HEATING VENTILATION &
  AIRCONDITIONING

   SYSTEM DESIGN




      FACULTY CO-ORDINATOR
         NEERAJ SHUKLA
CONTENTS
                                                        PAGE NO.
1.0   INTRODUCTION AND OVERVIEW                     -      2




2.0   FUNDAMENTALS OF REFRIGERATION                 -      5




3.0   BASIC REFRIGERATION SYSTEM                    -      12




4.0   ELEMENTS OF PSYCHROMETRY                      -      16




5.0   APPLIED PSYCHROMETRY                          -      23




6.0   HEAT LOAD ESTIMATION                          -      33




7.0   HEAT LOAD DATA SHEET & TYPICAL CALCULATION    -      47




8.0   HEATING VENTILATION & AIRCONDITIONING SYSTEMS -      52
1.0 INTRODUCTION AND
     OVERVIEW
INTRODUCTION AND OVERVIEW
A simple definition of air conditioning is the simultaneous control of temperature,
humidity, air movement, and the quality of air in a space.

The use of the conditioned space determines the temperature, humidity, air
movement, and quality of air that must be maintained.

The primary function of air conditioning is to maintain conditions that are (1)
conducive to human comfort, or (2) required by a product, or process within a
space.   To perform this function, equipment of the proper capacity must be
installed and controlled throughout the year.        The equipment capacity is
determined by the actual instantaneous peak load requirements; type of control
is determined by the conditions to be maintained during peak and partial load.
Generally, it is impossible to measure either the actual peak or the partial load in
any given space; these loads must be estimated.

The term ‘refrigeration’ may be defined as the process of removing heat from a
substance under controlled conditions. It also includes the process of reducing
and maintaining the temperature of a body below the general temperature of its
surroundings. In other words, the refrigeration means a continued extraction of
heat from a body whose temperature is already below the temperature of its
surroundings.

For example, if some space (say in cold storage) is to be kept at - 2 °C (271 K),
we must continuously extract heat which flows into it due to leakage through the
walls and also the heat which is brought into it with the articles stored after the
temperature is once reduced to - 2 °C (271 K). Thus in a refrigerator, heat is
virtually being pumped from a lower temperature to a higher temperature.
According to second law of Thermodynamics, this process can only be
performed with the aid of some external work. It is obvious that supply of power
(say electric motor) is regularly required to drive a refrigerator. Theoretically, a
refrigerator is a reversed heat engine or a heat pump which pumps heat from a
cold body. The substance which works in a heat pump to extract heat from a
cold body and to deliver to a hot body is called a refrigerant.


The refrigeration system is known to the man since the middle of nineteenth
century. The scientists, of the time, developed a few stray machines to achieve
some pleasure. But it paved the way by inviting the attention of scientists for
proper studies and research.      They were able to build a reasonably reliable
machine by the end of nineteenth century for refrigeration jobs. But with the
advent of efficient rotary compressors and gas turbines, the science of
refrigeration reached the used for the cooling of storage chambers in which
perishable foods, drinks and medicines are stored. The refrigeration has also
wide applications in submarine ships, aircraft and rockets.


Air conditioning has got wide range of applications and it is very much essential
in these days. Air conditioning is provided for some of the following reasons
   b) To improve productivity in offices, factories by maintaining comfort
       conditions for persons .
   c) To maintain comfortable conditions for working in hotels, labs, etc.,
   d) To avoid malfunctioning of some of the control panels in Electrical Control
       Buildings.
   e) To maintain over pressure inside the premises for avoiding outside (dusty)
       air in to the room.
   f) To create healthy atmosphere inside the room by supplying filtered air in
       to the room.
   g) To provide clean, filtered, healthy, comfortable conditions in hospitals etc.,
2.0 FUNDAMENTALS OF
    REFRIGERATION
FUNDAMENTALS OF REFRIGERATION


Refrigeration is the process by which heat is removed from a low temperature
level and rejected at a relatively higher temperature level. The Americans define
refrigeration in a somewhat different way, thus, refrigeration is the process by
which heat is removed from a place where it is not required and rejected into a
place where it is not objectionable.      This is not, strictly speaking, a proper
scientific definition, since it does not make any mention of its temperature levels.
No process can be called “refrigeration” unless removal of heat is at a
temperature lower than the surrounding temperature.


By nature heat always flows from one body to another body which is relatively at
a lower temperature.     This law of nature cannot be altered by any means.
Transferring heat from a low temperature level to a high temperature level is
analogous to transferring water from a lower level to a higher level. Imagine two
water tanks, one located at the ground floor full of water and another empty,
located at the roof level of a building. If water from the ground floor tank is to be
transferred to the roof tank, then the only thing to do is to bring a bucket, place it
at a level lower than the ground floor tank and allow the water to initially drain
into the bucket according to the law of nature. The second step would be to lift
this bucket full of water to a level above the roof tank and now allow the water
from the bucket to drain into the roof tank according to the natural flow by gravity.
In the foregoing process, we have used the bucket as the carrier and moved it up
and down, first to a level lower than the ground floor tank and then to a level
higher than the roof tank. Needless to add that in the process some mechanical
work has been performed for lifting the bucket from the lower level to the higher
level.
Applying this analogy to the process of refrigeration, it is evident, that we require
a substance as the carrier of heat analogous to the bucket. This substance
should be first brought to a temperature which is lower than the low level
temperature so that heat from the low temperature level will automatically flow
into this carrier substance which has been brought to a still lower level of
temperature. After this carrier substance has been fully loaded with heat it has
got to be raised to a temperature which is higher than the high level temperature
so that heat from this carrier will automatically flow according to the law of nature.
The carrier substance referred to above is what is known in refrigeration parlance
as “refrigerant”. We shall now see what a refrigerant is really like. All volatile
liquids including water have property whereby the temperature at which they
evaporate changes according to the pressure it is subjected to. Take water for
example. At normal atmospheric pressure it boils at 100°C (212°F). When the
water is subjected to higher pressure its boiling temperature also becomes higher
than 100°C.    Likewise, if the water is subjected to pressures lower than the
atmosphere its boiling temperature also falls below 100°C. In fact water can boil
even at as low a temperature as 4°C when it is kept in vacuum free of air. In this
case the only pressure it will have above is its own vapour pressure. Different
volatile substances have different pressure-boiling point characteristics.        For
refrigeration purpose the most commonly used refrigerants are refrigerant 12 and
refrigerant 22. By reference to a table giving the properties of these refrigerants
is will be seen that for each pressure there is a corresponding temperature at
which only the refrigerant will boil.   It goes without saying that at any given
pressure the temperature at which the liquid refrigerant boils is also the
temperature at which the refrigerant vapour would condense back to liquid form.
Whether it is boiling or condensing all depends on whether it is receiving heat or
giving heat.   For refrigerant purpose, therefore, we make use of this natural
property of the volatile refrigerant. For example, if the liquid refrigerant R-22 is
by some means or other brought down to an absolute pressure of say 83.72 psi,
then this liquid is now in a position to boil at a temperature of 40°F. In order to
make this liquid at low pressure boil, you will have to supply heat equivalent to
the latent heat of vaporization.

So any body which is above 40°F in temperature can supply this latent heat to
make this liquid boil and turn completely into gaseous form, it goes without
saying that the substance which supplies the heat for boiling the refrigerant will
itself naturally cool down, but in any case not to a temperature below 40°F which
is the temperature at which the refrigerant is boiling. Once the refrigerant liquid
has completely vaporized, it has no further capacity to absorb heat from the heat
supplying body, just in the same way that the bucket had no further capacity to
take more water the moment it was full. In the case of bucket in order to make it
useful again, we had to raise this to a higher level and empty out its contents in
the roof tank and then bring it back once again to take another bucket full from
the ground floor tank. In a similar way the completely vaporized refrigerant will
have to be raised to a high temperature level.         By raising it to a higher
temperature level, we do not mean that you simply heat up the refrigerant. What
is really to be done is this low pressure refrigerant will have to be compressed in
a compressor to a higher pressure. The pressure to which it is compressed must
be such that the boiling point or conversely the temperature at which the
refrigerant vapour would condense should be higher than the body to which we
want to empty out the heat content of the carrier refrigerant. If, for example, the
body to which we want to reject this heat is water which is at a temperature of
90°F, then the boiling temperature or condensing temperature of the refrigerant
should be higher than 90°F, say 106°F. Now 106°F happens to be the boiling
temperature of the refrigerant when it is at a pressure of 230 psi absolute. This
means that the low pressure refrigerant will have to be compressed to a pressure
of 230 psi absolute before it is in a position to empty out its heat content to the
cooling medium, namely, natural water. Note that in the process we have not
violated any natural law concerning heat flow. We have all along allowed heat to
flow from a certain temperature level to a lower temperature level. What we have
done is that we have changed the temperature level of the carrier refrigerant to
higher or lower temperature levels to conform to the natural law of heat flow.
This brings us to a stage where we have to know the definition of certain terms
which are generally used in refrigeration parlance.


Saturation Temperature
For any given refrigerant the temperature at which the liquid refrigerant would
boil (or conversely the refrigerant vapour would condense) when it is subjected to
a certain pressure is defined as the saturation temperature corresponding to that
pressure. It is obvious that at this temperature and pressure, refrigerant in liquid
and vapour form kept in a closed container would be in equilibrium with each
other. So long as the pressure inside this container is maintained steady the
liquid portion will vaporize if heat is added or the vapour portion will condense if
heat is removed. On this basis, saturation temperature for any given pressure is
defined as that temperature at which liquid refrigerant and its vapour remain in
contact with each other in equilibrium.


Superheat
We saw in the previous paragraph that liquid refrigerant and its vapour will be in
equilibrium with each other in a closed container at the saturation temperature
corresponding to the pressure. Any addition or removal of heat would only result
in either liquid vaporizing or the vapour condensing, pressure remaining same.
However, if the vaporized refrigerant is separated from the liquid portion, then
any heat added to this refrigerant in vapour form would only go to raise the
temperature of the vapour above its saturation temperature corresponding to its
pressure. This is superheated vapour. Superheat is usually expressed in terms
of degrees.    When we say 10° superheat, what we mean is the gaseous
refrigerant is at a temperature 10° above the saturation temperature
corresponding to its pressure.
Sub-cooling
In a like manner if the liquid portion of the refrigerant is separated and completely
isolated from the vapour which is in equilibrium with it then any removal of heat
from this refrigerant would lower its temperature to a value below its saturation
temperature. Such a liquid is called sub-cooled liquid. When we say the liquid is
15° below the saturation temperature corresponding to its pressure. It is obvious
that in the case of sub-cooled liquid when heat is added it will first rise up in
temperature till it reaches its saturation temperature and thereafter only it will
begin to boil as long as it is receiving heat. Likewise, in the case of superheated
gas, when heat is removed from the same it will first fall down in temperature till it
reaches the saturation temperature corresponding to its pressure (this is
generally referred to as de-superheating). Any further removal of heat after this
would result in condensation of the vapour into liquid form at constant
temperature, namely, the saturation temperature.         One thing that should be
borne in mind is neither sub-cooling of liquid nor superheating of the vapour is
possible when liquid and its vapour are in contact with each other in equilibrium,
because as already explained earlier, any removal or addition of heat in this case
would only respectively result in condensing of the vapour part or evaporating of
the liquid part, at constant temperature.


Enthalpy
Enthalpy is the terms which denotes the heat content of the refrigerant from a
base saturation temperature of 40°F. At this temperature and the corresponding
saturation pressure the heat content of the liquid has been arbitrarily fixed as 0.
It, therefore, follows that the enthalpy of the liquid above 40°F will be positive and
that below 40°F. will be negative. The enthalpy of the refrigerant when it is in
vapour form will be equal to the enthalpy of the liquid at the same pressure and
saturation temperature.
Adiabatic Compression
Any process which is performed without the addition of heat to or removal of heat
from the process is said to be an adiabatic process. Compression of gaseous
refrigerant without addition or removal of heat is called adiabatic compression.
The pressure enthalpy diagram of a refrigerant has also lines showing adiabatic
compression. It is, therefore, possible to find out the enthalpy and temperature of
the gas at various pressures during the course of compression.
3.0 BASIC REFRIGERATION
        SYSTEM
BASIC REFRIGERATION SYSTEM

The various components which form part of a refrigeration system can be
described as follows:

Evaporator
Let us start from the evaporator. Liquid at high pressure has to be admitted into
the evaporator. In order that this liquid may evaporate at low temperature, it is
essential that the liquid so admitted is simultaneously reduced in pressure. The
level to which the pressure has to be reduced of course is determined by the
temp. at which you want this liquid to evaporate.        For example, if you want
evaporation of refrigerant 22 at a temperature of 40°F, the absolute pressure
should be brought down to 83.72 psi or if the evaporation has to be at 10°F the
absolute pressure should be brought down to 31.29 psi. The pressures indicated
above   are   the   saturation   pressures    corresponding   to   the   respective
temperatures. This pressure reduction is brought about by the use of what is
known as an expansion valve. The expansion valve is just a needle valve which
throttles the flow of liquid refrigerant thereby bringing about a pressure drop.
This expansion valve can also be hand operated, automatic or thermostatic.
Liquid admitted into the evaporator now needs heat for evaporation. This head is
supplied by the air which is flowing over the evaporator coil. In the process, the
air gets cooled and the liquid refrigerant evaporates.

Compressor
Now if you have got to ensure continuous evaporation at the same temperature,
it is very vital that the vapour evaporating in the coil is removed from it is as
rapidly as it is evaporating. Unless this is done the evaporated vapour will build
up a pressure in the coil which would keep on rising. Any such rise in pressure
will naturally raise the evaporating temperature also since, the evaporation
temperature is higher and higher as the pressure increases. Removal of the
evaporator vapour is achieved by connecting the outlet of the evaporator to the
suction side of a refrigerating compressor.


Of course, the compressor has got to be sized so that it has got a volumetric rate
of displacement which matches with the evaporation rate. Thus the evaporation
pressure is maintained as steady and the liquid fed through the expansion valve
continues to evaporate at a steady temperature so long as heat for evaporation is
available at an equally steady rate from the air flowing over.


Condenser
The compressor compresses the vapour and discharges the same into the
condenser. It is in this condenser that the high pressure hot gas delivered by the
compressor has to be condensed. For the purpose of condensing the gas it is
necessary that heat is removed from the hot gas.          This removal of heat is
achieved by again creating an air flow over the condenser coil or water flow if
water cooled condensers are used.        The heat given up by the refrigerant is
picked up by the air or water. The hot gas which has given up the heat naturally
condenses into liquid form at the same pressure.         Now let us see how the
pressure built-up in the condenser coil it has got certain definite capacity to
transfer heat from within to the outside air or water for each degree of
temperature difference. We also know that for each 1b of refrigerant which has
got to be condensed into liquid form a definite capacity to transfer heat from
within to the outside air or water of refrigerant which has got to be condensed
into liquid form, a definite amount of heat, namely, the latent heat of
condensation has to be removed. If in a refrigeration system the F-22 circulation
is say, 5 1bs/minute, then the amount of heat which has got to be removed for
condensing this refrigerant gas is 5 x latent heat.          This means that the
temperature difference between the hot refrigerant gas within the condenser and
the air or water flowing over it should be such that the total amount of heat
transferred through the walls of the condenser tubes just balances with the total
amount of heat which has got to be removed. The condensation rate would,
therefore, automatically balance with the compressor discharge rate as soon as
the temperature difference has been built up.




The pressure inside the condenser also which initially starts building up will attain
a steady level when the corresponding saturation temperature results in the
desired temperature difference for creating the desired heat transfer rate. This is
called the condesing temperature of the system. It is obvious that if you use a
small size condenser the temperature difference has necessarily to be higher
and hence the condensing temperature and the corresponding pressure will also
have to be relatively higher.


Receiver
A receiver is a pressure vessel which is used as a storage tank for the
condensed liquid refrigerant leaving the condenser. It is from this receiver that
liquid is tapped and sent to the evaporator through the throttling device or
expansion valve. It is not on all systems that we have a separate liquid receiver.
In the case of systems having water cooled condensers, the shell of the
condenser itself serves as a storage vessel for the liquid refrigerant. In smaller
systems even with air cooled condensers, it is possible to dispense with the use
of a receiver if care is taken to charge the system with the correct amount of
refrigerant.


In order that the various components forming part of a refrigeration system can
be designed, it is necessary to make a more scientific study of the entire
operations. For this purpose we have to know the complete properties of the
refrigerant concerned when it is at gaseous form and also in liquid form. The
properties of each refrigerant are shown in what is called a Pressure Enthalpy
Diagram.
4.0 ELEMENTS OF
PSYCHROMETRY
ELEMENTS OF PSYCHROMETRY


Psychrometry
Since air conditioning, by its very name means treating air with a view to altering
its temperature and moisture content with the use of refrigeration, it is necessary
that we should know how exactly air would behave when it is subjected to
cooling, heating, humidifying or dehumidifying processes. For this purpose, it is
necessary to study the property of air at normal atmospheric pressure in so far as
it concerns air conditioning. Such a study is what is called psychrometry.


For the study of psychrometry, a chart has been devised, which is called
Psychrometric Chart.       We will just now see what the various lines of the
psychrometric chart are.


Dry Bulb Lines
Any vertical line is a line of constant temperature. Condition of air represented
by any point on this line will have the temperature corresponding to this vertical
line. These lines are called Dry Bulb Lines. By dry bulb what we really mean is
dry bulb temperature i.e., the temperature as recorded by a thermometer which is
dry.


Moisture Content
Each horizontal line in the chart is a line of constant moisture content. The
condition of air represented by any point on this line will all have the same
moisture content as applicable to this line.        Through any point on the
psychrometric chart you can always draw a horizontal line and a vertical line. Air
represented by this point has, therefore, a dry bulb temperature corresponding to
the vertical line and moisture content corresponding to the horizontal line. It is
easy to see that air at any given temperature can have varying moisture content.
Likewise, air containing any given moisture content can have varying
temperature as well.


Saturation Line
The curved line on the extreme left-hand side of the chart is what is called the
saturation line. Condition of air represented by any point on this line is said to be
saturated air, which means that the air is having the maximum possible moisture
content in it. It cannot hold any further moisture.


Wet Bulb Lines
There are number of parallel slant lines which are called wet bulb lines. By wet
bulb temperature what we really mean is the temperature of the air as recorded
by a thermometer with a wet wick on its bulb. You will also understand for the
moment that the air having a certain wet bulb temperature will have a definite
heat content although its dry bulb temperature may be anything.


Relative Humidity Lines
When the air contains its maximum moisture content, we call it saturated air;
when it contains anything less than this maximum limit then it is not saturated air
because it has still capacity to have more moisture. We therefore, say that such
air is, say 50% saturated or 60% saturated. Another term used to denote the
percentage saturation is “relative humidity”. Thus it is one and the same thing
whether you say air is 50% saturated or air has got a relative humidity of 50%.
Note that we have used the word “approximately” because the strict scientific
definition of relative humidity is not nearly the comparison of moisture content. In
fact relative humidity is defined as the ratio of the partial vapour pressure in the
air to the maximum vapour pressure that saturated air will have at this
temperature. However, for all practical purpose, this is equal to the ratio of the
actual moisture content present to the maximum moisture it can hold at that
temperature.
Dew Point
We have seen that at any given temperature air has a maximum limit of moisture
holding capacity when it is said to be saturated.          For example from the
psychrometric chart we can see that 70°F saturated air can hold a maximum of
110 grains per 1b of dry air. All temperatures above 70°F, air with the same
moisture content will be, say 80%, 90% etc., saturated depending on what its dry
bulb temperature would be. If air with this moisture content and at temperature
higher than 70° is cooled down, then its condition will move along the horizontal
110 grains line, till the temperature falls to 70°F. 70°F and 110 grains / 1b as we
have seen corresponds to saturated condition. This is the temperature at which
air with 110 grains of moisture / 1b will begin to shed its moisture by condensing
if you continue to cool the air. This temperature is called the DEW POINT of the
air. Needless to add, it is the moisture content which determines the dew point.
All you have to do is to move horizontally on the psychrometric chart and read
the temperature where you intersect the saturation line.

