                                                                                          Voltage Monitoring Inputs (V1 & V2)
                                                                                          One analog voltage input channel (designated as V1) is dedicated to monitoring a
                                                                                          circuit-breaker dc power supply or a coil voltage (0 to 255 volts, dc or peak ac).
                                                                                          A second voltage input channel (designated as V2) is dedicated to detecting volt-
                                                                                          age on/off status (presence or absence) of an A/B switch (an input range of 30-
                                                                                          300 V dc or peak ac).
                                                                                          Trip/Close Current Monitoring
                                                                                          A built-in Hall-effect current sensor records the Trip/Close current level and duration.
                                                                                          The Trip/Close coil current waveform (effectively, a performance “fingerprint” or cur-
                                                                                          rent profile) can be used as a diagnostic tool for analysis of a breaker’s performance.
                                                                                          Breaker Stroke and Velocity




CT-8000
                                                                                          Three digital travel transducer channels enable the CT-8000 to measure stroke, over-
                                                                                          travel, and bounce-back. Unlike other types of travel transducers, the digital transduc-
                                                                                          er requires no calibration or setup. A contact-velocity calculation is based on a contact’s
                                                                                          travel distance over a period of time, which is defined by the breaker manufacturer’s

                                              TM
                                                                                          specifications. A special feature lets users “slow-close” a breaker and produce a test-
                                                                                          result report.
                                                                                          Dynamic Contact Resistance
                                                                                          One channel of Dynamic Contact Resistance test is also available. A built-in 200-ampere
                                                                                          power supply provides the test current for this application. Resistance measurement
The Vanguard Instrument Company, Inc. Model CT-8000™ EHV Circuit-Breaker
                                                                                          ranges from 1 micro-ohm to 1999 micro-ohms. The dynamic resistance test allows the
Analyzer is a fifth-generation design configuration. The Model CT-8000 is a stand-
                                                                                          user to monitor contact resistance during circuit breaker operation. This feature allows
alone, microcomputer-controlled Circuit-Breaker Analyzer that is inexpensive and
                                                                                          the user to detect circuit-breaker contact erosion, or contact problems that can not be
easy to use. It operates in either of two modes: As a traditional Time-vs-Travel ana-
                                                                                          detected in static resistance test. The CT-8000 can be used as a 200-ampere, micro-ohm
lyzer or as a Quick-Shot (on-line timing). The CT-8000 is available with either 3
                                                                                          meter to check circuit-breaker contact resistance, bus connection, or other applications
dry contacts (CT-8000-3) or 6 dry contacts (CT-8000-6) configurations. Both
                                                                                          where a low-resistance measurement is required.
models are supplied with 3 digital travel transducer input channels.
Quick Shot Mode                                                                           Resistor Type Transducer Input Channel
In the Quick-Shot mode, the CT-8000 captures the breaker’s trip or close time, the        One resistor type input channel is also available with the CT-8000. This input channel
Trip/close-coil current “fingerprint,” and the battery-supply voltage (while the          allows the CT-8000 to interface directly with resistive type transducers. The transducer
breaker is still on-line and in service). Trip/close time is derived from the time of     resistance ranges from 200 ohm to 10K Ohm.
trip, or at the close-coil initiation, to the breaker’s bushing current-break or -make    Timing Shot Storage Capabilities
(detected by an ac clamp-on current-probe).                                               The CT-8000 uses Flash Electrically Erasable PROMs (EEPROMs) to store timing data.
With a simple connection, the Quick-Shot mode detects a breaker’s operating con-          Unlike other storage media, EEPROMs are immune to shock, temperature, and humid-
ditions with little or no down (out of service) time. The Quick-Shot mode captures        ity. Stored timing shots can be recalled to re-analyze test data, print copies, or transfer
the First-Trip Operation time of the breaker. When a breaker has been in service          data to an IBM-PC database for record keeping. Up to 150 timing shots can be stored
for a long time (such as sitting in a closed position), the time of the breaker's first   in the EEPROMs.
trip may be slow (e.g., due to a "sticky" mechanism). Traditional breaker timing          Circuit-Breaker Test Plan
may not detect this condition, since several operations may have occurred before          Up to 99 breaker test plans can be stored in the CT-8000. Test plans comprise all
the first timing test is conducted.                                                       breaker specifications (stroke, velocity, contact time). By recalling a test plan, the
Conventional Time-versus-Travel Analyses Mode                                             user can instantly test a breaker and view a pass/fail report (made by comparing
In the Time-Travel mode, the CT-8000 analyzes circuit-breaker performance,                performance with specifications in the stored test plan). A user doesn’t need to
namely: contact time, stroke, velocity, over-travel, and wipe. A 200-ampere, built-       look-up a breaker’s specifications to compare with test results to determine if the
in, power supply allows the CT-8000 to perform contact dynamic-resistance tests.          breaker passed performance tests or not. Test plans can be downloaded to the CT-
Contact-motion analyses include: Open, Close, Open-Close, Close-Open, and Open-           8000 via an RS-232C serial port or via a USB port.
Close-Open switching sequences. The timing window is selectable: 1-second, 10-            Breaker Initiate Features
second, or 20-second periods. The 10-second and 20-second windows allow tim-
                                                                                          A built-in, solid-state, initiate device allows users to remotely operate the breaker
ing of long-duration events (e.g., circuit-switching contacts).




