N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering
            Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                    Vol. 2, Issue 6, November- December 2012, pp.268-271
 Thermodynamic Optimization of Household Refrigerator Using
          Propane –Butane as Mixed Refrigerant
              N.Austin1, Dr.P.Senthil Kumar2, N.Kanthavelkumaran3
                    1
                      Research Scholar, Sathyabama University, Chennai, Tamilnadu, India
              2
                Professor, KSR College of Engineering & Technology, Thirucenkode, Tamilnadu
    3
      Associate Professor, Arunachala College of Engineering for Women, Vellichanthai, KK Dist – 629203


Abstract
         A household refrigerator designed to           had been previously pursued by William Cullen in
work with R-134a was used as an investigation           the eighteenth century. A refrigerator is a cooling
unit to assess the prospect of using mixed              appliance comprising a          thermally insulated
refrigerants. The recital of the refrigerator using     screened-off area and a heat pump - element or
mixed refrigerant was investigated and                  perfunctory means - to transfer heat from it to the
compared with the performance of refrigerator           external atmosphere cooling the contents to a
when R-134a was used as refrigerant. The effect         temperature below ambient. Refrigerators are
of condenser temperature and evaporator                 extensively used to store foods which deteriorate at
temperature on COP, refrigerating effect was            ambient temperatures; spoilage from bacterial
investigated. The energy consumption of the             growth and other processes is much slower at low
refrigerator during experiment with mixed               temperatures.
refrigerant and R-134a was measured. The                     An apparatus described as a “refrigerator
outcome shows the permanent running and                 maintains a temperature a slight degrees above the
cycling results showed that R134a with a charge         freezing point of water; a similar device which
of 100 g or mixed refrigerant with charge of            maintain a temperature below the freezing point of
80 mg or more satisfy the required freezer air          water is called a “freezer”. The refrigerator is a
temperature of −12 °C. The lowest electric              fairly modern invention among kitchen appliances.
energy consumption was achieved using mixed             It replaced the ice box, which had been a common
refrigerant with heat level is less than -15oC. This    domestic appliance for almost a century and a half
mixture achieved higher volumetric cooling              earlier. For this explanation, a refrigerator is
capacity and lower freezer air temperature              sometimes referred to as an "ice box". Freezers keep
compared to R134a. Experimental results of the          their contents frozen. They are used in households
refrigerator using mixed refrigerant were               and in industry and commerce. Most freezers
compare with those using R134a. Pull-down time,         operate around -18 °C (0 °F). Domestic freezers can
pressure ratio and power consumption of mixed           be included as a separate compartment in a
refrigerant refrigerator were under those of            refrigerator, or can be a separate appliance.
R134a refrigerator by about 7.6%, 5.5% and              Domestic freezers are generally standing units
4.3%, respectively. Also, actual COP of mixed           resembling refrigerators, or chests resembling
refrigerant refrigerator was higher than that of        upright units lay on their backs. Many standing
R134a by about 7.6%. Lower on-time ratio and            modern freezers come with an ice slot machine built
energy consumption of mixed refrigerant                 into their door.
refrigerator by nearly 14.3% and 10.8%,
respectively, compared to those of R134a                     Chlorofluorocarbons (CFCs) and hydro
refrigerator were achieved. The COP and other           chlorofluorocarbons (HCFCs) have many suitable
result obtain in this experiment show a positive        properties, for example, non flammability, low
indication of using mixed refrigerant as                toxicity and material compatibility that have led to
refrigerants in household refrigerator.                 their common widespread use by both consumers
                                                        and industries around the world, especially as
Key words: Butane, R134a, Mixed Refrigerant,            refrigerants in air conditioning and refrigerating
Chlorofluorocarbons, propane, Isobutane, COP            systems. Results from many researches show that
                                                        this ozone layer is being depleted. The general
1. INTRODUCTION                                         consensus for the cause of this event is that free
                                                        chlorine radicals remove ozone from the
         Normal frost was disseminated and used in      atmosphere, and later, chlorine atoms continue to
both commercial and domicile application in the         convert more ozone to oxygen. The presence of
middle of 1880s to refrigerate food. The suggestion     chlorine in the stratosphere is the result of the
that cold could be produced by the forced               migration of chlorine containing chemicals. The
evaporation of an impulsive liquid under reduced        chlorofluorocarbons     (CFCs)        and     hydro



                                                                                             268 | P a g e
N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering
            Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                    Vol. 2, Issue 6, November- December 2012, pp.268-271
chlorofluorocarbons (HCFCs) are a large class of
chemicals that behave in this manner. (Radermacher
and Kim, 1996, Akash and Said, 2003).

         Hydrocarbon particularly propane, butane
and isobutene are proposed as an environment
benign refrigerant. Hydrocarbons are free from
ozone depletion potential and have negligible global
warming potential. Lee and Su (2002) conducted an
experiment study on the use of isobutene as
refrigerant   in   domestic     refrigerator.   The
performance was comparable with those of CFC-12
and HCFC-22 was used as refrigerant.