Enthalpy
We were just now referring to the wet bulb as line of constant heat content of air.
Enthalpy is just another term used in place of “heat content”. Of course, the
enthalpies represented here are all values for samples of air containing 1 lb of
dry air.

The amount of moisture content in the air is generally expressed in terms of
grains of moisture per 1b of dry air. For your information, grain is a weight
measure. 7000 grains make 1 lb. When we say that the moisture content is 120
grains, what we mean is there is 1 lb, of dry air containing 120 grains of moisture.
The total weight of this moist air would, therefore, by 1 + 120/7000 lbs = 1.0171
lb. At any temperature there is a limit to the maximum moisture holding capacity
of air. This limit is something definite and does not alter except under different
atmospheric pressures. At higher and higher atmospheric pressure the moisture
holding capacity at any given temperature becomes less and less.
At any temperature when air contains the maximum amount of moisture it is said
to be saturated air. When air has attained saturation at any given temperature, it
is impossible to add any further moisture in vapour form.
Short Definitions


Dry-bulb Temperature
The temperature of air as registered by on ordinary temperature.


Wet-bulb Temperature
The temperature registered by a thermometer whose bulb is covered by a wetted
wick and exposed to a current of rapidly moving air.


Dewpoint Temperature
The temperature at which condensation of moisture begins when the air is
cooled.


Relative Humidity
Ratio of the actual water vapor pressure of the air to the saturated water vapor
pressure of the air at the same temperature.


Specific Humidity or Moisture Content
The weight of water vapor in grains or pounds of moisture per pound of dry air.


Enthalpy
A thermal property indicating the quantity of heat in the air above an arbitrary
datum. In BTU per pound of dry air. The datum for dry air is 0 °F and, for
moisture content, 32 °F water.


Enthalpy Deviation
Enthalpy indicated above, for any given condition, is the enthalpy of saturation. It
should be corrected by the enthalpy deviation due to the air not being in the
saturated state. Enthalpy deviations in BTU per pound of dry air. Enthalpy
deviation is applied where extreme accuracy is required : however, on normal air
conditioning estimates it is omitted.




Specific Volume
The cubic feet of the mixture per pound of dry air.


Sensible Heat Factor
The ratio of sensible to total heat.


Alignment Circle
Located at 80 °F db and 50% rh and used in conjunction with the sensible heat
factor to plot the various air conditioning process lines.


Pounds of Dry Air
The basis for all pyschrometric calculations, remains constant during all
psychrometric processes. The dry-bulb, wet-bulb, and dewpoint temperatures
and the relative humidity are so related that if two properties are known, all other
properties shown may then be determined. When air is saturated,           dry-bulb,
wet-bulb, and dewpoint temperatures are all equal.
5.0 APPLIED PSYCHROMETRY
APPLIED PSYCHROMETRY


Let us now see how the various air conditioning procedures will be represented
on a Psychrometric chart.


1.    Sensible Heating
      By sensible heating, we mean adding heat to air whereby the entire heat
      added goes to raise the temperature of the air. It is obvious that in such a
      process there is no change in the moisture content of the air. In other
      words, during sensible heating process the air retains a constant moisture
      content and accordingly, its condition will move on a horizontal line
      corresponding to its constant moisture content. Since heat is being added
      during such process, its enthalpy also rises. Therefore, during the heating
      process the wet bulb temperature of the air will also rise, because as we
      have already seen, it is the wet bulb temperature lines which are identified
      as constant enthalpy lines.


2.    Addition of Moisture
      Likewise, if moisture is somehow or the other added to the air without
      adding any sensible heat, the process would be represented by a vertical
      line corresponding to its dry bulb temperature. In this case also, since the
      moisture added carries with it the latent heat of vaporization of water, the
      heat content of the air also rises and hence its wet bulb temperature also
      rises.


3.    Heating and Humidifying
      If heat is added so that part of it goes to raise the temperature and the
      remaining part goes to vaporize water and add it to the air, such a process
      is called heating and humidifying.
4.   Cooling and Dehumidifying
     Cooling and dehumidifying is just the reverse of heating and humidifying.
     On a psychrometric chart such a process will also be represented in the
     same manner as for heating and humidifying, the only difference being the
     arrows representing the direction of movement of conditions would be just
     reverse.


5.   Evaporative Cooling
     Evaporative cooling is the process by which air is simply subjected to a
     spray of re-circulated water just as in the experiment described earlier, the
     only difference being, we do not provide an infinite number of spray banks
     as in the experiment. The chamber with the banks of spray is called an
     Air Washer. Air so subjected would of course tend to get saturated and
     change out at a temperature equal to its wet bulb temperature. However,
     since we do not provide adequate number of spray banks to completely
     humidify, the air comes out not at 100% humidity but somewhat lower than
     that. Needless to say, since this process is adiabatic, the air has constant
     enthalpy throughout the process and hence its condition moves along the
     line representing its wet bulb temperature.


     Psychrometry as Applied to Airconditioning
     It now remains for us to study psychrometry as applied to air conditioning
     process.   We will only see for the present what the heat load form is like
     and also the various sections into which it is divided. It is only after you
     understand this that you will be in a better position to understand
     psychrometry as applied to air conditioning.
When a space is maintained at a temperature below the atmospheric
temperature surrounding the space, then there is a transfer of heat from
outside into the conditioned area, which tends to raise the inside
temperature unless this heat is removed as fast as it enters this space.
Then you have heat or any other appliances which may be in the space.
All such heat which are either transmitted into the room or generated from
within due to occupants and appliances which tend to raise the inside
temperature are termed as room sensible heat. In the like manner, the
occupants within the room also release moisture from their body into the
room. There may be other sources inside the conditioned area which add
up more moisture into the atmosphere. If the space has not only to be
maintained at a particular temperature, but also to be held within certain
limits of relative humidity, then it is necessary that such moisture gain
inside the room should also be removed just as rapidly. By removal of
moisture what we have really mean is condensing this moisture from the
air and discarding it outside. For condensing the moisture, you have to
remove the latent heat of vaporisation of water. So instead of stating that
we have got to remove moisture gained, we state this in terms of the
corresponding total amount of latent heat to be removed for condensing
that quantity of moisture gained. This is also expressed in terms of heat
units viz. BTU. So the heat to be removed per hour for condensing the
moisture is termed as room latent heat. So what we really mean by heat
load is the room sensible heat and the room latent heat that are to be
removed from within the space at a calculated rate to effect the gain of
sensible and latent heats into the conditioned space.
In heat load, there is one more source which contributes to the room
sensible and room latent heat loads. This is on account of infiltration of
fresh air directly into the conditioned space and bypass of certain amount
of fresh air that is normally taken into the system through the air handling
apparatus. The form is designed so that the room sensible heat, latent
heat and the additional load due to outside air, not forming part of room
load are all calculated separately.

Here, we have used the term “Bypass”.          You must understand what
exactly the meaning of the term “Bypass” is. For removing sensible heat
and latent heat at the same rate at which they are being gained within the
conditioned space, conditioned air is admitted within this space at a
predetermined temperature and humidity condition such that this air would
absorb the room sensible and room latent heat loads and in the process
attain a final condition which is exactly equal to the condition to be
maintained in the room. This is achieved by continuously drawing from
within the room certain amount of air and adding to it a certain percentage
of fresh air for ventilation and cooling and dehumidifying this mixture in a
cooling coil.   It is this treated air, which is supplied back into the
conditioned area. On account of some free passages in between the fins
and tubes a small percentage of the air comes out on the other side of the
coil without undergoing any change. It is this, which we terms as bypass
of air. As far as the portion of the air, which is actually re-circulated from
the room is concerned, bypass will have no influence on the ultimate
result. It only means that some air has been withdrawn from the room and
just put back into the same room without any change in its condition either
upward or downward. But, what really influences is the bypass of the
fresh air, which is also passed through the cooling coil along with the re-
circulated air. Since this outside air is at a much higher temperature and
humidity conditions than the conditioned space, entry of such bypass air
would tend to upset the room conditions unless this bypass air is also
brought down to the room condition. The general formula for arriving at
the exact air quantity is:


cfm =                          =


However, you must realise it is not merely the selection of the condition of
the supply air that is important. We have also to consider how air can be
cooled down to the selected condition in a cooling apparatus. In a cooling
coil in which air is cooled, there is no practical means of ensuring that the
air leaving the coil would be at the exact temperature and humidity
condition corresponding any condition selected by us on the sensible heat
factor line. However, there is one temperature and humidity condition
which is very easy to keep under control. This is the condition which lies
not only on the sensible heat factor line but also on the saturation line on
the psychrometric chart. In other words, if the sensible heat factor line is
extended till it meets the saturation line, then the condition represented by
the point of intersection of these two lines is the one condition which can
be under our control. This temperature is called apparatus dew point.


Bypass Factor
The problem becomes a bit more complicated because in every cooling
coil there is always a small percentage of the total cfm which escapes
totally untreated. When outside air taken into the system bypasses the
coil, it will tend to raise the room temperature and humidity conditions
above the desired level.       It is, therefore, necessary to take into
consideration the effect of bypass right at the time of making the heat load
calculations.
PSYCHROMETRIC FORMULAS

A.   AIR MIXING EQUATIONS (Outdoor and Return Air)


     tm =                                            (1)



     hm =                                            (2)



     Wm =                                            (3)




B.   COOLING LOAD EQUATIONS
     ERSH          =   RSH + (BF) (OASH) + RSHS*     (4)
     ERLH          =   RLH + (BF) (OALH) + RLHS*     (5)
     ERTH          =   ERLH + ERSH                   (6)
     TSH           =   RSH + OASH + RSHS*            (7)
     TLH           =   RLH + OALH + RLHS*            (8)
     GTH           =   TSH + TLH + GLHS*             (9)
     RSH           =   1.08 x cfmsa x (trm - tsa)    (10)

     RLH           =   0.68 x cfmsa x (Wrm - Wsa)    (11)

     RTH           =   4.45 x cfmsa x (hrm - hsa)    (12)

     RTH           =   RSH + RLH                     (13)
     OASH          =   1.08 x cfmoa x (toa - trm)    (14)

     OALH          =   0.68 x cfmoa x (Woa - Wrm)    (15)

     OATH          =   4.45 x cfmoa x (hoa - hrm)    (16)
OATH          =    OASH + OALH                         (17)
     (BF) (OATH)   =    (BF) (OASH) + (BF) (OALH)           (18)
     ERSH          =    1.08 x cfmda x (trm - tadp)(1-BF)   (19)

     ERLH          =    0.68 x cfmda x (Wrm - Wadp)(1-BF)   (20)

     ERTH          =    4.45 x cfmda x (hrm - hadp)(1-BF)   (21)

     TSH           =    1.08 x cfmda x (tedb - tldp) **     (22)

     TLH           =    0.68 x cfmda x (Wea - Wta) **       (23)

     GTH           =    4.45 x cfmda x (hea - hta) **       (24)


C.   SENSIBLE HEAT FACTOR EQUATIONS


     RSHF =               =                                 (25)




     ESHF =                    =                            (26)




     GSHF =                =                                (27)


D.   BYPASS FACTOR EQUATIONS


     BF     =          ;(1-BF) =                            (28)




     BF     =            ;(1-BF) =                          (29)




     BF     =          ;(1-BF) =                            (30)
E.   TEMPERATURE EQUATIONS AT APPARATUS


     tedb ** =                                                 (31)


     tldb   =     tadp + BF (tedb – tadp)                      (32)

     tewb and tlwb correspond to the calculated values of hea and hla on the
     psychrometric chart.


     hea ** =                                                  (33)


     hta    =     hadp + BF (hea – hadp)                (34)


F.   TEMPERATURE EQUATIONS FOR SUPPLY AIR


     tsa    = t4m –                                            (35)


G.   AIR QUANTITY EQUATIONS


     cfmda =                                                   (36)




     cfmda =                                                   (37)




     cfmda =                                                   (38)




     cfmda =                                                   (39)
cfmda =                                                      (40)




     cfmda =                                                      (41)




     cfmsa =                                                      (42)




     cfmsa =                                                      (43)




     cfmsa =                                                      (44)




     cfmba = cfmsa - cfmda                                        (45)


     Note : cfmda will be less than cfmsa only when air is physically bypassed
            around the conditioning apparatus.


     cfmsa = cfmoa + cfmra                                        (46)


H.   DERIVATION OF AIR CONSTANTS


     1.08   = .224 X


     Where .224 =        Specific heat of moist air at 70 F db and 50% rh,
                         Btu/(deg F) (lb dry air)
            60     =     min/hr
            13.5   =     Specific volume of moist air at 70 F db and 50% rh
.68    =              X


       where     60 = min/hr
               13.5 = Specific volume of moist air at 70 F db and 50% rh


               1076 = Average heat removal required to condensate one
                          pound of water vapor from the room air.
               7000 = Grains per pound


4.45   =


       where     60 = min/hr
               13.5   = Specific volume of moist air at 70 F db and 50% rh.
6.0 HEAT LOAD ESTIMATION
HEAT LOAD ESTIMATION
Introduction
The primary objective is to provide a convenient consistent, and accurate method
of calculating heating and cooling loads and to enable the designer to select
systems that meet the requirements for efficient energy utilization and are also
responsive to environmental needs.


The ability to estimate loads more accurately due to changes in the calculation
procedure provides a lessened margin of error.            Therefore, it becomes
increasingly important to survey and check more carefully the load sources, each
item in the load and the effects of the system type on the load. This tightening up
on the hidden safety factors occurs for a number of reasons. There is greater
emphasis, by standards and codes, on sizing equipment closer to the expected
loads, as determined by outside design weather conditions. Also the suggested
indoor design temperatures are now usually 75 °F for cooling and 72 °F for
heating. Installed lighting levels are being reduced and the calculations are using
lighting loads closer to the actual loads. All of these factors require that the
designer introduce any margin of safety by a positive action, rather than rely on
an assumed hidden margin.


Purpose of Load Calculations
Load calculations can be used to accomplish one or more of the following
objectives :
   h) Provide information for equipment selection and HVAC system design
   i) Provide data for evaluation of the optimum possibilities for load reduction.
   j) Permit analysis of partial loads as required for system design, operation
       and control


These objectives can be obtained not only by making accurate load calculations
but also by understanding the basis for the loads. There a brief description of
cooling and heating loads are included.


Principles of Cooling Loads
In airconditioning design there are three distinct but related heat flow rates, each
of which varies which varies with time:
   k) Heat Gain or Loss
   l) Cooling load or Heating Load
   m) Heat Extraction or Heat Addition Rate


Heat Gain, or perhaps more correctly, instantaneous rate of heat gain, is the rate
at which heat enters or is generated within a space at a given instant of time.
There are two ways that heat gain is classified. They are the manner in which
heat enters the space and the type of heat gain.


The manner in which a load source enters a space is indicated as follows:
   n) Solar radiation through transparent surfaces such as windows
   o) Heat conduction through exterior walls and roofs
   p) Heat conduction through interior partitions ceilings and floors
   q) Heat generated within the space by occupants, lights, appliances,
       equipment and processes
   r) Loads as a result of ventilation and infiltration of outdoor air
   s) Other miscellaneous heat gains


The types of heat gain are sensible and latent. Proper selection of cooling and
humidifying equipment is made by determining whether the heat gain is sensible
or latent. Sensible heat gain is the direct addition of heat to an enclosure, apart
from any change in the moisture content, by any or all of the mechanisms of
conduction, convection and radiation. When moisture is added to the space, for
example, by vapor emitted by the occupants, there is an energy quantity
associated with that moisture which must be accounted for.
If a constant humidity ratio is to be maintained in the enclosure, then water vapor
must be condensed out in the cooling apparatus at a rate equal to its rate of
addition in the space. The amount of energy required to do this is essentially
equal to the product of the rate of condensation per hour and the latent heat of
condensation. This product is called the latent heat gain.


As a further example, the infiltration of outdoor air with a high dry-bulb
temperature and a high humidity ratio, and the corresponding escape of room air
at a lower dry-bulb temperature and a lower humidity ratio, would increase both
the sensible heat gain and the latent heat gain of the space.


The proper design of an airconditioning system requires the determination of the
sensible heat gain in the space, the latent heat gain in the space, and a value for
the total load, sensible plus latent, of the outdoor air used for ventilation.


The sensible cooling load is defined as the rate at which heat must be removed
from the space to maintain the room air temperature at a constant value. The
summation of all instantaneous sensible heat gains at a specific time does not
necessarily equal the sensible cooling load for the space at that time. The latent
load however is essentially an instantaneous cooling load.           That part of the
sensible heat gain which occur by radiation is partially absorbed by the surfaces
and contents of the space and is not felt by the room air until sometimes later.
The radiant energy must first be absorbed by the surface that enclose the space
such as walls and floor and by furniture and other objects. As soon as these
surfaces and objects become warmer than the air some heat will be transferred
to the air in the room by convection. The heat storage capacity of the building
components and item such as walls, floors and furniture governs the rate at
which their surface temperatures increase for a given radiant input. Thus, the
interior heat storage capacity governs the relationship between the radiant
portion of the sensible heat gain and how it contributes to the cooling load. The
thermal storage effect can be important in determining the cooling equipment
capacity.


The actual total cooling load is generally less than the peak total instantaneous
heat gain thus requiring smaller equipment than would be indicated by the heat
gain. If the design is based on the instantaneous heat gain, the rest of the
system may be oversized as well.


Heat extraction rate is the rate at which heat is removed from the conditioned
space.      Normal control systems operating in conjunction with the intermittent
operation of the cooling equipment will cause a “swing” in room temperature.
There, the room air temperature is constant only at those rare times when the
heat extraction rate equals the cooling load. Consequently, the computation of
the heat extraction rate gives a more realistic value of energy removal at the
cooling equipment than does just the instantaneous value of the cooling load
provided the control system is simulated properly. The determination of the heat
extraction rate must include the characteristics of the cooling equipment and the
operating schedule of thee equipment, in addition to the various sources of
cooling load.


If the equipment is operated some what longer before and after the peak load
periods, and / or the temperature in the space is allowed to rise a few degrees at
the peak periods during the cooling operation (floating temperature), a reduction
in the design equipment capacity my be made. A smaller system operating for
longer periods at times of peak loads will produce a lower first cost to the
customer with commensurate lower demand charges and lower operating costs.
Generally, equipment sized to more nearly meet the cooling requirements result
in a more efficient, better operating system particularly when is at a partially
loaded condition.


Usually a fraction of the sensible heat gain does not appear a cooling load, but
instead is shifted to the surroundings. The fraction Fc depends upon the thermal
conductance between the room air and the surroundings.                  It may be also
considered as a adjustment factor which results when the load components as
superimposed.


The adjustment factor, Fc is calculated by the following equation.


Fc      =      1 - 0.02 KT


Where KT the unit length conductance between the room air as surroundings in
Btu / (hr. ft2 F), is given by


KT      =      1/LF (UWAW + UowAow + UcAc)


Where
LF      =      Length of the exterior walls of the room, ft.


U       =      U-value of room enclosure element (subscript w for window, ow
               for outside wall and c for corridor), Btu (hr. ft2 F)


A       =      Area of the specific element


If the cooling load component has already been obtained by the technique used
in this manual, multiply that result by the calculated Fc factor.


The adjustment factor should be used only for individual small spaces or zones.
It is not to be used for block loads nor for industrial applications.


Diversity of Cooling Loads
Diverting of cooling load results from not using part of the load on a design day.
Therefore diversity factors are factors of usage and are applied to the
refrigeration capacity of large airconditioning systems. These factors vary with
location, type, and size of applicant and are based entirely on the judgment and
experience of the engineer.
Generally, diversity factors can be applied on loads from people and lights; there
is neither 100% occupancy nor total lighting at the time of such other peak loads
as peak solar and transmission loads. The reductions in cooling loads from
nonuse are real and should be accounted for.


