International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
178
PERFORMANCE EVALUATION OF A AIR CONDITIONER
ACCORDING TO DIFFERENT TEST STANDARDS
K. Ravi Kumar,
Asst Prof., Department of Mechanical Engineering,
AHCET, Chevella, Ranga Reddy – 515002(A.P.), India.
K. Ganesh Babu
Asst Prof., Department of Mechanical Engineering,
SITECH, Chevella, Ranga Reddy – 515002(A.P.), India
S. Udaya Bhaskar
Asso Prof., Department of Mechanical Engineering,
AHCET, Chevella, Ranga Reddy – 515002(A.P.), India.
ABSTRACT
The Paper reports on the performance of Air Conditioner at different test standards. The
future design of air conditioners is being driven primarily by (a) increased energy efficiency standards
and (b) the need to eliminate ozone-depleting working fluids. Various national and international
agencies continue to impose more stringent requirements for energy efficiency. In addition, consumer
pressure to select units with lower operating costs further drives the need for improved performance.
The main objective of this paper is to give wide understand of the standards and to maintain the
standard conditions in Psychrometric room (Air conditioner test room), which has been constructed to
test the air conditioners and to establish different test procedures. The tests that should be performed
in Air conditioner test room are cooling capacity test, power consumption test. The main objective of
the manufacturers is to produce the systems according to requirements of customers which can give
more cooling, low power consumption, high EER to with stand competition in the market. In every
country, the manufacturers follow some standards according to the climatic conditions to test the
appliances.
Keywords: Psychrometric room; EER; cooling capacity test; power consumption test; climatic
conditions
INTERNATIONAL JOURNAL OF ADVANCED RESEARCH IN
ENGINEERING AND TECHNOLOGY (IJARET)
ISSN 0976 - 6480 (Print)
ISSN 0976 - 6499 (Online)
Volume 4, Issue 3, April 2013, pp. 178-186
© IAEME: www.iaeme.com/ijaret.asp
Journal Impact Factor (2013): 5.8376 (Calculated by GISI)
www.jifactor.com
IJARET
© I A E M E
International Journal of Advanced Research in Engineering and
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
I INTRODUCTION
India falls in the hot zone therefore the comfort air
necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred
to the environment, which is at a higher temperature. This is done with the help of r
Though there are many methods to achieve cooling, one process that is predominantly applied in
refrigeration equipment and its application is vapor compression cycle. One of the applications of
vapor compression system is in Air conditioning
conditioners, and then comes the Packaged systems which are used for higher tonnages till 50Ton.
Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in
US in earlier 19th
Century, there has been a radical change in the methods and process used in
manufacturing air-conditioning equipment but there is no change in the principle i.e. Vapor
compression system used in the cycle.
II.EXPERIMENTAL SETUP
Air conditioner test room is constructed according to ASHREA standards. It consists of two rooms
made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side
room. The outside room ambient is controlled from 25
temperature control or load control. For testing or air conditioner, maintaining of temperatures is
important so these two rooms are made of adiabatic material. The method use in air conditioner test
room for finding capacity is air enthalpy
which the non-ducted equipment (test air conditioner) is mounted which the non
(test air conditioner) is mounted.
The equipments associated with air conditioner test room as follo
(a) Panel Boards
(b) Split AC Indoor Unit Installation
(c) Split AC Outdoor Unit Installation
(d) Packaged Air conditioners
(e) Humidifiers
(f) Code Tester
(g) Temperature measuring instrument
(h) Heaters
(g) Sampling device
Fig.1. Psychrometric Laboratory view
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
6499(Online) Volume 4, Issue 3, April (2013), © IAEME
179
therefore the comfort air-conditioning has always been felt to be a
necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred
to the environment, which is at a higher temperature. This is done with the help of r
Though there are many methods to achieve cooling, one process that is predominantly applied in
refrigeration equipment and its application is vapor compression cycle. One of the applications of
vapor compression system is in Air conditioning units, the more commonly used one is Room Air
conditioners, and then comes the Packaged systems which are used for higher tonnages till 50Ton.
Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in
Century, there has been a radical change in the methods and process used in
conditioning equipment but there is no change in the principle i.e. Vapor
compression system used in the cycle.
room is constructed according to ASHREA standards. It consists of two rooms
made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side
room. The outside room ambient is controlled from 25o
C to 55o
C. While indoor s
temperature control or load control. For testing or air conditioner, maintaining of temperatures is
important so these two rooms are made of adiabatic material. The method use in air conditioner test
room for finding capacity is air enthalpy method. These two rooms are separated by an opening in to
ducted equipment (test air conditioner) is mounted which the non-ducted equipment
The equipments associated with air conditioner test room as follows:
Split AC Indoor Unit Installation
Split AC Outdoor Unit Installation
Temperature measuring instrument
sychrometric Laboratory view Fig.2 Split AC Indoor Unit Installation
Technology (IJARET), ISSN
6499(Online) Volume 4, Issue 3, April (2013), © IAEME
conditioning has always been felt to be a
necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred
to the environment, which is at a higher temperature. This is done with the help of refrigeration.
Though there are many methods to achieve cooling, one process that is predominantly applied in
refrigeration equipment and its application is vapor compression cycle. One of the applications of
units, the more commonly used one is Room Air-
conditioners, and then comes the Packaged systems which are used for higher tonnages till 50Ton.
Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in
Century, there has been a radical change in the methods and process used in
conditioning equipment but there is no change in the principle i.e. Vapor
room is constructed according to ASHREA standards. It consists of two rooms
made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side
C. While indoor side has either
temperature control or load control. For testing or air conditioner, maintaining of temperatures is
important so these two rooms are made of adiabatic material. The method use in air conditioner test
method. These two rooms are separated by an opening in to