         Commercial fridge and freezer units, which
go by many other names, were in use for almost 40
years prior to the common home models. They used
toxic gas systems, which occasionally leaked,
making them unsafe for home use. Practical
household refrigerators were introduced in 1915 and
gained wider acceptance in the United States in the
1930s as prices fell and non-toxic, non-flammable
synthetic refrigerants such as Freon or R-12 were
introduced. It is notable that while 60% of
households in the US owned a refrigerator by the
1930s, it was not until 40 years later, in the 1970s,
that the refrigerator achieved a similar level of
penetration in the UK.
                                                         Fig. 1, Experimental setup of the investigation unit
          Refrigerant selection involves balancing                         and apparatus
conflicting requirements such as: ability to transfer
heat, chemical stability, and compatibility with
compressor lubricants, flammability, and toxicity.
Akash and Said (2003) studied the performance of
mixed refrigerant from local market (30%propane,
55% n-butane and 15% isobutene by mass) as an
alternative refrigerant for CFC-12 in domestic
refrigerator with masses of 50g, 80g and 100g.

         The result showed that a mass charge of
80g gave the best performance. Scientist and
researcher are searching the environment benign
refrigerant for the domestic refrigerator and freezer.
Finally we decide to choose the mixed refrigerant as
an alternate source of HFC-134.

2. EXPERIMENTAL SETUP AND TEST
   PROCEDURE

          This section provides a description of the
facilities developed for conducting experimental         Fig. 2, Schematic diagram of the investigation unit
work on a domestic refrigerator. The technique of                          and apparatus
charging and evacuation of the system is also
discussed here. Experimental data collection was         2.1 Experimental Methodology
carried out in the research laboratory of our                      The experimental setup of the household
institution. The experimental setup of the test unit     refrigerator used in the experiment is shown in Fig
and apparatus is shown in the Fig. 1.                    1. The domestic refrigerator consists of an
                                                         evaporator, wire mesh air-cooled condenser and
                                                         hermetically sealed reciprocating compressor. The
                                                         165 liters domestic refrigerator of tropical class


                                                                                              269 | P a g e
N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering
            Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                    Vol. 2, Issue 6, November- December 2012, pp.268-271
originally designed to work with HFC134a was             refrigerants continue to absorb heat. The experiment
taken for this study. The refrigerator was               was performed on the domestic refrigerator
instrumented with one pressure gauge at the inlet of     purchased from the market, the components of the
the compressor for measuring the suction pressure,       refrigerator was not changed or modified. This
one temperature sensor mounted at inside the             indicates the possibility of using mixed refrigerant
refrigerator (freezer) compartment. As per the           as an alternative of HFC-134a in the existing
refrigerator manufactures recommendation quantity        refrigerator system.
of charge requirement for HFC134a was 100 g. In                    The COP of the domestic refrigerator using
the experiment, refrigerant charge is 10% higher due     R-134a as a refrigerant was considered as
to the presence of instruments and connecting lines      benchmark and the COP of mixed refrigerant
etc. To optimize the mixed refrigerant charge, the       compared. The time versus COP is plotted at the
refrigerator is charged with 80g. The refrigerator       refrigerant R-134a and mixed refrigerant (without
was charged with 110 g of HFC134a and the base           load & different mode) in the same graph. The
line performance was studied. After completing the       results displayed in Figs. 2, 3, 4 and 5 shows a
base line test with HFC134a, the refrigerant was         progressive increase in COP as the temperature
recovered from the system and charged with 80g of        varies.
mixed refrigerant and the performance was studied.
The refrigerant       charge requirement        with
hydrocarbons is very small due to their higher latent
heat of vaporization. During the experimentation the
atmospheric is maintained at 28 ± 2oC. The
experimental procedures were repeated and take the
reading from the various modes. Service port is
installed at the inlet of expansion valve and
compressor for charging and recovering the
refrigerant is shown in Figure. Digital Temperature         Fig. 3. Mode 1 Time Vs COP (Without Load)
Indicator was used to measure the inside freezer
temperature.

2.2 Test Procedure
         The system was evacuated with the help of
vacuum pump to remove the moisture and charged
with the help of charging system. The temperature
inside the chamber was maintained at 25°C and
28°C. When the temperature and humidity inside the          Fig. 4. Mode 2 Time Vs COP (Without Load)
chamber was at steady state, the experiments were
started. The experiment has been conducted on the
domestic refrigerator at no load and closed door
conditions.

3. RESULTS AND DISCUSSIONS
          From this section the comparison of the
performance parameter of the refrigerants and
energy consumption by the refrigerator was                  Fig 5. Mode 3 Time Vs COP (Without Load)
discussed This investigation deals with mixed
refrigerant (hydrocarbon mixtures of propane,
butane and isobutane) in order to assess their
feasibility for replacing HFC-134a in refrigeration
systems by comparing their relevant parameters.
          The refrigerating effect is the main
purposes of the refrigeration system. The liquid
refrigerant at low pressure side enters the
evaporator. As the liquid refrigerant passes through
the evaporator coil, it continually absorbs heat             Fig. 6. Mode 4 Time Vs COP (Without Load)
through the coil walls, from the medium being                      The time versus COP is plotted at the
cooled. During this, the refrigerant continues to boil   refrigerant R134a and mixed refrigerant (without &
and evaporate. Finally the entire refrigerants have      different mode) in the same graph. The results
evaporated and only vapor refrigerant remains in the     displayed in Figs., 7, 8,9 and 10 shows a progressive
evaporator coil. The liquid refrigerant still colder     increase in COP as the temperature varies.
than the medium being cooled, therefore the vapor