In addition to the factors for people are lights a factor should also be applied to
the machinery load in industrial buildings. For instance, electric motors may
operate at a continuous overload, or may operate continuously at less than the
rate capacity or may operate intermittently. It is advisable to measure the power
input whenever possible; this will provide a diversity factor. It is also possible to
determine a diversity factor for a large existing building by reviewing the
maximum electrical demand and monthly energy consumption obtained from the
utility bills.


Principles and Procedures for Calculating Heating Load
The peak heating requirements may occur either at night during unoccupied
hours or in the morning pickup period following a shutdown. Therefore a number
of calculations are helpful in making a proper equipment selection and system
design.


Information Required (Input)
Before a cooling or heating load can be properly estimated a complete survey
must be made of the physical data. The more exact the information that can be
obtained about space characteristics, heat load sources, location of equipment
and services, weather data, etc. the more accurate will be the load estimate.


Required Input - External Loads - Cooling
For calculation of the outdoor loads the input information should include:
    t) Orientation and dimensions of building components.
    u) Construction materials for roof, walls, ceiling, interior partitions, floors and
fenestration
      v) Size and use of space to be conditioned
      w) Surrounding conditions outdoors and in adjoining spaces


Required Input - Heating Load
The input for calculation of heating load is essentially the same as that for the
cooling load. However, it may not be necessary to calculate the internal sources
and solar heat gain.


In heat load estimation we compute

a.       Room sensible and latent heat gains due to transmission, sunlight,
         occupancy and other internal sources of heat.
b.       Grand total heat comprising total room load under (1) plus additional loads
         due to outside air intake, heat gains in return air ducts, in chilled water
         distribution systems, pumping horse power load, etc.

Room load estimation under (a) is required for computing the condition and
quantity of supply air while the grand total heat under (b) is required for
terminating the total capacity of the cooling system.


In this discussion, we will confine ourselves to transmission gains and related
subjects only. There are certain similarities between heat transmission through
barriers and electric current transmission through conductors. We will use this
similarly wherever required for better understanding of the subject. The well
known formula relating to transmission of electric current is:


I =


Where “I” = current in Amperes, “V” = Voltage & “R”, the Resistance of the
conductor. In this formula, if (I) / (R) is considered as the conductance of the
conductor, say “C”, then the formula can be rewritten as:
I = VxC


For transmission of heat through a barrier, the motive force corresponding to “V”
is temperature difference between the two sides of the barrier. The formula for
rate of heat transmission per hour H is:
H = A x U x (T)

Where T is the temperature difference in °F and A is the area of the barrier in
sq.ft. and U is the overall heat transmission coefficient expressed in
BTU/Hr/Sq.ft/°F temperature difference. The product (AxU) corresponds to the
conductance “C” of the electric conductor.

Thermal conductivity of any material is the heat transmitted through the material
expressed as BTU/Hr/Sq.ft/Inch thickness/°F temperature difference and is
referred to by the symbol “K”. It K is the conductivity of the material, then 1/K is
the resistance of the material of 1 sq.ft. cross section and 1” thickness. If the
thickness “t” inches, the resistance becomes (t) / (K) per sq.ft.

In electrical system, resistance connected in series are added to find the total
resistance.

Similarly, if a barrier is made up of several materials, the individual resistances of
the components have to be added to arrive at the total barrier resistance. If a
barrier is made up of, say, three materials having thermal conductivities K1, K2 &
K3, the total thermal resistance of the barrier is:

t1/K1 + t2/K2 + t3/K3
Where t1, t2 & t3 are the thicknesses of the barriers.

Film Coefficient
In addition to the resistance of the various components of a barrier, we have to
consider one more resistance offered by a film of air (or fluid if the barrier is in a
fluid) which clings on to the barrier surfaces. This resistance is more when the
air is still and is relatively less when there is wind velocity.        Like thermal
conductivity, the heat transmission capacity of a film is expressed as the rate of
heat of transfer in BTU/Hr/Sq.ft/°F temperature difference (Note that this differs
from thermal conductivity in the sense it is not related to any film thickness as in
the case of materials). This is called the film coefficient and is expressed by the
symbol “f”. The reciprocal of “f” is the thermal resistance of the film. “f1” denotes
the film coefficient on the interior surface of the barrier and “f0” denotes the film
coefficient on the exterior surface of the barrier. The resistance of the complete
barrier is:

1/f1 + t1/K1 + t2/K2 + t3/K3 + 1/f0

If “U” is the overall heat transmission of the barrier in BTU/Hr/Sq.ft./°F, then 1/0 is
the overall thermal resistance of the barrier.

1/U = 1/f1 + t1/K1 + t2/K2 + t3/K3 + 1/f0
U   = 1/(1/f1 + t1/K1 + t2/K2 + t3/K3 + 1/f0)

Storage Effect
Suppose T0 is the temperatures on both sides of the barrier. There will be no
heat transmission through the barrier and the temperatures at all points within the
barrier will also be the same. There is, therefore, no temperature gradient. Now
suppose the temperature on one side of the barrier is raised from T0 to T7, do
you think that heat transmission through the barrier will commence immediately?
No, since all points within the barrier is at the same temperature, no heat can
flow through any interior section. The first thing that happens is the outermost
layer of the barrier absorbs the heat from the outside and rises in temperature.
Heat then flows over to the next layer of the barrier because of the temperature
difference between the first and second layers. The second layer also will first
rise in temperature before heat begins to flow over to the third layer.          Thus
progressively all the layers within the barrier rise in temperature thereby
establishing the total temperature gradient from one side to the other side of the
barrier. It is only after the complete gradient has been established that heat will
begin to flow to the other side of the barrier. The temperature at various points
within the barrier will now be as determined by the gradient.


Attic Spaces
Whenever a false ceiling is provided in a room, the space enclosed between the
false ceiling and the concrete ceiling is called ATTIC SPACE. If the attic space is
not ventilated the entire space within the attic will assume an intermediate
temperature which will be more than the room temperature and less than the
outside temperature. This temperature can be worked out as follows:


Ag     =      area of the concrete ceiling
A1     =      area of the false ceiling
U0     =      “U” factor of the concrete ceiling
Uf     =      “U” factor of the false ceiling
T2     =      Outside temperature
T1     =      Inside temperature
T      =      Temperature of the attic space


When steady heat transmission from outside to inside takes place through the
attic space, then the rate of flow of heat from outside into the attic space is equal
to the rate of flow of heat from the attic space into the room, i.e.,


Ac.Uc.(T2 – T) = Af.Uf.(T – T1)


“T” can therefore be calculated from this equation. After “T” has been worked
out, the transmission load into the room from the ceiling can be worked out by
substituting the value of “T” in the above equation.


Solar Gain
Solar Gain, as the name implies, comes from direct sunlight. There are two
kinds of solar gains:
a.   Radiation from sun which directly enters the conditioned space through
     glass and absorbed by objects in the room and then by the air within the
     room. The effect of such gain into the space is felt almost immediate.


     The amount of radiation for various exposures and time of the day and
     year are given in tables for the various latitudes on the earth. Depending
     on the type of glass, about 5 to 6% of the radiation is reflected while the
     rest pass into the room. Solar gain is not confined merely to the side
     which directly faces the sun. You get solar heat even from other sides
     through glasses, but to a much smaller degree. This is diffused radiation.


b.   Solar & Transmission Gain
     This is due to transmission through sunlit walls whose temperature rises
     above the ambient temperature due to absorption of direct radiation and
     hence causes a larger temperature differential than the ambient
     temperature. The equivalent temperature difference that is to be taken
     are given in tables, taking into consideration the exposure, sun time and
     storage effect.


c.   Transmission Gain through Glass & Partition
     In addition to solar gain through glass, you have also to work out
     transmission      gain   through   glass   due   to   temperature   difference.
     Transmission through partitions between conditioned and non-conditioned
     areas are worked out on the basis of actual temperature difference. No
     storage effect apply for these cases.


d.   Internal Load
     This comprises load from:
        x) Occupancy: The sensible/latent heat gains from people are given
            in tables, based on the nature of their activities in the room.
        y) Lights: Lighting is generally specified in terms of watts per sq.ft.
The total watt has to be converted into BTU/Hr by multiplying by
             conversion factors.
         z) Appliances: Electrical, gas burners, steam generation, etc.
         aa)Electric   Motors:      Applies   generally    in   some of industrial
             applications.     This load will have to be properly analysed by
             discussion with user and appropriate diversity factors should be
             applied for estimating the actual load. Convert the HP into BTU/Hr.
We shall now briefly lay down the procedure for heat load estimating with
explanations wherever required.




1.    Collect architect’s drawings for the building giving all details and
      dimensions of walls, floors, windows, etc.          If such drawings are not
      available, survey the place and get the particulars.

2.    For every application, there are certain things which the ultimate user has
      to specify. These are:

       bb)Temperature & humidity conditions to be maintained inside the space
          and tolerance.
       cc) Occupancy – i.e. maximum no. of people likely to occupy the space
          and the nature of their activity.
       dd)Lighting load and other internal source of heat generation.
       ee)Period of operation – e.g. 8 a.m. to 7 p.m. or 10 a.m. to 8 p.m. etc.
       ff) For industrial application you require also the HP load in the
          conditioned space and diversity factor thereon.
       gg)Minimum ventilation required.


3.    Outside Design Conditions
       hh)For comfort air conditioning application, use the mean maximum DB
          temperature & the WB temperature which occurs simultaneously with
the assumed DB.
     ii) For industrial applications where temperatures and humidities are to
         be maintained within very close tolerance through the year, tank the
         maximum DB and the simultaneously occurring WB temperature.


4.   For all applications make a second load estimate for monsoon conditions.


5.   For applications where the conditioned spaces are spread over very vast
     floor areas, divide the entire area into convenient zones and make load
     estimates.
6.   Occupancy - In certain applications a diversity factor may have to be used
     even in respect of occupancy.      Examples are: Office areas where a
     separate conference room is also provided. The conference room may be
     designed for a large number of people. But you must realize that it is
     mostly the people in the office who go into conferences and hence any
     occupancy in the conference room brings about an equal reduction in the
     occupancy in other areas of the office.
7.0 HEAT LOAD DATA SHEET &
   TYPICAL CALCULATION
TYPICAL DIVERSITY FACTORS FOR LARGE BUILDINGS
                   (APPLY TO REFRIGERATION CAPACITY)



                                     DIVERSITY FACTOR



                                 PEOPLE          LIGHTS


Office                          0.75 to 0.90    0.70 to 0.85


Apartment, Hotel                0.40 to 0.60    0.30 to 0.50


Department storage              0.80 to 0.90    0.90 to 1.0


Industrial                      0.85 to 0.95    0.80 to 0.90
Fresh air requirement   -     2.0 air changes / hr.
                                     or
                              10 CFM per person


Design conditions
a - indoor          -   70 °F ± 2 °F DBT ; 55% ± 5% RH
b - Outdoor         -   103 °F DBT ; 82 ° F WBT
U - FACTOR CALCULATIONS
a.     Exposed Walls




Total resistance RT         =   R o + X1 R 1 + X2 R 2 + X3 R 3 + R i


                            =   0.25 + 12.5 x 0.2 + 230 x 0.2 + 12.5 x 0.2 + 0.68
                                          25          25           25

                            =   2.97 hr. ft2. °F /BTU


Overall heat transfer Co-efficient
       =      1_        =         1_
              RT                2.97


       =      0.337 BTU / hr. ft2. °F


b.     Partitions
                   RT       =   R i + X1 R 1 + X2 R 2 + X3 R 3 + R i
=   0.68 + 12.5 x 0.2 + 230 x 0.2 + 12.5 x 0.2 + 0.68
                                          25          25           25

                            =   3.40 hr. ft2. °F /BTU


Overall heat transfer Co-efficient
       =      1_        =         1_
              RT                3.40


       =      0.294 BTU / hr. ft2. °F


c.     Roof exposed to sun




                   RT       =   R i + X1 R 1 + X2 R 2 + R i


                            =   0.25 + 150 x 0.2 + 50 x 4.0 + 0.92
                                          25          25

                            =   10.37 hr. ft2. °F /BTU


Overall heat transfer Co-efficient
       =      1_        =        1_
              RT                10.37
=   0.096 BTU / hr. ft2. °F
8.0 HEATING, VENTILATION &
AIRCONDITIONING SYSTEMS
HEATING, VENTILATION & AIRCONDITIONING SYSTEMS


A.   AIR CONDITIONING SYSTEMS


     Airconditioning is defined as the simultaneous control of temperature,
     humidity, quality and movement of air in a conditioned space or building.


     An air conditioning system is therefore, defined as an arrangement of
     equipment which will air condition a space or a building. Thus, a complete
     air conditioning system includes a means of refrigeration, one or more
     heat transfer units, air filters, a means of air transport and distribution, an
     arrangement for piping the refrigerant and heating medium, and controls
     to regulate the proper capacity and operation of these components.


     The items outlined above are considered to be the components of a
     complete air conditioning system.


     There has been a tendency by many designers to classify an air
     conditioning system by referring to one of its components. For example,
     the airconditioning system in a building may include a dual duct air
     transport arrangement to distribute the conditioned air and is then referred
     to as a dual duct system. This classification makes no reference to the
     type of refrigeration, the piping arrangement or the type of controls.


     For the purpose of classification, the following definitions will be used:


     An Airconditining unit is understood to consist of heat transfer surface
     for heating and cooling, a fan for air circulation, means of cleaning the air,
     a motor, a drive, and a casing.
A self-contained airconditioning unit is understood to be an
airconditioning unit that is complete with compressor, condenser, controls,
and a casing.


An air handling unit consist of a fan heat transfer surface, a motor, a
drive and a casing


A remote air handling unit or a remote air conditioning unit is a unit
located outside of the conditioned space which it serves.

The most common types of refrigeration machines, classified according to
their type of operation are (1) mechanical compression, (2) absorption and
(3) vacuum.

Apart from      the above types the airconditioning system are generally
clarified is to following categories:
1.     Window (room) airconditioners
2.     Split airconditioning units
3.     Packaged airconditioning units
4.     Centralised airconditioning plant - DX system
5.     Centralised airconditioning plant – chilled water system


The details of the above are further detailed in the subsequent pages.


The types of refrigeration machines which are further explained as under:


Mechanical Compression machines may be divided into reciprocating,
centrifugal, and rotary types.


The term “heat pump” is occasionally used to describe a refrigeration
machine.     However, a heat pump is a refrigeration cycle – either
reciprocating, rotary or centrifugal - in which the cooling effect as well as
the heat rejected is used to furnish cooling or heating to the air
conditioning units, either simultaneously or separately.


Reciprocating or rotary compressor can be used in systems that
circulate the refrigerant through remote direct expansion heat transfer
surfaces. Alternately they can be used in conjunction with a water chilling
heat exchanger, to produce chilled water for circulation through remote
heat transfer surfaces that cool and dehumidify the air.




Centrifugal refrigeration machines are generally not suitable for
circulating and expanding the liquid refrigerant in remote heat exchanges
surfaces. Centrifugal machines are therefore used only to chill water or
brine for circulation through remote heat exchange surfaces.




Absorption machine cycles are similarly to mechanical compression
machine cycles only to the extent that both cycles evaporate and
condense a refrigerant liquid. They differ in the mechanical compression
cycle use purely mechanical processes, while the absorption cycle uses
physiochemical processes to produce the refrigeration effect.




Vacuum refrigeration machines, such as steam jet and water vapor
units, are seldom used in modern airconditioning systems.
1.   Room Airconditioner
     This is the simplest form of an air conditioning system.             It has a
     hermetically sealed motor compressor assembly, an air cooled condenser
     coil, an evaporator coil, condenser fan and evaporator fan.          It has a
     capillary tube in place of an expansion valve for metering refrigerant flow
     to the evaporator. Room air conditioners are generally made of capacities
     ranging from 3/4 ton to 1-1/2 tons suitable for operation on 230 V, single
     phase, 50 cycles supply. It is completely factory assembled and can be
     straightaway plugged into power supply when installed.


     Application
     Generally used for small office rooms, shops and residential rooms where
     the where the load will generally be within 1-1/2 tons. Sometimes, these
     units are used in multiple for larger areas.


     Advantages
     The main advantage is that the unit can be switched ON and OFF as
     required.   Where multiple units are used, there is no fear of a total
     breakdown of air conditioning since it is most unlikely that all the units will
     breakdown simultaneously.


     Disadvantages
     The hermetically sealed compressor is susceptible to burn out when the
     supply voltage fluctuates widely and whenever such burnouts occur, the
     whole system has to be thoroughly cleaned before a new compressor can
     be fitted. The life of the unit is generally between 10 to 15 years only.
2.   Packages type air conditioner
     These are larger versions of Room Air Conditioners except that they are
     generally made with water-cooled condensers. They can also be made
     with air cooled condensers either built in with the package or for remote
     installation. They are generally made in capacities ranging from 5 to 10
     tons.   Units with water cooled condensers require condenser water
     circulating system and cooling tower. The units may also require external
     duct work for air distribution. This unit operates on 400 V, phase, 50
     cycles supply.

     Application
     These units are most ideal where the load is between 5 to 20 tons.
     Sometimes, they are also used for much larger loads by using more
     number of units interconnected on the supply air side.

     Advantages
     Installation and commissioning can be done in the shortest possible time
     since the field work involved only relates to condenser water piping, air
     distribution system and electrical wiring. When multiple units are used for
     larger areas, the number of units in operation can be varied according to
     the load requirement, thereby saving on power consumption.


     Disadvantages
     These units also have hermetically sealed motor compressor assemblies
     and hence have the same disadvantage as Room Air Conditioners.


3.   General plant - DX systems
     The system consists of an open type compressor ranging in capacity from
     5 tons to 120 tons operating on refrigerant 22. They are motor driven
     either through belt drive or direct coupling. They can also be driven by
     diesel engine, but then only by direct drive. Belt drive should not be used
when diesel engine is used.            They are generally with water-cooled
condensers even though they can also be built with air-cooled
condensers.


Application
The DX system of Central Plant is perhaps the most widely used system
for medium loads between 20 and 100 tons. It can be used for almost all
types of application.


Advantages
The DX system is perhaps the most efficient of all system from a thermo
dynamic point of view since the heat transfer is directly between the
conditioned air and the refrigerant. The open type compressors used for
these systems have built in capacity controls to take care of load
fluctuations. Plants of any capacity can be built with DX systems using
multiple compressors, condensers and evaporators.             Although it is
preferable to keep each compressor with its condenser and evaporator as
a single unit, these plants can also be built with interconnection between
them on the refrigerant side.         Such interconnections naturally provide
more flexibility in operation.


Disadvantages
DX systems should not be used where air distribution through duct work
has to be carried out from a central air handling unit to various zones
because of fire hazard.          Therefore, a single air handling unit should
necessarily be confined to a single zone. Where there are multiple zones
use of DX system is permissible only when separate DX plants are used
for each zone without any interconnection on the air distribution size.
Where the building condition has got number of floors one above the
other, DX systems could be considered only if it is possible to install
separate Central Plant for each floor. Of course, such decision would
involve installation of the plant on upper floors where vibration and other
     problems have to be effectively tackled in order to eliminate transmission
     of vibrations to the occupied zones.     Cost wise also, such individual
     systems in each floor may prove to be much higher.




4.   Central plant - Chilled Water System
     A central chilled water system is made up on one or more water chilling
     plants.   Each water chilling plant may be built with either one or two
     compressors to work with one or two chillers (DX chiller or shell and tube
     flooded chiller) and one or two water cooled condensers.       Each such
     water chilling unit is field assembled on structural framework with the
     necessary refrigerant pipes so as to make a compact assembly. Where
     such multiple water chilling units are used, they are generally
     interconnected on the water side both in the condenser circulating system
     and chilled water circulating system.


     Application
     Multiple water chilling units with reciprocating compressors are generally
     suitable for multistoreyed office buildings where the load is between 100
     and 300 tons. However, there is no bar against using more number of
     water chilling units with reciprocating compressors even for loads higher
     than 300 tons. For loads exceeding 300 tons. Water chilling units with
     centrifugal compressors would be preferable.