Circuit Breaker Time-Travel Analy
                                                                                          from the CT-8000. The operational mode includes: Open, Close, Open-Close,
Breaker Contact Timing Inputs                                                             Close-Open, and Open-Close-Open. Multiple operation (e.g., Open-Close, Open-
Contact timing uses dry-contact input channels. Each contact-input channel can detect     Close-Open) can be initiated by using a programmable delay time or by sensing the
main contact and insertion-resistor contact times (displayed in milliseconds & cycles).   breaker’s contact condition.




2
alyze
   Computer Interface
                            OCB, Vacuum, and SF6 Circuit
                            Breakers with Vanguard’s CT-8000
                                                                                          User Interface
   One RS-232C Interface port and one USB port allows the CT-8000 to be controlled        An alpha-numeric keypad allows users to enter breaker ID and control functions.
   from an IBM-PC-compatible computer. From the PC, circuit breakers can be timed         A 4-line by 20-character LCD readout displays user messages. The LCD is back
   and users can retrieve timing shots that have been saved in the CT-8000 flash EEP-     lighted so messages can be viewed in low light levels. Display contrast is controlled
   ROM. Windows® XP-based Breaker-Analysis software lets users retrieve test-shot         via the CT-8000 keypad.
   data stored in the computer’s hard-drive disk, re-analyze the stored data, and gen-
   erate reports in the office on an IBM-compatible computer. This PC software also
                                                                                          Built-in Thermal Printer
   allows users generate customized test-result reports and to create a circuit-breaker   A built-in thermal printer prints the breaker contact analysis results in both tab-
   database library. Additionally, users can create circuit-breaker test plans to be      ular and graphic formats on 4.5-inch-wide thermal paper.
   downloaded to the CT-8000.

         Voltage Input                                                                                                                Linear
             Channels
                                                                                                                                      Transducer
                                                                                                            Current Lead
       Contact Timing                                                                                       Connector
            Channels

                                                                                                            Sense Lead
     Travel Transducer                                                                                      Connector
            Connectors
                                                                                                            Power Receptacle
       USB Connector                                                                                        Module
                                                                                                            Resistor Transducer
             RS-232C                                                                                        Input
            Connector                                                                                       Breaker Initiate
          4x20 Backlit                                                                                      Output
          LCD Display
                                                                                                            4.5-inch
                                                                                                            Thermal Printer


      Rugged 16-Key
                                                                                                            Breaker Initiate
   Membrane Keyboard
                                                                                                            Arm Switch




                                                                                                                                     ABB
                                                                                                                                     AHMA-8




yzer
                                                                                                                                     Mechanism
                                                                                                                                     Transducer




                                                                          Vanguard Instruments Company
                                                                                                               Reliability Through Instrumentation
                                                                                                                                                                  RV April 06
Microcomputer Accuracy in an Inexp
                                                     Graphic and
                                               Tabulated Printouts

                                                                                  M Built-in Thermal Printer Output




                 EEPROM Stored Test Parameters
                                                               M




                                               M Trip Time Using Quickshot Mode




                                                                                                                      CT-8000
Trip Time Using Bushing CT
                                Trip Coil Current Profile



 PARTS ORDERING INFORMATION for the CT-8000 CIRCUIT BREAKER TIMER:
 All of the below listed replacement parts may be ordered from Vanguard Instruments Company, Inc.
 PC software and cables for CT-8000, 3 contact channels              Part No: CT-8000-3
 PC software and cables for CT-8000, 6 contact channels              Part No: CT-8000-6
 Carrying case for the CT-8000                                       Part No: CT-8000-CASE
 Printer paper, thermally sensitive                                  Part No: Paper-TP4
 CT-8000 TRAVEL TRANSDUCERS:
 10 inch linear transducer:                                          Part   No:   LT-10
 25 inch linear transducer:                                          Part   No:   LT-25
 30 inch linear transducer:                                          Part   No:   LT-30
 Rotary transducer:                                                  Part   No:   RT
 15 inch universal transducer:                                       Part   No:   UT-15
 ABB AHMA-8 Transducer                                               Part   No:   ST-AHMA-8
 ABB AHMB-8 Transducer                                               Part   No:   ST-AHMB-8




Circuit Breaker Time-Travel Analy
 Westinghouse SF/SFA transducer:                                     Part   No:   ST-SF/SFA
 Linear transducer case                                              Part   No:   LT-CASE
pensive Digital Circuit Breaker Tester
                         •   On-Line Timing/Capture First Trip Time
  FEATURES




                         •   Static & Dynamic Resistance Tests
                         •   Full Breaker Tabulated & Graphic Data Printout
                         •   Output Test Results to Built-in Thermal Printer
                         •   Digital Travel Transducer; No Setup or Calibration Required
                         •   Supports Resistance Type Transducers
                         •   Detect Main Contact and Insertion Resistor Contact on the Same Input Channel
                         •   On-Board Flash EEPROM Shot Storage/Test Plan Storage
                         •   Computer Interface (RS-232C or USB)