                                                                                               270 | P a g e
N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering
            Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com
                    Vol. 2, Issue 6, November- December 2012, pp.268-271
                                                        and the coefficient of performance (COP). The
                                                        refrigerator worked efficiently when mixed
                                                        refrigerant was used as refrigerant instead of R134a.
                                                        The evaporator temperature reached -20°C with
                                                        COP value of 6.4 and an ambient temperature of
                                                        30°C. The results of the present work indicate the
                                                        successful use of this mixed refrigerant as an
                                                        alternative to R134a in domestic refrigerators. The
     Fig. 7. Mode 1 Time Vs COP (With Load)             co-efficient of performance for the mixed refrigerant
                                                        is comparable with the co-efficient of performance
                                                        of HFC-134a The domestic refrigerator was charged
                                                        with 140g of HFC-134a and 80g of mixed
                                                        refrigerant. This is an indication of better
                                                        performance of mixed refrigerant as refrigerants.
                                                        The following conclusions can be elicited from our
                                                        investigation
                                                        1. Every mode of mixed refrigerant yields higher
                                                        COP than HFC-134a.
                                                        2. From using the mixed refrigerant in domestic
     Fig. 8. Mode 2 Time Vs COP (With Load)             refrigerator, we were observed the freezer
                                                        temperature lower than that of the R134a.
                                                        3. When the evaporator temperature increases, COP
                                                        will be increases and the condenser temperature
                                                        decreases, COP will also increases.

                                                        REFERENCES
                                                          [1]    Inan C, Gonul T, Tanes MY. X-ray
                                                                 investigation of a domestic refrigerator.
                                                                 Observations at 25°C ambient temperature.
                                                                 Int. J Refrig. 2003;26(2):205-213.
     Fig. 9. Mode 3 Time Vs COP (With Load)               [2]    Didion DA, Bivens DB. Role of refrigerant
                                                                 mixtures as alternatives to CFCs. Int J
                                                                 Refrig 1990;13:163–75.
                                                          [3]    Gunther D, Steimle F. Mixing rules for the
                                                                 specific heat capacities of several HFC-
                                                                 mixtures.      International    Journal    of
                                                                 Refrigeration 1997;20:235–436
                                                          [4]    R. Radermacher, K. Kim, Domestic
                                                                 refrigerator:       recent      development,
                                                                 International journal of refrigeration
    Fig. 10. Mode 4 Time Vs COP (With Load)                      19(1996) 61-69
                                                          [5]    B. A.Akash, S.A. Said, Assessment of LPG
                                                                 as a possible alternative to R-12 in
4. CONCLUSION
                                                                 domestic refrigerators. Energy conversion
          This project invested an ozone friendly,
                                                                 and Management 44 (2003) 381-388.
energy efficient, user friendly, safe and cost-
                                                          [6]    S. Devotta, A. V. Wagmare, N. N. Sawant,
effective alternative refrigerant for HFC134a in
                                                                 B.M. Domkundwar, Alternatives to HFC-
domestic refrigeration systems. After the successful
                                                                 22 for air conditioners, Applied Thermal
investigation on the performance of mixed
                                                                 Engineering 21(2001) 703-715.
refrigerants the following conclusions can be drawn
                                                          [7]    Joseph Sekhar, D.Mohan Lal, S. Renga
based on the results obtained. This experimental
                                                                 narayanan, Improved energy efficiency for
investigation carried out to determine the
                                                                 CFC domestic refrigerators with ozone-
performance of a domestic refrigerator when a
                                                                 friendly HFC134a/HC refrigerant mixture,
propane/butane mixture is used as a possible
                                                                 International Journal of thermal Science
replacement to the traditional refrigerant R134a.
                                                                 43(2004) 307-314
          The used mixed refrigerant which is locally
                                                          [8]    Jung D, Kim CB, Song K, Park B. Testing
available and comprises in various properties like,
                                                                 of propane/isobutane mixture in domestic
24.4% propane, 56.4% butane and 17.2% isobutene.
                                                                 refrigerators. Int. J Refrig. 2000;23(7):517-
The performance parameters investigated are the
                                                                 527.
refrigeration capacity, the evaporator temperature



                                                                                              271 | P a g e

More Related Content

What's hot

Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...IAEME Publication
 
Coefficient of Performance Enhancement of Refrigeration Cycles
Coefficient of Performance Enhancement of Refrigeration CyclesCoefficient of Performance Enhancement of Refrigeration Cycles
Coefficient of Performance Enhancement of Refrigeration CyclesIJERA Editor
 
Refrigerants and the environment
Refrigerants and the environmentRefrigerants and the environment
Refrigerants and the environment123Tino
 
Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...
Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...
Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...IRJET Journal
 
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...theijes
 
PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...
PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...
PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...Niyas PP
 