ducted equipment
Split AC Indoor Unit Installation
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
180
Fig.3 Split AC Outdoor Unit Installation Fig.4. Code Tester
Fig.5. Temperature Measuring Device
III. COOLING CAPACITY TEST AND CALCULATIONS
TEST CONDITIONS: The test conditions that should be maintained are as follows:
ISO 5151 standard
Indoor side Outdoor side
DBT o
C WBT o
C DBT o
C WBT o
C
27 19 35 24
PROCEDURE
Out let of air conditioner (which is going to be tested) is attached to the receiving chamber of
the code tester through the proper ducting. Before starting the main switch, ensure that all the
switches of panel Board are in disable or not. Before starting the test, clean all the sensors and fill
water in all sampling devices. Set the temperatures values, which are going, to be maintained in PID’S
of the panel boards Switch on the test unit by adjusting dimmer to 230 volts.
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
181
For example: we are maintaining DBT–35°C, WBT-24°c in outdoor side and DBT-27°C, WBT-
19°C indoor side (according to ISO standard) When temperature is stabilized there arithmetic mean
value should have
Outdoor side conditions o
C Outdoor side conditions o
C
DBT 35±0.3 DBT 27±0.3
WBT 24±0.2 WBT 19±0.2
After stabilization, to maintain the test conditions for 4 hours, and record the data after 30 minutes so
that there are 7 set of readings for every 5 min.
During this 30 min duration, record the code tester nozzle pressure drop. When receiving
chamber pressure shows 0.0 and record code tester DBT and WBT readings also.
The sensor temperature that should be recorded are:
102 Indoors side DBT
103 Indoors side WBT
104 Outdoors side DBT
105 Outdoors side WBT
106 Indoor side Code tester DBT
107 Indoor side Code tester WBT
Average the recorded data. So that we can get more appropriate one value.
For convenience not indoor side room temperature from 102 and 103 sensors and leaving air
condition from 106 and 107 sensors.
For calculation of CFM:
Cfm =Ci*Ai*Yi*√2Dp/p*3600*0.5885
Where
ρ=density of air at the air sampling condition kg/m3
.
Ci= Discharge co-efficient of its nozzle dimensionless.
Ai=Area of the nozzle in m2
.
Yi=expansion factor, dimensionless.
Dp=pressure drop across the nozzle in Pa.
Ci, Yi can be calculated from ASHRAE 41
FORMULAE FOR COOLING CAPACITY CALCULATIONS:
Volume Flow rate of air Qva(m3
/sec)= Cfm/2118.88
Enthalpy difference Dh = Enthalpy of moist air entering - Enthalpy of moist air leaving
Mass flow rate of air Ma(kg/s) =Volume flow rate of air/Specific volume of air
Cooling capacity in KW =Mass flow rate of air*Enthalpy difference
Cooling capacity in Btu/hr=Cooling capacity in KW*3412.14
Cooling capacity in Ton of refrigeration=Cooling capacity in KW/3.5167
CALCULATIONS
Calculations at 35
o
C Ambient:
Entering air conditions: DBT-27.11
o
C,WBT-19.27
o
C
Saturation pr.at DBT,
Ps= 610.78*EXP(DBT/(DBT+238.3)*17.2694)/1000
=610.78*EXP(27.11/(27.11+238.3)*17.2694)/1000
=3.5642 kpa
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
182
vSaturation pr. at WBT, P
l
= 610.78*EXP(WBT/(WBT+238.3)*17.2694)/1000
=610.78*EXP(19.27/(19.27+238.3)*17.2694)/1000
=2.2232 kpa
Actual vapour pressure,
l l
Pv = Pv -(((Pt- Pv )*(DBT-WBT)*(1.8))/(2800-1.3((1.8*DBT)+32))
= 2.2232-(((101.325-2.2232)*(27.11-19.27)*(1.8))/(2800-1.3((1.8*27.11)+32))
= 1.7042 kpa
Humidity ratio, W = 0.622*(Pv/(Pt-Pv))
= 0.622*(1.7042/(101.325-1.7042))
= 0.01064
Enthalpy of moist air, hen = (1.005*DBT) + (W*(2500+(1.88*DBT)))
= (1.005*27.11) + (0.01064*(2500+(1.88*27.11)))
= 54.3878 kj/kg
Specific volume of air, Ven = (287.3*(273+DBT))/((Pt-Pv)*1000)
= (287.3*(273+27.11))/((101.325-1.7042)*1000)
= 0.8654 m
3
/kg
Density of moist air, Den = 1/Ven
= 1/0.8653
= 1.1556 kg/m
3
Leaving air conditions: DBT-13.78
o
C,WBT-12.25
o
C
Saturation pr. at DBT,
Ps = 610.78*EXP(DBT/(DBT+238.3)*17.2694)/1000
=610.78*EXP(13.78/(13.78+238.3)*17.2694)/1000
=1.5699 kpa
Saturation pr. At WBT,
P = 610.78*EXP(WBT/(WBT+238.3)*17.2694)/1000
=610.78*EXP(12.25/(12.25+238.3)*17.2694)/1000
=1.4209 kpa40
Actual vapour pressure,
l
Pv = Pv -(((Pt- Pv )*(DBT-WBT)*(1.8))/(2800-1.3((1.8*DBT)+32))
= 1.4209-(((101.325-1.4209)*(13.78-12.25)*(1.8))/(2800-1.3((1.8*13.78)+32))
= 1.3199 kpa
Humidity ratio, W = 0.622*(Pv/(Pt-Pv))
= 0.622*(1.3199/(101.325-1.3199))
= 0.0082
Enthalpy of moist air, hle = (1.005*DBT) + (W*(2500+(1.88*DBT)))
= (1.005*13.78) + (0.0082*(2500+(1.88*13.78)))
= 34.5613 kj/kg
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
183
Specific volume of air, Vle = (287.3*(273+DBT))/((Pt-Pv)*1000)
= (287.3*(273+13.78))/((101.325-1.3199)*1000)
= 0.8238 m
3
/kg
Density of moist air, Dle = 1/Vle
= 1/0.8238
=1.2138 kg/m
3
Calculations for Cooling capacity :
Area, Ai = ((22/7*4)*SQRT(48.66/1000))+((22/7*4)*SQRT(99.43/1000))
= 0.00962 m
2
Cubic flow per minute,
Cfm = Ci*Yi*Ai*SQRT((2*Dp)/Dle)*3600*0.5885
=0.985*0.998*0.00962*SQRT((2*445)/1.2138)*3600* 0.5885
= 542.56 or 543
Volume flow rate,Qva= Cfm/2118.88
= 543/2118.88
= 0.2562 m
3
/sec
Enthalpy difference, Dh = hen-hle
= 54.3878 - 34.5613
= 19.8265 kj/kg
Mass flow rate, Ma = Volume flow rate (Qva)/Specific volume of leaving air (Vle)
= 0.2562/0.8238
= 0.3109 kg/sec
Cooling capacity in KW = Mass flow rate (Ma)*Enthalpy difference (Dh)
= 0.3109*19.8265
= 6.1640 kw
Cooling capacity in Btu/hr = cooling capacity in kw*3412.14
= 6.1640*3412.14
= 21032.43 Btu/hr
Cooling capacity in TON of refrigeration = cooling capacity in kw / 3.516
= 6.1640 / 3.516
= 1.7531 Ton
Energy efficiency ratio,EER = (cooling capacity in Btu/hr) / (Input power in watts)
= 21032/2240
= 9.389 Btu/W-hr
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
184
POWER CONSUMPTION TEST
Test conditions:
The various test conditions that should be maintained for Power consumption test are as
Follows:ISO 5151 Standard
Indoor side Outdoor side
DBT o
C WBT o
C DBT o
C WBT o
C
27 19 35 24
CALCULATIONS
Power Consumption Test of AC at 35o
C Ambient
Power consumed by air conditioner for 24hr = Final Energy meter reading –
Initial Energy meter reading
=5332.7 – 5316.2
= 16.5 Kw-hr
Power consumed of 1hr = 16.5/24
=0.687 Kw/hr
Power Consumption Test of AC at 46o
C Ambient
Power consumed by air conditioner for 24hr = Final Energy meter reading –
Initial Energy meter reading
=5358.5 – 5334
= 24.5 Kw-hr
Power consumed of 1hr = 24.5/24
=1.021 Kw/hr
STARTABILITY TEST
Test conditions: -
The various test conditions that should be maintained are given below:
(a) BIS 1391:1992
Indoor side room °C Outdoor side room °C Voltage
DBT WBT DBT WBT V
35 24 46 27 90% &110% of rated voltage.
(b) BIS 1391:1992(For Export A &B)
Indoor side room °C Outdoor side room °C Voltage
DBT WBT DBT WBT V
32 23 43 26 90% &110% of rated voltage.
32 23 52 31
95% minimum voltage&110%
of maximum voltage with dual
rated voltage.
International Journal of Advanced Research in Engineering and
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
Procedure for Down Trip:
(1) Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before
