation of structural drawings can be quite
difficult and may call for a good amount of
judgment and experience from the structural
engineer. This process may involve the following:
 Taking actual measurements of the
dimensions of the structural frames and
member sizes
 Ascertaining the quality of concrete by using
appropriate non-destructive tests. These tests
should be carried out, if necessary. Effects of
sulphates and chlorides should also be
ascertained.
 For columns below plinth (or ground),
foundations and sometimes for plinth beams,
it may be necessary to excavate up to the
foundation level for inspection.
 Qualitative assessment of the structure (from the
original drawings or from in expert inspection)
should be undertaken with respect to a list of
seismic sensitivity parameters such as:
 Architectural: Planning, shape, dimensions,
symmetry and soft storey etc.
 Structural: Load-carrying system, frames,
shear walls, floating columns and plinth
beams etc.
 Geo-technical: Foundation depth, supporting
strata, type of foundation, etc.
6.5.3 Compilation of data:
While compiling the data collected, efforts
should be made to establish rational correlation
amongst:
1851 | P a g e
S D V S N Rao et al Int. Journal of Engineering Research and Applications

www.ijera.com

ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855




Original/ prepared architectural and structural
drawings and specifications
Seismic vulnerability report based on seismic
sensitivity parameters
Report on the visual inspection recording:
 Observations about structural health of
structural members
 Deviations from original planning
 Effects of earlier earthquakes
 Earlier rehabilitation works.
 Test reports
 Record of past rehabilitation works, if any.

6.5.4 Feasibility of Retrofitting:
Based on the data Collected, the structural
feasibility of various alternative schemes of retrofitting
can be checked by modeling such schemes vis-a-vis
the existing structure. If any addition/ extension is
contemplated in the near future, the same should also
be modeled in suggesting the schemes. Thereafter,
alternative estimate of cost and time can be prepared.
The practicality of each of the alternatives can then be
evaluated with reference to the following criteria.
 Estimated cost.
 Estimated time required for retrofitting.
 Convenience of the implementation of the
scheme from the point of views of the owners
/ complaints.
 Limitations of the scheme.
It is very important to note that the
structurally best scheme may not necessarily be
the most practical one. More ever the
limitations of the each scheme should also be
clearly understood. The comprehensive data
collected can be very useful in quickly
revising, a scheme to take care of the problems
/ apprehensions of the owners whenever
possible.

VI.

VII.

RETROFITTING FOR VARIOUS
PARTS OF THE BUILDING

6.7.1 Foundations:
In rare cases, when there is net uplift in a
column, column footings may tend to fail before the
supported column can develop a plastic hinge. This is
usually due to the absence of a top layer of
reinforcement and vertical ties in footing which need
the capability to resist uplift forces. During an
earthquake, this can result in flexural cracking of the
footing concrete or de-lamination of the concrete
footing and may also result in a loss of anchorage for
the column longitudinal reinforcement.
This deficiency could be rectified by
thickening the existing foundation and by providing
additional steel in it. Dowels between the new and old
concrete should be capable of transferring the shear
stress on the interface. Alternately, tested chemicals
may be considered for this purpose. Increasing the
depth of the footing will also increase the positive
moment capacity as a result of increased section depth.
If this is still inadequate, widening of the footing will
be needed, with additional bottom steel. However,
rebars should be placed within a distance equal to the
depth of the footing on either side of the column for
these rebars to be effective. Strengthening of
Foundation by Widening
6.7.2 Column Strengthening:
The philosophy behind seismic column
strengthening is that the axial load strength of a
column after concrete has spalled off should be at least
equal to the axial load strength before spalling and
should plastic hinges occur at column ends, ductility
must be ensured by confining the concrete with special
confining steel. The conventional retrofitting
technique for columns is described below.

STEPS FOR RETROFITTING

Before undertaking any retrofit, it is
imperative to carry out the following procedures:
 Compile all available information on the structure
including existing drawings.
 An exhaustive photo-documentation of any
distress patterns visible in the structure needs to
be done if it has already been subjected to seismic
loading.
 A thorough visual inspection of the structure with
special attention to the vulnerable spots - beamcolumn junctions, frame members, re-entrant
corners of shear walls, and water tanks at roof is
required.
 Perform an analysis based on the above data and
determine the inherent capacity of the structure to
resist the code-specified design seismic forces
with a reasonable degree of confidence.
 Review the detailing and design of the as-built
structure and determine its inherent capacity.
www.ijera.com

Fig 2 STRAP JACKETING

Fig 3 STRAP JACKETING
6.7.3 Concrete jacketing:
This method of column retrofit is very
popular and is used when the columns are deficient in
strength. It involves addition of a comparatively thick
1852 | P a g e
S D V S N Rao et al Int. Journal of Engineering Research and Applications

www.ijera.com

ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855
layer of reinforced concrete in the form of a jacket
around an existing column. Adequate confinement of
rectangular columns by a rectangular jacket requires
extensive doweling to connect the jacket to the
existing column (which also act as lateral ties for the
newly introduced column vertical reinforcement)
and/or use of suitable bonding chemicals at the
interface of the old and new concrete shown in
Concrete Jacket for Column.

Fig 5 Beam Strengthening

6.7.4 Beam-Column Joint:
Doweling vertically through the existing
beams is required to ensure continuity in strength
enhancement at the beam-column junctions shown in.
If this is not done, only local strength enhancement is
achieved and the beam column junctions may continue
to remind vulnerable.

Fig 6 Beam Strengthening
6.7.6 Retrofit of Shear Wall Building:
The existing shear walls may be strengthened
by increasing the stiffness of these walls; this can be
achieved by providing additional thickness to the wall.
The additional wall thickness may be provided by
means of shotcreting (gunting). The new thickness of
wall must be connected to the existing wall by means
of doweling, designed to transfer the interface shear
forces, or by suitable tested chemicals.