Power plant chemistry parts of power plant and its function
Power plant chemistry   parts of power plant and its functionPower plant chemistry   parts of power plant and its function
Power plant chemistry parts of power plant and its functionumar farooq
 
Ijri te-03-012 design and optimization of water cool condenser for central ai...
Ijri te-03-012 design and optimization of water cool condenser for central ai...Ijri te-03-012 design and optimization of water cool condenser for central ai...
Ijri te-03-012 design and optimization of water cool condenser for central ai...Ijripublishers Ijri
 
Optimization of Skin Condenser Using Bundy Tube In Place Of Copper Tube
Optimization of Skin Condenser Using Bundy Tube In Place Of Copper TubeOptimization of Skin Condenser Using Bundy Tube In Place Of Copper Tube
Optimization of Skin Condenser Using Bundy Tube In Place Of Copper TubeIJMER
 
IRJET- Thermoelectric Air-Conditioner Tricycle
IRJET-  	  Thermoelectric Air-Conditioner TricycleIRJET-  	  Thermoelectric Air-Conditioner Tricycle
IRJET- Thermoelectric Air-Conditioner TricycleIRJET Journal
 
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ijiert bestjournal
 
Refrigeration Equipments
Refrigeration EquipmentsRefrigeration Equipments
Refrigeration EquipmentsSawan Wani
 
Cryogenics and its space applications
Cryogenics and its space applicationsCryogenics and its space applications
Cryogenics and its space applicationsssshoaib
 
A Review on Design and Development of Three in One Air Cooling System
A Review on Design and Development of Three in One Air Cooling SystemA Review on Design and Development of Three in One Air Cooling System
A Review on Design and Development of Three in One Air Cooling SystemIRJET Journal
 

What's hot (20)

Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...
 
I04701072079
I04701072079I04701072079
I04701072079
 
Coefficient of Performance Enhancement of Refrigeration Cycles
Coefficient of Performance Enhancement of Refrigeration CyclesCoefficient of Performance Enhancement of Refrigeration Cycles
Coefficient of Performance Enhancement of Refrigeration Cycles
 
B012250811
B012250811B012250811
B012250811
 
Refrigerants and the environment
Refrigerants and the environmentRefrigerants and the environment
Refrigerants and the environment
 
Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...
Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...
Design of New Evaporative Cooler and Usage of Different Cooling Pad Materials...
 
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
Thermodynamic analysis of_actual_vapour_compression_system_with_r22_and_its_e...
 
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
Performance Evaluation of Domestic Refrigerator Using Hc-12a Refrigerant as a...
 
Ijet v1 i1p6
Ijet v1 i1p6Ijet v1 i1p6
Ijet v1 i1p6
 
PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...
PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...
PERFORMANCE ENHANCEMENT OF HOUSEHOLD REFRIGERATOR BY USING TiO2 NANO LUBRICAN...
 
I1303056370
I1303056370I1303056370
I1303056370
 
Power plant chemistry parts of power plant and its function
Power plant chemistry   parts of power plant and its functionPower plant chemistry   parts of power plant and its function
Power plant chemistry parts of power plant and its function
 
Ijri te-03-012 design and optimization of water cool condenser for central ai...
Ijri te-03-012 design and optimization of water cool condenser for central ai...Ijri te-03-012 design and optimization of water cool condenser for central ai...
Ijri te-03-012 design and optimization of water cool condenser for central ai...
 
Optimization of Skin Condenser Using Bundy Tube In Place Of Copper Tube
Optimization of Skin Condenser Using Bundy Tube In Place Of Copper TubeOptimization of Skin Condenser Using Bundy Tube In Place Of Copper Tube
Optimization of Skin Condenser Using Bundy Tube In Place Of Copper Tube
 
IRJET- Thermoelectric Air-Conditioner Tricycle
IRJET-  	  Thermoelectric Air-Conditioner TricycleIRJET-  	  Thermoelectric Air-Conditioner Tricycle
IRJET- Thermoelectric Air-Conditioner Tricycle
 
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...
 
Refrigeration Equipments
Refrigeration EquipmentsRefrigeration Equipments
Refrigeration Equipments
 
Cryogenics and its space applications
Cryogenics and its space applicationsCryogenics and its space applications
Cryogenics and its space applications
 
A Review on Design and Development of Three in One Air Cooling System
A Review on Design and Development of Three in One Air Cooling SystemA Review on Design and Development of Three in One Air Cooling System
A Review on Design and Development of Three in One Air Cooling System
 
[IJET-V1I1P6] Author : P.Mallikarjuna1 ,Dr. B.Uma Maheswar Gowd
  [IJET-V1I1P6] Author : P.Mallikarjuna1  ,Dr. B.Uma Maheswar Gowd   [IJET-V1I1P6] Author : P.Mallikarjuna1  ,Dr. B.Uma Maheswar Gowd
[IJET-V1I1P6] Author : P.Mallikarjuna1 ,Dr. B.Uma Maheswar Gowd
 

Viewers also liked

Competencias tic
Competencias ticCompetencias tic
Competencias tic33144294
 
ITP UNS SEMESTER 2 Reaksi alkohol + eter
ITP UNS SEMESTER 2 Reaksi alkohol + eterITP UNS SEMESTER 2 Reaksi alkohol + eter
ITP UNS SEMESTER 2 Reaksi alkohol + eterFransiska Puteri
 