starting the system.
(2) Start the appliance at 220/230V according to the request by maintaining Indoor sideroom
DBT27o
C, WBT-19 o
C and Outdoor side room DBT
stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard
suction 70±5 psig anddischarge 300
placed at different places in the applian
(a) Indoor side room DBT and WBT
(b) Outdoor side room DBT and WBT
(c) Top shell and bottom shell
(d) Condenser in and condenser out
(e) Evaporator in an evaporator out
(f) Suction line and Dischar
IV RESULTS AND CONCLUSIONS
Every product that is manufactured is tested to know how it works and up to what level it can
satisfy the requirements of customers. The main objective of this project is testing the Air conditioner
appliance according to different standards by maintaining different climatic conditions in Air
conditioner test room. The testing includes cooling test, power consumption test.
From capacity test, cooling capacity of system at different temperatures is known. Cooling
capacity test is done on air conditioner appliance. The specification given by manufacturer for cooling
capacity of Air Conditioner at 35o
C ambient is 21200 Btu/hr, by conducting capacity test in the Air
conditioner test room it is found that its capacity is lower
Similarly cooling capacity at 46o
C and 54
Figure
Power consumption test is done on air conditioner and found that it
16.5 Kwhr units power i.e 0.687 kw/hr at 35
24.5 Kwhr units of power i.e 1.021 kw/hr in Air conditioner test room.
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
6499(Online) Volume 4, Issue 3, April (2013), © IAEME
185
Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before
Start the appliance at 220/230V according to the request by maintaining Indoor sideroom
C and Outdoor side room DBT-35 o
C, WBT-24 o
C. After reaching the
stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard
5 psig anddischarge 300±10 psig), temperatures, current and power. Sensors are
placed at different places in the appliance to record the temperatures of the following
Indoor side room DBT and WBT
Outdoor side room DBT and WBT
Top shell and bottom shell
Condenser in and condenser out
Evaporator in an evaporator out
Suction line and Discharge line
IV RESULTS AND CONCLUSIONS
Every product that is manufactured is tested to know how it works and up to what level it can
satisfy the requirements of customers. The main objective of this project is testing the Air conditioner
to different standards by maintaining different climatic conditions in Air
conditioner test room. The testing includes cooling test, power consumption test.
From capacity test, cooling capacity of system at different temperatures is known. Cooling
test is done on air conditioner appliance. The specification given by manufacturer for cooling
C ambient is 21200 Btu/hr, by conducting capacity test in the Air
conditioner test room it is found that its capacity is lower by 1.4% i.e 20908 Btu/hr at 35
C and 54o
C ambient is found as 19332Btu/hr and 5582 Btu/hr.
Figure 6 EER Vs Temperature
Power consumption test is done on air conditioner and found that it consumes when operated for 24 hr
16.5 Kwhr units power i.e 0.687 kw/hr at 35o
C Ambient. At 46o
C Ambient it is found that it consumes
24.5 Kwhr units of power i.e 1.021 kw/hr in Air conditioner test room.
Technology (IJARET), ISSN
6499(Online) Volume 4, Issue 3, April (2013), © IAEME
Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before
Start the appliance at 220/230V according to the request by maintaining Indoor sideroom
C. After reaching the
stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard
10 psig), temperatures, current and power. Sensors are
ce to record the temperatures of the following
Every product that is manufactured is tested to know how it works and up to what level it can
satisfy the requirements of customers. The main objective of this project is testing the Air conditioner
to different standards by maintaining different climatic conditions in Air
From capacity test, cooling capacity of system at different temperatures is known. Cooling
test is done on air conditioner appliance. The specification given by manufacturer for cooling
C ambient is 21200 Btu/hr, by conducting capacity test in the Air
by 1.4% i.e 20908 Btu/hr at 35o
C ambient.
C ambient is found as 19332Btu/hr and 5582 Btu/hr.
consumes when operated for 24 hr
C Ambient it is found that it consumes
International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN
0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME
186
Figure 7 Power(Units) Vs Temperature
The various factors observed amidst the testing were, amount of charge of refrigerant,
pressure drop, suction and discharge pressures, power, current etc. From these work different
procedures for testing air conditioners are established. The test results will give awareness to the
customers and manufacturers. Useful data is generated for the air conditioning engineers.
REFERENCES
[1] Akintunde, M.A. 2004b. Experimental Investigation of The performance of Vapor
Compression Refrigeration Systems. Federal University of Technology, Akure, Nigeria
[2] American Society Heating Refrigeration and Air Conditioning. ASHRAE Hand Book. 2001
[3] Wernick, B.J. “Effectiveness method”, RACA journal 2004.
[4]. C.P Arora, Refrigeration and Air conditioning. Tata McGraw-Hill Book Company
[5]. Stoecker, W.F. and Jones J.W. (1982), Refrigeration & Air Conditioning. McGraw-Hill Book
Company, Singapore
[6] Analytical expressions for optimum flow rates in evaporators and condensers of heat pumping
systems International Journal of Refrigeration, Volume 33, Issue 7, November 2010,
Pages 1211-1220 Granryd, E.
[7] Yumrutas R, kunduz M, Kanoglu M. Exergy analysis of vapor compression refrigeration
systems. Exergy, An international journal 2002;2(4);266-72.
[8] Dr.S.S. Banwait and Dr.S.C. Laroiya, “Properties of refrigerant and psychometric tables
and charts
[9] “Technical Manual Air-conditioning application, Tecumseh”. Tecumseh Products India Pvt.
Ltd., Hyderabad.
[10] Calorimeter Test Facility Lab manual (CTFLM) Tecumseh Products India Pvt. Ltd.
[11] Eckert, E.R.G.; Goldstein, R.J.; Ibele, W.E.; Patankar, S.V.; Simon, T.W.; Strykowski, P.J.;
Tamma, K.K.; Kuehn, T.H.; Bar-Cohen, A.; Heberlein, J.V.R.; (Sep 1997), Heat transfer--a
review of 1994 literature, International Journal of Heat and Mass Transfer 40-16, 3729-3804.
[12] N. Thangadurai and Dr. R. Dhanasekaran, “Effective Power Consumption Model for a
Network With Uniform Traffic Pattern”, International Journal of Computer Engineering &
Technology (IJCET), Volume 3, Issue 2, 2012, pp. 561 - 570, ISSN Print: 0976 – 6367, ISSN
Online: 0976 – 6375.
[13] Kapil Chopra, Dinesh Jain, Tushar Chandana and Anil Sharma, “Evaluation of Existing
Cooling Systems for Reducing Cooling Power Consumption”, International Journal of
Mechanical Engineering & Technology (IJMET), Volume 3, Issue 2, 2012, pp. 210 - 216,
ISSN Print: 0976 – 6340, ISSN Online: 0976 – 6359.
0
2
4
6
8
10
35 46 54
EER