Fig 4
The advantage of this retrofit method is that it
enhances both ductility and overall flexural strength.
This method of retrofit is carried out by many agencies
and information is easily available. There are no
additional fire and corrosion protection required.
6.7.5 Beam Retrofit:
Deficiency in seismic behaviour of beams
may be in shear, flexure or joint shear. Enhancing
flexural capacity of integral beams is difficult because
of the constraints placed by the existing superstructure
on the sides. To augment the positive moment capacity
(which usually is not a critical issue except it, the end
supports under seismic loading), additional bottom
reinforcement may be provided by introducing
additional beams on either side of the existing beam,
or by alternatively providing additional steel on the
bottom by enhancing the depth of the beam by means
of polymer concrete, a resin concrete or micro
concrete depending on the suitability for the beam
under consideration.
Negative moment capacity can be increased
by removing top concrete and providing additional
reinforcement. This is not so difficult in a country
such as India where there is a total flooring cover of
about 50 mm. Most often, both moment and shear
capacity need to be enhanced for ductile behaviour and
in such cases a beam jacket, on similar lines to column
jacketing complete with additional stirrups may be
provided. This may require propping of the adjacent
slabs.
www.ijera.com

Fig 7 Strengthening of Existing Shear Wall
Alternately, end bolster columns may be added and
connected sufficiently well with the existing wall. This
may, however, also need enhancement of the
foundations,

Fig 8 Building Retrofitted with steel bracing

VIII.

RETROFIT SCHEMES

The various retrofit schemes adopted in
Ahmadabad and other areas of the State of Gujarat
include

1853 | P a g e
S D V S N Rao et al Int. Journal of Engineering Research and Applications

www.ijera.com

ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855

Fig 9 Infill walls and columns






Pointing and re-plaster of cracked infill walls and
columns
Replace all the infill walls in the RC frame panels
Jacket RC columns in the open ground story .In
many cases of column jacketing, the new
reinforcement was not anchored into the
foundations or the building frame, and the plaster
on the old concrete column surface was not
removed.
Prop beams with masonry pillars, or steel joists or
built-up sections
Provide steel braces in open bays

6.8.1 FRP jacketing
Several researches have investigated the
possibility and feasibility of fibre reinforced polymer
composite jackets for seismic strengthening of
columns winding them with high strength carbon
fibres around column surface to add spiral hoops. The
merits of this method are: (i) carbon fiber is flexible
and can be made to contact the surface tightly for a
high degree of confinement; (ii) confinement is of high
degree because carbon fibers of high strength and high
modules of elasticity are used; (iii) the carbon fiber
has light weight and rusting does not occur.
The most critical type of structural damage is
the slab column connection which results in the
punching shear failure due to the transfer of
unbalanced moments. The retrofitting of slab column
connection is beneficial for the prevention of punching
shear failures.

Fig 10 FRP JACKETING
6.8.2 JACKETING COLUMNS:
Jacketing of RC columns in the ground story
is the most common measure being adopted. In most
cases, the additional concrete and reinforcement is just
added around the old column and in some cases, the
old column is snugly strapped with steel angles and
flats and then the concreting is done. There was at
www.ijera.com

least one building in Ahmadabad, where immediately
after the earthquake, the columns in the ground story
were jacketed to an unusually large size. In many
cases, the jacketing has been done without removing
the plaster, if any, or roughening the surface of the old
column. Jacketing often starts from the finished
ground floor level as against the foundation. In some
cases, the jacketing has been started from the
foundation. Furthermore, the longitudinal bars added
in the additional concrete portion are often left
projecting out without any connection to the older RC
beam and column members.
The some of the other retrofitting methods
adopted are as follows:










Numerous buildings in the affected area sustained
only frame-infills separation. In most of the cases
the separations were cleaned and filled with rich
cement mortar.
Large block sand stone masonry infills in cement
mortar at two-story school building in
Ahmadabad were completely replaced with burntclay brick masonry infill in cement mortar.
Jacketing of a rectangular column of the ground
storey of a seven-storey old age home in
Gandhidham, was performed from the floor level
to a level well below the beams at the top of that
column. The column bars are seen curtailed by the
side of the beam.
RC columns of the three-story residential RC
frame building in Gandhidham are adjoined with
brick masonry columns from the floor level to the
beam soffit. The beam is propped at intermediate
locations with hot-rolled steel I-sections.
Instances where column jacketing was started at
the footing level were few. Even in this case, the
column reinforcement may not have been
anchored into the footing.

IX.

RECOMMENDATIONS

The measures to be adopted in case of
inadequacy without making structural retrofitting are
adequately discussed in this study. A the structural
retrofitting is costlier, time consuming and inconvenience
for the occupants, the study has been taken up to evolve a
scientific approach for retrofitting.
The following are the some of the recommendations:
 If the strength of the column in the building found
to be deficit, they are strengthened /
retrofitted .Beams and foundations are adequately
safe.
 To perform well in an earthquake, a building
should possess four main attributes, namely simple
and regular configuration, adequate lateral
strength, stiffness and ductility.
 The cantilever overhang should be minimized and
the efforts should be made to ensure direct vertical
transfer of the gravity loads.
 All of the frames continue to the building base.
1854 | P a g e
S D V S N Rao et al Int. Journal of Engineering Research and Applications

www.ijera.com

ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855







Shear failure being brittle, it must be avoided in the
design of RC beams.
Steel reinforcement up to grade Fe415 shall be used.
Limitation on flexural reinforcement ratio is
recommended so as to ensure tension failure in the
beams.
All longitudinal column steel is should be dowelled
into the foundation.
The top as well as bottom reinforcement shall
consist of at least two bars throughout the member
length.
The positive steel at a joint face must be at least
equal to half the negative steel at that face.