                                                         SPECIFICATIONS
                                           TYPE             Special purpose test equipment, portable circuit breaker analyzer
                         PHYSICAL SPECIFICATIONS            16” W by 11” H by 14” D (40.6 cm x 29.9 cm x 35.6 cm); Weight; 25 lbs (11.3 kg)
                                    INPUT POWER             90-130 Vac or 200-240 Vac (selectable), 50/60Hz
                              DRY-CONTACT INPUT             3 or 6 dry-input channels; Each channel detects Main and Insertion-Resistor Contacts
                                TIMING WINDOWS              Selectable: 1-second, 10-seconds or 20-seconds
                              TIMING RESOLUTION             50 microseconds at 1-second duration; 0.5 milliseconds at 10-second duration;
                                                            1.00 milliseconds at 20-second duration
                              TIMING ACCURACY               0.05% of reading, ±50 microseconds at 1-second duration
                      CONTACT DETECTION RANGE               Closed: <20 ohms, Open:> 5,000 ohms
                     RESISTOR DETECTION RANGE               50 – 5,000 Ohms
                            CT CURRENT SENSOR               One, None Contacting, 0-150 Amp
                        EXTERNAL TRIGGER INPUT              Open/Close: 30-300V dc or peak ac
                   VOLTAGE SENSING INPUT RANGE              V1: analog input; 0–255 V, dc or peak ac, Sensitivity: ± 1 V; V2: voltage detector (present/absent)
                                                            input; 30-300V, dc or peak ac
                             BREAKER OPERATION              Open, Close, Open-Close, Close-Open, Open-Close-Open
                      BREAKER INITIATE CAPACITY             25 A/250 V ac/dc max (100A Inrush)
                INITIATE CURRENT READING RANGE              One, Non-contact, Hall-Effect sensor, 0-20-amp range, dc to 5 kHz
                       TRAVEL TRANSDUCER INPUT              3 digital travel transducer channels; Linear range, 0.0-30.0 in (±0.01 in); Rotary range 0-360° (±0.36°)
              CONTACT TRAVEL POINT DIFFERENCE               Measures “Slow-Close” contact-point distances (hard copy printout)
              DYNAMIC/STATIC RESISTANCE RANGE               0.1 to 1,999 micro-ohm, Accuracy: ±2% of reading, ±5 micro-ohm
                       RESISTANCE TEST CURRENT              200 Amperes Typical
             RESISTOR TYPE TRANSUCER CHANNEL                200 Ohm to 10 K Ohm
                                        DISPLAY             4 lines by 20 character back-lit LCD, sunlight viewable
                                       PRINTOUT             Both graphic contact-travel waveforms & tabulated results are printed on a 4.5-inch thermal printer
                           TEST RECORD STORAGE              Store up to 150 timing records and 99 test plans
                             COMPUTE INTERFACE              RS-232C port, USB Port
                                   PC SOFTWARE              Furnished Circuit breaker analysis software running under Windows XP; features graphic display,
                                                            numerical reports, and data base utility for use at shop or office.
                                              SAFETY        Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92
                                        ENVIRONMENT         Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)
                                             OPTIONS        Hard case for shipping; available for both Travel Transducers and CT-8000




yzer
                                          WARRANTY          One-year warranty on parts and labor


             Note: The above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice.




                                                                             Vanguard Instruments Company
                                                                                                                   Reliability Through Instrumentation
                                                                                                                   Reliability Through Instrumentation
                                                                                                                                                                      RV April 06
Instruments Designed and Developed by the Hearts
and Minds of Utility Electricians Around the World
    You’ve seen a lot of utility test equipment in your time. You work with it routinely.
Your facility relies upon it to ensure peak performance. Often times, your maintenance
tasks are tedious, time-consuming and repetitive. But timely and accurate information
is the currency of maintaining maximum uptime and minimal repair, thus testing must
be done. Your instruments must be up to the task.
   Vanguard Instruments is familiar with your problems and shares in your desire to
make transformer and breaker testing fast, reliable, and simple. These principles
are the basis for every Vanguard design. They also form the premise for our ongoing
research and development as well as every innovative feature we introduce.
   How do we know what you’re looking for in utility test equipment? We’re there in
the trenches with you! Our Chief Engineer is frequently on-site at power utility sub-
stations around the country and all over the world; working, listening and talking
with electricians and technicians just like you. More than that, you’ve shown us the
real nitty-gritty of testing. We’ve taken that to heart and then back to the lab to solve
your problems. The results of your recommendations are embodied in utility test
equipment that is easy to use, lightweight, rugged and dependable. The EZCT-2000TM,
along with Vanguard’s full line of test equipment, leads the industry in accuracy and
automatically performs a range of tasks and calculations that were once the bane of
every utility electrician.
   We hope that you will take a few moments to consider the technological innovations
that are engineered into every Vanguard test instrument. Equally important, we want to
know that our past efforts make a present difference in your testing routines and on-line
uptime. We’re not done though. You can be confident we’re looking for new ways to
improve the results of your testing regimen. Thanks for choosing Vanguard Instruments.