Mais conteúdo relacionado

Mais procurados

Industrial energy efficiency techniques and energy management (1)
Industrial energy efficiency techniques and energy management (1)Industrial energy efficiency techniques and energy management (1)
Industrial energy efficiency techniques and energy management (1)
Anish Maman
 
Hybrid power generation by and solar –wind
Hybrid power generation by and solar –windHybrid power generation by and solar –wind
Hybrid power generation by and solar –wind
Uday Wankar
 
Energy management & audit
Energy management & auditEnergy management & audit
Energy management & audit
PINAKI ROY
 

Mais procurados (20)

Ppt on power saving
Ppt on power savingPpt on power saving
Ppt on power saving
 
Cogeneration
CogenerationCogeneration
Cogeneration
 
Photovoltaic modules & sizing of pv system
Photovoltaic modules & sizing of pv systemPhotovoltaic modules & sizing of pv system
Photovoltaic modules & sizing of pv system
 
Energy audit
Energy auditEnergy audit
Energy audit
 
Operation and Maintenance of Diesel Power Generating Plants
Operation and Maintenance of Diesel Power Generating PlantsOperation and Maintenance of Diesel Power Generating Plants
Operation and Maintenance of Diesel Power Generating Plants
 
Smart grid
Smart gridSmart grid
Smart grid
 
3. solar water heater
3. solar water heater3. solar water heater
3. solar water heater
 
Industrial energy efficiency techniques and energy management (1)
Industrial energy efficiency techniques and energy management (1)Industrial energy efficiency techniques and energy management (1)
Industrial energy efficiency techniques and energy management (1)
 
Scada and power system automation
Scada and power system automationScada and power system automation
Scada and power system automation
 
Hybrid power generation by and solar –wind
Hybrid power generation by and solar –windHybrid power generation by and solar –wind
Hybrid power generation by and solar –wind
 
Energy conservation in electric drives
Energy conservation in electric drives Energy conservation in electric drives
Energy conservation in electric drives
 
H&D lithium ion battery for energy storage and electrical vehicles
H&D lithium ion battery for energy storage and electrical vehiclesH&D lithium ion battery for energy storage and electrical vehicles
H&D lithium ion battery for energy storage and electrical vehicles
 
Scada in hydropower plant
Scada  in  hydropower plantScada  in  hydropower plant
Scada in hydropower plant
 
WIND ENERGY (A SOURCE OF RENEWABLE ENERGY)
WIND ENERGY (A SOURCE OF RENEWABLE ENERGY)WIND ENERGY (A SOURCE OF RENEWABLE ENERGY)
WIND ENERGY (A SOURCE OF RENEWABLE ENERGY)
 
Introduction to energy management system
Introduction to energy management system Introduction to energy management system
Introduction to energy management system
 
Micro-grid
Micro-gridMicro-grid
Micro-grid
 
Energy Monitoring System - WiEnergy Energy Monitoring Solution
Energy Monitoring System - WiEnergy Energy Monitoring SolutionEnergy Monitoring System - WiEnergy Energy Monitoring Solution
Energy Monitoring System - WiEnergy Energy Monitoring Solution
 
Transmission and distribution system of nepal
Transmission and distribution system of nepalTransmission and distribution system of nepal
Transmission and distribution system of nepal
 
IoT Based Battery Management System in Electric Vehicles.pdf
IoT Based Battery Management System in Electric Vehicles.pdfIoT Based Battery Management System in Electric Vehicles.pdf
IoT Based Battery Management System in Electric Vehicles.pdf
 
Energy management & audit
Energy management & auditEnergy management & audit
Energy management & audit
 

Semelhante a Performance evaluation of a air conditioner according to different test standards

CFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the ClassroomCFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the Classroom
ijtsrd
 
Performance improvement by reducing compressor work of r 134 a and r22 used r...
Performance improvement by reducing compressor work of r 134 a and r22 used r...Performance improvement by reducing compressor work of r 134 a and r22 used r...
Performance improvement by reducing compressor work of r 134 a and r22 used r...
IAEME Publication
 
Experimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hallExperimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hall
eSAT Publishing House
 
Experimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hallExperimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hall
eSAT Journals
 

Semelhante a Performance evaluation of a air conditioner according to different test standards (20)

Aircon design volvo bus
Aircon design volvo busAircon design volvo bus
Aircon design volvo bus
 
Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...Experimental investigation of waste heat recovery system for domestic refrige...
Experimental investigation of waste heat recovery system for domestic refrige...
 
Design Calculation of Main Components for Lab Based Refrigeration System
Design Calculation of Main Components for Lab Based Refrigeration SystemDesign Calculation of Main Components for Lab Based Refrigeration System
Design Calculation of Main Components for Lab Based Refrigeration System
 
IRJET- A Case Study of Cooling Load Estimation of an Auditorium
IRJET- A Case Study of Cooling Load Estimation of an AuditoriumIRJET- A Case Study of Cooling Load Estimation of an Auditorium
IRJET- A Case Study of Cooling Load Estimation of an Auditorium
 
IRJET- AC Room Design on HVAC
IRJET- AC Room Design on HVACIRJET- AC Room Design on HVAC
IRJET- AC Room Design on HVAC
 
Life Cycle Analysis of Multi Split VRF System
Life Cycle Analysis of Multi Split VRF SystemLife Cycle Analysis of Multi Split VRF System
Life Cycle Analysis of Multi Split VRF System
 
CFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the ClassroomCFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the Classroom
 
IRJET- Experimental Model Design and Simulation of Air Conditioning System fo...
IRJET- Experimental Model Design and Simulation of Air Conditioning System fo...IRJET- Experimental Model Design and Simulation of Air Conditioning System fo...
IRJET- Experimental Model Design and Simulation of Air Conditioning System fo...
 