The following recommendations on
detailing of the structure should be avoid ed in
construction:
 Large spacing of lateral ties in columns can lead to
lack of confinement for the concrete core and/or
shear failures.
 Insufficient column lap lengths can cause concrete
to spall.
 Location of inadequate splices for all column bars
at the same section can lead to column
failure.
 If the column shear strength is insufficient to
develop the full moment hinge capacity, the
column can exhibit a brittle shear failure.

Insufficient anchorage of shear tie reinforcing
in column cores can prevent the column from
developing its full shear capacity.
 Lack of continuous beam reinforcement can cause
hinge formation during load reversals.
 Inadequate reinforcing of beam-column joints or
location of beam bar splices at columns
can lead to joint failures.
 Foundation dowels that are insufficient to develop
the capacity of the column steel above
can lead to local column distress, the pedestals the
above the footing mitigates such failure.
 Use of bent-up longitudinal reinforcing in beams as
shear reinforcement can result in shear failure
during load reversal.
 The relatively low stiffness of the frames can lead
to excessive inter storey drifts. These
large drifts can cause damage to non-structural
items such as partitions, window, etc.

[4]

[5]

[6]

[7]

[8]

[9]

Pankaj Agrawal and S.K. Thakkar. Proc.
Tenth Symp. On Earthquake Engineering,
Nov 16-18, 1994, Roorkee. Paper presented
on Assessment of seismic vulnerability of
existing reinforced concrete building.
Rajeev Sharma, Jitendra S. Thakur. Proc. Of
workshop on “Advances in structural
Engineering” 21-22 December, 2001,
Tirupathi. Paper presented on structural
evaluation of existing building – A case
study.
J.N.Bandyopadhyay. “Earthquake resistant
design and detailing of RCC structures as per
codal provisions” chapter 17- SE 106, IIT
Kharagpur.
R.N.Iyengar, proc. Of workshop on
“Advances in structural Engineering”, 21-22
Decmber, 2001, Tirupathi. Paper presented
on Earthquake in India an engineering
perspective.
Dr.Durgesh C Rai IIT Kanpu “Review of
documents as seismic evaluation of existing
buildings-Document
No:IITK-GSDMAEQ03-V1.O,Interim Report I: A- Earthquake
Codes,IITK-GSDMA Project on Building
Codes”.
Dr.Shailesh Kumar Agarwal and Ajay
Chourasia “Methodology for seismic
vulnerability assessment of building stock in
megacities.

REFERENCES
[1]

[2]

[3]

Anil K.Chopra (2001). “Dynamics of
Structures”, Prentice Hall of India Pvt., New
Delhi.
A.R. Chndrasekaram and D.S. Prakash Rao.
Paper presented on :”A seismic Design of
Multi-storied RCC Buildings” IIT, Roorkee.
“Low-Cost
construction
resistant
to
earthquakes” United nations, New Yark,
1975

www.ijera.com

1855 | P a g e

Mais conteúdo relacionado

Mais procurados

IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced FramesIRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced FramesIRJET Journal
 
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...IRJET Journal
 
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET Journal
 
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET Journal
 
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...IRJET Journal
 
IRJET- Analysis of Irregular Structure under Linear Time History
IRJET- Analysis of Irregular Structure under Linear Time HistoryIRJET- Analysis of Irregular Structure under Linear Time History
IRJET- Analysis of Irregular Structure under Linear Time HistoryIRJET Journal
 
IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...
IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...
IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...IRJET Journal
 
Behaviour of Flat Slab by Varying Stiffness in High Seismic Zone
Behaviour of Flat Slab by Varying Stiffness in High Seismic ZoneBehaviour of Flat Slab by Varying Stiffness in High Seismic Zone
Behaviour of Flat Slab by Varying Stiffness in High Seismic ZoneIRJET Journal
 
IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...
IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...
IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...IRJET Journal
 
Depremyonetmeligiing
DepremyonetmeligiingDepremyonetmeligiing
Depremyonetmeligiing__cyber__
 
Ap's IS-1893.1.2002
Ap's IS-1893.1.2002Ap's IS-1893.1.2002
Ap's IS-1893.1.2002Ayaz Pirkhan
 
Analysis of Foundation Failure in Concrete Structure
Analysis of Foundation Failure in Concrete StructureAnalysis of Foundation Failure in Concrete Structure
Analysis of Foundation Failure in Concrete StructureIRJET Journal
 
Etabs BY Subash Pathak
Etabs BY Subash PathakEtabs BY Subash Pathak
Etabs BY Subash PathakSubash Pathak
 
Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...
Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...
Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...IRJET Journal
 

Mais procurados (19)

IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced FramesIRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
IRJET- Seismic Analysis of a Multi-Storey Building using Steel Braced Frames
 
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
Seismic Evolution of Soft Storeyed Buildings when Subjected to Real Time Eart...
 
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
IRJET- Seismic Analysis and Design of Multistorey Building in Different Seism...
 
F012443844
F012443844F012443844
F012443844
 
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
 
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...IRJET-  	  A Review on Seismic Analysis of Buildings using Passive Energy Dis...
IRJET- A Review on Seismic Analysis of Buildings using Passive Energy Dis...
 
IRJET- Analysis of Irregular Structure under Linear Time History
IRJET- Analysis of Irregular Structure under Linear Time HistoryIRJET- Analysis of Irregular Structure under Linear Time History
IRJET- Analysis of Irregular Structure under Linear Time History
 
IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...
IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...
IRJET- An Innovative Method of Electricity Generation from Speed-Breakers of ...
 
