IS : 1641-1988
Indian Standard
CODE OF PRACTICE FOR
FIRE SAFETY OF BUILDING (GENERAL):
GENERAL PRINCIPLES OF FIRE
GRADING AND CLASSIFICATION
( First Revision)
0. FOREWORD
0.1 The Indian Standard ( First Revision ) was
adopted by the Bureau of Indian Standards on
2 May 1988, after the draft finalized by the Fire
Safety Sectional Committee had been approved
by the Civil Engineering Division Council.
0.2 A series of Indian Standards covering fire,
safety of buildings in general principles of fire
grading details of construction, exit requirements
and exposure hazards have been formulated.
This Indian Standard covers general principles
of fire grading and classification, which has been
adopted in various Indian standards in respect to
fire safety aspects. This standard was first issued
in 1960. Based on considerable research done
on field of fire protection in the past 25 years in
advanced countries like USA, UK and Canada, the
method of classification of building has been
revised and covered in this revision. Further the
calorific values and list of hazardous materials
as existing have been deleted as the same are
available in all standard text Books.
NOTE- The information relating to calorific values
and hazardous, materials in detail is covered in Hand-
book on Fire Protection ( under preparation ).
0.3 For the purpose of deciding whether a parti- -
cular requirements of this standard is complied
with, the final value, observed or calculated,
expressing the result of a test or analysis, shall be
rounded off in accordance wilh IS : 2 - 1960*.
The number of significant places retained in the
rounded off value should be the same as that of
the specified value in this standard.
*Rulesfor rounding off numerical values ( revised ).
1. SCOPE
1.1 This code covers the general principles of
fire grading of buildings and classification.
2. FIRE LOAD
2.1 Classification - Fire load is the amount of
heat in kilocalories which is liberated per square
metre of floor area of a compartment by the
combustion of the contents of the building and
any combustible parts of the building itself. This
amount of heat is used as the basis for classifica-
tion of occupancies.
2.2 The fire load is determined by multiplying
the weight of all combustible materials by their
calorific values and dividing the figure by the
floor area under consideration.
2.3 Different materials having the same weight
and same calorific value may present different
hazards on account of their other properties,
such as ease of ignition, speed of burning, and
liberation of heat and fumes. Thus, some
‘inateirals are more readily ignited than others,
1
again, some burn more rapidly than others, some
materials when heated on fire liberate dangerous
fumes, and some may readily cause ignition of
other materials.
2.4 The content of a building are rarely distri-
buted uniformly over the whole floor area. ,From
the fire protection point, it would be undesirable
to have all combustible material concentrated on
a fraction of the floor area, as the average taken
over the whole area would not give a true
representation of the actual conditions, and the
resulting effects on the structure immediately
surrounding would be out of all proportion to
these expected on the basis of average fire load.
3. CLASSIFICATION OF BUILDING BASED
ON OCMJPANCY
3.1 General Classifhation -All buildings
should be classified, according to the use or the
character of occupancy in one of the following
groups :
Group A Residential
XS:1641-1988
Group B Educational
Group C Institutional
Group D Assembly
Group E Business
Group F Mercantile
Group G Industrial
Group H Storage
Group J Hazardous
3.1.1 Minor occupancy incidental to operations
in another type of occupancy should be consi-
dered as part of the main occupancy and should
be classified under the relevant group for the
main occupancy.
Examples of buildings in each group are given
in 3.1.1.1 to 3.1.1.9.
3.1.1.1 Group A residential buildings -
These should include any building in which
sleeping accommodation is provided for normal
residential purposes, with or without cooking or
dining or both facilities, except any building
classified under Group C.
Buildings and structures under Group A
shou!d be further subdivided as follows:
a) Subdivision A-l lodging for rooming
houses - These should include any build-
ing or group of buildings under the same
management, in which separate sleeping
accommodation for total of not more than
15 persons, on transient or permanent
basis, with or without dining facilities, but
without cooking facilities for individuals,
is provided.