5.   Chilled Water for Process Cooling
     Advantages
     The best advantage of a chilling water system in that the Central Plant can
     be installed in as remote a location as desired from the conditioned areas.
     In fact, they can even be built in a remote plant room with chilled water
     piping either underground or overhead running to all the zones where air
handling units are installed. This system provides maximum flexibility in
     operation since the air handling units serving individual zones can be cut
     off from the chilled water circulating system whenever air conditioning is
     not required in any particular zone. Since each zone will have its own air
     handling unit, no interconnecting duct work will be required thereby
     eliminating all possibilities of fire spreading from one zone to another. In
     the case of large hotels, fan coil units in individual


     rooms can be switched off whenever the room is not occupied. Individual
     temperature controls can be provided for each zone or individual rooms by
     regulating the chilled water flow through the coil either thermostatically or
     manually.


     Disadvantages
     On application where the load is small, this system would prove very much
     costlier than the DX system. Another disadvantage is that since one more
     heat transfer medium viz. chilled water, has been introduced, the heat
     transfer is now from air to water and then from water to refrigerant. This
     naturally lowers the evaporating temperature as compared to a DX system
     for the same load. Hence the power consumption will be relatively higher
     than that for DX system.


6.   Air conditioning System for Operation Theatres
     It is desirable that a DX system is used for each Operation Theatre.
     However, in large hospitals, if there are several operation theatres located
     in various floors, there is no bar against using a central chilled water
     system, but exclusively for the operation theatre only. Each operation
     theatre must however have individual air treatment units with pre-filters on
     the air suction side of fan and supplementary microves filters on the air
     discharge side of the fan. For operation theatres no        re-circulation of
     room air is permitted. You should, therefore, estimate the heat load on the
basis of 100% fresh air.
7.   Screw Chillers
     Refer to figure showing single line diagram of refrigeration cycle for the
     above and for piping schematics.         Each vertical screw compressor
     discharges hot, high pressure gas through a discharge service valve (A)
     (or check valve in multiple compressor units) into the condenser, where it
     condenses outside tubes, rejecting heat to cooling tower water flowing
     inside the tubes.      The liquid refrigerant drains to the bottom of the
     condenser and exits into the economizer feed line.


     The refrigerant flows through the economizer feed ball valve (B), dropping
     its pressure, causing it to flash. It then flows into the flash economizer
     tank (C) which is at an intermediate pressure between condenser and
     evaporator, liquid is centrifugally separated from the flash gas and the
     liquid drains to the bottom of the tank, exits via the economizer drain line,
     and passes through the economizer drain ball valve (D). Both economizer
     ball valves are actuated by a modutrol motor (U) that adjusts flow to
     maintain an appropriate refrigerant level in the evaporator, determined by
     a liquid level float switch (V).


     From the drain line, liquid refrigerant flows into the flooded evaporator,
     where it boils, cooling the water flowing inside evaporator tubes. Vapor
     from the boiling refrigerant flows up the suction pipes through a shut-off
     valve (E) (optional), suction check valve (F) and suction filter (G) (inside
     compressor) into the compressor where it is compressed and starts cycle
     again.


     Vapor flows from the top of flash economizer into the compressor at the
     vapor injection port, which feeds it into the compressor part way through
     the compression process.           Check valve (H) prevents backflow at
     shutdown in multi compressor units. Al compressors operate in parallel on
a common evaporator and condenser.
8.   Ice Storage Systems for Airconditioning Applications

     Use of Ice for Airconditioning
     Building air conditioning in summer daylight hours is one of the largest
     contributors to electrical utility demand peaks. Typically between 2-4 PM
     in the afternoon when solar loading peaks, more air conditioners are
     needed to maintain comfortable environments in buildings. Add to this the
     electricity utilized by lighting, computers, building subsystems plus other
     equipment and the utility is faced with a peak load condition dictating that
     it bring on-line additional, more costly peak power generating sources to
     handle the load.


     Traditional air conditioning systems operate during the day to meet cooling
     demand and remain idle at night.        Chillers are selected to satisfy the
     maximum demand, which occurs only a few hours per year, and thus
     spend the majority of their operational life at reduced capacity and low
     efficiency.


     The ice storage system, which is suitable for any A/C application, allows
     installed chiller capacity (and size of other components) to be significantly
     reduced – typically between 40% and 60%. This enables efficient and real
     energy management whilst taking advantage of low tariff electricity.


     Large commercial users whose air conditioning loads contribute to the
     utility peaking problem are assessed an added charge typically based on
     their highest 15 minutes window of peak demand for electricity. This is
     called a “demand charge” which in many areas of the country can account
     for as much as 40 percent of the building owner’s total electrical bill.
The use of ice storage to minimize peak energy usage is not a new or
experimental idea. It has been used for years on applications with short
peak energy usage such as churches, meeting facilities and theaters. On
these applications, however, the longer peak uses were handled by
conventional rooftop cooling or water chilling / air handling systems.


Now, however, there is renewed interest in a broad use of ice making and
storage systems by both users and utility companies as the best way of
offsetting rising demand loads and resulting utility cost increases.


Ice storage systems can not only cut operating costs substantially, but
they can also reduce capital outlays when systems are properly applied
for both new and existing buildings and commercial and industrial types.
Simply stated, engineers can specify smaller chillers operating 24 hours a
day rather than larger chillers operating 10-12 hours a day and cut the
capital outlay for air conditioning equipment substantially.


An ice storage system can utilize either a load shifting or a load leveling
strategy to significantly lower demand charges during the cooling season.
Because this lowers energy demand, it substantially lowers the total
energy costs. It typically utilizes a standard packaged chiller to produce
ice at night or during off-peak periods when the building’s electrical needs
are at a minimum. The ice is stored in modular tanks to provide cooling
ton-hours to help meet the buildings cooling load requirements the
following day. By doing so, it minimizes the peak energy usage during the
utility daylight peaking period.
Full Storage Or Partial Storage?
Two load management strategies are possible with ice storage systems.
When utility rates call for complete load shifting, a conventionally sized
chiller can be used to shift the entire load into off-peak hours. This is
called a full storage system and is used most often in existing building
renovation or retrofit applications using existing installed chiller capacity.

In new construction, a partial, storage system is usually the most practical
and cost effective load management strategy.             In this load leveling
method, the chiller is sized to run continuously except for scheduled
preventive maintenance down time. It usually charges the ice storage
tanks at night and cools the load directly during the daytime peak hours
with help from stored cooling capacity.


This will greatly reduce the installed chiller capacity and its required capital
expenditure, as well as the demand charge for electricity to run the chiller
during utility peaking periods. Typically reductions can be 50 percent or
more.


How the Ice Storage System Works
A common ice storage system is a modular, insulated tank. Tanks are
typically available in several ton-hour rated sizes. Typically at night a mild
concentration of glycol-water solution (typically 25 percent ethylene glycol
based industrial coolant such as Dow Chemical Company Dowtherm SR-1
or Union Carbine Corporation’s UCAR Thermofluid 17) from a standard
packaged air conditioning water chiller system circulates through the heat
exchanger and extracts heat until eventually all the water in the tank is
frozen solid. The ice is built uniformly throughout the tank.
Typical schematic flow diagrams for a partial storage system are shown in
figure1&2. At night, the water-glycol solution circulates through the chiller
and the ice bank heat exchanger, bypassing the air handling coil that
supplies conditioned air to occupied building spaces. During the day, the
solution is cooled by the ice bank from 52 F to 34 F. A temperature
modulation valve set at 44 F in a bypass loop around the ice bank permits
a sufficient quantity of 52 F fluid to bypass the ice bank permits a sufficient
quantity of 52 F fluid to bypass the ice bank, mix with the 34F fluid, and
achieve the desired 44 F temperature. The 44 F fluid then enters the coil,
where it cools air from approximately 75 F to 55 F. The fluid then leaves
the coil at an elevated temperature (approximately 60F) and enters the
water chiller where it is cooled 60F to 52 F.


It is important to note that while making ice at night, the chiller must cool
the water- glycol solution down to 26 F, rather than producing 44 F water
required for conventional air conditioning systems.


Chillers with air-cooled condensing also benefit from cooler outdoor
ambient dry bulb temperatures to lower the system condensing
temperature at night.


The temperature modulating valve in the bypass loop has the added
advantage of providing excellent capacity control.               During mild
temperature days, typically in the spring and fall, the chiller will often be
capable of providing all the necessary cooling capacity for the building
without the use of cooling capacity from the ice storage system. When the
building’s actual cooling load is equal to or less than the chiller capacity at
the time, all of the system coolant will flow through the bypass loop as
shown in fig.3
It is important that the coolant chosen by an ethylene glycol-based
industrial coolant, such as Dowtherm SR-1 or UCAR Thermofluid 17,
which is specially formulated for low viscosity and good heat transfer
properties.   Either of these fluids contain a multi-component corrosion
inhibitor which is effective with most materials of construction including
aluminium, copper, silver solder and plastics. Further, they contain no
anti-leak agents and produce no films to interfere with heat transfer
efficiency.   They also permit use of standard pumps, seals and air
handling coils. It should be noted, however, that because of the slight
difference in heat transfer properties between water and the mild glycol
solution, the cooling coil capacities will need to be increased by
approximately 5 percent. It is also important that the water and glycol
solution be thoroughly mixed before the solution is placed into the system.


The use of ice storage system technology opens new doors to other
economic opportunities in system design. These offer significant potential
for not only first-cost savings but also operating cost savings that should
be evaluated on a life cycle cost basis using a computerized economic
analysis program.


Back-Up
Most A/C and refrigeration systems require some form of stand-by, or
back-up, facility to protect against system failure and costly lost production
time.   The ice storage system, is an ideal, efficient solution for these
applications. The ice storage system offers rapid response back-up in the
form of an independent, static technology solution which ensures the
highest degree of reliability.
Advantages of Ice Storage Systems
•   Reduced installed plant capacity.
•   Reduced electrical installation for lower investment and saving in demand
    charges.
•   Reduced installed cooling tower capacity incase of water cooled system.
•   Reduced installed D.G. set capacity.
•   Better plant utilization with longer equipment life and lower operating
    costs.
•   Use of off-peak energy for lower energy bill, where differential tariff is
    applicable.


Applications of Ice Storage System
•   Air-conditioning of industrial and commercial buildings - Offices, Hotels,
    Shopping Complexes, Supermarkets, etc.
•   Air-conditioning   of   data-processing    centers,   hospitals,   telephone
    exchanges, etc. requiring added system reliability and security.
•   Dairy plants, Breweries, Food Processing, Bottling Plants, Chemical and
    Fertilizer Plants, Pharmaceuticals, etc.
DUCTING DESIGN
The satisfactory distribution of conditioned air requires a well designed and
energy efficient air transport system with appropriate ducts and fans plus air
treatment and control devices.


The various method of duct designs, proper fan selection and control and
methods of air distribution system control for acceptable comfort and air quality in
the conditioned spaces are some of the points to be discussed.


The various methods of duct designing are
a.       Constant Velocity method
b.       Equal friction method
c.       Static regain method


Classification of Ducts
Supply and return duct systems are classified with respect to the velocity and
pressure of the air within the duct.


Velocity
There are tow types of air transmission systems used for airconditioning
application.    They are called Coventional or Low Velocity and High Velocity
system. The dividing line between these systems is rather nebulous but, for the
purpose of this section, the following initial supply air velocities are offered as a
guide.


1.       Commercial comfort air conditioning
         a.    Low velocity – upto 2500 fpm normally between 1200 & 220 fpm
         b.    High velocity – above 2500 fpm

2.       Factory comfort airconditioning
a.     Low velocity - upto 2500 normally between 2200 and 2500 fpm.
       b.     High velocity - above 2500 to 5000 fpm


Normally return air systems for both low and high velocity supply air systems are
designed as low velocity systems. The velocity range for commercial and factory
comfort application is as follows:


1.     Commercial comfort airconditioning - low velocity upto 2000 fpm.
       Normally between 1500 and 1800 fpm.
2.     Factory comfort airconditioning - low velocity upto 2500 fpm. Normally
       between 1800 and 2200 fpm.


Pressure
Air distribution systems are divided into three pressure categories; low, medium
and high. These divisions have the same pressure ranges as Class I, II & III fans
and indicated:


1.     Low pressure - upto 3¾ inch wg - class I fan
2.     Medium pressure - from 3¾ to 6 ¾ inch wg - class II fan
3.     High pressure - from 6 ¾ to 12 ¾ inch wg - class III


These pressure ranges are total pressure, including the losses through the air
handling apparatus, ductwork and the air terminal in the space.


The choice of design method depends almost entirely upon the size of the
ductwork installation. Small duct systems (homes, shops or a few office rooms)
are commonly designed by the velocity method. Large high pressure systems
are most frequently designed by computer software programs using the static
regain method.    Duct arrangements between these two extremes are nearly
always laid out by the equal friction method. Sometimes a duct arrangement will
be designed by a combination of two methods. For instance, the trunk duct will
be laid out by the static regain method and the branch duct runs designed by the
equal friction method.




In designing ductwork, a new term called “unit friction” will be utilized which
means the friction loss per 100 ft of duct work equivalent length.


Regardless of the duct design method chosen by the air transport system
designer, the final design and duct layout will likely result from the use of
computerized duct design and drafting programs available that are based on
algorithms from the ASHRAE hand book of fundamentals and other test data
from SMACNA.


  Recommended and maximum Duct Velocities for Conventional System
  DESIGNATION                        RECOMMEND VELOCITIES, FPM
                         RESIDENCES SCHOOLS, THEATERS,       INDUSTRIAL
                                         PUBLIC BUILDINGS     BUILDING
Outdoor air intakes1         500                   500            500
Filters1                     250                   300            350
Heating coils1,2             450                   500            600
Cooling coils1               450                   500            600
Air washers1                 500                   500            500
Fan outlets               1000 - 1600          1300 - 2000    1600 - 2400
Main ducts2                700 - 900           1000 - 1300    1200 - 1800
Branch ducts2                600                600 - 900     800 - 1000
Branch risers2               500                600 - 700         800
                              Maximum velocities, FPM
Outdoor air intakes1         800                   900           1200
Filters1                     300                   350            350
Heating coils1,2             500                   600            700
Cooling coils1               450                   500            600
Air washers                  500                   500            500
Fan outlets                  1700              1500 - 2200    1700 - 2800
Main ducts2               800 - 1200           1100 - 1600    1300 - 2200
Branch ducts2             700 - 1000           800 - 1300     1000 - 1800
Branch risers2             650 - 800           800 - 1200     1000 - 1600
1   These velocities are for total face area, not the net free area : other velocities in
table are for net free are
2   For low velocity systems only.
@ 1965 American society of heating, refrigerating and airconditioning engineers,
inc. reprinted by permission for ASHRAE guide and data book.




PIPING DESIGN
The water piping system are divided into once thru and re-circulating types. In a
once thru system water passes thru the equipment only once and is discharged.
In a re-circulating system water is not discharged, but flows in a repeating circuit
from the heat exchanger to the refrigeration equipment and back to the heat
exchanger.


Open and Closed
Both types are further classified as open or closed systems. An open system is
one in which the water flows into a reservoir open to the atmosphere; cooling
towers and air washers are examples of reservoirs open to the atmosphere. A
closed system is one in which the flow of water is not exposed to the atmosphere
at any point. This system usually contains an expansion tank that is open to the
atmosphere but the water area exposed is insignificant.


Water Piping Design
There is a friction loss in any pipe thru which water is flowing. This loss depends
         on the following factors:
1.       Water velocity
2.       Pipe diameter
3.       Interior surface roughness
4.       Pipe length
System pressure has not effect on the head loss of the equipment in the system.
However, higher than normal system pressures may dictate the use of heavier
pipe, fittings and valves along with specially designed equipment.


To properly design a water piping system, the engineer must evaluate not only
the pipe friction loss by the loss thru valves, fittings and other equipment. In
addition to these friction losses, the use of diversity in reducing the water quantity
and pipe size is to be considered in designing the water piping system.
Pipe Friction Loss
The pipe friction loss in a system depends on water velocity, pipe diameter,
interior surface roughness and pipe length. Varying any one of these factors
influences the total friction loss in the pipe.


Most air conditioning applications use either steel pipe or copper tubing in the
piping system.


Charts enclosed are for schedule 40 pipe upto 24 inch diameter. Chart shows
the friction losses for closed re-circulation piping systems and for once thru /
open re-circulation piping systems.


These charts show water velocity, pipe or tube diameter, and water quantity, in
addition to the friction rate per 100 ft of equivalent pipe length. Knowing any two
of these factors, the other two can be easily determined from the chart. The
effect of inside roughness of the pipe or tube is considered in all these values.


The water quantity is determined from the airconditioning load and the water
velocity by pre-determined recommendations. These two factors are used to
establish pipe size and friction rate.


Water Velocity
The velocities recommended for water piping depend on two conditions;
1.     The service for which the pipe is to be used.
2.     The effect of erosion.


The design of the water piping system is limited by the maximum permissible
flow velocity.
Recommend Water Velocity



             SERVICE       VELOCITY RANGE
                                (FPS)


Pump discharge                 8 - 12


Pump suction                    4-7


Drain line                      4-7


Header                         4 - 15


Riser                          3 - 10


General service                3 - 10


City water                      3-7
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material
Hva Cprogramme Material

Mais conteúdo relacionado

Mais procurados

HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & ComponentsUmang Patel
 
AUTOMOTIVE AIR-CONDITIONING SYSTEM
AUTOMOTIVE AIR-CONDITIONING SYSTEMAUTOMOTIVE AIR-CONDITIONING SYSTEM
AUTOMOTIVE AIR-CONDITIONING SYSTEMvensonsarita
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learnQaimuddin SODHO
 
Introduction to hvac systems
Introduction to hvac systemsIntroduction to hvac systems
Introduction to hvac systemsmichaeljmack
 
Chapter 7 heating ventilation air conditioning
Chapter 7 heating ventilation air conditioningChapter 7 heating ventilation air conditioning
Chapter 7 heating ventilation air conditioningvenky venkat
 
HVAC System (Heating, Ventilation and Air Conditioning)
HVAC System (Heating, Ventilation and Air Conditioning)HVAC System (Heating, Ventilation and Air Conditioning)
HVAC System (Heating, Ventilation and Air Conditioning)Maliha Mehr
 
All About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling SolutionsAll About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling SolutionsDr Vijay Gehlot
 
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)MOHAMMED KHAN
 
Psychrometry and air conditioning
Psychrometry and air conditioningPsychrometry and air conditioning
Psychrometry and air conditioningnitin184shukla
 
Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System SilkThreadJewellery
 
Refrigeration & hvac system final
Refrigeration & hvac system finalRefrigeration & hvac system final
Refrigeration & hvac system finalAkilaEdirisinghe1
 

Mais procurados (20)

Hvac Basics
Hvac Basics Hvac Basics
Hvac Basics
 
Airconditioning ppt
Airconditioning pptAirconditioning ppt
Airconditioning ppt
 
Module (1.2) psychometrics-air parameters-hvac_by ss-eng. juma
Module (1.2) psychometrics-air parameters-hvac_by ss-eng. jumaModule (1.2) psychometrics-air parameters-hvac_by ss-eng. juma
Module (1.2) psychometrics-air parameters-hvac_by ss-eng. juma
 
HVAC - Concept & Components
HVAC - Concept & ComponentsHVAC - Concept & Components
HVAC - Concept & Components
 
AUTOMOTIVE AIR-CONDITIONING SYSTEM
AUTOMOTIVE AIR-CONDITIONING SYSTEMAUTOMOTIVE AIR-CONDITIONING SYSTEM
AUTOMOTIVE AIR-CONDITIONING SYSTEM
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learn
 
Introduction to hvac systems
Introduction to hvac systemsIntroduction to hvac systems
Introduction to hvac systems
 
Chapter 7 heating ventilation air conditioning
Chapter 7 heating ventilation air conditioningChapter 7 heating ventilation air conditioning
Chapter 7 heating ventilation air conditioning
 