Behaviour of Flat Slab by Varying Stiffness in High Seismic Zone
Behaviour of Flat Slab by Varying Stiffness in High Seismic ZoneBehaviour of Flat Slab by Varying Stiffness in High Seismic Zone
Behaviour of Flat Slab by Varying Stiffness in High Seismic Zone
 
IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...
IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...
IRJET-Analytical Study on Horizontal Irregularities in RCC Structures with La...
 
1893 1
1893 11893 1
1893 1
 
Lf3519191924
Lf3519191924Lf3519191924
Lf3519191924
 
Depremyonetmeligiing
DepremyonetmeligiingDepremyonetmeligiing
Depremyonetmeligiing
 
Ap's IS-1893.1.2002
Ap's IS-1893.1.2002Ap's IS-1893.1.2002
Ap's IS-1893.1.2002
 
IS.1893.1.2002
IS.1893.1.2002IS.1893.1.2002
IS.1893.1.2002
 
Presentation04_shj
Presentation04_shjPresentation04_shj
Presentation04_shj
 
Analysis of Foundation Failure in Concrete Structure
Analysis of Foundation Failure in Concrete StructureAnalysis of Foundation Failure in Concrete Structure
Analysis of Foundation Failure in Concrete Structure
 
Etabs BY Subash Pathak
Etabs BY Subash PathakEtabs BY Subash Pathak
Etabs BY Subash Pathak
 
Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...
Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...
Evaluation of Response Reduction Factor for Moment Resisting Steel Frames- A ...
 

Destaque (20)

Kx3618681871
Kx3618681871Kx3618681871
Kx3618681871
 
La3618791882
La3618791882La3618791882
La3618791882
 
Kt3618371840
Kt3618371840Kt3618371840
Kt3618371840
 
Kw3618561867
Kw3618561867Kw3618561867
Kw3618561867
 
Ku3618411849
Ku3618411849Ku3618411849
Ku3618411849
 
Prenda futurista.creación de una bolsa reciclada
Prenda futurista.creación de una bolsa recicladaPrenda futurista.creación de una bolsa reciclada
Prenda futurista.creación de una bolsa reciclada
 
Cuestionario cop (1)
Cuestionario cop (1)Cuestionario cop (1)
Cuestionario cop (1)
 
Recorido
RecoridoRecorido
Recorido
 
Pintxo andaluz
Pintxo andaluz Pintxo andaluz
Pintxo andaluz
 
Fútbol
FútbolFútbol
Fútbol
 
LA CRÓNICA 650
LA CRÓNICA 650LA CRÓNICA 650
LA CRÓNICA 650
 
3º basico a 05 de junio
3º basico a  05 de junio3º basico a  05 de junio
3º basico a 05 de junio
 
Moda Club liquidación Total volumen 3
Moda Club liquidación Total volumen 3Moda Club liquidación Total volumen 3
Moda Club liquidación Total volumen 3
 
H.c.d.n 22 directivos (1).docx vale
H.c.d.n 22 directivos (1).docx valeH.c.d.n 22 directivos (1).docx vale
H.c.d.n 22 directivos (1).docx vale
 
Taller2 internet ariza
Taller2 internet arizaTaller2 internet ariza
Taller2 internet ariza
 
mi experiencia
mi experiencia mi experiencia
mi experiencia
 
The Art of Pinterest for WordPress - WordCamp Hamilton 2015
The Art of Pinterest for WordPress - WordCamp Hamilton 2015The Art of Pinterest for WordPress - WordCamp Hamilton 2015
The Art of Pinterest for WordPress - WordCamp Hamilton 2015
 
Recorido
RecoridoRecorido
Recorido
 
Business division key note final
Business division key note finalBusiness division key note final
Business division key note final
 
Piratas del caribe
Piratas del caribePiratas del caribe
Piratas del caribe
 

Semelhante a Kv3618501855

PRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDING
PRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDINGPRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDING
PRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDINGMohammedHashim81
 
Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...
Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...
Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...IRJET Journal
 
IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...
IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...
IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...IRJET Journal
 
Response Spectrum and Time History Analysis of a Multistorey Building
Response Spectrum and Time History Analysis of a Multistorey BuildingResponse Spectrum and Time History Analysis of a Multistorey Building
Response Spectrum and Time History Analysis of a Multistorey BuildingIRJET Journal
 
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...IRJET Journal
 
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...IRJET Journal
 
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...IRJET Journal
 
SEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDING
SEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDINGSEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDING
SEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDINGIRJET Journal
 
A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...IRJET Journal
 
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
IRJET-  	  Study of Literature on Seismic Response of RC Irregular StructureIRJET-  	  Study of Literature on Seismic Response of RC Irregular Structure
IRJET- Study of Literature on Seismic Response of RC Irregular StructureIRJET Journal
 
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...IJERA Editor
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...IRJET Journal
 
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...IRJET Journal
 
Seismic Performance of RC Frame Building with Different Position of Shear Wall
Seismic Performance of RC Frame Building with Different Position of Shear WallSeismic Performance of RC Frame Building with Different Position of Shear Wall
Seismic Performance of RC Frame Building with Different Position of Shear Wallijtsrd
 
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...IRJET Journal
 
Review paper on seismic responses of multistored rcc building with mass irreg...
Review paper on seismic responses of multistored rcc building with mass irreg...Review paper on seismic responses of multistored rcc building with mass irreg...
Review paper on seismic responses of multistored rcc building with mass irreg...eSAT Journals
 
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGSSEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGSIRJET Journal
 
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...IRJET Journal
 
1 1 9-bhavar-dadasaheb-o.-et-al (2)
1 1 9-bhavar-dadasaheb-o.-et-al (2)1 1 9-bhavar-dadasaheb-o.-et-al (2)
1 1 9-bhavar-dadasaheb-o.-et-al (2)Riddhi Patel
 
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET Journal
 

Semelhante a Kv3618501855 (20)

PRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDING
PRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDINGPRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDING
PRESENTATION ON SEISMIC ANALYSIS AND DESIGN OF COLLEGE BUILDING
 
Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...
Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...
Performance Of Multistoried (20 Storey) RCC Setback Buildings By Using Pushov...
 
IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...
IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...
IRJET- Pushover Analysis of Existing RC Frame Structure : A State of the Art ...
 
Response Spectrum and Time History Analysis of a Multistorey Building
Response Spectrum and Time History Analysis of a Multistorey BuildingResponse Spectrum and Time History Analysis of a Multistorey Building
Response Spectrum and Time History Analysis of a Multistorey Building
 
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
 
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
 
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
IRJET- Seismic Evolution of Soft Storeyed Structures When Exposed to Earth Qu...
 
SEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDING
SEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDINGSEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDING
SEISMIC RESISTIVITY AND RETROFITTING OF RC FRAME BUILDING
 
A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...A Review on Comparative Analysis of Multistorey Buildings Under Various India...
A Review on Comparative Analysis of Multistorey Buildings Under Various India...
 
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
IRJET-  	  Study of Literature on Seismic Response of RC Irregular StructureIRJET-  	  Study of Literature on Seismic Response of RC Irregular Structure
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
 
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
Comparative study of Performance of RCC Multi-Storey Building for Koyna and B...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
Comparative Study on Masonry Infill, Friction Dampers and Bare Frame Structur...
 
Seismic Performance of RC Frame Building with Different Position of Shear Wall
Seismic Performance of RC Frame Building with Different Position of Shear WallSeismic Performance of RC Frame Building with Different Position of Shear Wall
Seismic Performance of RC Frame Building with Different Position of Shear Wall
 
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
Comparative Seismic Analysis of G+20 RC Framed Structure Building for Maximum...
 
Review paper on seismic responses of multistored rcc building with mass irreg...
Review paper on seismic responses of multistored rcc building with mass irreg...Review paper on seismic responses of multistored rcc building with mass irreg...
Review paper on seismic responses of multistored rcc building with mass irreg...
 
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGSSEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
 
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
 
1 1 9-bhavar-dadasaheb-o.-et-al (2)
1 1 9-bhavar-dadasaheb-o.-et-al (2)1 1 9-bhavar-dadasaheb-o.-et-al (2)
1 1 9-bhavar-dadasaheb-o.-et-al (2)
 
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
 

Último

What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyAlfredo García Lavilla
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr LapshynFwdays
 
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks..."LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...Fwdays
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationSlibray Presentation
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticscarlostorres15106
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfAlex Barbosa Coqueiro
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piececharlottematthew16
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embeddingZilliz
 

Último (20)

What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Commit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easyCommit 2024 - Secret Management made easy
Commit 2024 - Secret Management made easy
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
 
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks..."LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
"LLMs for Python Engineers: Advanced Data Analysis and Semantic Kernel",Oleks...
 
Connect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck PresentationConnect Wave/ connectwave Pitch Deck Presentation
Connect Wave/ connectwave Pitch Deck Presentation
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Unraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdfUnraveling Multimodality with Large Language Models.pdf
Unraveling Multimodality with Large Language Models.pdf
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 
DMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special EditionDMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special Edition
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piece
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
Training state-of-the-art general text embedding
Training state-of-the-art general text embeddingTraining state-of-the-art general text embedding
Training state-of-the-art general text embedding
 