A lodging or rooming house should be
classified as a dwelling in Subdivision A-2,
if no room in any of its private dwelling
units is rented to more than three persons.
b) Subdivision A-2 one- or two-family private
dwelling - These should include any
private dwelling which is occupied by
members of a single family and has a total
sleeping accommodation for not more than
20 persons.
If rooms in a private dwelling are rented
to outsiders, these should be For accommo-
dating not more than three persons per
room.
If sleeping accommodation for more than
20 persons is provided in any one resi-
dential building, it shall be classiiied as a
building in Subdivision A-3 or A-4 as the
case may be.
Subdivision A 3 dormitories - These should
include any building in which group
sleeping accommodation is provided, with
or without dining facilities, -for persons
4
4
who are not members of the same family,
in one room or a series of closely associ-
ated rooms under joint occupancy and
single management, for example, school
and college dormitories, students’ and
their hostels, and military barracks.
Subdivision A-4 apartment houses ( j?ats )
- These should include any building or
structure in which living quarters are
provided for three or more families, living
independently of each other and with
independent cooking facilities, for example,
apartment houses, mansions and chawls.
Subdivision A-5 hotels - These should
include any building or group of buildings
under single management, in which sleep-
ing accommodation with or without
dining facilities, is provided for hire to
more than 15 persons who are primarily
transient, for example, hotels, inns, clubs
and motels.
3.1.1.2Group B educational buildings -
These should include any buildings used for
school, college or day-care purposes involving
assembly for instruction, education or recreation
and which is not covered by Group D.
3.1.1.3 Group C institutional buildings -
These should include any building or part thereof,
which is used for purposes, such as medical or
other treatment or care of persons suffering from
physical or mental illness, disease or infirmity;
care of infants, convalescents or aged persons
and for penal or correctional detention in which
the Iiberty of the inmates is restricted. Insti-
tutional buildings ordinarily provide sleeping
accommodation for the occupants.
Buildings and structures under Group C
should be further subdivided as follows:
a)
b)
cl
Subdivision C-I hospitals and sanatoria -
This subdivision include any buildmg or a
group of buildings under single manage-
ment, which is used for housing persons
suffering from physical limitations because
of health or age, for example, hospitals,
infirmaries, sanatoria and nursing homes.
Subdivision C-2 custodial institutions -
This subdivision should include any build-
ing or a group of buildings under single
management, which is used for the custody
and care of persons, such as children con-
valescents and the aged, for example,
homes for the aged and infirm, convales-
cent homes and orphanages.
Subdivision C-3 penal and mental insti-
tutions - This subdivision should include
any building or a group of buildings under
single management, which is used for hous-
ing persons under restraint, or who are
2.
detained for penal or corrective purposes,
in which the Iiberty of the inmates is
restricted, for example, jails, prisons,
mental hospitals, mental sanatoria and
reformatories.
3.1.1.4 GPOUPD, assembly buildings - These
should include any building or part of a
building, where groups of people congregate or
-gather for amusement, recreation, social, reli-
gious, patriotic, civil, travel and similar purposes,
for example, theatres, motion picture houses,
assembly halls, auditoria, exhibition halls,
museums, skating rinks, gymnasiums, restaurants,
places of worship, dance halls, club rooms,
passenger stations and terminals of air, surface
.and marine public transportation services, recre-
ation piers and stadia, etc.
Buildings under Group D should be further
subdivided as follows:
a)
b)
4
4
Subdivision D-I - This subdivision should
include any building primarily meant for
theatrical or operatic performance and
exhibitions, and which has a raised stage,
proscenium curtain, fixed or portable
scenery or scenery loft, lights, motion
picture booth, mechanical appliances or
other theatrical accessories and equipment,
and which is provided with fixed seats for
over 1 000 persons.
Subdivision D-2 - This subdivision should
include any building primarily meant for
use as described for Subdivision D-1, but
with fixed seats for less than 1 000 persons.