HVAC System (Heating, Ventilation and Air Conditioning)
HVAC System (Heating, Ventilation and Air Conditioning)HVAC System (Heating, Ventilation and Air Conditioning)
HVAC System (Heating, Ventilation and Air Conditioning)
 
Chapter 1 hvac
Chapter 1 hvacChapter 1 hvac
Chapter 1 hvac
 
All About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling SolutionsAll About HVAC System - Created by MG Cooling Solutions
All About HVAC System - Created by MG Cooling Solutions
 
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
 
Psychrometry and air conditioning
Psychrometry and air conditioningPsychrometry and air conditioning
Psychrometry and air conditioning
 
Air washer
Air washerAir washer
Air washer
 
Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System
 
HVAC
HVACHVAC
HVAC
 
Refrigeration & hvac system final
Refrigeration & hvac system finalRefrigeration & hvac system final
Refrigeration & hvac system final
 
Energy efficient hvac
Energy efficient hvac Energy efficient hvac
Energy efficient hvac
 
HVAC System
HVAC SystemHVAC System
HVAC System
 
HVAC Basics
HVAC BasicsHVAC Basics
HVAC Basics
 

Semelhante a Hva Cprogramme Material

REFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONINGREFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONINGDivakar Ketha
 
refrigeration and air conditioning
refrigeration and air conditioningrefrigeration and air conditioning
refrigeration and air conditioningGear Abohar
 
evaporative cooler
evaporative coolerevaporative cooler
evaporative cooleramit prasad
 
thermodynamic property of Refrigerator
 thermodynamic property of Refrigerator thermodynamic property of Refrigerator
thermodynamic property of Refrigeratorkrishnanand kushwaha
 
Humidification in textile mill
Humidification in textile millHumidification in textile mill
Humidification in textile millAman Deep
 
Chapter 48
Chapter 48Chapter 48
Chapter 48mcfalltj
 
Refrigeration & Air conditioning
Refrigeration & Air conditioningRefrigeration & Air conditioning
Refrigeration & Air conditioningmkmanik
 
refrigeration in hvac
refrigeration in hvacrefrigeration in hvac
refrigeration in hvacsonam singh
 
Report on Air Cooler
Report on Air CoolerReport on Air Cooler
Report on Air CoolerSuman Gop
 
Refrigeration PPT to present.ppt
Refrigeration PPT to present.pptRefrigeration PPT to present.ppt
Refrigeration PPT to present.pptBodhiSeal1
 
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdfDr. Ahamed Saleel C
 
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLEJim Webb
 
Refrigeration cycle paper
Refrigeration cycle paperRefrigeration cycle paper
Refrigeration cycle paperkek243
 
Portable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A ReviewPortable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A ReviewIRJET Journal
 
Mechanism of refrigerator asrafi tonmoy-diu
Mechanism of refrigerator  asrafi tonmoy-diuMechanism of refrigerator  asrafi tonmoy-diu
Mechanism of refrigerator asrafi tonmoy-diuAsrafi-Tonmoy
 
process design of water chilling plant
process design of water chilling plantprocess design of water chilling plant
process design of water chilling plantDinesh Sannepally
 

Semelhante a Hva Cprogramme Material (20)

REFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONINGREFRIGERATION AND AIR CONDITIONING
REFRIGERATION AND AIR CONDITIONING
 
refrigeration and air conditioning
refrigeration and air conditioningrefrigeration and air conditioning
refrigeration and air conditioning
 
Project Report
Project ReportProject Report
Project Report
 
evaporative cooler
evaporative coolerevaporative cooler
evaporative cooler
 
thermodynamic property of Refrigerator
 thermodynamic property of Refrigerator thermodynamic property of Refrigerator
thermodynamic property of Refrigerator
 
Humidification in textile mill
Humidification in textile millHumidification in textile mill
Humidification in textile mill
 
Chapter 48
Chapter 48Chapter 48
Chapter 48
 
Kapes project
Kapes projectKapes project
Kapes project
 
Refrigeration & Air conditioning
Refrigeration & Air conditioningRefrigeration & Air conditioning
Refrigeration & Air conditioning
 
refrigeration in hvac
refrigeration in hvacrefrigeration in hvac
refrigeration in hvac
 
Report on Air Cooler
Report on Air CoolerReport on Air Cooler
Report on Air Cooler
 
Refrigeration PPT to present.ppt
Refrigeration PPT to present.pptRefrigeration PPT to present.ppt
Refrigeration PPT to present.ppt
 
UTM SSC industrial chemical process
UTM SSC industrial chemical process UTM SSC industrial chemical process
UTM SSC industrial chemical process
 
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
7_Refrigeration_Cycle_UNIT_2_REFRIGERATI.pdf
 
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
7 Refrigeration Cycle UNIT 2 REFRIGERATION CYCLE
 
CHAPTER 11.pdf
CHAPTER 11.pdfCHAPTER 11.pdf
CHAPTER 11.pdf
 
Refrigeration cycle paper
Refrigeration cycle paperRefrigeration cycle paper
Refrigeration cycle paper
 
Portable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A ReviewPortable Air Cooling and Air Conditioning Technologies: A Review
Portable Air Cooling and Air Conditioning Technologies: A Review
 
Mechanism of refrigerator asrafi tonmoy-diu
Mechanism of refrigerator  asrafi tonmoy-diuMechanism of refrigerator  asrafi tonmoy-diu
Mechanism of refrigerator asrafi tonmoy-diu
 
process design of water chilling plant
process design of water chilling plantprocess design of water chilling plant
process design of water chilling plant
 

Último

shot list for my tv series two steps back
shot list for my tv series two steps backshot list for my tv series two steps back
shot list for my tv series two steps back17lcow074
 
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degreeyuu sss
 
西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造kbdhl05e
 
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一A SSS
 
group_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdfgroup_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdfneelspinoy
 
3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdf3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdfSwaraliBorhade
 
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...Rishabh Aryan
 
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degreeyuu sss
 
How to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AIHow to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AIyuj
 
Untitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptxUntitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptxmapanig881
 
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024CristobalHeraud
 
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一F dds
 
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一F La
 
Pharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdfPharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdfAayushChavan5
 
Design principles on typography in design
Design principles on typography in designDesign principles on typography in design
Design principles on typography in designnooreen17
 
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书zdzoqco
 
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...mrchrns005
 
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services DubaiDubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubaikojalkojal131
 
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree 毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree ttt fff
 

Último (20)

shot list for my tv series two steps back
shot list for my tv series two steps backshot list for my tv series two steps back
shot list for my tv series two steps back
 
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 
西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造
 
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
 
group_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdfgroup_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdf
 
3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdf3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdf
 
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
 
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 
How to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AIHow to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AI
 
Untitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptxUntitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptx
 
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
 
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
 
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
 
Pharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdfPharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdf
 
Design principles on typography in design
Design principles on typography in designDesign principles on typography in design
Design principles on typography in design
 
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
 
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
 
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services DubaiDubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
 
Call Girls in Pratap Nagar, 9953056974 Escort Service
Call Girls in Pratap Nagar,  9953056974 Escort ServiceCall Girls in Pratap Nagar,  9953056974 Escort Service
Call Girls in Pratap Nagar, 9953056974 Escort Service
 
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree 毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 