Performance improvement by reducing compressor work of r 134 a and r22 used r...
Performance improvement by reducing compressor work of r 134 a and r22 used r...Performance improvement by reducing compressor work of r 134 a and r22 used r...
Performance improvement by reducing compressor work of r 134 a and r22 used r...
 
Design of HVAC system for commercial building
Design of HVAC system for commercial buildingDesign of HVAC system for commercial building
Design of HVAC system for commercial building
 
Performance Analysis and Optimization of Air Preheater in Thermal Power Plant
Performance Analysis and Optimization of Air Preheater in Thermal Power PlantPerformance Analysis and Optimization of Air Preheater in Thermal Power Plant
Performance Analysis and Optimization of Air Preheater in Thermal Power Plant
 
IRJET- Research of Cooling Characteristics of Hot Surface using Two Inclined ...
IRJET- Research of Cooling Characteristics of Hot Surface using Two Inclined ...IRJET- Research of Cooling Characteristics of Hot Surface using Two Inclined ...
IRJET- Research of Cooling Characteristics of Hot Surface using Two Inclined ...
 
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...
 
IRJET- Development of Generalize Software to Estimate Cooling Load for Air Co...
IRJET- Development of Generalize Software to Estimate Cooling Load for Air Co...IRJET- Development of Generalize Software to Estimate Cooling Load for Air Co...
IRJET- Development of Generalize Software to Estimate Cooling Load for Air Co...
 
IRJET - Variable Refrigerant Volume:- Air Conditioning Part: A Review
IRJET - Variable Refrigerant Volume:- Air Conditioning Part: A ReviewIRJET - Variable Refrigerant Volume:- Air Conditioning Part: A Review
IRJET - Variable Refrigerant Volume:- Air Conditioning Part: A Review
 
Experimental Investigation of Mini Cooler cum Freezer
Experimental Investigation of Mini Cooler cum FreezerExperimental Investigation of Mini Cooler cum Freezer
Experimental Investigation of Mini Cooler cum Freezer
 
Experimental Investigation of Mini Cooler cum Freezer
Experimental Investigation of Mini Cooler cum FreezerExperimental Investigation of Mini Cooler cum Freezer
Experimental Investigation of Mini Cooler cum Freezer
 
Experimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hallExperimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hall
 
Experimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hallExperimental analysis and thermal comfort index of air conditioned meeting hall
Experimental analysis and thermal comfort index of air conditioned meeting hall
 
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
IRJET- A Review on Developing a Model that Uses Waste Heat from Condenser in ...
 

Mais de IAEME Publication

A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSA STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
IAEME Publication
 
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSBROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
IAEME Publication
 
GANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEGANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICE
IAEME Publication
 
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
IAEME Publication
 
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
IAEME Publication
 
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
IAEME Publication
 
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
IAEME Publication
 
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
IAEME Publication
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
IAEME Publication
 
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
IAEME Publication
 

Mais de IAEME Publication (20)

IAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdf
 
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
 
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSA STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
 
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSBROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
 
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSDETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
 
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
 
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOVOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
 
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
 
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYVISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
 
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
 
GANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEGANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICE
 
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
 
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
 
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
 
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
 
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
 
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
 
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
 
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTA MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
 

Último

Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service NoidaCall Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
dlhescort
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
amitlee9823
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
amitlee9823
 
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
lizamodels9
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
amitlee9823
 
Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000
Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000
Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000
dlhescort
 

Último (20)

Falcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in indiaFalcon Invoice Discounting platform in india
Falcon Invoice Discounting platform in india
 
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service NoidaCall Girls In Noida 959961⊹3876 Independent Escort Service Noida
Call Girls In Noida 959961⊹3876 Independent Escort Service Noida
 
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort ServiceMalegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
Malegaon Call Girls Service ☎ ️82500–77686 ☎️ Enjoy 24/7 Escort Service
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
Falcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to ProsperityFalcon's Invoice Discounting: Your Path to Prosperity
Falcon's Invoice Discounting: Your Path to Prosperity
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
Organizational Transformation Lead with Culture
Organizational Transformation Lead with CultureOrganizational Transformation Lead with Culture
Organizational Transformation Lead with Culture
 
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
Call Girls Kengeri Satellite Town Just Call 👗 7737669865 👗 Top Class Call Gir...
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
Russian Call Girls In Rajiv Chowk Gurgaon ❤️8448577510 ⊹Best Escorts Service ...
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
Call Girls Zirakpur👧 Book Now📱7837612180 📞👉Call Girl Service In Zirakpur No A...
 
Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024Marel Q1 2024 Investor Presentation from May 8, 2024
Marel Q1 2024 Investor Presentation from May 8, 2024
 
Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000
Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000
Call Girls In Majnu Ka Tilla 959961~3876 Shot 2000 Night 8000
 
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort ServiceEluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
Eluru Call Girls Service ☎ ️93326-06886 ❤️‍🔥 Enjoy 24/7 Escort Service
 
JAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
JAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRLJAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
JAYNAGAR CALL GIRL IN 98274*61493 ❤CALL GIRLS IN ESCORT SERVICE❤CALL GIRL
 
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 

Performance evaluation of a air conditioner according to different test standards