Kv3618501855

  • 1. S D V S N Rao et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855 RESEARCH ARTICLE OPEN ACCESS Promotion of Seismic Retrofitting For Existing Low Earthquake Resistant Structures S D V S N Rao1, J Vikranth2 M.E. (Ph.D.) 1 Assistant Professor, Department of Civil Engineering, PYDAH College of Engineering and Tech., Visakhapatnam 2 Associate Professor, Department of Civil Engineering, ANITS, Sangivalasa, Visakhapatnam ABSTARCT The aftermath of an earthquake manifests great devastation due to unpredicted seismic motion striking extensive damage to innumerable buildings of varying degree i.e. either full or partial or slight. This damage to structures in its turn causes irreparable loss of life with a large number of casualties. As a result frightened occupants may refuse to enter the building unless assured of the safety of the building from future earthquake. It has been observed that majority of such earthquake damaged buildings may be safely reused, if they are converted into seismically resistant structures by employing a few retrofitting measures. This proves to be a better option catering to the economic considerations and immediate shelter problems rather than replacement of buildings. Seismic retrofitting of building structures is one of the most important aspects for mitigating seismic hazards especially in earthquake-prone countries. Various terms are associated to retrofitting with a marginal difference like repair, strengthening, retrofitting, remolding, rehabilitation, reconstruction etc. but there is no consensus on them. The main objective of this thesis work is the measures to be adopted in case of inadequacy without making structural retrofitting. Keywords: Earth quake, Retrofitting, Assessment. mode of failure, structural behavior and weak and strong design aspects as derived from the earthquake I. INTRODUCTION damage surveys exercise considerable influence on The need of seismic retrofitting of buildings selection of retrofitting methods of buildings. Usually arises under two circumstances: the retrofitting method is aimed at increasing the (i) Earthquake damaged buildings and lateral resistance of the structure. The lateral (ii) Earthquake-vulnerable buildings that have not yet resistance includes the lateral strength or stiffness and experienced severe earthquake. lateral displacement or ductility of the structures. The The problems faced by a structural engineer in lateral resistance is often provided through retrofitting earthquake damaged buildings are: modification or addition of retrofitting elements of an (a) lack of standards for methods of retrofitting; existing structure in certain areas only. (b) effectiveness of retrofitting techniques since there is a considerable dearth of experience and data on retrofitted structure; III. NEED FOR SEISMIC (c) absence of consensus on appropriate methods for RETROFITTING: the wide range of parameters like type of structures, An existing structure may need seismic condition of materials, type of damage, amount of retrofitting, if the structure was initially not designed damage, location of damage, significance of damage, and constructed to resist an earthquake. Further, condition under which a damaged element can be retrofitting would be essential if the structure was retrofitted etc. Therefore, a catalogue of available initially designed and constructed to resist an options regarding feasible and practical retrofitting earthquake but method is needed by the structural engineer due to i) The loading/ load carrying parameters have changed great variability of retrofitting requirements differing since its construction due to: from building to building.  The present structural quality being bad due to poor maintenance or aging II. CONSIDERATION IN  Loads have increased due to change of mode of RETROFITTING OF STRUCTURES use. The method of retrofitting principally  Alterations / extensions are carried out or are depends on the horizontal and vertical load resisting contemplated. system of the structure and type of materials used for ii) The design criteria have changed due to: parent construction. It also relies on the technology  Up gradation of the seismic zone, importance that is feasible and economical. The understanding of factor etc. www.ijera.com 1850 | P a g e
  • 2. S D V S N Rao et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855  Revisions in the methodology or specifications of structural design/detailing. IV. CLASSIFICATION OF RETROFITTING TECHNIQUES There are two ways to enhance the seismic capacity of existing structures. The first is a structural-level approach of retrofitting which involves global modifications to the structural system. The second is a member level approach of retrofitting or local retrofitting which deals with an increase of the ductility of components with adequate capacities to satisfy their specific limit states. Based on the above concept the available techniques of retrofitting of reinforced concrete buildings may be classified as in Figure 7.1.1 Fig.1 V. Retrofitting Techniques SEISMIC ASSESSMENT Seismic assessment is a natural prerequisite to seismic retrofitting. Ideally, the purpose of a comprehensive assessment should be to “assess the seismic resistance of the structure for the present criteria and to check the feasibility of one or more (alternative) practical schemes of retrofitting keeping in mind the aspects of economy and convenience to the owners”. Hence, every task of assessment should pass through a set of well-defined steps, should refer to or create useful references and end with a wellstructured report giving recommendations for the schemes of retrofitting along with their merits, demerits and limitations. Primarily, the process of assessment will consist of: Fieldwork: This will entail collection of data by detailed inspection of the structure. References: References should comprise original drawings, drawings of extensions, test results etc as compiled data. Office work: This would mainly involve structural analysis to suggest feasible schemes of retrofitting. 6.5.1 STEPS OF ASSESSMENT: The standard and comprehensive assessment should involve data collection, compilation of data and www.ijera.com assessing the feasibility of retrofitting. The details are given below. 6.5.2 Data Collection: Data collection is a primary process in assessment work. Following are the steps involved in the data collection for seismic assessment.  Review of original architectural and structural drawings (if available) from the angles of structural design and detailing. This has to be done by checking whether the structure was originally designed for earthquake from:  The loading specifications and provisions for future extensions.  The materials specifications.  The soil properties.  The seismic design parameters (if the structure was designed for seismic loads).  The design methodology. Even if the original drawings are available, before using them, it is necessary to compare them with the existing building and to confirm that they indeed represent the actual building.  If original drawings are not available or if they do not match the existing building, as in-built drawings may be prepared for future use in modeling for feasibility assessment. While it would be easy to prepare architectural drawings, preparation of structural drawings can be quite difficult and may call for a good amount of judgment and experience from the structural engineer. This process may involve the following:  Taking actual measurements of the dimensions of the structural frames and member sizes  Ascertaining the quality of concrete by using appropriate non-destructive tests. These tests should be carried out, if necessary. Effects of sulphates and chlorides should also be ascertained.  For columns below plinth (or ground), foundations and sometimes for plinth beams, it may be necessary to excavate up to the foundation level for inspection.  Qualitative assessment of the structure (from the original drawings or from in expert inspection) should be undertaken with respect to a list of seismic sensitivity parameters such as:  Architectural: Planning, shape, dimensions, symmetry and soft storey etc.  Structural: Load-carrying system, frames, shear walls, floating columns and plinth beams etc.  Geo-technical: Foundation depth, supporting strata, type of foundation, etc. 6.5.3 Compilation of data: While compiling the data collected, efforts should be made to establish rational correlation amongst: 1851 | P a g e