      Vanguard Instruments Company, Inc.
               1520 S Hellman Ave. • Ontario, Calilfornia 91761 USA
                     Phone 909-923-9390 • Fax 909-923-9391
                     Website: www.vanguard-instruments.com

Mais conteúdo relacionado

Mais procurados

Brymen BM157 BM357 User's Manual
Brymen BM157 BM357 User's ManualBrymen BM157 BM357 User's Manual
Brymen BM157 BM357 User's Manualdegarden
 
Modular Multilevel Converter MMC tutorial
Modular Multilevel Converter MMC tutorialModular Multilevel Converter MMC tutorial
Modular Multilevel Converter MMC tutorialGhazal Falahi
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relaysRoberto Costa
 
Ahmed zahran power electronics projects portfolio
Ahmed zahran power electronics projects portfolioAhmed zahran power electronics projects portfolio
Ahmed zahran power electronics projects portfolioahmed_zahran
 
Power transformer maintenance
Power transformer maintenancePower transformer maintenance
Power transformer maintenanceLucian Lazar
 
LT3755 - High Side Sense LED Controller for High Current LED Applications
LT3755 - High Side Sense LED Controller for  High Current LED ApplicationsLT3755 - High Side Sense LED Controller for  High Current LED Applications
LT3755 - High Side Sense LED Controller for High Current LED ApplicationsPremier Farnell
 
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...Manmeet Singh
 
Optically Isolated Sigma-Delta Modulator ACPL-796J
Optically Isolated Sigma-Delta Modulator ACPL-796JOptically Isolated Sigma-Delta Modulator ACPL-796J
Optically Isolated Sigma-Delta Modulator ACPL-796JPremier Farnell
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsPower System Operation
 
Transformer protection commissioning tools
Transformer protection commissioning toolsTransformer protection commissioning tools
Transformer protection commissioning toolsmichaeljmack
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Default test templates raptor
Default test templates raptorDefault test templates raptor
Default test templates raptorEduardo Marchesi
 
Current sensor
Current sensorCurrent sensor
Current sensormiracu
 
Power Topologies_Full Deck_04251964_Mappus
Power Topologies_Full Deck_04251964_MappusPower Topologies_Full Deck_04251964_Mappus
Power Topologies_Full Deck_04251964_MappusSteve Mappus
 
Numerical protection 2
Numerical protection 2Numerical protection 2
Numerical protection 2angila95
 

Mais procurados (20)

Brymen BM157 BM357 User's Manual
Brymen BM157 BM357 User's ManualBrymen BM157 BM357 User's Manual
Brymen BM157 BM357 User's Manual
 
Modular Multilevel Converter MMC tutorial
Modular Multilevel Converter MMC tutorialModular Multilevel Converter MMC tutorial
Modular Multilevel Converter MMC tutorial
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Ahmed zahran power electronics projects portfolio
Ahmed zahran power electronics projects portfolioAhmed zahran power electronics projects portfolio
Ahmed zahran power electronics projects portfolio
 
Power transformer maintenance
Power transformer maintenancePower transformer maintenance
Power transformer maintenance
 
Ee2259 lab-manual
Ee2259 lab-manualEe2259 lab-manual
Ee2259 lab-manual
 
LT3755 - High Side Sense LED Controller for High Current LED Applications
LT3755 - High Side Sense LED Controller for  High Current LED ApplicationsLT3755 - High Side Sense LED Controller for  High Current LED Applications
LT3755 - High Side Sense LED Controller for High Current LED Applications
 
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
Presentation_ON-CHIP CURRENT SENSING TECHNIQUE FOR CMOS MONOLITHIC SWITCH-MOD...
 
Optically Isolated Sigma-Delta Modulator ACPL-796J
Optically Isolated Sigma-Delta Modulator ACPL-796JOptically Isolated Sigma-Delta Modulator ACPL-796J
Optically Isolated Sigma-Delta Modulator ACPL-796J
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Transformer protection commissioning tools
Transformer protection commissioning toolsTransformer protection commissioning tools
Transformer protection commissioning tools
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Default test templates raptor
Default test templates raptorDefault test templates raptor
Default test templates raptor
 
Syllabus
SyllabusSyllabus
Syllabus
 
Current sensor
Current sensorCurrent sensor
Current sensor
 
Bx26501512
Bx26501512Bx26501512
Bx26501512
 
Power Topologies_Full Deck_04251964_Mappus
Power Topologies_Full Deck_04251964_MappusPower Topologies_Full Deck_04251964_Mappus
Power Topologies_Full Deck_04251964_Mappus
 
Numerical protection 2
Numerical protection 2Numerical protection 2
Numerical protection 2
 
Uln2804
Uln2804Uln2804
Uln2804
 

Semelhante a Ct8000

Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSatish Pydimarla
 
Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315Kyoritsu India
 
Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315Kyoritsu India
 
Relay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdfRelay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdfEngrSyedGhulamMustaf
 
SMC TriRaptor Three-phase Primary Injection
SMC TriRaptor Three-phase Primary InjectionSMC TriRaptor Three-phase Primary Injection
SMC TriRaptor Three-phase Primary InjectionErika Herbozo
 
SMC PTE-100-C Current & Voltage Relay Testing
SMC PTE-100-C Current & Voltage Relay TestingSMC PTE-100-C Current & Voltage Relay Testing
SMC PTE-100-C Current & Voltage Relay TestingErika Herbozo
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchMiller Energy, Inc.
 