Hva Cprogramme Material

  • 1. HEATING VENTILATION & AIRCONDITIONING SYSTEM DESIGN FACULTY CO-ORDINATOR NEERAJ SHUKLA
  • 2. CONTENTS PAGE NO. 1.0 INTRODUCTION AND OVERVIEW - 2 2.0 FUNDAMENTALS OF REFRIGERATION - 5 3.0 BASIC REFRIGERATION SYSTEM - 12 4.0 ELEMENTS OF PSYCHROMETRY - 16 5.0 APPLIED PSYCHROMETRY - 23 6.0 HEAT LOAD ESTIMATION - 33 7.0 HEAT LOAD DATA SHEET & TYPICAL CALCULATION - 47 8.0 HEATING VENTILATION & AIRCONDITIONING SYSTEMS - 52
  • 4. INTRODUCTION AND OVERVIEW A simple definition of air conditioning is the simultaneous control of temperature, humidity, air movement, and the quality of air in a space. The use of the conditioned space determines the temperature, humidity, air movement, and quality of air that must be maintained. The primary function of air conditioning is to maintain conditions that are (1) conducive to human comfort, or (2) required by a product, or process within a space. To perform this function, equipment of the proper capacity must be installed and controlled throughout the year. The equipment capacity is determined by the actual instantaneous peak load requirements; type of control is determined by the conditions to be maintained during peak and partial load. Generally, it is impossible to measure either the actual peak or the partial load in any given space; these loads must be estimated. The term ‘refrigeration’ may be defined as the process of removing heat from a substance under controlled conditions. It also includes the process of reducing and maintaining the temperature of a body below the general temperature of its surroundings. In other words, the refrigeration means a continued extraction of heat from a body whose temperature is already below the temperature of its surroundings. For example, if some space (say in cold storage) is to be kept at - 2 °C (271 K), we must continuously extract heat which flows into it due to leakage through the walls and also the heat which is brought into it with the articles stored after the temperature is once reduced to - 2 °C (271 K). Thus in a refrigerator, heat is virtually being pumped from a lower temperature to a higher temperature. According to second law of Thermodynamics, this process can only be performed with the aid of some external work. It is obvious that supply of power (say electric motor) is regularly required to drive a refrigerator. Theoretically, a
  • 5. refrigerator is a reversed heat engine or a heat pump which pumps heat from a cold body. The substance which works in a heat pump to extract heat from a cold body and to deliver to a hot body is called a refrigerant. The refrigeration system is known to the man since the middle of nineteenth century. The scientists, of the time, developed a few stray machines to achieve some pleasure. But it paved the way by inviting the attention of scientists for proper studies and research. They were able to build a reasonably reliable machine by the end of nineteenth century for refrigeration jobs. But with the advent of efficient rotary compressors and gas turbines, the science of refrigeration reached the used for the cooling of storage chambers in which perishable foods, drinks and medicines are stored. The refrigeration has also wide applications in submarine ships, aircraft and rockets. Air conditioning has got wide range of applications and it is very much essential in these days. Air conditioning is provided for some of the following reasons b) To improve productivity in offices, factories by maintaining comfort conditions for persons . c) To maintain comfortable conditions for working in hotels, labs, etc., d) To avoid malfunctioning of some of the control panels in Electrical Control Buildings. e) To maintain over pressure inside the premises for avoiding outside (dusty) air in to the room. f) To create healthy atmosphere inside the room by supplying filtered air in to the room. g) To provide clean, filtered, healthy, comfortable conditions in hospitals etc.,
  • 6. 2.0 FUNDAMENTALS OF REFRIGERATION
  • 7. FUNDAMENTALS OF REFRIGERATION Refrigeration is the process by which heat is removed from a low temperature level and rejected at a relatively higher temperature level. The Americans define refrigeration in a somewhat different way, thus, refrigeration is the process by which heat is removed from a place where it is not required and rejected into a place where it is not objectionable. This is not, strictly speaking, a proper scientific definition, since it does not make any mention of its temperature levels. No process can be called “refrigeration” unless removal of heat is at a temperature lower than the surrounding temperature. By nature heat always flows from one body to another body which is relatively at a lower temperature. This law of nature cannot be altered by any means. Transferring heat from a low temperature level to a high temperature level is analogous to transferring water from a lower level to a higher level. Imagine two water tanks, one located at the ground floor full of water and another empty, located at the roof level of a building. If water from the ground floor tank is to be transferred to the roof tank, then the only thing to do is to bring a bucket, place it at a level lower than the ground floor tank and allow the water to initially drain into the bucket according to the law of nature. The second step would be to lift this bucket full of water to a level above the roof tank and now allow the water from the bucket to drain into the roof tank according to the natural flow by gravity. In the foregoing process, we have used the bucket as the carrier and moved it up and down, first to a level lower than the ground floor tank and then to a level higher than the roof tank. Needless to add that in the process some mechanical work has been performed for lifting the bucket from the lower level to the higher level.
  • 8. Applying this analogy to the process of refrigeration, it is evident, that we require a substance as the carrier of heat analogous to the bucket. This substance should be first brought to a temperature which is lower than the low level temperature so that heat from the low temperature level will automatically flow into this carrier substance which has been brought to a still lower level of temperature. After this carrier substance has been fully loaded with heat it has got to be raised to a temperature which is higher than the high level temperature so that heat from this carrier will automatically flow according to the law of nature. The carrier substance referred to above is what is known in refrigeration parlance as “refrigerant”. We shall now see what a refrigerant is really like. All volatile liquids including water have property whereby the temperature at which they evaporate changes according to the pressure it is subjected to. Take water for example. At normal atmospheric pressure it boils at 100°C (212°F). When the water is subjected to higher pressure its boiling temperature also becomes higher than 100°C. Likewise, if the water is subjected to pressures lower than the atmosphere its boiling temperature also falls below 100°C. In fact water can boil even at as low a temperature as 4°C when it is kept in vacuum free of air. In this case the only pressure it will have above is its own vapour pressure. Different volatile substances have different pressure-boiling point characteristics. For refrigeration purpose the most commonly used refrigerants are refrigerant 12 and refrigerant 22. By reference to a table giving the properties of these refrigerants is will be seen that for each pressure there is a corresponding temperature at which only the refrigerant will boil. It goes without saying that at any given pressure the temperature at which the liquid refrigerant boils is also the temperature at which the refrigerant vapour would condense back to liquid form. Whether it is boiling or condensing all depends on whether it is receiving heat or giving heat. For refrigerant purpose, therefore, we make use of this natural property of the volatile refrigerant. For example, if the liquid refrigerant R-22 is by some means or other brought down to an absolute pressure of say 83.72 psi, then this liquid is now in a position to boil at a temperature of 40°F. In order to make this liquid at low pressure boil, you will have to supply heat equivalent to
  • 9. the latent heat of vaporization. So any body which is above 40°F in temperature can supply this latent heat to make this liquid boil and turn completely into gaseous form, it goes without saying that the substance which supplies the heat for boiling the refrigerant will itself naturally cool down, but in any case not to a temperature below 40°F which is the temperature at which the refrigerant is boiling. Once the refrigerant liquid has completely vaporized, it has no further capacity to absorb heat from the heat supplying body, just in the same way that the bucket had no further capacity to take more water the moment it was full. In the case of bucket in order to make it useful again, we had to raise this to a higher level and empty out its contents in the roof tank and then bring it back once again to take another bucket full from the ground floor tank. In a similar way the completely vaporized refrigerant will have to be raised to a high temperature level. By raising it to a higher temperature level, we do not mean that you simply heat up the refrigerant. What is really to be done is this low pressure refrigerant will have to be compressed in a compressor to a higher pressure. The pressure to which it is compressed must be such that the boiling point or conversely the temperature at which the refrigerant vapour would condense should be higher than the body to which we want to empty out the heat content of the carrier refrigerant. If, for example, the body to which we want to reject this heat is water which is at a temperature of 90°F, then the boiling temperature or condensing temperature of the refrigerant should be higher than 90°F, say 106°F. Now 106°F happens to be the boiling temperature of the refrigerant when it is at a pressure of 230 psi absolute. This means that the low pressure refrigerant will have to be compressed to a pressure of 230 psi absolute before it is in a position to empty out its heat content to the cooling medium, namely, natural water. Note that in the process we have not violated any natural law concerning heat flow. We have all along allowed heat to flow from a certain temperature level to a lower temperature level. What we have done is that we have changed the temperature level of the carrier refrigerant to higher or lower temperature levels to conform to the natural law of heat flow.
  • 10. This brings us to a stage where we have to know the definition of certain terms which are generally used in refrigeration parlance. Saturation Temperature For any given refrigerant the temperature at which the liquid refrigerant would boil (or conversely the refrigerant vapour would condense) when it is subjected to a certain pressure is defined as the saturation temperature corresponding to that pressure. It is obvious that at this temperature and pressure, refrigerant in liquid and vapour form kept in a closed container would be in equilibrium with each other. So long as the pressure inside this container is maintained steady the liquid portion will vaporize if heat is added or the vapour portion will condense if heat is removed. On this basis, saturation temperature for any given pressure is defined as that temperature at which liquid refrigerant and its vapour remain in contact with each other in equilibrium. Superheat We saw in the previous paragraph that liquid refrigerant and its vapour will be in equilibrium with each other in a closed container at the saturation temperature corresponding to the pressure. Any addition or removal of heat would only result in either liquid vaporizing or the vapour condensing, pressure remaining same. However, if the vaporized refrigerant is separated from the liquid portion, then any heat added to this refrigerant in vapour form would only go to raise the temperature of the vapour above its saturation temperature corresponding to its pressure. This is superheated vapour. Superheat is usually expressed in terms of degrees. When we say 10° superheat, what we mean is the gaseous refrigerant is at a temperature 10° above the saturation temperature corresponding to its pressure.
  • 11. Sub-cooling In a like manner if the liquid portion of the refrigerant is separated and completely isolated from the vapour which is in equilibrium with it then any removal of heat from this refrigerant would lower its temperature to a value below its saturation temperature. Such a liquid is called sub-cooled liquid. When we say the liquid is 15° below the saturation temperature corresponding to its pressure. It is obvious that in the case of sub-cooled liquid when heat is added it will first rise up in temperature till it reaches its saturation temperature and thereafter only it will begin to boil as long as it is receiving heat. Likewise, in the case of superheated gas, when heat is removed from the same it will first fall down in temperature till it reaches the saturation temperature corresponding to its pressure (this is generally referred to as de-superheating). Any further removal of heat after this would result in condensation of the vapour into liquid form at constant temperature, namely, the saturation temperature. One thing that should be borne in mind is neither sub-cooling of liquid nor superheating of the vapour is possible when liquid and its vapour are in contact with each other in equilibrium, because as already explained earlier, any removal or addition of heat in this case would only respectively result in condensing of the vapour part or evaporating of the liquid part, at constant temperature. Enthalpy Enthalpy is the terms which denotes the heat content of the refrigerant from a base saturation temperature of 40°F. At this temperature and the corresponding saturation pressure the heat content of the liquid has been arbitrarily fixed as 0. It, therefore, follows that the enthalpy of the liquid above 40°F will be positive and that below 40°F. will be negative. The enthalpy of the refrigerant when it is in vapour form will be equal to the enthalpy of the liquid at the same pressure and saturation temperature.
  • 12. Adiabatic Compression Any process which is performed without the addition of heat to or removal of heat from the process is said to be an adiabatic process. Compression of gaseous refrigerant without addition or removal of heat is called adiabatic compression. The pressure enthalpy diagram of a refrigerant has also lines showing adiabatic compression. It is, therefore, possible to find out the enthalpy and temperature of the gas at various pressures during the course of compression.
  • 14. BASIC REFRIGERATION SYSTEM The various components which form part of a refrigeration system can be described as follows: Evaporator Let us start from the evaporator. Liquid at high pressure has to be admitted into the evaporator. In order that this liquid may evaporate at low temperature, it is essential that the liquid so admitted is simultaneously reduced in pressure. The level to which the pressure has to be reduced of course is determined by the temp. at which you want this liquid to evaporate. For example, if you want evaporation of refrigerant 22 at a temperature of 40°F, the absolute pressure should be brought down to 83.72 psi or if the evaporation has to be at 10°F the absolute pressure should be brought down to 31.29 psi. The pressures indicated above are the saturation pressures corresponding to the respective temperatures. This pressure reduction is brought about by the use of what is known as an expansion valve. The expansion valve is just a needle valve which throttles the flow of liquid refrigerant thereby bringing about a pressure drop. This expansion valve can also be hand operated, automatic or thermostatic. Liquid admitted into the evaporator now needs heat for evaporation. This head is supplied by the air which is flowing over the evaporator coil. In the process, the air gets cooled and the liquid refrigerant evaporates. Compressor Now if you have got to ensure continuous evaporation at the same temperature, it is very vital that the vapour evaporating in the coil is removed from it is as rapidly as it is evaporating. Unless this is done the evaporated vapour will build up a pressure in the coil which would keep on rising. Any such rise in pressure will naturally raise the evaporating temperature also since, the evaporation temperature is higher and higher as the pressure increases. Removal of the evaporator vapour is achieved by connecting the outlet of the evaporator to the
  • 15. suction side of a refrigerating compressor. Of course, the compressor has got to be sized so that it has got a volumetric rate of displacement which matches with the evaporation rate. Thus the evaporation pressure is maintained as steady and the liquid fed through the expansion valve continues to evaporate at a steady temperature so long as heat for evaporation is available at an equally steady rate from the air flowing over. Condenser The compressor compresses the vapour and discharges the same into the condenser. It is in this condenser that the high pressure hot gas delivered by the compressor has to be condensed. For the purpose of condensing the gas it is necessary that heat is removed from the hot gas. This removal of heat is achieved by again creating an air flow over the condenser coil or water flow if water cooled condensers are used. The heat given up by the refrigerant is picked up by the air or water. The hot gas which has given up the heat naturally condenses into liquid form at the same pressure. Now let us see how the pressure built-up in the condenser coil it has got certain definite capacity to transfer heat from within to the outside air or water for each degree of temperature difference. We also know that for each 1b of refrigerant which has got to be condensed into liquid form a definite capacity to transfer heat from within to the outside air or water of refrigerant which has got to be condensed into liquid form, a definite amount of heat, namely, the latent heat of condensation has to be removed. If in a refrigeration system the F-22 circulation is say, 5 1bs/minute, then the amount of heat which has got to be removed for condensing this refrigerant gas is 5 x latent heat. This means that the temperature difference between the hot refrigerant gas within the condenser and the air or water flowing over it should be such that the total amount of heat transferred through the walls of the condenser tubes just balances with the total amount of heat which has got to be removed. The condensation rate would, therefore, automatically balance with the compressor discharge rate as soon as
  • 16. the temperature difference has been built up. The pressure inside the condenser also which initially starts building up will attain a steady level when the corresponding saturation temperature results in the desired temperature difference for creating the desired heat transfer rate. This is called the condesing temperature of the system. It is obvious that if you use a small size condenser the temperature difference has necessarily to be higher and hence the condensing temperature and the corresponding pressure will also have to be relatively higher. Receiver A receiver is a pressure vessel which is used as a storage tank for the condensed liquid refrigerant leaving the condenser. It is from this receiver that liquid is tapped and sent to the evaporator through the throttling device or expansion valve. It is not on all systems that we have a separate liquid receiver. In the case of systems having water cooled condensers, the shell of the condenser itself serves as a storage vessel for the liquid refrigerant. In smaller systems even with air cooled condensers, it is possible to dispense with the use of a receiver if care is taken to charge the system with the correct amount of refrigerant. In order that the various components forming part of a refrigeration system can be designed, it is necessary to make a more scientific study of the entire operations. For this purpose we have to know the complete properties of the refrigerant concerned when it is at gaseous form and also in liquid form. The properties of each refrigerant are shown in what is called a Pressure Enthalpy Diagram.
  • 18. ELEMENTS OF PSYCHROMETRY Psychrometry Since air conditioning, by its very name means treating air with a view to altering its temperature and moisture content with the use of refrigeration, it is necessary that we should know how exactly air would behave when it is subjected to cooling, heating, humidifying or dehumidifying processes. For this purpose, it is necessary to study the property of air at normal atmospheric pressure in so far as it concerns air conditioning. Such a study is what is called psychrometry. For the study of psychrometry, a chart has been devised, which is called Psychrometric Chart. We will just now see what the various lines of the psychrometric chart are. Dry Bulb Lines Any vertical line is a line of constant temperature. Condition of air represented by any point on this line will have the temperature corresponding to this vertical line. These lines are called Dry Bulb Lines. By dry bulb what we really mean is dry bulb temperature i.e., the temperature as recorded by a thermometer which is dry. Moisture Content Each horizontal line in the chart is a line of constant moisture content. The condition of air represented by any point on this line will all have the same moisture content as applicable to this line. Through any point on the psychrometric chart you can always draw a horizontal line and a vertical line. Air represented by this point has, therefore, a dry bulb temperature corresponding to the vertical line and moisture content corresponding to the horizontal line. It is easy to see that air at any given temperature can have varying moisture content. Likewise, air containing any given moisture content can have varying
  • 19. temperature as well. Saturation Line The curved line on the extreme left-hand side of the chart is what is called the saturation line. Condition of air represented by any point on this line is said to be saturated air, which means that the air is having the maximum possible moisture content in it. It cannot hold any further moisture. Wet Bulb Lines There are number of parallel slant lines which are called wet bulb lines. By wet bulb temperature what we really mean is the temperature of the air as recorded by a thermometer with a wet wick on its bulb. You will also understand for the moment that the air having a certain wet bulb temperature will have a definite heat content although its dry bulb temperature may be anything. Relative Humidity Lines When the air contains its maximum moisture content, we call it saturated air; when it contains anything less than this maximum limit then it is not saturated air because it has still capacity to have more moisture. We therefore, say that such air is, say 50% saturated or 60% saturated. Another term used to denote the percentage saturation is “relative humidity”. Thus it is one and the same thing whether you say air is 50% saturated or air has got a relative humidity of 50%. Note that we have used the word “approximately” because the strict scientific definition of relative humidity is not nearly the comparison of moisture content. In fact relative humidity is defined as the ratio of the partial vapour pressure in the air to the maximum vapour pressure that saturated air will have at this temperature. However, for all practical purpose, this is equal to the ratio of the actual moisture content present to the maximum moisture it can hold at that temperature.
  • 20.
  • 21. Dew Point We have seen that at any given temperature air has a maximum limit of moisture holding capacity when it is said to be saturated. For example from the psychrometric chart we can see that 70°F saturated air can hold a maximum of 110 grains per 1b of dry air. All temperatures above 70°F, air with the same moisture content will be, say 80%, 90% etc., saturated depending on what its dry bulb temperature would be. If air with this moisture content and at temperature higher than 70° is cooled down, then its condition will move along the horizontal 110 grains line, till the temperature falls to 70°F. 70°F and 110 grains / 1b as we have seen corresponds to saturated condition. This is the temperature at which air with 110 grains of moisture / 1b will begin to shed its moisture by condensing if you continue to cool the air. This temperature is called the DEW POINT of the air. Needless to add, it is the moisture content which determines the dew point. All you have to do is to move horizontally on the psychrometric chart and read the temperature where you intersect the saturation line. Enthalpy We were just now referring to the wet bulb as line of constant heat content of air. Enthalpy is just another term used in place of “heat content”. Of course, the enthalpies represented here are all values for samples of air containing 1 lb of dry air. The amount of moisture content in the air is generally expressed in terms of grains of moisture per 1b of dry air. For your information, grain is a weight measure. 7000 grains make 1 lb. When we say that the moisture content is 120 grains, what we mean is there is 1 lb, of dry air containing 120 grains of moisture. The total weight of this moist air would, therefore, by 1 + 120/7000 lbs = 1.0171 lb. At any temperature there is a limit to the maximum moisture holding capacity of air. This limit is something definite and does not alter except under different atmospheric pressures. At higher and higher atmospheric pressure the moisture holding capacity at any given temperature becomes less and less.
  • 22. At any temperature when air contains the maximum amount of moisture it is said to be saturated air. When air has attained saturation at any given temperature, it is impossible to add any further moisture in vapour form.
  • 23. Short Definitions Dry-bulb Temperature The temperature of air as registered by on ordinary temperature. Wet-bulb Temperature The temperature registered by a thermometer whose bulb is covered by a wetted wick and exposed to a current of rapidly moving air. Dewpoint Temperature The temperature at which condensation of moisture begins when the air is cooled. Relative Humidity Ratio of the actual water vapor pressure of the air to the saturated water vapor pressure of the air at the same temperature. Specific Humidity or Moisture Content The weight of water vapor in grains or pounds of moisture per pound of dry air. Enthalpy A thermal property indicating the quantity of heat in the air above an arbitrary datum. In BTU per pound of dry air. The datum for dry air is 0 °F and, for moisture content, 32 °F water. Enthalpy Deviation Enthalpy indicated above, for any given condition, is the enthalpy of saturation. It should be corrected by the enthalpy deviation due to the air not being in the saturated state. Enthalpy deviations in BTU per pound of dry air. Enthalpy deviation is applied where extreme accuracy is required : however, on normal air
  • 24. conditioning estimates it is omitted. Specific Volume The cubic feet of the mixture per pound of dry air. Sensible Heat Factor The ratio of sensible to total heat. Alignment Circle Located at 80 °F db and 50% rh and used in conjunction with the sensible heat factor to plot the various air conditioning process lines. Pounds of Dry Air The basis for all pyschrometric calculations, remains constant during all psychrometric processes. The dry-bulb, wet-bulb, and dewpoint temperatures and the relative humidity are so related that if two properties are known, all other properties shown may then be determined. When air is saturated, dry-bulb, wet-bulb, and dewpoint temperatures are all equal.
  • 26. APPLIED PSYCHROMETRY Let us now see how the various air conditioning procedures will be represented on a Psychrometric chart. 1. Sensible Heating By sensible heating, we mean adding heat to air whereby the entire heat added goes to raise the temperature of the air. It is obvious that in such a process there is no change in the moisture content of the air. In other words, during sensible heating process the air retains a constant moisture content and accordingly, its condition will move on a horizontal line corresponding to its constant moisture content. Since heat is being added during such process, its enthalpy also rises. Therefore, during the heating process the wet bulb temperature of the air will also rise, because as we have already seen, it is the wet bulb temperature lines which are identified as constant enthalpy lines. 2. Addition of Moisture Likewise, if moisture is somehow or the other added to the air without adding any sensible heat, the process would be represented by a vertical line corresponding to its dry bulb temperature. In this case also, since the moisture added carries with it the latent heat of vaporization of water, the heat content of the air also rises and hence its wet bulb temperature also rises. 3. Heating and Humidifying If heat is added so that part of it goes to raise the temperature and the remaining part goes to vaporize water and add it to the air, such a process is called heating and humidifying.
  • 27. 4. Cooling and Dehumidifying Cooling and dehumidifying is just the reverse of heating and humidifying. On a psychrometric chart such a process will also be represented in the same manner as for heating and humidifying, the only difference being the arrows representing the direction of movement of conditions would be just reverse. 5. Evaporative Cooling Evaporative cooling is the process by which air is simply subjected to a spray of re-circulated water just as in the experiment described earlier, the only difference being, we do not provide an infinite number of spray banks as in the experiment. The chamber with the banks of spray is called an Air Washer. Air so subjected would of course tend to get saturated and change out at a temperature equal to its wet bulb temperature. However, since we do not provide adequate number of spray banks to completely humidify, the air comes out not at 100% humidity but somewhat lower than that. Needless to say, since this process is adiabatic, the air has constant enthalpy throughout the process and hence its condition moves along the line representing its wet bulb temperature. Psychrometry as Applied to Airconditioning It now remains for us to study psychrometry as applied to air conditioning process. We will only see for the present what the heat load form is like and also the various sections into which it is divided. It is only after you understand this that you will be in a better position to understand psychrometry as applied to air conditioning.