Subdivision D-3 - This subdivision should
include any building, its lobbies, rooms
and other spaces connected thereto, pri-
marily intended for assembly of people,
but which has no theatrical stage or theat-
rical and/or cinematographic accessories,
and has accommodation for more than 300
persons, for example, dance halls, night
clubs, halls for incidental picture shows,
dramatic, theatrical or educational present-
ation, lectures or other simiiar purposes,
having no theatrical stage except a raised
platform and used without permanent
seating arrangement; art galleries,
museums, lecture halls, libraries, passenger
terminals; and buildings used for educa-
tional purposes for less than 8 hours per
week.
Subdivision D-4 - This subdivision should
include any building primarily intended
for use as described in Subdivision D-3;
but with accommodation for less than 300
persons.
Subdivision D-5 - This subdivision should
include any building meant for outdoor
assembiy of people not covered by Sub-
8s : 1641- 1988
divisions D-l to D-4, for example, grand-
stands, stadia, amusement park structures,
reviewing stands and circus tents.
3.1.1.5 Group E business buildings - These
should include any building or part of a
building which is used for transaction of business
( other than that covered by Group F and parts of
buildings covered by 3.1.1 ) for keeping of
accounts and records and similar purposes,
professional establishments, service facilities, etc.
City halls, town halls, court houses and libraries
should be classified in this group so far as the
principal function of these is transaction of
public business and keeping of books and records.
Business buildings should be further sub-
classified as follows:
a) Subdivision E-I - Offices, banks, pro-
fessional establishments, like offices of
architects, engineers, doctors, lawyers, etc.
b) Subdivision E-2 - Laboratories, research
establishments and test houses.
c) Subdivision E-3 - Computer installations.
3.1.1.6 Group F mercantile buildings -
These should include any building or part of a
building, which is used as shops, stores, market,
for display and sale of merchandise, either whole-
sale or retail.
Mercantile buildings should be further sub-
classified as follows :
a) Subdivision F-l - Shops, stores, markets
with rrea up to 500 ma.
b) Subdivkion F-2 - Underground shopping
centres, departmental stores with area
more than 500 m2.
Storage and service facilities incidental to the
sale of merchandise and located in the same
building should be included under this group.
3.1.1.7 Group G industrial buildings - These
should include any building or part of a
building or structure, in which products or
materials of all kinds and properties are fabti-
cated, assembled, manufactured or processed,
for example, assembly plants, laboratories,’ dry
cleaning plants, power plants, pumping stations,
smoke houses, laundries, gas plants, refineries,
dairies and mills.
The hazard of occupancy, for the purpose of
the Code should be the relative danger of the
start and spread of fire, the danger sf smoke or
gases generated, the danger of explosion or
other occurrence potentially endangering the lives
and safety of the occupants of the buildings.
Hazard of occupancy should be determined
by the authority on the basis of the character of
the contents and the processes or operations
3
Is;.!.1641 - 1988
conducted in. the building, provided, however,
that the combustibility .of the building, the flame
spread rating of the interior finish or other
features of the building or structure are such as
to involve a greater than the occupancy hazard,
the greater degree of hazard should govern the
classification.
Where different degrees of hazard of occu-
pancy exist in different parts of a building, the
most hazardous of those should govern the
classification for the purpose of this code, except
in as far as hazardous areas are segregated or
protected as specified in the code.
Buildings under Group G shall be further
sub-divided as follows:
a)
b)
4
Subdivision G-I - This subdivision should
include any building in which the contents
are of such low combustibility and the
industrial processes or operations con-
ducted therein are of such a nature that
there are no possibilities for any self-
propagating fire to occur and the only
consequent danger to life and property
may arise from panic, fumes or smoke, or
fire from some external source.
Subdivision G-2 - This subdivision should
include any building in which the contents
or industrial processes of operations con-
ducted therein are liable to give rise to a
fire which will burn with extreme rapidity
and give off a considerable volume of
smoke, but from which neither toxic fumes
nor explosions are to be feared in the event
of a fire.
Subdivision G-3 - This subdivision should
include any building in which the contents
or industrial processes or operations con-
ducted therein are liable to give :ise to
a fire which will burn with extreme rapi-
dity or from which poisonous fumes are
explosions are to be feared in the event of
a fire.