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUSData Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUSPT. Siwali Swantika
 
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configuredJavier Cuzco
 
Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...
Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...
Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...PT. Siwali Swantika
 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFjang041
 
7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relay7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relayashwini reliserv
 
Measurement and Relay Indications.pptx
Measurement and Relay Indications.pptxMeasurement and Relay Indications.pptx
Measurement and Relay Indications.pptxEngrSyedGhulamMustaf
 
UE One Series Safety Transmitter
UE One Series Safety TransmitterUE One Series Safety Transmitter
UE One Series Safety TransmitterIves Equipment
 
KG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meterKG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meterNIHON DENKEI SINGAPORE
 
Kg catalogue dc electronic load distributed by Nihon Denkei
Kg catalogue dc electronic load  distributed by Nihon DenkeiKg catalogue dc electronic load  distributed by Nihon Denkei
Kg catalogue dc electronic load distributed by Nihon DenkeiNIHON DENKEI SINGAPORE
 
Data Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COIL
Data Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COILData Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COIL
Data Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COILPT. Siwali Swantika
 

Semelhante a Ct8000 (20)

Substation_equipment_ (1).pptx
Substation_equipment_ (1).pptxSubstation_equipment_ (1).pptx
Substation_equipment_ (1).pptx
 
Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315
 
Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315Power Quality Analyzer Kew 6315
Power Quality Analyzer Kew 6315
 
Relay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdfRelay and Indications by sgm for protection engineers.pdf
Relay and Indications by sgm for protection engineers.pdf
 
SMC TriRaptor Three-phase Primary Injection
SMC TriRaptor Three-phase Primary InjectionSMC TriRaptor Three-phase Primary Injection
SMC TriRaptor Three-phase Primary Injection
 
SMC PTE-100-C Current & Voltage Relay Testing
SMC PTE-100-C Current & Voltage Relay TestingSMC PTE-100-C Current & Voltage Relay Testing
SMC PTE-100-C Current & Voltage Relay Testing
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
 
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUSData Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
 
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
1 mrk511232 ben-e_en_product_guide__rec670_1.2_pre-configured
 
Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...
Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...
Data Teknis Gossen Metrawatt Multimeter METRAHIT : PM TECH, PM XTRA, EBASE, E...
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEF
 
7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relay7SR23 High Impedance Bus Bar Protection Relay
7SR23 High Impedance Bus Bar Protection Relay
 
Measurement and Relay Indications.pptx
Measurement and Relay Indications.pptxMeasurement and Relay Indications.pptx
Measurement and Relay Indications.pptx
 
UE One Series Safety Transmitter
UE One Series Safety TransmitterUE One Series Safety Transmitter
UE One Series Safety Transmitter
 
KG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meterKG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meter
 
Kg catalogue dc electronic load
Kg catalogue dc electronic loadKg catalogue dc electronic load
Kg catalogue dc electronic load
 
Kg catalogue dc electronic load distributed by Nihon Denkei
Kg catalogue dc electronic load  distributed by Nihon DenkeiKg catalogue dc electronic load  distributed by Nihon Denkei
Kg catalogue dc electronic load distributed by Nihon Denkei
 
Data Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COIL
Data Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COILData Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COIL
Data Teknis Gossen Metrawatt Multimeter : METRAHIT ISO & METRAHIT COIL
 
havells ppt
havells ppthavells ppt
havells ppt
 

Último

Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin ClassesCeline George
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxVishalSingh1417
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphThiyagu K
 
Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.MateoGardella
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docxPoojaSen20
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingTechSoup
 
fourth grading exam for kindergarten in writing
fourth grading exam for kindergarten in writingfourth grading exam for kindergarten in writing
fourth grading exam for kindergarten in writingTeacherCyreneCayanan
 
Making and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfMaking and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfChris Hunter
 
Gardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch LetterGardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch LetterMateoGardella
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfJayanti Pande
 
Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Disha Kariya
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17Celine George
 
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...KokoStevan
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxAreebaZafar22
 
Unit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptxUnit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptxVishalSingh1417
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfagholdier
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityGeoBlogs
 

Último (20)

Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17  How to Extend Models Using Mixin ClassesMixin Classes in Odoo 17  How to Extend Models Using Mixin Classes
Mixin Classes in Odoo 17 How to Extend Models Using Mixin Classes
 
Unit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptxUnit-V; Pricing (Pharma Marketing Management).pptx
Unit-V; Pricing (Pharma Marketing Management).pptx
 
Z Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot GraphZ Score,T Score, Percential Rank and Box Plot Graph
Z Score,T Score, Percential Rank and Box Plot Graph
 
Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.Gardella_Mateo_IntellectualProperty.pdf.
Gardella_Mateo_IntellectualProperty.pdf.
 