  • 3. S D V S N Rao et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855    Original/ prepared architectural and structural drawings and specifications Seismic vulnerability report based on seismic sensitivity parameters Report on the visual inspection recording:  Observations about structural health of structural members  Deviations from original planning  Effects of earlier earthquakes  Earlier rehabilitation works.  Test reports  Record of past rehabilitation works, if any. 6.5.4 Feasibility of Retrofitting: Based on the data Collected, the structural feasibility of various alternative schemes of retrofitting can be checked by modeling such schemes vis-a-vis the existing structure. If any addition/ extension is contemplated in the near future, the same should also be modeled in suggesting the schemes. Thereafter, alternative estimate of cost and time can be prepared. The practicality of each of the alternatives can then be evaluated with reference to the following criteria.  Estimated cost.  Estimated time required for retrofitting.  Convenience of the implementation of the scheme from the point of views of the owners / complaints.  Limitations of the scheme. It is very important to note that the structurally best scheme may not necessarily be the most practical one. More ever the limitations of the each scheme should also be clearly understood. The comprehensive data collected can be very useful in quickly revising, a scheme to take care of the problems / apprehensions of the owners whenever possible. VI. VII. RETROFITTING FOR VARIOUS PARTS OF THE BUILDING 6.7.1 Foundations: In rare cases, when there is net uplift in a column, column footings may tend to fail before the supported column can develop a plastic hinge. This is usually due to the absence of a top layer of reinforcement and vertical ties in footing which need the capability to resist uplift forces. During an earthquake, this can result in flexural cracking of the footing concrete or de-lamination of the concrete footing and may also result in a loss of anchorage for the column longitudinal reinforcement. This deficiency could be rectified by thickening the existing foundation and by providing additional steel in it. Dowels between the new and old concrete should be capable of transferring the shear stress on the interface. Alternately, tested chemicals may be considered for this purpose. Increasing the depth of the footing will also increase the positive moment capacity as a result of increased section depth. If this is still inadequate, widening of the footing will be needed, with additional bottom steel. However, rebars should be placed within a distance equal to the depth of the footing on either side of the column for these rebars to be effective. Strengthening of Foundation by Widening 6.7.2 Column Strengthening: The philosophy behind seismic column strengthening is that the axial load strength of a column after concrete has spalled off should be at least equal to the axial load strength before spalling and should plastic hinges occur at column ends, ductility must be ensured by confining the concrete with special confining steel. The conventional retrofitting technique for columns is described below. STEPS FOR RETROFITTING Before undertaking any retrofit, it is imperative to carry out the following procedures:  Compile all available information on the structure including existing drawings.  An exhaustive photo-documentation of any distress patterns visible in the structure needs to be done if it has already been subjected to seismic loading.  A thorough visual inspection of the structure with special attention to the vulnerable spots - beamcolumn junctions, frame members, re-entrant corners of shear walls, and water tanks at roof is required.  Perform an analysis based on the above data and determine the inherent capacity of the structure to resist the code-specified design seismic forces with a reasonable degree of confidence.  Review the detailing and design of the as-built structure and determine its inherent capacity. www.ijera.com Fig 2 STRAP JACKETING Fig 3 STRAP JACKETING 6.7.3 Concrete jacketing: This method of column retrofit is very popular and is used when the columns are deficient in strength. It involves addition of a comparatively thick 1852 | P a g e
  • 4. S D V S N Rao et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855 layer of reinforced concrete in the form of a jacket around an existing column. Adequate confinement of rectangular columns by a rectangular jacket requires extensive doweling to connect the jacket to the existing column (which also act as lateral ties for the newly introduced column vertical reinforcement) and/or use of suitable bonding chemicals at the interface of the old and new concrete shown in Concrete Jacket for Column. Fig 5 Beam Strengthening 6.7.4 Beam-Column Joint: Doweling vertically through the existing beams is required to ensure continuity in strength enhancement at the beam-column junctions shown in. If this is not done, only local strength enhancement is achieved and the beam column junctions may continue to remind vulnerable. Fig 6 Beam Strengthening 6.7.6 Retrofit of Shear Wall Building: The existing shear walls may be strengthened by increasing the stiffness of these walls; this can be achieved by providing additional thickness to the wall. The additional wall thickness may be provided by means of shotcreting (gunting). The new thickness of wall must be connected to the existing wall by means of doweling, designed to transfer the interface shear forces, or by suitable tested chemicals. Fig 4 The advantage of this retrofit method is that it enhances both ductility and overall flexural strength. This method of retrofit is carried out by many agencies and information is easily available. There are no additional fire and corrosion protection required. 6.7.5 Beam Retrofit: Deficiency in seismic behaviour of beams may be in shear, flexure or joint shear. Enhancing flexural capacity of integral beams is difficult because of the constraints placed by the existing superstructure on the sides. To augment the positive moment capacity (which usually is not a critical issue except it, the end supports under seismic loading), additional bottom reinforcement may be provided by introducing additional beams on either side of the existing beam, or by alternatively providing additional steel on the bottom by enhancing the depth of the beam by means of polymer concrete, a resin concrete or micro concrete depending on the suitability for the beam under consideration. Negative moment capacity can be increased by removing top concrete and providing additional reinforcement. This is not so difficult in a country such as India where there is a total flooring cover of about 50 mm. Most often, both moment and shear capacity need to be enhanced for ductile behaviour and in such cases a beam jacket, on similar lines to column jacketing complete with additional stirrups may be provided. This may require propping of the adjacent slabs. www.ijera.com Fig 7 Strengthening of Existing Shear Wall Alternately, end bolster columns may be added and connected sufficiently well with the existing wall. This may, however, also need enhancement of the foundations, Fig 8 Building Retrofitted with steel bracing VIII. RETROFIT SCHEMES The various retrofit schemes adopted in Ahmadabad and other areas of the State of Gujarat include 1853 | P a g e