  • 1. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 178 PERFORMANCE EVALUATION OF A AIR CONDITIONER ACCORDING TO DIFFERENT TEST STANDARDS K. Ravi Kumar, Asst Prof., Department of Mechanical Engineering, AHCET, Chevella, Ranga Reddy – 515002(A.P.), India. K. Ganesh Babu Asst Prof., Department of Mechanical Engineering, SITECH, Chevella, Ranga Reddy – 515002(A.P.), India S. Udaya Bhaskar Asso Prof., Department of Mechanical Engineering, AHCET, Chevella, Ranga Reddy – 515002(A.P.), India. ABSTRACT The Paper reports on the performance of Air Conditioner at different test standards. The future design of air conditioners is being driven primarily by (a) increased energy efficiency standards and (b) the need to eliminate ozone-depleting working fluids. Various national and international agencies continue to impose more stringent requirements for energy efficiency. In addition, consumer pressure to select units with lower operating costs further drives the need for improved performance. The main objective of this paper is to give wide understand of the standards and to maintain the standard conditions in Psychrometric room (Air conditioner test room), which has been constructed to test the air conditioners and to establish different test procedures. The tests that should be performed in Air conditioner test room are cooling capacity test, power consumption test. The main objective of the manufacturers is to produce the systems according to requirements of customers which can give more cooling, low power consumption, high EER to with stand competition in the market. In every country, the manufacturers follow some standards according to the climatic conditions to test the appliances. Keywords: Psychrometric room; EER; cooling capacity test; power consumption test; climatic conditions INTERNATIONAL JOURNAL OF ADVANCED RESEARCH IN ENGINEERING AND TECHNOLOGY (IJARET) ISSN 0976 - 6480 (Print) ISSN 0976 - 6499 (Online) Volume 4, Issue 3, April 2013, pp. 178-186 © IAEME: www.iaeme.com/ijaret.asp Journal Impact Factor (2013): 5.8376 (Calculated by GISI) www.jifactor.com IJARET © I A E M E
  • 2. International Journal of Advanced Research in Engineering and 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME I INTRODUCTION India falls in the hot zone therefore the comfort air necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred to the environment, which is at a higher temperature. This is done with the help of r Though there are many methods to achieve cooling, one process that is predominantly applied in refrigeration equipment and its application is vapor compression cycle. One of the applications of vapor compression system is in Air conditioning conditioners, and then comes the Packaged systems which are used for higher tonnages till 50Ton. Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in US in earlier 19th Century, there has been a radical change in the methods and process used in manufacturing air-conditioning equipment but there is no change in the principle i.e. Vapor compression system used in the cycle. II.EXPERIMENTAL SETUP Air conditioner test room is constructed according to ASHREA standards. It consists of two rooms made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side room. The outside room ambient is controlled from 25 temperature control or load control. For testing or air conditioner, maintaining of temperatures is important so these two rooms are made of adiabatic material. The method use in air conditioner test room for finding capacity is air enthalpy which the non-ducted equipment (test air conditioner) is mounted which the non (test air conditioner) is mounted. The equipments associated with air conditioner test room as follo (a) Panel Boards (b) Split AC Indoor Unit Installation (c) Split AC Outdoor Unit Installation (d) Packaged Air conditioners (e) Humidifiers (f) Code Tester (g) Temperature measuring instrument (h) Heaters (g) Sampling device Fig.1. Psychrometric Laboratory view International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 179 therefore the comfort air-conditioning has always been felt to be a necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred to the environment, which is at a higher temperature. This is done with the help of r Though there are many methods to achieve cooling, one process that is predominantly applied in refrigeration equipment and its application is vapor compression cycle. One of the applications of vapor compression system is in Air conditioning units, the more commonly used one is Room Air conditioners, and then comes the Packaged systems which are used for higher tonnages till 50Ton. Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in Century, there has been a radical change in the methods and process used in conditioning equipment but there is no change in the principle i.e. Vapor compression system used in the cycle. room is constructed according to ASHREA standards. It consists of two rooms made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side room. The outside room ambient is controlled from 25o C to 55o C. While indoor s temperature control or load control. For testing or air conditioner, maintaining of temperatures is important so these two rooms are made of adiabatic material. The method use in air conditioner test room for finding capacity is air enthalpy method. These two rooms are separated by an opening in to ducted equipment (test air conditioner) is mounted which the non-ducted equipment The equipments associated with air conditioner test room as follows: Split AC Indoor Unit Installation Split AC Outdoor Unit Installation Temperature measuring instrument sychrometric Laboratory view Fig.2 Split AC Indoor Unit Installation Technology (IJARET), ISSN 6499(Online) Volume 4, Issue 3, April (2013), © IAEME conditioning has always been felt to be a necessity for mankind. To achieve comfort, heat is extracted from the comfort region and transferred to the environment, which is at a higher temperature. This is done with the help of refrigeration. Though there are many methods to achieve cooling, one process that is predominantly applied in refrigeration equipment and its application is vapor compression cycle. One of the applications of units, the more commonly used one is Room Air- conditioners, and then comes the Packaged systems which are used for higher tonnages till 50Ton. Ever since the invention of Air Conditioning as one of Refrigeration application by W H Carrier in Century, there has been a radical change in the methods and process used in conditioning equipment but there is no change in the principle i.e. Vapor room is constructed according to ASHREA standards. It consists of two rooms made of adiabatic material of rigid polyurethane, one is indoor side room and another is outdoor side C. While indoor side has either temperature control or load control. For testing or air conditioner, maintaining of temperatures is important so these two rooms are made of adiabatic material. The method use in air conditioner test method. These two rooms are separated by an opening in to ducted equipment Split AC Indoor Unit Installation