PROCESS RECORDING FORMAT.docx
PROCESS      RECORDING        FORMAT.docxPROCESS      RECORDING        FORMAT.docx
PROCESS RECORDING FORMAT.docx
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 
fourth grading exam for kindergarten in writing
fourth grading exam for kindergarten in writingfourth grading exam for kindergarten in writing
fourth grading exam for kindergarten in writing
 
Making and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdfMaking and Justifying Mathematical Decisions.pdf
Making and Justifying Mathematical Decisions.pdf
 
Gardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch LetterGardella_PRCampaignConclusion Pitch Letter
Gardella_PRCampaignConclusion Pitch Letter
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdf
 
Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..Sports & Fitness Value Added Course FY..
Sports & Fitness Value Added Course FY..
 
How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17How to Give a Domain for a Field in Odoo 17
How to Give a Domain for a Field in Odoo 17
 
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
SECOND SEMESTER TOPIC COVERAGE SY 2023-2024 Trends, Networks, and Critical Th...
 
Advance Mobile Application Development class 07
Advance Mobile Application Development class 07Advance Mobile Application Development class 07
Advance Mobile Application Development class 07
 
ICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptxICT Role in 21st Century Education & its Challenges.pptx
ICT Role in 21st Century Education & its Challenges.pptx
 
Unit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptxUnit-IV; Professional Sales Representative (PSR).pptx
Unit-IV; Professional Sales Representative (PSR).pptx
 
Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024Mehran University Newsletter Vol-X, Issue-I, 2024
Mehran University Newsletter Vol-X, Issue-I, 2024
 
Holdier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdfHoldier Curriculum Vitae (April 2024).pdf
Holdier Curriculum Vitae (April 2024).pdf
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 