ULI Real Estate Trends Conference & Dinner 2013, London
ULI Real Estate Trends Conference & Dinner 2013, LondonULI Real Estate Trends Conference & Dinner 2013, London
ULI Real Estate Trends Conference & Dinner 2013, Londonlizwaller1
 
Apresentação de pesquisa de mestrado
Apresentação de pesquisa de mestradoApresentação de pesquisa de mestrado
Apresentação de pesquisa de mestradoAlexandre Rodriguez
 
D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...
D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...
D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...guest406b84
 
Investigación Cualitativa
Investigación CualitativaInvestigación Cualitativa
Investigación CualitativaPavel Vargas
 
Actividad inicial gestion_ambiental
Actividad inicial gestion_ambientalActividad inicial gestion_ambiental
Actividad inicial gestion_ambientalFabián Novoa
 
Power point de gestion
Power point de gestionPower point de gestion
Power point de gestionmromado_19
 

Viewers also liked (20)

Bx26501512
Bx26501512Bx26501512
Bx26501512
 
Ah26210213
Ah26210213Ah26210213
Ah26210213
 
Ae26192196
Ae26192196Ae26192196
Ae26192196
 
An26247254
An26247254An26247254
An26247254
 
Ab26180184
Ab26180184Ab26180184
Ab26180184
 
Fn2611681170
Fn2611681170Fn2611681170
Fn2611681170
 
Fa25939942
Fa25939942Fa25939942
Fa25939942
 
Con mucho afecto
Con mucho afectoCon mucho afecto
Con mucho afecto
 
Tic Project
Tic ProjectTic Project
Tic Project
 
Competencias tic
Competencias ticCompetencias tic
Competencias tic
 
El corazón
El corazónEl corazón
El corazón
 
ITP UNS SEMESTER 2 Reaksi alkohol + eter
ITP UNS SEMESTER 2 Reaksi alkohol + eterITP UNS SEMESTER 2 Reaksi alkohol + eter
ITP UNS SEMESTER 2 Reaksi alkohol + eter
 
ULI Real Estate Trends Conference & Dinner 2013, London
ULI Real Estate Trends Conference & Dinner 2013, LondonULI Real Estate Trends Conference & Dinner 2013, London
ULI Real Estate Trends Conference & Dinner 2013, London
 
Apresentação de pesquisa de mestrado
Apresentação de pesquisa de mestradoApresentação de pesquisa de mestrado
Apresentação de pesquisa de mestrado
 
Chimney rocky
Chimney rockyChimney rocky
Chimney rocky
 
Cl company catalogue
Cl company catalogueCl company catalogue
Cl company catalogue
 
D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...
D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...
D:\Archivos Gabi\ArtíCulos\2010 Articulos Y Resumenes\Power Jornada Marzo 201...
 
Investigación Cualitativa
Investigación CualitativaInvestigación Cualitativa
Investigación Cualitativa
 
Actividad inicial gestion_ambiental
Actividad inicial gestion_ambientalActividad inicial gestion_ambiental
Actividad inicial gestion_ambiental
 
Power point de gestion
Power point de gestionPower point de gestion
Power point de gestion
 

Similar to Aq26268271

EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANTEXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANTIAEME Publication
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceinventy
 
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134aExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134aIOSRJMCE
 
H0502 01 3747
H0502 01 3747H0502 01 3747
H0502 01 3747IJMER
 
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...IJMER
 
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...inventy
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET Journal
 
Refrigeration and air conditioning (repaired)
Refrigeration and air conditioning (repaired)Refrigeration and air conditioning (repaired)
Refrigeration and air conditioning (repaired)Prashanth J
 
Cryoref
CryorefCryoref
Cryorefritu70
 
Experimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
Experimental Investigation of Water Cooler Test Rig Using R-22 as RefrigerantExperimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
Experimental Investigation of Water Cooler Test Rig Using R-22 as RefrigerantIJMERJOURNAL
 
Performance Improvement of a Domestic Refrigerator Using Phase change Materia...
Performance Improvement of a Domestic Refrigerator Using Phase change Materia...Performance Improvement of a Domestic Refrigerator Using Phase change Materia...
Performance Improvement of a Domestic Refrigerator Using Phase change Materia...IOSR Journals
 
To study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a reviewTo study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a revieweSAT Journals
 
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...IJERA Editor
 
Experimental Investigation & Performance of VCRS system by using Air cooled C...
Experimental Investigation & Performance of VCRS system by using Air cooled C...Experimental Investigation & Performance of VCRS system by using Air cooled C...
Experimental Investigation & Performance of VCRS system by using Air cooled C...Akash Gaikwad
 

Similar to Aq26268271 (20)

EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANTEXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
EXPERIMENTAL STUDY ON A DOMESTIC REFRIGERATOR USING LPG AS A REFRIGARANT
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134aExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
 
H0502 01 3747
H0502 01 3747H0502 01 3747
H0502 01 3747
 
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
Experimental Performance Evaluation of R152a to replace R134a in Vapour Compr...
 