  • 3. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 180 Fig.3 Split AC Outdoor Unit Installation Fig.4. Code Tester Fig.5. Temperature Measuring Device III. COOLING CAPACITY TEST AND CALCULATIONS TEST CONDITIONS: The test conditions that should be maintained are as follows: ISO 5151 standard Indoor side Outdoor side DBT o C WBT o C DBT o C WBT o C 27 19 35 24 PROCEDURE Out let of air conditioner (which is going to be tested) is attached to the receiving chamber of the code tester through the proper ducting. Before starting the main switch, ensure that all the switches of panel Board are in disable or not. Before starting the test, clean all the sensors and fill water in all sampling devices. Set the temperatures values, which are going, to be maintained in PID’S of the panel boards Switch on the test unit by adjusting dimmer to 230 volts.
  • 4. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 181 For example: we are maintaining DBT–35°C, WBT-24°c in outdoor side and DBT-27°C, WBT- 19°C indoor side (according to ISO standard) When temperature is stabilized there arithmetic mean value should have Outdoor side conditions o C Outdoor side conditions o C DBT 35±0.3 DBT 27±0.3 WBT 24±0.2 WBT 19±0.2 After stabilization, to maintain the test conditions for 4 hours, and record the data after 30 minutes so that there are 7 set of readings for every 5 min. During this 30 min duration, record the code tester nozzle pressure drop. When receiving chamber pressure shows 0.0 and record code tester DBT and WBT readings also. The sensor temperature that should be recorded are: 102 Indoors side DBT 103 Indoors side WBT 104 Outdoors side DBT 105 Outdoors side WBT 106 Indoor side Code tester DBT 107 Indoor side Code tester WBT Average the recorded data. So that we can get more appropriate one value. For convenience not indoor side room temperature from 102 and 103 sensors and leaving air condition from 106 and 107 sensors. For calculation of CFM: Cfm =Ci*Ai*Yi*√2Dp/p*3600*0.5885 Where ρ=density of air at the air sampling condition kg/m3 . Ci= Discharge co-efficient of its nozzle dimensionless. Ai=Area of the nozzle in m2 . Yi=expansion factor, dimensionless. Dp=pressure drop across the nozzle in Pa. Ci, Yi can be calculated from ASHRAE 41 FORMULAE FOR COOLING CAPACITY CALCULATIONS: Volume Flow rate of air Qva(m3 /sec)= Cfm/2118.88 Enthalpy difference Dh = Enthalpy of moist air entering - Enthalpy of moist air leaving Mass flow rate of air Ma(kg/s) =Volume flow rate of air/Specific volume of air Cooling capacity in KW =Mass flow rate of air*Enthalpy difference Cooling capacity in Btu/hr=Cooling capacity in KW*3412.14 Cooling capacity in Ton of refrigeration=Cooling capacity in KW/3.5167 CALCULATIONS Calculations at 35 o C Ambient: Entering air conditions: DBT-27.11 o C,WBT-19.27 o C Saturation pr.at DBT, Ps= 610.78*EXP(DBT/(DBT+238.3)*17.2694)/1000 =610.78*EXP(27.11/(27.11+238.3)*17.2694)/1000 =3.5642 kpa
  • 5. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 182 vSaturation pr. at WBT, P l = 610.78*EXP(WBT/(WBT+238.3)*17.2694)/1000 =610.78*EXP(19.27/(19.27+238.3)*17.2694)/1000 =2.2232 kpa Actual vapour pressure, l l Pv = Pv -(((Pt- Pv )*(DBT-WBT)*(1.8))/(2800-1.3((1.8*DBT)+32)) = 2.2232-(((101.325-2.2232)*(27.11-19.27)*(1.8))/(2800-1.3((1.8*27.11)+32)) = 1.7042 kpa Humidity ratio, W = 0.622*(Pv/(Pt-Pv)) = 0.622*(1.7042/(101.325-1.7042)) = 0.01064 Enthalpy of moist air, hen = (1.005*DBT) + (W*(2500+(1.88*DBT))) = (1.005*27.11) + (0.01064*(2500+(1.88*27.11))) = 54.3878 kj/kg Specific volume of air, Ven = (287.3*(273+DBT))/((Pt-Pv)*1000) = (287.3*(273+27.11))/((101.325-1.7042)*1000) = 0.8654 m 3 /kg Density of moist air, Den = 1/Ven = 1/0.8653 = 1.1556 kg/m 3 Leaving air conditions: DBT-13.78 o C,WBT-12.25 o C Saturation pr. at DBT, Ps = 610.78*EXP(DBT/(DBT+238.3)*17.2694)/1000 =610.78*EXP(13.78/(13.78+238.3)*17.2694)/1000 =1.5699 kpa Saturation pr. At WBT, P = 610.78*EXP(WBT/(WBT+238.3)*17.2694)/1000 =610.78*EXP(12.25/(12.25+238.3)*17.2694)/1000 =1.4209 kpa40 Actual vapour pressure, l Pv = Pv -(((Pt- Pv )*(DBT-WBT)*(1.8))/(2800-1.3((1.8*DBT)+32)) = 1.4209-(((101.325-1.4209)*(13.78-12.25)*(1.8))/(2800-1.3((1.8*13.78)+32)) = 1.3199 kpa Humidity ratio, W = 0.622*(Pv/(Pt-Pv)) = 0.622*(1.3199/(101.325-1.3199)) = 0.0082 Enthalpy of moist air, hle = (1.005*DBT) + (W*(2500+(1.88*DBT))) = (1.005*13.78) + (0.0082*(2500+(1.88*13.78))) = 34.5613 kj/kg
  • 6. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 183 Specific volume of air, Vle = (287.3*(273+DBT))/((Pt-Pv)*1000) = (287.3*(273+13.78))/((101.325-1.3199)*1000) = 0.8238 m 3 /kg Density of moist air, Dle = 1/Vle = 1/0.8238 =1.2138 kg/m 3 Calculations for Cooling capacity : Area, Ai = ((22/7*4)*SQRT(48.66/1000))+((22/7*4)*SQRT(99.43/1000)) = 0.00962 m 2 Cubic flow per minute, Cfm = Ci*Yi*Ai*SQRT((2*Dp)/Dle)*3600*0.5885 =0.985*0.998*0.00962*SQRT((2*445)/1.2138)*3600* 0.5885 = 542.56 or 543 Volume flow rate,Qva= Cfm/2118.88 = 543/2118.88 = 0.2562 m 3 /sec Enthalpy difference, Dh = hen-hle = 54.3878 - 34.5613 = 19.8265 kj/kg Mass flow rate, Ma = Volume flow rate (Qva)/Specific volume of leaving air (Vle) = 0.2562/0.8238 = 0.3109 kg/sec Cooling capacity in KW = Mass flow rate (Ma)*Enthalpy difference (Dh) = 0.3109*19.8265 = 6.1640 kw Cooling capacity in Btu/hr = cooling capacity in kw*3412.14 = 6.1640*3412.14 = 21032.43 Btu/hr Cooling capacity in TON of refrigeration = cooling capacity in kw / 3.516 = 6.1640 / 3.516 = 1.7531 Ton Energy efficiency ratio,EER = (cooling capacity in Btu/hr) / (Input power in watts) = 21032/2240 = 9.389 Btu/W-hr
  • 7. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 184 POWER CONSUMPTION TEST Test conditions: The various test conditions that should be maintained for Power consumption test are as Follows:ISO 5151 Standard Indoor side Outdoor side DBT o C WBT o C DBT o C WBT o C 27 19 35 24 CALCULATIONS Power Consumption Test of AC at 35o C Ambient Power consumed by air conditioner for 24hr = Final Energy meter reading – Initial Energy meter reading =5332.7 – 5316.2 = 16.5 Kw-hr Power consumed of 1hr = 16.5/24 =0.687 Kw/hr Power Consumption Test of AC at 46o C Ambient Power consumed by air conditioner for 24hr = Final Energy meter reading – Initial Energy meter reading =5358.5 – 5334 = 24.5 Kw-hr Power consumed of 1hr = 24.5/24 =1.021 Kw/hr STARTABILITY TEST Test conditions: - The various test conditions that should be maintained are given below: (a) BIS 1391:1992 Indoor side room °C Outdoor side room °C Voltage DBT WBT DBT WBT V 35 24 46 27 90% &110% of rated voltage. (b) BIS 1391:1992(For Export A &B) Indoor side room °C Outdoor side room °C Voltage DBT WBT DBT WBT V 32 23 43 26 90% &110% of rated voltage. 32 23 52 31 95% minimum voltage&110% of maximum voltage with dual rated voltage.