Ct8000

  • 1.
  • 2. Rapidly Ana Voltage Monitoring Inputs (V1 & V2) One analog voltage input channel (designated as V1) is dedicated to monitoring a circuit-breaker dc power supply or a coil voltage (0 to 255 volts, dc or peak ac). A second voltage input channel (designated as V2) is dedicated to detecting volt- age on/off status (presence or absence) of an A/B switch (an input range of 30- 300 V dc or peak ac). Trip/Close Current Monitoring A built-in Hall-effect current sensor records the Trip/Close current level and duration. The Trip/Close coil current waveform (effectively, a performance “fingerprint” or cur- rent profile) can be used as a diagnostic tool for analysis of a breaker’s performance. Breaker Stroke and Velocity CT-8000 Three digital travel transducer channels enable the CT-8000 to measure stroke, over- travel, and bounce-back. Unlike other types of travel transducers, the digital transduc- er requires no calibration or setup. A contact-velocity calculation is based on a contact’s travel distance over a period of time, which is defined by the breaker manufacturer’s TM specifications. A special feature lets users “slow-close” a breaker and produce a test- result report. Dynamic Contact Resistance One channel of Dynamic Contact Resistance test is also available. A built-in 200-ampere power supply provides the test current for this application. Resistance measurement The Vanguard Instrument Company, Inc. Model CT-8000™ EHV Circuit-Breaker ranges from 1 micro-ohm to 1999 micro-ohms. The dynamic resistance test allows the Analyzer is a fifth-generation design configuration. The Model CT-8000 is a stand- user to monitor contact resistance during circuit breaker operation. This feature allows alone, microcomputer-controlled Circuit-Breaker Analyzer that is inexpensive and the user to detect circuit-breaker contact erosion, or contact problems that can not be easy to use. It operates in either of two modes: As a traditional Time-vs-Travel ana- detected in static resistance test. The CT-8000 can be used as a 200-ampere, micro-ohm lyzer or as a Quick-Shot (on-line timing). The CT-8000 is available with either 3 meter to check circuit-breaker contact resistance, bus connection, or other applications dry contacts (CT-8000-3) or 6 dry contacts (CT-8000-6) configurations. Both where a low-resistance measurement is required. models are supplied with 3 digital travel transducer input channels. Quick Shot Mode Resistor Type Transducer Input Channel In the Quick-Shot mode, the CT-8000 captures the breaker’s trip or close time, the One resistor type input channel is also available with the CT-8000. This input channel Trip/close-coil current “fingerprint,” and the battery-supply voltage (while the allows the CT-8000 to interface directly with resistive type transducers. The transducer breaker is still on-line and in service). Trip/close time is derived from the time of resistance ranges from 200 ohm to 10K Ohm. trip, or at the close-coil initiation, to the breaker’s bushing current-break or -make Timing Shot Storage Capabilities (detected by an ac clamp-on current-probe). The CT-8000 uses Flash Electrically Erasable PROMs (EEPROMs) to store timing data. With a simple connection, the Quick-Shot mode detects a breaker’s operating con- Unlike other storage media, EEPROMs are immune to shock, temperature, and humid- ditions with little or no down (out of service) time. The Quick-Shot mode captures ity. Stored timing shots can be recalled to re-analyze test data, print copies, or transfer the First-Trip Operation time of the breaker. When a breaker has been in service data to an IBM-PC database for record keeping. Up to 150 timing shots can be stored for a long time (such as sitting in a closed position), the time of the breaker's first in the EEPROMs. trip may be slow (e.g., due to a "sticky" mechanism). Traditional breaker timing Circuit-Breaker Test Plan may not detect this condition, since several operations may have occurred before Up to 99 breaker test plans can be stored in the CT-8000. Test plans comprise all the first timing test is conducted. breaker specifications (stroke, velocity, contact time). By recalling a test plan, the Conventional Time-versus-Travel Analyses Mode user can instantly test a breaker and view a pass/fail report (made by comparing In the Time-Travel mode, the CT-8000 analyzes circuit-breaker performance, performance with specifications in the stored test plan). A user doesn’t need to namely: contact time, stroke, velocity, over-travel, and wipe. A 200-ampere, built- look-up a breaker’s specifications to compare with test results to determine if the in, power supply allows the CT-8000 to perform contact dynamic-resistance tests. breaker passed performance tests or not. Test plans can be downloaded to the CT- Contact-motion analyses include: Open, Close, Open-Close, Close-Open, and Open- 8000 via an RS-232C serial port or via a USB port. Close-Open switching sequences. The timing window is selectable: 1-second, 10- Breaker Initiate Features second, or 20-second periods. The 10-second and 20-second windows allow tim- A built-in, solid-state, initiate device allows users to remotely operate the breaker ing of long-duration events (e.g., circuit-switching contacts). Circuit Breaker Time-Travel Analy from the CT-8000. The operational mode includes: Open, Close, Open-Close, Breaker Contact Timing Inputs Close-Open, and Open-Close-Open. Multiple operation (e.g., Open-Close, Open- Contact timing uses dry-contact input channels. Each contact-input channel can detect Close-Open) can be initiated by using a programmable delay time or by sensing the main contact and insertion-resistor contact times (displayed in milliseconds & cycles). breaker’s contact condition. 2
  • 3. alyze Computer Interface OCB, Vacuum, and SF6 Circuit Breakers with Vanguard’s CT-8000 User Interface One RS-232C Interface port and one USB port allows the CT-8000 to be controlled An alpha-numeric keypad allows users to enter breaker ID and control functions. from an IBM-PC-compatible computer. From the PC, circuit breakers can be timed A 4-line by 20-character LCD readout displays user messages. The LCD is back and users can retrieve timing shots that have been saved in the CT-8000 flash EEP- lighted so messages can be viewed in low light levels. Display contrast is controlled ROM. Windows® XP-based Breaker-Analysis software lets users retrieve test-shot via the CT-8000 keypad. data stored in the computer’s hard-drive disk, re-analyze the stored data, and gen- erate reports in the office on an IBM-compatible computer. This PC software also Built-in Thermal Printer allows users generate customized test-result reports and to create a circuit-breaker A built-in thermal printer prints the breaker contact analysis results in both tab- database library. Additionally, users can create circuit-breaker test plans to be ular and graphic formats on 4.5-inch-wide thermal paper. downloaded to the CT-8000. Voltage Input Linear Channels Transducer Current Lead Contact Timing Connector Channels Sense Lead Travel Transducer Connector Connectors Power Receptacle USB Connector Module Resistor Transducer RS-232C Input Connector Breaker Initiate 4x20 Backlit Output LCD Display 4.5-inch Thermal Printer Rugged 16-Key Breaker Initiate Membrane Keyboard Arm Switch ABB AHMA-8 yzer Mechanism Transducer Vanguard Instruments Company Reliability Through Instrumentation RV April 06