  • 5. S D V S N Rao et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855 Fig 9 Infill walls and columns     Pointing and re-plaster of cracked infill walls and columns Replace all the infill walls in the RC frame panels Jacket RC columns in the open ground story .In many cases of column jacketing, the new reinforcement was not anchored into the foundations or the building frame, and the plaster on the old concrete column surface was not removed. Prop beams with masonry pillars, or steel joists or built-up sections Provide steel braces in open bays 6.8.1 FRP jacketing Several researches have investigated the possibility and feasibility of fibre reinforced polymer composite jackets for seismic strengthening of columns winding them with high strength carbon fibres around column surface to add spiral hoops. The merits of this method are: (i) carbon fiber is flexible and can be made to contact the surface tightly for a high degree of confinement; (ii) confinement is of high degree because carbon fibers of high strength and high modules of elasticity are used; (iii) the carbon fiber has light weight and rusting does not occur. The most critical type of structural damage is the slab column connection which results in the punching shear failure due to the transfer of unbalanced moments. The retrofitting of slab column connection is beneficial for the prevention of punching shear failures. Fig 10 FRP JACKETING 6.8.2 JACKETING COLUMNS: Jacketing of RC columns in the ground story is the most common measure being adopted. In most cases, the additional concrete and reinforcement is just added around the old column and in some cases, the old column is snugly strapped with steel angles and flats and then the concreting is done. There was at www.ijera.com least one building in Ahmadabad, where immediately after the earthquake, the columns in the ground story were jacketed to an unusually large size. In many cases, the jacketing has been done without removing the plaster, if any, or roughening the surface of the old column. Jacketing often starts from the finished ground floor level as against the foundation. In some cases, the jacketing has been started from the foundation. Furthermore, the longitudinal bars added in the additional concrete portion are often left projecting out without any connection to the older RC beam and column members. The some of the other retrofitting methods adopted are as follows:      Numerous buildings in the affected area sustained only frame-infills separation. In most of the cases the separations were cleaned and filled with rich cement mortar. Large block sand stone masonry infills in cement mortar at two-story school building in Ahmadabad were completely replaced with burntclay brick masonry infill in cement mortar. Jacketing of a rectangular column of the ground storey of a seven-storey old age home in Gandhidham, was performed from the floor level to a level well below the beams at the top of that column. The column bars are seen curtailed by the side of the beam. RC columns of the three-story residential RC frame building in Gandhidham are adjoined with brick masonry columns from the floor level to the beam soffit. The beam is propped at intermediate locations with hot-rolled steel I-sections. Instances where column jacketing was started at the footing level were few. Even in this case, the column reinforcement may not have been anchored into the footing. IX. RECOMMENDATIONS The measures to be adopted in case of inadequacy without making structural retrofitting are adequately discussed in this study. A the structural retrofitting is costlier, time consuming and inconvenience for the occupants, the study has been taken up to evolve a scientific approach for retrofitting. The following are the some of the recommendations:  If the strength of the column in the building found to be deficit, they are strengthened / retrofitted .Beams and foundations are adequately safe.  To perform well in an earthquake, a building should possess four main attributes, namely simple and regular configuration, adequate lateral strength, stiffness and ductility.  The cantilever overhang should be minimized and the efforts should be made to ensure direct vertical transfer of the gravity loads.  All of the frames continue to the building base. 1854 | P a g e
  • 6. S D V S N Rao et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 3, Issue 6, Nov-Dec 2013, pp.1850-1855       Shear failure being brittle, it must be avoided in the design of RC beams. Steel reinforcement up to grade Fe415 shall be used. Limitation on flexural reinforcement ratio is recommended so as to ensure tension failure in the beams. All longitudinal column steel is should be dowelled into the foundation. The top as well as bottom reinforcement shall consist of at least two bars throughout the member length. The positive steel at a joint face must be at least equal to half the negative steel at that face. The following recommendations on detailing of the structure should be avoid ed in construction:  Large spacing of lateral ties in columns can lead to lack of confinement for the concrete core and/or shear failures.  Insufficient column lap lengths can cause concrete to spall.  Location of inadequate splices for all column bars at the same section can lead to column failure.  If the column shear strength is insufficient to develop the full moment hinge capacity, the column can exhibit a brittle shear failure.  Insufficient anchorage of shear tie reinforcing in column cores can prevent the column from developing its full shear capacity.  Lack of continuous beam reinforcement can cause hinge formation during load reversals.  Inadequate reinforcing of beam-column joints or location of beam bar splices at columns can lead to joint failures.  Foundation dowels that are insufficient to develop the capacity of the column steel above can lead to local column distress, the pedestals the above the footing mitigates such failure.  Use of bent-up longitudinal reinforcing in beams as shear reinforcement can result in shear failure during load reversal.  The relatively low stiffness of the frames can lead to excessive inter storey drifts. These large drifts can cause damage to non-structural items such as partitions, window, etc. [4] [5] [6] [7] [8] [9] Pankaj Agrawal and S.K. Thakkar. Proc. Tenth Symp. On Earthquake Engineering, Nov 16-18, 1994, Roorkee. Paper presented on Assessment of seismic vulnerability of existing reinforced concrete building. Rajeev Sharma, Jitendra S. Thakur. Proc. Of workshop on “Advances in structural Engineering” 21-22 December, 2001, Tirupathi. Paper presented on structural evaluation of existing building – A case study. J.N.Bandyopadhyay. “Earthquake resistant design and detailing of RCC structures as per codal provisions” chapter 17- SE 106, IIT Kharagpur. R.N.Iyengar, proc. Of workshop on “Advances in structural Engineering”, 21-22 Decmber, 2001, Tirupathi. Paper presented on Earthquake in India an engineering perspective. Dr.Durgesh C Rai IIT Kanpu “Review of documents as seismic evaluation of existing buildings-Document No:IITK-GSDMAEQ03-V1.O,Interim Report I: A- Earthquake Codes,IITK-GSDMA Project on Building Codes”. Dr.Shailesh Kumar Agarwal and Ajay Chourasia “Methodology for seismic vulnerability assessment of building stock in megacities. REFERENCES [1] [2] [3] Anil K.Chopra (2001). “Dynamics of Structures”, Prentice Hall of India Pvt., New Delhi. A.R. Chndrasekaram and D.S. Prakash Rao. Paper presented on :”A seismic Design of Multi-storied RCC Buildings” IIT, Roorkee. “Low-Cost construction resistant to earthquakes” United nations, New Yark, 1975 www.ijera.com 1855 | P a g e