Q01245139144
Q01245139144Q01245139144
Q01245139144
 
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
Performance Evaluation of Household Refrigerator using CuO Nanoparticle Lubri...
 
ref.pdf
ref.pdfref.pdf
ref.pdf
 
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review PaperIRJET-  	  R134a Refrigerant in Vapour Compression Cycle: A Review Paper
IRJET- R134a Refrigerant in Vapour Compression Cycle: A Review Paper
 
refrigrants.pptx
refrigrants.pptxrefrigrants.pptx
refrigrants.pptx
 
lpg content
lpg contentlpg content
lpg content
 
Refrigeration and air conditioning (repaired)
Refrigeration and air conditioning (repaired)Refrigeration and air conditioning (repaired)
Refrigeration and air conditioning (repaired)
 
Cryoref
CryorefCryoref
Cryoref
 
Experimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
Experimental Investigation of Water Cooler Test Rig Using R-22 as RefrigerantExperimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
Experimental Investigation of Water Cooler Test Rig Using R-22 as Refrigerant
 
Performance Improvement of a Domestic Refrigerator Using Phase change Materia...
Performance Improvement of a Domestic Refrigerator Using Phase change Materia...Performance Improvement of a Domestic Refrigerator Using Phase change Materia...
Performance Improvement of a Domestic Refrigerator Using Phase change Materia...
 
To study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a reviewTo study the application of nanorefrigerant in refrigeration system a review
To study the application of nanorefrigerant in refrigeration system a review
 
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
Experimental Investigation on Adsorption Capacity of a Variety of Activated C...
 
Experimental Investigation & Performance of VCRS system by using Air cooled C...
Experimental Investigation & Performance of VCRS system by using Air cooled C...Experimental Investigation & Performance of VCRS system by using Air cooled C...
Experimental Investigation & Performance of VCRS system by using Air cooled C...
 