  • 8. International Journal of Advanced Research in Engineering and 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME Procedure for Down Trip: (1) Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before starting the system. (2) Start the appliance at 220/230V according to the request by maintaining Indoor sideroom DBT27o C, WBT-19 o C and Outdoor side room DBT stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard suction 70±5 psig anddischarge 300 placed at different places in the applian (a) Indoor side room DBT and WBT (b) Outdoor side room DBT and WBT (c) Top shell and bottom shell (d) Condenser in and condenser out (e) Evaporator in an evaporator out (f) Suction line and Dischar IV RESULTS AND CONCLUSIONS Every product that is manufactured is tested to know how it works and up to what level it can satisfy the requirements of customers. The main objective of this project is testing the Air conditioner appliance according to different standards by maintaining different climatic conditions in Air conditioner test room. The testing includes cooling test, power consumption test. From capacity test, cooling capacity of system at different temperatures is known. Cooling capacity test is done on air conditioner appliance. The specification given by manufacturer for cooling capacity of Air Conditioner at 35o C ambient is 21200 Btu/hr, by conducting capacity test in the Air conditioner test room it is found that its capacity is lower Similarly cooling capacity at 46o C and 54 Figure Power consumption test is done on air conditioner and found that it 16.5 Kwhr units power i.e 0.687 kw/hr at 35 24.5 Kwhr units of power i.e 1.021 kw/hr in Air conditioner test room. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 185 Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before Start the appliance at 220/230V according to the request by maintaining Indoor sideroom C and Outdoor side room DBT-35 o C, WBT-24 o C. After reaching the stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard 5 psig anddischarge 300±10 psig), temperatures, current and power. Sensors are placed at different places in the appliance to record the temperatures of the following Indoor side room DBT and WBT Outdoor side room DBT and WBT Top shell and bottom shell Condenser in and condenser out Evaporator in an evaporator out Suction line and Discharge line IV RESULTS AND CONCLUSIONS Every product that is manufactured is tested to know how it works and up to what level it can satisfy the requirements of customers. The main objective of this project is testing the Air conditioner to different standards by maintaining different climatic conditions in Air conditioner test room. The testing includes cooling test, power consumption test. From capacity test, cooling capacity of system at different temperatures is known. Cooling test is done on air conditioner appliance. The specification given by manufacturer for cooling C ambient is 21200 Btu/hr, by conducting capacity test in the Air conditioner test room it is found that its capacity is lower by 1.4% i.e 20908 Btu/hr at 35 C and 54o C ambient is found as 19332Btu/hr and 5582 Btu/hr. Figure 6 EER Vs Temperature Power consumption test is done on air conditioner and found that it consumes when operated for 24 hr 16.5 Kwhr units power i.e 0.687 kw/hr at 35o C Ambient. At 46o C Ambient it is found that it consumes 24.5 Kwhr units of power i.e 1.021 kw/hr in Air conditioner test room. Technology (IJARET), ISSN 6499(Online) Volume 4, Issue 3, April (2013), © IAEME Take the cold resistance of the system (i.e. Main, Auxiliary and Total resistances) before Start the appliance at 220/230V according to the request by maintaining Indoor sideroom C. After reaching the stable conditions and optimizing for 3 to 4 hours record the data of pressures (standard 10 psig), temperatures, current and power. Sensors are ce to record the temperatures of the following Every product that is manufactured is tested to know how it works and up to what level it can satisfy the requirements of customers. The main objective of this project is testing the Air conditioner to different standards by maintaining different climatic conditions in Air From capacity test, cooling capacity of system at different temperatures is known. Cooling test is done on air conditioner appliance. The specification given by manufacturer for cooling C ambient is 21200 Btu/hr, by conducting capacity test in the Air by 1.4% i.e 20908 Btu/hr at 35o C ambient. C ambient is found as 19332Btu/hr and 5582 Btu/hr. consumes when operated for 24 hr C Ambient it is found that it consumes
  • 9. International Journal of Advanced Research in Engineering and Technology (IJARET), ISSN 0976 – 6480(Print), ISSN 0976 – 6499(Online) Volume 4, Issue 3, April (2013), © IAEME 186 Figure 7 Power(Units) Vs Temperature The various factors observed amidst the testing were, amount of charge of refrigerant, pressure drop, suction and discharge pressures, power, current etc. From these work different procedures for testing air conditioners are established. The test results will give awareness to the customers and manufacturers. Useful data is generated for the air conditioning engineers. REFERENCES [1] Akintunde, M.A. 2004b. Experimental Investigation of The performance of Vapor Compression Refrigeration Systems. Federal University of Technology, Akure, Nigeria [2] American Society Heating Refrigeration and Air Conditioning. ASHRAE Hand Book. 2001 [3] Wernick, B.J. “Effectiveness method”, RACA journal 2004. [4]. C.P Arora, Refrigeration and Air conditioning. Tata McGraw-Hill Book Company [5]. Stoecker, W.F. and Jones J.W. (1982), Refrigeration & Air Conditioning. McGraw-Hill Book Company, Singapore [6] Analytical expressions for optimum flow rates in evaporators and condensers of heat pumping systems International Journal of Refrigeration, Volume 33, Issue 7, November 2010, Pages 1211-1220 Granryd, E. [7] Yumrutas R, kunduz M, Kanoglu M. Exergy analysis of vapor compression refrigeration systems. Exergy, An international journal 2002;2(4);266-72. [8] Dr.S.S. Banwait and Dr.S.C. Laroiya, “Properties of refrigerant and psychometric tables and charts [9] “Technical Manual Air-conditioning application, Tecumseh”. Tecumseh Products India Pvt. Ltd., Hyderabad. [10] Calorimeter Test Facility Lab manual (CTFLM) Tecumseh Products India Pvt. Ltd. [11] Eckert, E.R.G.; Goldstein, R.J.; Ibele, W.E.; Patankar, S.V.; Simon, T.W.; Strykowski, P.J.; Tamma, K.K.; Kuehn, T.H.; Bar-Cohen, A.; Heberlein, J.V.R.; (Sep 1997), Heat transfer--a review of 1994 literature, International Journal of Heat and Mass Transfer 40-16, 3729-3804. [12] N. Thangadurai and Dr. R. Dhanasekaran, “Effective Power Consumption Model for a Network With Uniform Traffic Pattern”, International Journal of Computer Engineering & Technology (IJCET), Volume 3, Issue 2, 2012, pp. 561 - 570, ISSN Print: 0976 – 6367, ISSN Online: 0976 – 6375. [13] Kapil Chopra, Dinesh Jain, Tushar Chandana and Anil Sharma, “Evaluation of Existing Cooling Systems for Reducing Cooling Power Consumption”, International Journal of Mechanical Engineering & Technology (IJMET), Volume 3, Issue 2, 2012, pp. 210 - 216, ISSN Print: 0976 – 6340, ISSN Online: 0976 – 6359. 0 2 4 6 8 10 35 46 54 EER