  • 28. When a space is maintained at a temperature below the atmospheric temperature surrounding the space, then there is a transfer of heat from outside into the conditioned area, which tends to raise the inside temperature unless this heat is removed as fast as it enters this space. Then you have heat or any other appliances which may be in the space. All such heat which are either transmitted into the room or generated from within due to occupants and appliances which tend to raise the inside temperature are termed as room sensible heat. In the like manner, the occupants within the room also release moisture from their body into the room. There may be other sources inside the conditioned area which add up more moisture into the atmosphere. If the space has not only to be maintained at a particular temperature, but also to be held within certain limits of relative humidity, then it is necessary that such moisture gain inside the room should also be removed just as rapidly. By removal of moisture what we have really mean is condensing this moisture from the air and discarding it outside. For condensing the moisture, you have to remove the latent heat of vaporisation of water. So instead of stating that we have got to remove moisture gained, we state this in terms of the corresponding total amount of latent heat to be removed for condensing that quantity of moisture gained. This is also expressed in terms of heat units viz. BTU. So the heat to be removed per hour for condensing the moisture is termed as room latent heat. So what we really mean by heat load is the room sensible heat and the room latent heat that are to be removed from within the space at a calculated rate to effect the gain of sensible and latent heats into the conditioned space.
  • 29. In heat load, there is one more source which contributes to the room sensible and room latent heat loads. This is on account of infiltration of fresh air directly into the conditioned space and bypass of certain amount of fresh air that is normally taken into the system through the air handling apparatus. The form is designed so that the room sensible heat, latent heat and the additional load due to outside air, not forming part of room load are all calculated separately. Here, we have used the term “Bypass”. You must understand what exactly the meaning of the term “Bypass” is. For removing sensible heat and latent heat at the same rate at which they are being gained within the conditioned space, conditioned air is admitted within this space at a predetermined temperature and humidity condition such that this air would absorb the room sensible and room latent heat loads and in the process attain a final condition which is exactly equal to the condition to be maintained in the room. This is achieved by continuously drawing from within the room certain amount of air and adding to it a certain percentage of fresh air for ventilation and cooling and dehumidifying this mixture in a cooling coil. It is this treated air, which is supplied back into the conditioned area. On account of some free passages in between the fins and tubes a small percentage of the air comes out on the other side of the coil without undergoing any change. It is this, which we terms as bypass of air. As far as the portion of the air, which is actually re-circulated from the room is concerned, bypass will have no influence on the ultimate result. It only means that some air has been withdrawn from the room and just put back into the same room without any change in its condition either upward or downward. But, what really influences is the bypass of the fresh air, which is also passed through the cooling coil along with the re- circulated air. Since this outside air is at a much higher temperature and humidity conditions than the conditioned space, entry of such bypass air would tend to upset the room conditions unless this bypass air is also
  • 30. brought down to the room condition. The general formula for arriving at the exact air quantity is: cfm = = However, you must realise it is not merely the selection of the condition of the supply air that is important. We have also to consider how air can be cooled down to the selected condition in a cooling apparatus. In a cooling coil in which air is cooled, there is no practical means of ensuring that the air leaving the coil would be at the exact temperature and humidity condition corresponding any condition selected by us on the sensible heat factor line. However, there is one temperature and humidity condition which is very easy to keep under control. This is the condition which lies not only on the sensible heat factor line but also on the saturation line on the psychrometric chart. In other words, if the sensible heat factor line is extended till it meets the saturation line, then the condition represented by the point of intersection of these two lines is the one condition which can be under our control. This temperature is called apparatus dew point. Bypass Factor The problem becomes a bit more complicated because in every cooling coil there is always a small percentage of the total cfm which escapes totally untreated. When outside air taken into the system bypasses the coil, it will tend to raise the room temperature and humidity conditions above the desired level. It is, therefore, necessary to take into consideration the effect of bypass right at the time of making the heat load calculations.
  • 31. PSYCHROMETRIC FORMULAS A. AIR MIXING EQUATIONS (Outdoor and Return Air) tm = (1) hm = (2) Wm = (3) B. COOLING LOAD EQUATIONS ERSH = RSH + (BF) (OASH) + RSHS* (4) ERLH = RLH + (BF) (OALH) + RLHS* (5) ERTH = ERLH + ERSH (6) TSH = RSH + OASH + RSHS* (7) TLH = RLH + OALH + RLHS* (8) GTH = TSH + TLH + GLHS* (9) RSH = 1.08 x cfmsa x (trm - tsa) (10) RLH = 0.68 x cfmsa x (Wrm - Wsa) (11) RTH = 4.45 x cfmsa x (hrm - hsa) (12) RTH = RSH + RLH (13) OASH = 1.08 x cfmoa x (toa - trm) (14) OALH = 0.68 x cfmoa x (Woa - Wrm) (15) OATH = 4.45 x cfmoa x (hoa - hrm) (16)
  • 32. OATH = OASH + OALH (17) (BF) (OATH) = (BF) (OASH) + (BF) (OALH) (18) ERSH = 1.08 x cfmda x (trm - tadp)(1-BF) (19) ERLH = 0.68 x cfmda x (Wrm - Wadp)(1-BF) (20) ERTH = 4.45 x cfmda x (hrm - hadp)(1-BF) (21) TSH = 1.08 x cfmda x (tedb - tldp) ** (22) TLH = 0.68 x cfmda x (Wea - Wta) ** (23) GTH = 4.45 x cfmda x (hea - hta) ** (24) C. SENSIBLE HEAT FACTOR EQUATIONS RSHF = = (25) ESHF = = (26) GSHF = = (27) D. BYPASS FACTOR EQUATIONS BF = ;(1-BF) = (28) BF = ;(1-BF) = (29) BF = ;(1-BF) = (30)
  • 33. E. TEMPERATURE EQUATIONS AT APPARATUS tedb ** = (31) tldb = tadp + BF (tedb – tadp) (32) tewb and tlwb correspond to the calculated values of hea and hla on the psychrometric chart. hea ** = (33) hta = hadp + BF (hea – hadp) (34) F. TEMPERATURE EQUATIONS FOR SUPPLY AIR tsa = t4m – (35) G. AIR QUANTITY EQUATIONS cfmda = (36) cfmda = (37) cfmda = (38) cfmda = (39)
  • 34. cfmda = (40) cfmda = (41) cfmsa = (42) cfmsa = (43) cfmsa = (44) cfmba = cfmsa - cfmda (45) Note : cfmda will be less than cfmsa only when air is physically bypassed around the conditioning apparatus. cfmsa = cfmoa + cfmra (46) H. DERIVATION OF AIR CONSTANTS 1.08 = .224 X Where .224 = Specific heat of moist air at 70 F db and 50% rh, Btu/(deg F) (lb dry air) 60 = min/hr 13.5 = Specific volume of moist air at 70 F db and 50% rh
  • 35. .68 = X where 60 = min/hr 13.5 = Specific volume of moist air at 70 F db and 50% rh 1076 = Average heat removal required to condensate one pound of water vapor from the room air. 7000 = Grains per pound 4.45 = where 60 = min/hr 13.5 = Specific volume of moist air at 70 F db and 50% rh.
  • 36. 6.0 HEAT LOAD ESTIMATION
  • 37. HEAT LOAD ESTIMATION Introduction The primary objective is to provide a convenient consistent, and accurate method of calculating heating and cooling loads and to enable the designer to select systems that meet the requirements for efficient energy utilization and are also responsive to environmental needs. The ability to estimate loads more accurately due to changes in the calculation procedure provides a lessened margin of error. Therefore, it becomes increasingly important to survey and check more carefully the load sources, each item in the load and the effects of the system type on the load. This tightening up on the hidden safety factors occurs for a number of reasons. There is greater emphasis, by standards and codes, on sizing equipment closer to the expected loads, as determined by outside design weather conditions. Also the suggested indoor design temperatures are now usually 75 °F for cooling and 72 °F for heating. Installed lighting levels are being reduced and the calculations are using lighting loads closer to the actual loads. All of these factors require that the designer introduce any margin of safety by a positive action, rather than rely on an assumed hidden margin. Purpose of Load Calculations Load calculations can be used to accomplish one or more of the following objectives : h) Provide information for equipment selection and HVAC system design i) Provide data for evaluation of the optimum possibilities for load reduction. j) Permit analysis of partial loads as required for system design, operation and control These objectives can be obtained not only by making accurate load calculations but also by understanding the basis for the loads. There a brief description of
  • 38. cooling and heating loads are included. Principles of Cooling Loads In airconditioning design there are three distinct but related heat flow rates, each of which varies which varies with time: k) Heat Gain or Loss l) Cooling load or Heating Load m) Heat Extraction or Heat Addition Rate Heat Gain, or perhaps more correctly, instantaneous rate of heat gain, is the rate at which heat enters or is generated within a space at a given instant of time. There are two ways that heat gain is classified. They are the manner in which heat enters the space and the type of heat gain. The manner in which a load source enters a space is indicated as follows: n) Solar radiation through transparent surfaces such as windows o) Heat conduction through exterior walls and roofs p) Heat conduction through interior partitions ceilings and floors q) Heat generated within the space by occupants, lights, appliances, equipment and processes r) Loads as a result of ventilation and infiltration of outdoor air s) Other miscellaneous heat gains The types of heat gain are sensible and latent. Proper selection of cooling and humidifying equipment is made by determining whether the heat gain is sensible or latent. Sensible heat gain is the direct addition of heat to an enclosure, apart from any change in the moisture content, by any or all of the mechanisms of conduction, convection and radiation. When moisture is added to the space, for example, by vapor emitted by the occupants, there is an energy quantity associated with that moisture which must be accounted for.
  • 39. If a constant humidity ratio is to be maintained in the enclosure, then water vapor must be condensed out in the cooling apparatus at a rate equal to its rate of addition in the space. The amount of energy required to do this is essentially equal to the product of the rate of condensation per hour and the latent heat of condensation. This product is called the latent heat gain. As a further example, the infiltration of outdoor air with a high dry-bulb temperature and a high humidity ratio, and the corresponding escape of room air at a lower dry-bulb temperature and a lower humidity ratio, would increase both the sensible heat gain and the latent heat gain of the space. The proper design of an airconditioning system requires the determination of the sensible heat gain in the space, the latent heat gain in the space, and a value for the total load, sensible plus latent, of the outdoor air used for ventilation. The sensible cooling load is defined as the rate at which heat must be removed from the space to maintain the room air temperature at a constant value. The summation of all instantaneous sensible heat gains at a specific time does not necessarily equal the sensible cooling load for the space at that time. The latent load however is essentially an instantaneous cooling load. That part of the sensible heat gain which occur by radiation is partially absorbed by the surfaces and contents of the space and is not felt by the room air until sometimes later. The radiant energy must first be absorbed by the surface that enclose the space such as walls and floor and by furniture and other objects. As soon as these surfaces and objects become warmer than the air some heat will be transferred to the air in the room by convection. The heat storage capacity of the building components and item such as walls, floors and furniture governs the rate at which their surface temperatures increase for a given radiant input. Thus, the interior heat storage capacity governs the relationship between the radiant portion of the sensible heat gain and how it contributes to the cooling load. The thermal storage effect can be important in determining the cooling equipment
  • 40. capacity. The actual total cooling load is generally less than the peak total instantaneous heat gain thus requiring smaller equipment than would be indicated by the heat gain. If the design is based on the instantaneous heat gain, the rest of the system may be oversized as well. Heat extraction rate is the rate at which heat is removed from the conditioned space. Normal control systems operating in conjunction with the intermittent operation of the cooling equipment will cause a “swing” in room temperature. There, the room air temperature is constant only at those rare times when the heat extraction rate equals the cooling load. Consequently, the computation of the heat extraction rate gives a more realistic value of energy removal at the cooling equipment than does just the instantaneous value of the cooling load provided the control system is simulated properly. The determination of the heat extraction rate must include the characteristics of the cooling equipment and the operating schedule of thee equipment, in addition to the various sources of cooling load. If the equipment is operated some what longer before and after the peak load periods, and / or the temperature in the space is allowed to rise a few degrees at the peak periods during the cooling operation (floating temperature), a reduction in the design equipment capacity my be made. A smaller system operating for longer periods at times of peak loads will produce a lower first cost to the customer with commensurate lower demand charges and lower operating costs. Generally, equipment sized to more nearly meet the cooling requirements result in a more efficient, better operating system particularly when is at a partially loaded condition. Usually a fraction of the sensible heat gain does not appear a cooling load, but instead is shifted to the surroundings. The fraction Fc depends upon the thermal
  • 41. conductance between the room air and the surroundings. It may be also considered as a adjustment factor which results when the load components as superimposed. The adjustment factor, Fc is calculated by the following equation. Fc = 1 - 0.02 KT Where KT the unit length conductance between the room air as surroundings in Btu / (hr. ft2 F), is given by KT = 1/LF (UWAW + UowAow + UcAc) Where LF = Length of the exterior walls of the room, ft. U = U-value of room enclosure element (subscript w for window, ow for outside wall and c for corridor), Btu (hr. ft2 F) A = Area of the specific element If the cooling load component has already been obtained by the technique used in this manual, multiply that result by the calculated Fc factor. The adjustment factor should be used only for individual small spaces or zones. It is not to be used for block loads nor for industrial applications. Diversity of Cooling Loads Diverting of cooling load results from not using part of the load on a design day. Therefore diversity factors are factors of usage and are applied to the
  • 42. refrigeration capacity of large airconditioning systems. These factors vary with location, type, and size of applicant and are based entirely on the judgment and experience of the engineer.
  • 43. Generally, diversity factors can be applied on loads from people and lights; there is neither 100% occupancy nor total lighting at the time of such other peak loads as peak solar and transmission loads. The reductions in cooling loads from nonuse are real and should be accounted for. In addition to the factors for people are lights a factor should also be applied to the machinery load in industrial buildings. For instance, electric motors may operate at a continuous overload, or may operate continuously at less than the rate capacity or may operate intermittently. It is advisable to measure the power input whenever possible; this will provide a diversity factor. It is also possible to determine a diversity factor for a large existing building by reviewing the maximum electrical demand and monthly energy consumption obtained from the utility bills. Principles and Procedures for Calculating Heating Load The peak heating requirements may occur either at night during unoccupied hours or in the morning pickup period following a shutdown. Therefore a number of calculations are helpful in making a proper equipment selection and system design. Information Required (Input) Before a cooling or heating load can be properly estimated a complete survey must be made of the physical data. The more exact the information that can be obtained about space characteristics, heat load sources, location of equipment and services, weather data, etc. the more accurate will be the load estimate. Required Input - External Loads - Cooling For calculation of the outdoor loads the input information should include: t) Orientation and dimensions of building components. u) Construction materials for roof, walls, ceiling, interior partitions, floors and
  • 44. fenestration v) Size and use of space to be conditioned w) Surrounding conditions outdoors and in adjoining spaces Required Input - Heating Load The input for calculation of heating load is essentially the same as that for the cooling load. However, it may not be necessary to calculate the internal sources and solar heat gain. In heat load estimation we compute a. Room sensible and latent heat gains due to transmission, sunlight, occupancy and other internal sources of heat. b. Grand total heat comprising total room load under (1) plus additional loads due to outside air intake, heat gains in return air ducts, in chilled water distribution systems, pumping horse power load, etc. Room load estimation under (a) is required for computing the condition and quantity of supply air while the grand total heat under (b) is required for terminating the total capacity of the cooling system. In this discussion, we will confine ourselves to transmission gains and related subjects only. There are certain similarities between heat transmission through barriers and electric current transmission through conductors. We will use this similarly wherever required for better understanding of the subject. The well known formula relating to transmission of electric current is: I = Where “I” = current in Amperes, “V” = Voltage & “R”, the Resistance of the conductor. In this formula, if (I) / (R) is considered as the conductance of the conductor, say “C”, then the formula can be rewritten as:
  • 45. I = VxC For transmission of heat through a barrier, the motive force corresponding to “V” is temperature difference between the two sides of the barrier. The formula for rate of heat transmission per hour H is: H = A x U x (T) Where T is the temperature difference in °F and A is the area of the barrier in sq.ft. and U is the overall heat transmission coefficient expressed in BTU/Hr/Sq.ft/°F temperature difference. The product (AxU) corresponds to the conductance “C” of the electric conductor. Thermal conductivity of any material is the heat transmitted through the material expressed as BTU/Hr/Sq.ft/Inch thickness/°F temperature difference and is referred to by the symbol “K”. It K is the conductivity of the material, then 1/K is the resistance of the material of 1 sq.ft. cross section and 1” thickness. If the thickness “t” inches, the resistance becomes (t) / (K) per sq.ft. In electrical system, resistance connected in series are added to find the total resistance. Similarly, if a barrier is made up of several materials, the individual resistances of the components have to be added to arrive at the total barrier resistance. If a barrier is made up of, say, three materials having thermal conductivities K1, K2 & K3, the total thermal resistance of the barrier is: t1/K1 + t2/K2 + t3/K3 Where t1, t2 & t3 are the thicknesses of the barriers. Film Coefficient In addition to the resistance of the various components of a barrier, we have to consider one more resistance offered by a film of air (or fluid if the barrier is in a fluid) which clings on to the barrier surfaces. This resistance is more when the air is still and is relatively less when there is wind velocity. Like thermal
  • 46. conductivity, the heat transmission capacity of a film is expressed as the rate of heat of transfer in BTU/Hr/Sq.ft/°F temperature difference (Note that this differs from thermal conductivity in the sense it is not related to any film thickness as in the case of materials). This is called the film coefficient and is expressed by the symbol “f”. The reciprocal of “f” is the thermal resistance of the film. “f1” denotes the film coefficient on the interior surface of the barrier and “f0” denotes the film coefficient on the exterior surface of the barrier. The resistance of the complete barrier is: 1/f1 + t1/K1 + t2/K2 + t3/K3 + 1/f0 If “U” is the overall heat transmission of the barrier in BTU/Hr/Sq.ft./°F, then 1/0 is the overall thermal resistance of the barrier. 1/U = 1/f1 + t1/K1 + t2/K2 + t3/K3 + 1/f0 U = 1/(1/f1 + t1/K1 + t2/K2 + t3/K3 + 1/f0) Storage Effect Suppose T0 is the temperatures on both sides of the barrier. There will be no heat transmission through the barrier and the temperatures at all points within the barrier will also be the same. There is, therefore, no temperature gradient. Now suppose the temperature on one side of the barrier is raised from T0 to T7, do you think that heat transmission through the barrier will commence immediately? No, since all points within the barrier is at the same temperature, no heat can flow through any interior section. The first thing that happens is the outermost layer of the barrier absorbs the heat from the outside and rises in temperature. Heat then flows over to the next layer of the barrier because of the temperature difference between the first and second layers. The second layer also will first rise in temperature before heat begins to flow over to the third layer. Thus progressively all the layers within the barrier rise in temperature thereby establishing the total temperature gradient from one side to the other side of the barrier. It is only after the complete gradient has been established that heat will
  • 47. begin to flow to the other side of the barrier. The temperature at various points within the barrier will now be as determined by the gradient. Attic Spaces Whenever a false ceiling is provided in a room, the space enclosed between the false ceiling and the concrete ceiling is called ATTIC SPACE. If the attic space is not ventilated the entire space within the attic will assume an intermediate temperature which will be more than the room temperature and less than the outside temperature. This temperature can be worked out as follows: Ag = area of the concrete ceiling A1 = area of the false ceiling U0 = “U” factor of the concrete ceiling Uf = “U” factor of the false ceiling T2 = Outside temperature T1 = Inside temperature T = Temperature of the attic space When steady heat transmission from outside to inside takes place through the attic space, then the rate of flow of heat from outside into the attic space is equal to the rate of flow of heat from the attic space into the room, i.e., Ac.Uc.(T2 – T) = Af.Uf.(T – T1) “T” can therefore be calculated from this equation. After “T” has been worked out, the transmission load into the room from the ceiling can be worked out by substituting the value of “T” in the above equation. Solar Gain Solar Gain, as the name implies, comes from direct sunlight. There are two kinds of solar gains:
  • 48. a. Radiation from sun which directly enters the conditioned space through glass and absorbed by objects in the room and then by the air within the room. The effect of such gain into the space is felt almost immediate. The amount of radiation for various exposures and time of the day and year are given in tables for the various latitudes on the earth. Depending on the type of glass, about 5 to 6% of the radiation is reflected while the rest pass into the room. Solar gain is not confined merely to the side which directly faces the sun. You get solar heat even from other sides through glasses, but to a much smaller degree. This is diffused radiation. b. Solar & Transmission Gain This is due to transmission through sunlit walls whose temperature rises above the ambient temperature due to absorption of direct radiation and hence causes a larger temperature differential than the ambient temperature. The equivalent temperature difference that is to be taken are given in tables, taking into consideration the exposure, sun time and storage effect. c. Transmission Gain through Glass & Partition In addition to solar gain through glass, you have also to work out transmission gain through glass due to temperature difference. Transmission through partitions between conditioned and non-conditioned areas are worked out on the basis of actual temperature difference. No storage effect apply for these cases. d. Internal Load This comprises load from: x) Occupancy: The sensible/latent heat gains from people are given in tables, based on the nature of their activities in the room. y) Lights: Lighting is generally specified in terms of watts per sq.ft.
  • 49. The total watt has to be converted into BTU/Hr by multiplying by conversion factors. z) Appliances: Electrical, gas burners, steam generation, etc. aa)Electric Motors: Applies generally in some of industrial applications. This load will have to be properly analysed by discussion with user and appropriate diversity factors should be applied for estimating the actual load. Convert the HP into BTU/Hr. We shall now briefly lay down the procedure for heat load estimating with explanations wherever required. 1. Collect architect’s drawings for the building giving all details and dimensions of walls, floors, windows, etc. If such drawings are not available, survey the place and get the particulars. 2. For every application, there are certain things which the ultimate user has to specify. These are: bb)Temperature & humidity conditions to be maintained inside the space and tolerance. cc) Occupancy – i.e. maximum no. of people likely to occupy the space and the nature of their activity. dd)Lighting load and other internal source of heat generation. ee)Period of operation – e.g. 8 a.m. to 7 p.m. or 10 a.m. to 8 p.m. etc. ff) For industrial application you require also the HP load in the conditioned space and diversity factor thereon. gg)Minimum ventilation required. 3. Outside Design Conditions hh)For comfort air conditioning application, use the mean maximum DB temperature & the WB temperature which occurs simultaneously with
  • 50. the assumed DB. ii) For industrial applications where temperatures and humidities are to be maintained within very close tolerance through the year, tank the maximum DB and the simultaneously occurring WB temperature. 4. For all applications make a second load estimate for monsoon conditions. 5. For applications where the conditioned spaces are spread over very vast floor areas, divide the entire area into convenient zones and make load estimates.
  • 51. 6. Occupancy - In certain applications a diversity factor may have to be used even in respect of occupancy. Examples are: Office areas where a separate conference room is also provided. The conference room may be designed for a large number of people. But you must realize that it is mostly the people in the office who go into conferences and hence any occupancy in the conference room brings about an equal reduction in the occupancy in other areas of the office.
  • 52. 7.0 HEAT LOAD DATA SHEET & TYPICAL CALCULATION
  • 53. TYPICAL DIVERSITY FACTORS FOR LARGE BUILDINGS (APPLY TO REFRIGERATION CAPACITY) DIVERSITY FACTOR PEOPLE LIGHTS Office 0.75 to 0.90 0.70 to 0.85 Apartment, Hotel 0.40 to 0.60 0.30 to 0.50 Department storage 0.80 to 0.90 0.90 to 1.0 Industrial 0.85 to 0.95 0.80 to 0.90
  • 54. Fresh air requirement - 2.0 air changes / hr. or 10 CFM per person Design conditions a - indoor - 70 °F ± 2 °F DBT ; 55% ± 5% RH b - Outdoor - 103 °F DBT ; 82 ° F WBT
  • 55. U - FACTOR CALCULATIONS a. Exposed Walls Total resistance RT = R o + X1 R 1 + X2 R 2 + X3 R 3 + R i = 0.25 + 12.5 x 0.2 + 230 x 0.2 + 12.5 x 0.2 + 0.68 25 25 25 = 2.97 hr. ft2. °F /BTU Overall heat transfer Co-efficient = 1_ = 1_ RT 2.97 = 0.337 BTU / hr. ft2. °F b. Partitions RT = R i + X1 R 1 + X2 R 2 + X3 R 3 + R i
  • 56. = 0.68 + 12.5 x 0.2 + 230 x 0.2 + 12.5 x 0.2 + 0.68 25 25 25 = 3.40 hr. ft2. °F /BTU Overall heat transfer Co-efficient = 1_ = 1_ RT 3.40 = 0.294 BTU / hr. ft2. °F c. Roof exposed to sun RT = R i + X1 R 1 + X2 R 2 + R i = 0.25 + 150 x 0.2 + 50 x 4.0 + 0.92 25 25 = 10.37 hr. ft2. °F /BTU Overall heat transfer Co-efficient = 1_ = 1_ RT 10.37