REFREGRANT
REFREGRANTREFREGRANT
REFREGRANT
 
Green refrigeration
Green refrigerationGreen refrigeration
Green refrigeration
 

Aq26268271

  • 1. N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 2, Issue 6, November- December 2012, pp.268-271 Thermodynamic Optimization of Household Refrigerator Using Propane –Butane as Mixed Refrigerant N.Austin1, Dr.P.Senthil Kumar2, N.Kanthavelkumaran3 1 Research Scholar, Sathyabama University, Chennai, Tamilnadu, India 2 Professor, KSR College of Engineering & Technology, Thirucenkode, Tamilnadu 3 Associate Professor, Arunachala College of Engineering for Women, Vellichanthai, KK Dist – 629203 Abstract A household refrigerator designed to had been previously pursued by William Cullen in work with R-134a was used as an investigation the eighteenth century. A refrigerator is a cooling unit to assess the prospect of using mixed appliance comprising a thermally insulated refrigerants. The recital of the refrigerator using screened-off area and a heat pump - element or mixed refrigerant was investigated and perfunctory means - to transfer heat from it to the compared with the performance of refrigerator external atmosphere cooling the contents to a when R-134a was used as refrigerant. The effect temperature below ambient. Refrigerators are of condenser temperature and evaporator extensively used to store foods which deteriorate at temperature on COP, refrigerating effect was ambient temperatures; spoilage from bacterial investigated. The energy consumption of the growth and other processes is much slower at low refrigerator during experiment with mixed temperatures. refrigerant and R-134a was measured. The An apparatus described as a “refrigerator outcome shows the permanent running and maintains a temperature a slight degrees above the cycling results showed that R134a with a charge freezing point of water; a similar device which of 100 g or mixed refrigerant with charge of maintain a temperature below the freezing point of 80 mg or more satisfy the required freezer air water is called a “freezer”. The refrigerator is a temperature of −12 °C. The lowest electric fairly modern invention among kitchen appliances. energy consumption was achieved using mixed It replaced the ice box, which had been a common refrigerant with heat level is less than -15oC. This domestic appliance for almost a century and a half mixture achieved higher volumetric cooling earlier. For this explanation, a refrigerator is capacity and lower freezer air temperature sometimes referred to as an "ice box". Freezers keep compared to R134a. Experimental results of the their contents frozen. They are used in households refrigerator using mixed refrigerant were and in industry and commerce. Most freezers compare with those using R134a. Pull-down time, operate around -18 °C (0 °F). Domestic freezers can pressure ratio and power consumption of mixed be included as a separate compartment in a refrigerant refrigerator were under those of refrigerator, or can be a separate appliance. R134a refrigerator by about 7.6%, 5.5% and Domestic freezers are generally standing units 4.3%, respectively. Also, actual COP of mixed resembling refrigerators, or chests resembling refrigerant refrigerator was higher than that of upright units lay on their backs. Many standing R134a by about 7.6%. Lower on-time ratio and modern freezers come with an ice slot machine built energy consumption of mixed refrigerant into their door. refrigerator by nearly 14.3% and 10.8%, respectively, compared to those of R134a Chlorofluorocarbons (CFCs) and hydro refrigerator were achieved. The COP and other chlorofluorocarbons (HCFCs) have many suitable result obtain in this experiment show a positive properties, for example, non flammability, low indication of using mixed refrigerant as toxicity and material compatibility that have led to refrigerants in household refrigerator. their common widespread use by both consumers and industries around the world, especially as Key words: Butane, R134a, Mixed Refrigerant, refrigerants in air conditioning and refrigerating Chlorofluorocarbons, propane, Isobutane, COP systems. Results from many researches show that this ozone layer is being depleted. The general 1. INTRODUCTION consensus for the cause of this event is that free chlorine radicals remove ozone from the Normal frost was disseminated and used in atmosphere, and later, chlorine atoms continue to both commercial and domicile application in the convert more ozone to oxygen. The presence of middle of 1880s to refrigerate food. The suggestion chlorine in the stratosphere is the result of the that cold could be produced by the forced migration of chlorine containing chemicals. The evaporation of an impulsive liquid under reduced chlorofluorocarbons (CFCs) and hydro 268 | P a g e
  • 2. N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 2, Issue 6, November- December 2012, pp.268-271 chlorofluorocarbons (HCFCs) are a large class of chemicals that behave in this manner. (Radermacher and Kim, 1996, Akash and Said, 2003). Hydrocarbon particularly propane, butane and isobutene are proposed as an environment benign refrigerant. Hydrocarbons are free from ozone depletion potential and have negligible global warming potential. Lee and Su (2002) conducted an experiment study on the use of isobutene as refrigerant in domestic refrigerator. The performance was comparable with those of CFC-12 and HCFC-22 was used as refrigerant. Commercial fridge and freezer units, which go by many other names, were in use for almost 40 years prior to the common home models. They used toxic gas systems, which occasionally leaked, making them unsafe for home use. Practical household refrigerators were introduced in 1915 and gained wider acceptance in the United States in the 1930s as prices fell and non-toxic, non-flammable synthetic refrigerants such as Freon or R-12 were introduced. It is notable that while 60% of households in the US owned a refrigerator by the 1930s, it was not until 40 years later, in the 1970s, that the refrigerator achieved a similar level of penetration in the UK. Fig. 1, Experimental setup of the investigation unit Refrigerant selection involves balancing and apparatus conflicting requirements such as: ability to transfer heat, chemical stability, and compatibility with compressor lubricants, flammability, and toxicity. Akash and Said (2003) studied the performance of mixed refrigerant from local market (30%propane, 55% n-butane and 15% isobutene by mass) as an alternative refrigerant for CFC-12 in domestic refrigerator with masses of 50g, 80g and 100g. The result showed that a mass charge of 80g gave the best performance. Scientist and researcher are searching the environment benign refrigerant for the domestic refrigerator and freezer. Finally we decide to choose the mixed refrigerant as an alternate source of HFC-134. 2. EXPERIMENTAL SETUP AND TEST PROCEDURE This section provides a description of the facilities developed for conducting experimental Fig. 2, Schematic diagram of the investigation unit work on a domestic refrigerator. The technique of and apparatus charging and evacuation of the system is also discussed here. Experimental data collection was 2.1 Experimental Methodology carried out in the research laboratory of our The experimental setup of the household institution. The experimental setup of the test unit refrigerator used in the experiment is shown in Fig and apparatus is shown in the Fig. 1. 1. The domestic refrigerator consists of an evaporator, wire mesh air-cooled condenser and hermetically sealed reciprocating compressor. The 165 liters domestic refrigerator of tropical class 269 | P a g e