  • 4. Microcomputer Accuracy in an Inexp Graphic and Tabulated Printouts M Built-in Thermal Printer Output EEPROM Stored Test Parameters M M Trip Time Using Quickshot Mode CT-8000 Trip Time Using Bushing CT Trip Coil Current Profile PARTS ORDERING INFORMATION for the CT-8000 CIRCUIT BREAKER TIMER: All of the below listed replacement parts may be ordered from Vanguard Instruments Company, Inc. PC software and cables for CT-8000, 3 contact channels Part No: CT-8000-3 PC software and cables for CT-8000, 6 contact channels Part No: CT-8000-6 Carrying case for the CT-8000 Part No: CT-8000-CASE Printer paper, thermally sensitive Part No: Paper-TP4 CT-8000 TRAVEL TRANSDUCERS: 10 inch linear transducer: Part No: LT-10 25 inch linear transducer: Part No: LT-25 30 inch linear transducer: Part No: LT-30 Rotary transducer: Part No: RT 15 inch universal transducer: Part No: UT-15 ABB AHMA-8 Transducer Part No: ST-AHMA-8 ABB AHMB-8 Transducer Part No: ST-AHMB-8 Circuit Breaker Time-Travel Analy Westinghouse SF/SFA transducer: Part No: ST-SF/SFA Linear transducer case Part No: LT-CASE
  • 5. pensive Digital Circuit Breaker Tester • On-Line Timing/Capture First Trip Time FEATURES • Static & Dynamic Resistance Tests • Full Breaker Tabulated & Graphic Data Printout • Output Test Results to Built-in Thermal Printer • Digital Travel Transducer; No Setup or Calibration Required • Supports Resistance Type Transducers • Detect Main Contact and Insertion Resistor Contact on the Same Input Channel • On-Board Flash EEPROM Shot Storage/Test Plan Storage • Computer Interface (RS-232C or USB) SPECIFICATIONS TYPE Special purpose test equipment, portable circuit breaker analyzer PHYSICAL SPECIFICATIONS 16” W by 11” H by 14” D (40.6 cm x 29.9 cm x 35.6 cm); Weight; 25 lbs (11.3 kg) INPUT POWER 90-130 Vac or 200-240 Vac (selectable), 50/60Hz DRY-CONTACT INPUT 3 or 6 dry-input channels; Each channel detects Main and Insertion-Resistor Contacts TIMING WINDOWS Selectable: 1-second, 10-seconds or 20-seconds TIMING RESOLUTION 50 microseconds at 1-second duration; 0.5 milliseconds at 10-second duration; 1.00 milliseconds at 20-second duration TIMING ACCURACY 0.05% of reading, ±50 microseconds at 1-second duration CONTACT DETECTION RANGE Closed: <20 ohms, Open:> 5,000 ohms RESISTOR DETECTION RANGE 50 – 5,000 Ohms CT CURRENT SENSOR One, None Contacting, 0-150 Amp EXTERNAL TRIGGER INPUT Open/Close: 30-300V dc or peak ac VOLTAGE SENSING INPUT RANGE V1: analog input; 0–255 V, dc or peak ac, Sensitivity: ± 1 V; V2: voltage detector (present/absent) input; 30-300V, dc or peak ac BREAKER OPERATION Open, Close, Open-Close, Close-Open, Open-Close-Open BREAKER INITIATE CAPACITY 25 A/250 V ac/dc max (100A Inrush) INITIATE CURRENT READING RANGE One, Non-contact, Hall-Effect sensor, 0-20-amp range, dc to 5 kHz TRAVEL TRANSDUCER INPUT 3 digital travel transducer channels; Linear range, 0.0-30.0 in (±0.01 in); Rotary range 0-360° (±0.36°) CONTACT TRAVEL POINT DIFFERENCE Measures “Slow-Close” contact-point distances (hard copy printout) DYNAMIC/STATIC RESISTANCE RANGE 0.1 to 1,999 micro-ohm, Accuracy: ±2% of reading, ±5 micro-ohm RESISTANCE TEST CURRENT 200 Amperes Typical RESISTOR TYPE TRANSUCER CHANNEL 200 Ohm to 10 K Ohm DISPLAY 4 lines by 20 character back-lit LCD, sunlight viewable PRINTOUT Both graphic contact-travel waveforms & tabulated results are printed on a 4.5-inch thermal printer TEST RECORD STORAGE Store up to 150 timing records and 99 test plans COMPUTE INTERFACE RS-232C port, USB Port PC SOFTWARE Furnished Circuit breaker analysis software running under Windows XP; features graphic display, numerical reports, and data base utility for use at shop or office. SAFETY Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92 ENVIRONMENT Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F) OPTIONS Hard case for shipping; available for both Travel Transducers and CT-8000 yzer WARRANTY One-year warranty on parts and labor Note: The above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice. Vanguard Instruments Company Reliability Through Instrumentation Reliability Through Instrumentation RV April 06
  • 6. Instruments Designed and Developed by the Hearts and Minds of Utility Electricians Around the World You’ve seen a lot of utility test equipment in your time. You work with it routinely. Your facility relies upon it to ensure peak performance. Often times, your maintenance tasks are tedious, time-consuming and repetitive. But timely and accurate information is the currency of maintaining maximum uptime and minimal repair, thus testing must be done. Your instruments must be up to the task. Vanguard Instruments is familiar with your problems and shares in your desire to make transformer and breaker testing fast, reliable, and simple. These principles are the basis for every Vanguard design. They also form the premise for our ongoing research and development as well as every innovative feature we introduce. How do we know what you’re looking for in utility test equipment? We’re there in the trenches with you! Our Chief Engineer is frequently on-site at power utility sub- stations around the country and all over the world; working, listening and talking with electricians and technicians just like you. More than that, you’ve shown us the real nitty-gritty of testing. We’ve taken that to heart and then back to the lab to solve your problems. The results of your recommendations are embodied in utility test equipment that is easy to use, lightweight, rugged and dependable. The EZCT-2000TM, along with Vanguard’s full line of test equipment, leads the industry in accuracy and automatically performs a range of tasks and calculations that were once the bane of every utility electrician. We hope that you will take a few moments to consider the technological innovations that are engineered into every Vanguard test instrument. Equally important, we want to know that our past efforts make a present difference in your testing routines and on-line uptime. We’re not done though. You can be confident we’re looking for new ways to improve the results of your testing regimen. Thanks for choosing Vanguard Instruments. Vanguard Instruments Company, Inc. 1520 S Hellman Ave. • Ontario, Calilfornia 91761 USA Phone 909-923-9390 • Fax 909-923-9391 Website: www.vanguard-instruments.com