  • 57. = 0.096 BTU / hr. ft2. °F
  • 58. 8.0 HEATING, VENTILATION & AIRCONDITIONING SYSTEMS
  • 59. HEATING, VENTILATION & AIRCONDITIONING SYSTEMS A. AIR CONDITIONING SYSTEMS Airconditioning is defined as the simultaneous control of temperature, humidity, quality and movement of air in a conditioned space or building. An air conditioning system is therefore, defined as an arrangement of equipment which will air condition a space or a building. Thus, a complete air conditioning system includes a means of refrigeration, one or more heat transfer units, air filters, a means of air transport and distribution, an arrangement for piping the refrigerant and heating medium, and controls to regulate the proper capacity and operation of these components. The items outlined above are considered to be the components of a complete air conditioning system. There has been a tendency by many designers to classify an air conditioning system by referring to one of its components. For example, the airconditioning system in a building may include a dual duct air transport arrangement to distribute the conditioned air and is then referred to as a dual duct system. This classification makes no reference to the type of refrigeration, the piping arrangement or the type of controls. For the purpose of classification, the following definitions will be used: An Airconditining unit is understood to consist of heat transfer surface for heating and cooling, a fan for air circulation, means of cleaning the air, a motor, a drive, and a casing.
  • 60. A self-contained airconditioning unit is understood to be an airconditioning unit that is complete with compressor, condenser, controls, and a casing. An air handling unit consist of a fan heat transfer surface, a motor, a drive and a casing A remote air handling unit or a remote air conditioning unit is a unit located outside of the conditioned space which it serves. The most common types of refrigeration machines, classified according to their type of operation are (1) mechanical compression, (2) absorption and (3) vacuum. Apart from the above types the airconditioning system are generally clarified is to following categories: 1. Window (room) airconditioners 2. Split airconditioning units 3. Packaged airconditioning units 4. Centralised airconditioning plant - DX system 5. Centralised airconditioning plant – chilled water system The details of the above are further detailed in the subsequent pages. The types of refrigeration machines which are further explained as under: Mechanical Compression machines may be divided into reciprocating, centrifugal, and rotary types. The term “heat pump” is occasionally used to describe a refrigeration machine. However, a heat pump is a refrigeration cycle – either reciprocating, rotary or centrifugal - in which the cooling effect as well as
  • 61. the heat rejected is used to furnish cooling or heating to the air conditioning units, either simultaneously or separately. Reciprocating or rotary compressor can be used in systems that circulate the refrigerant through remote direct expansion heat transfer surfaces. Alternately they can be used in conjunction with a water chilling heat exchanger, to produce chilled water for circulation through remote heat transfer surfaces that cool and dehumidify the air. Centrifugal refrigeration machines are generally not suitable for circulating and expanding the liquid refrigerant in remote heat exchanges surfaces. Centrifugal machines are therefore used only to chill water or brine for circulation through remote heat exchange surfaces. Absorption machine cycles are similarly to mechanical compression machine cycles only to the extent that both cycles evaporate and condense a refrigerant liquid. They differ in the mechanical compression cycle use purely mechanical processes, while the absorption cycle uses physiochemical processes to produce the refrigeration effect. Vacuum refrigeration machines, such as steam jet and water vapor units, are seldom used in modern airconditioning systems.
  • 62. 1. Room Airconditioner This is the simplest form of an air conditioning system. It has a hermetically sealed motor compressor assembly, an air cooled condenser coil, an evaporator coil, condenser fan and evaporator fan. It has a capillary tube in place of an expansion valve for metering refrigerant flow to the evaporator. Room air conditioners are generally made of capacities ranging from 3/4 ton to 1-1/2 tons suitable for operation on 230 V, single phase, 50 cycles supply. It is completely factory assembled and can be straightaway plugged into power supply when installed. Application Generally used for small office rooms, shops and residential rooms where the where the load will generally be within 1-1/2 tons. Sometimes, these units are used in multiple for larger areas. Advantages The main advantage is that the unit can be switched ON and OFF as required. Where multiple units are used, there is no fear of a total breakdown of air conditioning since it is most unlikely that all the units will breakdown simultaneously. Disadvantages The hermetically sealed compressor is susceptible to burn out when the supply voltage fluctuates widely and whenever such burnouts occur, the whole system has to be thoroughly cleaned before a new compressor can be fitted. The life of the unit is generally between 10 to 15 years only.
  • 63. 2. Packages type air conditioner These are larger versions of Room Air Conditioners except that they are generally made with water-cooled condensers. They can also be made with air cooled condensers either built in with the package or for remote installation. They are generally made in capacities ranging from 5 to 10 tons. Units with water cooled condensers require condenser water circulating system and cooling tower. The units may also require external duct work for air distribution. This unit operates on 400 V, phase, 50 cycles supply. Application These units are most ideal where the load is between 5 to 20 tons. Sometimes, they are also used for much larger loads by using more number of units interconnected on the supply air side. Advantages Installation and commissioning can be done in the shortest possible time since the field work involved only relates to condenser water piping, air distribution system and electrical wiring. When multiple units are used for larger areas, the number of units in operation can be varied according to the load requirement, thereby saving on power consumption. Disadvantages These units also have hermetically sealed motor compressor assemblies and hence have the same disadvantage as Room Air Conditioners. 3. General plant - DX systems The system consists of an open type compressor ranging in capacity from 5 tons to 120 tons operating on refrigerant 22. They are motor driven either through belt drive or direct coupling. They can also be driven by diesel engine, but then only by direct drive. Belt drive should not be used
  • 64. when diesel engine is used. They are generally with water-cooled condensers even though they can also be built with air-cooled condensers. Application The DX system of Central Plant is perhaps the most widely used system for medium loads between 20 and 100 tons. It can be used for almost all types of application. Advantages The DX system is perhaps the most efficient of all system from a thermo dynamic point of view since the heat transfer is directly between the conditioned air and the refrigerant. The open type compressors used for these systems have built in capacity controls to take care of load fluctuations. Plants of any capacity can be built with DX systems using multiple compressors, condensers and evaporators. Although it is preferable to keep each compressor with its condenser and evaporator as a single unit, these plants can also be built with interconnection between them on the refrigerant side. Such interconnections naturally provide more flexibility in operation. Disadvantages DX systems should not be used where air distribution through duct work has to be carried out from a central air handling unit to various zones because of fire hazard. Therefore, a single air handling unit should necessarily be confined to a single zone. Where there are multiple zones use of DX system is permissible only when separate DX plants are used for each zone without any interconnection on the air distribution size. Where the building condition has got number of floors one above the other, DX systems could be considered only if it is possible to install separate Central Plant for each floor. Of course, such decision would
  • 65. involve installation of the plant on upper floors where vibration and other problems have to be effectively tackled in order to eliminate transmission of vibrations to the occupied zones. Cost wise also, such individual systems in each floor may prove to be much higher. 4. Central plant - Chilled Water System A central chilled water system is made up on one or more water chilling plants. Each water chilling plant may be built with either one or two compressors to work with one or two chillers (DX chiller or shell and tube flooded chiller) and one or two water cooled condensers. Each such water chilling unit is field assembled on structural framework with the necessary refrigerant pipes so as to make a compact assembly. Where such multiple water chilling units are used, they are generally interconnected on the water side both in the condenser circulating system and chilled water circulating system. Application Multiple water chilling units with reciprocating compressors are generally suitable for multistoreyed office buildings where the load is between 100 and 300 tons. However, there is no bar against using more number of water chilling units with reciprocating compressors even for loads higher than 300 tons. For loads exceeding 300 tons. Water chilling units with centrifugal compressors would be preferable. 5. Chilled Water for Process Cooling Advantages The best advantage of a chilling water system in that the Central Plant can be installed in as remote a location as desired from the conditioned areas. In fact, they can even be built in a remote plant room with chilled water piping either underground or overhead running to all the zones where air
  • 66. handling units are installed. This system provides maximum flexibility in operation since the air handling units serving individual zones can be cut off from the chilled water circulating system whenever air conditioning is not required in any particular zone. Since each zone will have its own air handling unit, no interconnecting duct work will be required thereby eliminating all possibilities of fire spreading from one zone to another. In the case of large hotels, fan coil units in individual rooms can be switched off whenever the room is not occupied. Individual temperature controls can be provided for each zone or individual rooms by regulating the chilled water flow through the coil either thermostatically or manually. Disadvantages On application where the load is small, this system would prove very much costlier than the DX system. Another disadvantage is that since one more heat transfer medium viz. chilled water, has been introduced, the heat transfer is now from air to water and then from water to refrigerant. This naturally lowers the evaporating temperature as compared to a DX system for the same load. Hence the power consumption will be relatively higher than that for DX system. 6. Air conditioning System for Operation Theatres It is desirable that a DX system is used for each Operation Theatre. However, in large hospitals, if there are several operation theatres located in various floors, there is no bar against using a central chilled water system, but exclusively for the operation theatre only. Each operation theatre must however have individual air treatment units with pre-filters on the air suction side of fan and supplementary microves filters on the air discharge side of the fan. For operation theatres no re-circulation of room air is permitted. You should, therefore, estimate the heat load on the
  • 67. basis of 100% fresh air.
  • 68. 7. Screw Chillers Refer to figure showing single line diagram of refrigeration cycle for the above and for piping schematics. Each vertical screw compressor discharges hot, high pressure gas through a discharge service valve (A) (or check valve in multiple compressor units) into the condenser, where it condenses outside tubes, rejecting heat to cooling tower water flowing inside the tubes. The liquid refrigerant drains to the bottom of the condenser and exits into the economizer feed line. The refrigerant flows through the economizer feed ball valve (B), dropping its pressure, causing it to flash. It then flows into the flash economizer tank (C) which is at an intermediate pressure between condenser and evaporator, liquid is centrifugally separated from the flash gas and the liquid drains to the bottom of the tank, exits via the economizer drain line, and passes through the economizer drain ball valve (D). Both economizer ball valves are actuated by a modutrol motor (U) that adjusts flow to maintain an appropriate refrigerant level in the evaporator, determined by a liquid level float switch (V). From the drain line, liquid refrigerant flows into the flooded evaporator, where it boils, cooling the water flowing inside evaporator tubes. Vapor from the boiling refrigerant flows up the suction pipes through a shut-off valve (E) (optional), suction check valve (F) and suction filter (G) (inside compressor) into the compressor where it is compressed and starts cycle again. Vapor flows from the top of flash economizer into the compressor at the vapor injection port, which feeds it into the compressor part way through the compression process. Check valve (H) prevents backflow at shutdown in multi compressor units. Al compressors operate in parallel on
  • 69. a common evaporator and condenser.
  • 70. 8. Ice Storage Systems for Airconditioning Applications Use of Ice for Airconditioning Building air conditioning in summer daylight hours is one of the largest contributors to electrical utility demand peaks. Typically between 2-4 PM in the afternoon when solar loading peaks, more air conditioners are needed to maintain comfortable environments in buildings. Add to this the electricity utilized by lighting, computers, building subsystems plus other equipment and the utility is faced with a peak load condition dictating that it bring on-line additional, more costly peak power generating sources to handle the load. Traditional air conditioning systems operate during the day to meet cooling demand and remain idle at night. Chillers are selected to satisfy the maximum demand, which occurs only a few hours per year, and thus spend the majority of their operational life at reduced capacity and low efficiency. The ice storage system, which is suitable for any A/C application, allows installed chiller capacity (and size of other components) to be significantly reduced – typically between 40% and 60%. This enables efficient and real energy management whilst taking advantage of low tariff electricity. Large commercial users whose air conditioning loads contribute to the utility peaking problem are assessed an added charge typically based on their highest 15 minutes window of peak demand for electricity. This is called a “demand charge” which in many areas of the country can account for as much as 40 percent of the building owner’s total electrical bill.
  • 71. The use of ice storage to minimize peak energy usage is not a new or experimental idea. It has been used for years on applications with short peak energy usage such as churches, meeting facilities and theaters. On these applications, however, the longer peak uses were handled by conventional rooftop cooling or water chilling / air handling systems. Now, however, there is renewed interest in a broad use of ice making and storage systems by both users and utility companies as the best way of offsetting rising demand loads and resulting utility cost increases. Ice storage systems can not only cut operating costs substantially, but they can also reduce capital outlays when systems are properly applied for both new and existing buildings and commercial and industrial types. Simply stated, engineers can specify smaller chillers operating 24 hours a day rather than larger chillers operating 10-12 hours a day and cut the capital outlay for air conditioning equipment substantially. An ice storage system can utilize either a load shifting or a load leveling strategy to significantly lower demand charges during the cooling season. Because this lowers energy demand, it substantially lowers the total energy costs. It typically utilizes a standard packaged chiller to produce ice at night or during off-peak periods when the building’s electrical needs are at a minimum. The ice is stored in modular tanks to provide cooling ton-hours to help meet the buildings cooling load requirements the following day. By doing so, it minimizes the peak energy usage during the utility daylight peaking period.
  • 72. Full Storage Or Partial Storage? Two load management strategies are possible with ice storage systems. When utility rates call for complete load shifting, a conventionally sized chiller can be used to shift the entire load into off-peak hours. This is called a full storage system and is used most often in existing building renovation or retrofit applications using existing installed chiller capacity. In new construction, a partial, storage system is usually the most practical and cost effective load management strategy. In this load leveling method, the chiller is sized to run continuously except for scheduled preventive maintenance down time. It usually charges the ice storage tanks at night and cools the load directly during the daytime peak hours with help from stored cooling capacity. This will greatly reduce the installed chiller capacity and its required capital expenditure, as well as the demand charge for electricity to run the chiller during utility peaking periods. Typically reductions can be 50 percent or more. How the Ice Storage System Works A common ice storage system is a modular, insulated tank. Tanks are typically available in several ton-hour rated sizes. Typically at night a mild concentration of glycol-water solution (typically 25 percent ethylene glycol based industrial coolant such as Dow Chemical Company Dowtherm SR-1 or Union Carbine Corporation’s UCAR Thermofluid 17) from a standard packaged air conditioning water chiller system circulates through the heat exchanger and extracts heat until eventually all the water in the tank is frozen solid. The ice is built uniformly throughout the tank.
  • 73. Typical schematic flow diagrams for a partial storage system are shown in figure1&2. At night, the water-glycol solution circulates through the chiller and the ice bank heat exchanger, bypassing the air handling coil that supplies conditioned air to occupied building spaces. During the day, the solution is cooled by the ice bank from 52 F to 34 F. A temperature modulation valve set at 44 F in a bypass loop around the ice bank permits a sufficient quantity of 52 F fluid to bypass the ice bank permits a sufficient quantity of 52 F fluid to bypass the ice bank, mix with the 34F fluid, and achieve the desired 44 F temperature. The 44 F fluid then enters the coil, where it cools air from approximately 75 F to 55 F. The fluid then leaves the coil at an elevated temperature (approximately 60F) and enters the water chiller where it is cooled 60F to 52 F. It is important to note that while making ice at night, the chiller must cool the water- glycol solution down to 26 F, rather than producing 44 F water required for conventional air conditioning systems. Chillers with air-cooled condensing also benefit from cooler outdoor ambient dry bulb temperatures to lower the system condensing temperature at night. The temperature modulating valve in the bypass loop has the added advantage of providing excellent capacity control. During mild temperature days, typically in the spring and fall, the chiller will often be capable of providing all the necessary cooling capacity for the building without the use of cooling capacity from the ice storage system. When the building’s actual cooling load is equal to or less than the chiller capacity at the time, all of the system coolant will flow through the bypass loop as shown in fig.3
  • 74. It is important that the coolant chosen by an ethylene glycol-based industrial coolant, such as Dowtherm SR-1 or UCAR Thermofluid 17, which is specially formulated for low viscosity and good heat transfer properties. Either of these fluids contain a multi-component corrosion inhibitor which is effective with most materials of construction including aluminium, copper, silver solder and plastics. Further, they contain no anti-leak agents and produce no films to interfere with heat transfer efficiency. They also permit use of standard pumps, seals and air handling coils. It should be noted, however, that because of the slight difference in heat transfer properties between water and the mild glycol solution, the cooling coil capacities will need to be increased by approximately 5 percent. It is also important that the water and glycol solution be thoroughly mixed before the solution is placed into the system. The use of ice storage system technology opens new doors to other economic opportunities in system design. These offer significant potential for not only first-cost savings but also operating cost savings that should be evaluated on a life cycle cost basis using a computerized economic analysis program. Back-Up Most A/C and refrigeration systems require some form of stand-by, or back-up, facility to protect against system failure and costly lost production time. The ice storage system, is an ideal, efficient solution for these applications. The ice storage system offers rapid response back-up in the form of an independent, static technology solution which ensures the highest degree of reliability.
  • 75. Advantages of Ice Storage Systems • Reduced installed plant capacity. • Reduced electrical installation for lower investment and saving in demand charges. • Reduced installed cooling tower capacity incase of water cooled system. • Reduced installed D.G. set capacity. • Better plant utilization with longer equipment life and lower operating costs. • Use of off-peak energy for lower energy bill, where differential tariff is applicable. Applications of Ice Storage System • Air-conditioning of industrial and commercial buildings - Offices, Hotels, Shopping Complexes, Supermarkets, etc. • Air-conditioning of data-processing centers, hospitals, telephone exchanges, etc. requiring added system reliability and security. • Dairy plants, Breweries, Food Processing, Bottling Plants, Chemical and Fertilizer Plants, Pharmaceuticals, etc.
  • 76. DUCTING DESIGN The satisfactory distribution of conditioned air requires a well designed and energy efficient air transport system with appropriate ducts and fans plus air treatment and control devices. The various method of duct designs, proper fan selection and control and methods of air distribution system control for acceptable comfort and air quality in the conditioned spaces are some of the points to be discussed. The various methods of duct designing are a. Constant Velocity method b. Equal friction method c. Static regain method Classification of Ducts Supply and return duct systems are classified with respect to the velocity and pressure of the air within the duct. Velocity There are tow types of air transmission systems used for airconditioning application. They are called Coventional or Low Velocity and High Velocity system. The dividing line between these systems is rather nebulous but, for the purpose of this section, the following initial supply air velocities are offered as a guide. 1. Commercial comfort air conditioning a. Low velocity – upto 2500 fpm normally between 1200 & 220 fpm b. High velocity – above 2500 fpm 2. Factory comfort airconditioning
  • 77. a. Low velocity - upto 2500 normally between 2200 and 2500 fpm. b. High velocity - above 2500 to 5000 fpm Normally return air systems for both low and high velocity supply air systems are designed as low velocity systems. The velocity range for commercial and factory comfort application is as follows: 1. Commercial comfort airconditioning - low velocity upto 2000 fpm. Normally between 1500 and 1800 fpm. 2. Factory comfort airconditioning - low velocity upto 2500 fpm. Normally between 1800 and 2200 fpm. Pressure Air distribution systems are divided into three pressure categories; low, medium and high. These divisions have the same pressure ranges as Class I, II & III fans and indicated: 1. Low pressure - upto 3¾ inch wg - class I fan 2. Medium pressure - from 3¾ to 6 ¾ inch wg - class II fan 3. High pressure - from 6 ¾ to 12 ¾ inch wg - class III These pressure ranges are total pressure, including the losses through the air handling apparatus, ductwork and the air terminal in the space. The choice of design method depends almost entirely upon the size of the ductwork installation. Small duct systems (homes, shops or a few office rooms) are commonly designed by the velocity method. Large high pressure systems are most frequently designed by computer software programs using the static regain method. Duct arrangements between these two extremes are nearly always laid out by the equal friction method. Sometimes a duct arrangement will be designed by a combination of two methods. For instance, the trunk duct will
  • 78. be laid out by the static regain method and the branch duct runs designed by the equal friction method. In designing ductwork, a new term called “unit friction” will be utilized which means the friction loss per 100 ft of duct work equivalent length. Regardless of the duct design method chosen by the air transport system designer, the final design and duct layout will likely result from the use of computerized duct design and drafting programs available that are based on algorithms from the ASHRAE hand book of fundamentals and other test data from SMACNA. Recommended and maximum Duct Velocities for Conventional System DESIGNATION RECOMMEND VELOCITIES, FPM RESIDENCES SCHOOLS, THEATERS, INDUSTRIAL PUBLIC BUILDINGS BUILDING Outdoor air intakes1 500 500 500 Filters1 250 300 350 Heating coils1,2 450 500 600 Cooling coils1 450 500 600 Air washers1 500 500 500 Fan outlets 1000 - 1600 1300 - 2000 1600 - 2400 Main ducts2 700 - 900 1000 - 1300 1200 - 1800 Branch ducts2 600 600 - 900 800 - 1000 Branch risers2 500 600 - 700 800 Maximum velocities, FPM Outdoor air intakes1 800 900 1200 Filters1 300 350 350 Heating coils1,2 500 600 700 Cooling coils1 450 500 600 Air washers 500 500 500 Fan outlets 1700 1500 - 2200 1700 - 2800 Main ducts2 800 - 1200 1100 - 1600 1300 - 2200 Branch ducts2 700 - 1000 800 - 1300 1000 - 1800 Branch risers2 650 - 800 800 - 1200 1000 - 1600
  • 79. 1 These velocities are for total face area, not the net free area : other velocities in table are for net free are 2 For low velocity systems only. @ 1965 American society of heating, refrigerating and airconditioning engineers, inc. reprinted by permission for ASHRAE guide and data book. PIPING DESIGN The water piping system are divided into once thru and re-circulating types. In a once thru system water passes thru the equipment only once and is discharged. In a re-circulating system water is not discharged, but flows in a repeating circuit from the heat exchanger to the refrigeration equipment and back to the heat exchanger. Open and Closed Both types are further classified as open or closed systems. An open system is one in which the water flows into a reservoir open to the atmosphere; cooling towers and air washers are examples of reservoirs open to the atmosphere. A closed system is one in which the flow of water is not exposed to the atmosphere at any point. This system usually contains an expansion tank that is open to the atmosphere but the water area exposed is insignificant. Water Piping Design There is a friction loss in any pipe thru which water is flowing. This loss depends on the following factors: 1. Water velocity 2. Pipe diameter 3. Interior surface roughness 4. Pipe length System pressure has not effect on the head loss of the equipment in the system. However, higher than normal system pressures may dictate the use of heavier
  • 80. pipe, fittings and valves along with specially designed equipment. To properly design a water piping system, the engineer must evaluate not only the pipe friction loss by the loss thru valves, fittings and other equipment. In addition to these friction losses, the use of diversity in reducing the water quantity and pipe size is to be considered in designing the water piping system.
  • 81. Pipe Friction Loss The pipe friction loss in a system depends on water velocity, pipe diameter, interior surface roughness and pipe length. Varying any one of these factors influences the total friction loss in the pipe. Most air conditioning applications use either steel pipe or copper tubing in the piping system. Charts enclosed are for schedule 40 pipe upto 24 inch diameter. Chart shows the friction losses for closed re-circulation piping systems and for once thru / open re-circulation piping systems. These charts show water velocity, pipe or tube diameter, and water quantity, in addition to the friction rate per 100 ft of equivalent pipe length. Knowing any two of these factors, the other two can be easily determined from the chart. The effect of inside roughness of the pipe or tube is considered in all these values. The water quantity is determined from the airconditioning load and the water velocity by pre-determined recommendations. These two factors are used to establish pipe size and friction rate. Water Velocity The velocities recommended for water piping depend on two conditions; 1. The service for which the pipe is to be used. 2. The effect of erosion. The design of the water piping system is limited by the maximum permissible flow velocity.
  • 82. Recommend Water Velocity SERVICE VELOCITY RANGE (FPS) Pump discharge 8 - 12 Pump suction 4-7 Drain line 4-7 Header 4 - 15 Riser 3 - 10 General service 3 - 10 City water 3-7