  • 3. N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 2, Issue 6, November- December 2012, pp.268-271 originally designed to work with HFC134a was refrigerants continue to absorb heat. The experiment taken for this study. The refrigerator was was performed on the domestic refrigerator instrumented with one pressure gauge at the inlet of purchased from the market, the components of the the compressor for measuring the suction pressure, refrigerator was not changed or modified. This one temperature sensor mounted at inside the indicates the possibility of using mixed refrigerant refrigerator (freezer) compartment. As per the as an alternative of HFC-134a in the existing refrigerator manufactures recommendation quantity refrigerator system. of charge requirement for HFC134a was 100 g. In The COP of the domestic refrigerator using the experiment, refrigerant charge is 10% higher due R-134a as a refrigerant was considered as to the presence of instruments and connecting lines benchmark and the COP of mixed refrigerant etc. To optimize the mixed refrigerant charge, the compared. The time versus COP is plotted at the refrigerator is charged with 80g. The refrigerator refrigerant R-134a and mixed refrigerant (without was charged with 110 g of HFC134a and the base load & different mode) in the same graph. The line performance was studied. After completing the results displayed in Figs. 2, 3, 4 and 5 shows a base line test with HFC134a, the refrigerant was progressive increase in COP as the temperature recovered from the system and charged with 80g of varies. mixed refrigerant and the performance was studied. The refrigerant charge requirement with hydrocarbons is very small due to their higher latent heat of vaporization. During the experimentation the atmospheric is maintained at 28 ± 2oC. The experimental procedures were repeated and take the reading from the various modes. Service port is installed at the inlet of expansion valve and compressor for charging and recovering the refrigerant is shown in Figure. Digital Temperature Fig. 3. Mode 1 Time Vs COP (Without Load) Indicator was used to measure the inside freezer temperature. 2.2 Test Procedure The system was evacuated with the help of vacuum pump to remove the moisture and charged with the help of charging system. The temperature inside the chamber was maintained at 25°C and 28°C. When the temperature and humidity inside the Fig. 4. Mode 2 Time Vs COP (Without Load) chamber was at steady state, the experiments were started. The experiment has been conducted on the domestic refrigerator at no load and closed door conditions. 3. RESULTS AND DISCUSSIONS From this section the comparison of the performance parameter of the refrigerants and energy consumption by the refrigerator was Fig 5. Mode 3 Time Vs COP (Without Load) discussed This investigation deals with mixed refrigerant (hydrocarbon mixtures of propane, butane and isobutane) in order to assess their feasibility for replacing HFC-134a in refrigeration systems by comparing their relevant parameters. The refrigerating effect is the main purposes of the refrigeration system. The liquid refrigerant at low pressure side enters the evaporator. As the liquid refrigerant passes through the evaporator coil, it continually absorbs heat Fig. 6. Mode 4 Time Vs COP (Without Load) through the coil walls, from the medium being The time versus COP is plotted at the cooled. During this, the refrigerant continues to boil refrigerant R134a and mixed refrigerant (without & and evaporate. Finally the entire refrigerants have different mode) in the same graph. The results evaporated and only vapor refrigerant remains in the displayed in Figs., 7, 8,9 and 10 shows a progressive evaporator coil. The liquid refrigerant still colder increase in COP as the temperature varies. than the medium being cooled, therefore the vapor 270 | P a g e
  • 4. N.Austin, Dr.P.Senthil Kumar, N.Kanthavelkumaran / International Journal of Engineering Research and Applications (IJERA) ISSN: 2248-9622 www.ijera.com Vol. 2, Issue 6, November- December 2012, pp.268-271 and the coefficient of performance (COP). The refrigerator worked efficiently when mixed refrigerant was used as refrigerant instead of R134a. The evaporator temperature reached -20°C with COP value of 6.4 and an ambient temperature of 30°C. The results of the present work indicate the successful use of this mixed refrigerant as an alternative to R134a in domestic refrigerators. The Fig. 7. Mode 1 Time Vs COP (With Load) co-efficient of performance for the mixed refrigerant is comparable with the co-efficient of performance of HFC-134a The domestic refrigerator was charged with 140g of HFC-134a and 80g of mixed refrigerant. This is an indication of better performance of mixed refrigerant as refrigerants. The following conclusions can be elicited from our investigation 1. Every mode of mixed refrigerant yields higher COP than HFC-134a. 2. From using the mixed refrigerant in domestic Fig. 8. Mode 2 Time Vs COP (With Load) refrigerator, we were observed the freezer temperature lower than that of the R134a. 3. When the evaporator temperature increases, COP will be increases and the condenser temperature decreases, COP will also increases. REFERENCES [1] Inan C, Gonul T, Tanes MY. X-ray investigation of a domestic refrigerator. Observations at 25°C ambient temperature. Int. J Refrig. 2003;26(2):205-213. Fig. 9. Mode 3 Time Vs COP (With Load) [2] Didion DA, Bivens DB. Role of refrigerant mixtures as alternatives to CFCs. Int J Refrig 1990;13:163–75. [3] Gunther D, Steimle F. Mixing rules for the specific heat capacities of several HFC- mixtures. International Journal of Refrigeration 1997;20:235–436 [4] R. Radermacher, K. Kim, Domestic refrigerator: recent development, International journal of refrigeration Fig. 10. Mode 4 Time Vs COP (With Load) 19(1996) 61-69 [5] B. A.Akash, S.A. Said, Assessment of LPG as a possible alternative to R-12 in 4. CONCLUSION domestic refrigerators. Energy conversion This project invested an ozone friendly, and Management 44 (2003) 381-388. energy efficient, user friendly, safe and cost- [6] S. Devotta, A. V. Wagmare, N. N. Sawant, effective alternative refrigerant for HFC134a in B.M. Domkundwar, Alternatives to HFC- domestic refrigeration systems. After the successful 22 for air conditioners, Applied Thermal investigation on the performance of mixed Engineering 21(2001) 703-715. refrigerants the following conclusions can be drawn [7] Joseph Sekhar, D.Mohan Lal, S. Renga based on the results obtained. This experimental narayanan, Improved energy efficiency for investigation carried out to determine the CFC domestic refrigerators with ozone- performance of a domestic refrigerator when a friendly HFC134a/HC refrigerant mixture, propane/butane mixture is used as a possible International Journal of thermal Science replacement to the traditional refrigerant R134a. 43(2004) 307-314 The used mixed refrigerant which is locally [8] Jung D, Kim CB, Song K, Park B. Testing available and comprises in various properties like, of propane/isobutane mixture in domestic 24.4% propane, 56.4% butane and 17.2% isobutene. refrigerators. Int. J Refrig. 2000;23(7):517- The performance parameters investigated are the 527. refrigeration capacity, the evaporator temperature 271 | P a g e