3.1.1.8 Group H storage buildings - These
should include any building or part of a
building. used primarily for the storage or
sheltering ( including servicing, processing or
repairs incidental to storage ) of goods wares or
merchandise ( except ) those that. involve highly
combustible or explosive products or materials ),
vehicles or animals, for example, warehouses,
cold storage, freight depots, transit sheds, store-
houses, truck and marine terminals garages,
hangars ( other than aircraft repair hangars )
grain elevators, barns and stables.
Storage properties are characterized by t,he
presence of relatively small number of persons in
proportion to the area. Any new use which
increases the number of occupants to a figure
comparable with other classes of occupancy
should change the classification of the building
to that of. the new use, example, hangars used
for assembly purposes, warehouses used for office
purposes, garage buildings used or manu-
facturing.
3.1.1.9 Group J hazardms hri1di:lg.r- These
should include any building or part of a
building which is used for the storage, handling,.
manufacture or processing of highly combustible
or explosive materials or products are liable to
burn with extreme rapidity and/or which may
produce poisonous fumes or explosions for
storage, handling, manufacturing or processing
which involve highly corrosive, toxic or noxious
alkalis, acids or other liquids or chemicals
producing flame, fumes and explosive poisonous..
irritant or corrosive gases; and for the storag.,
handling or processing of any material corrosive
gases; and for the storage, handling or processing
of any material producing explosive mixtures of
dust which result in the division of matter into
line particles subject to spontaneous ignition.
Examples of buildings in this class are those
buildings which are used for:
a) Storage, under pressure of more than
0’1 N/mm2 and in quantities exceeding
70 m3 .of acetylene, hydrogen, illuminating
and natural gases, ammonia, chlorine,
phosgene, sulphur dioxide, carbon dioxide,
methyloxide and all gases subject to
explosion, fume or toxic hazard, cryogenic
gases, etc;
b)
d)
Storage and handling of hazardous and
highly flammable liquids, rocket propel-
lants, etc;
Storage and handling of hazardous and
highly flammable or explosive materials,
other than liquids; and
Manufacture of artificial flowers, synthetic
leather, ammunition, explosives and fire-
works.
3.2 Any building not covered by the above
should be classified in the group which most
nearly resembles its existing or proposed use.
3.3 Where change in the occupancy of any build-
ing places it in a different group or in a different
subdivision of the same group, such building
should be made to comply with the requirements
of the code the new group or its subdivision.
3.4 Where the new occupancy of any building
is less hazardous, based on life and fire risk than
its existing occupancy, it should not be, necessary
to conform to the requirements of the code for
the new group or Its subdivision.
4. FIRE ZONES
4.1 Demarcatioq - The city or area should,.
for the purpose of the code,, be demarcated into,
distinct zones, based on fire hazard inherent in
4
the buildings and structures according to occu-
pancy ( see 3 ), which should be called the ‘Fire
Zones’.
,4.2 Number and Designation of Fire Zones
4.2.1 The number of fire zones in a city or
area under the jurisdiction of the authority
,depends upon the existing layout, types of build-
ing construction classification of existing buiidings
based on occupancy ( see 2 ) and the expected
future development of the city or area. In large
cities on areas, three fire zones may be necessary,
while in smaller ones, one or two may be
adequate.
4.2.2 The fire zones should be made use of in
land use development plan and should be desig-
nated as follows:
4.2.2.1 Fire Zone No. 1 - This should com-
prise areas having residential ( Group A ),
educational ( Group B ), institutional ( Group C 1,
assembly ( Group D ), small business ( Sub-
division E-l ) and retail mercantile ( Group F >
buildings, or areas which are under development
for such occupancies.
4.2.2.2 Fire Zone No. 2 - This should com-
prise business ( Subdivisions E-2 and E-3 )
and industrial buildings ( Subdivisions G-l and
G-2 ) except high hazard industrial buildings
( Subdivision G-3 ) or areas which are under
development for such occupancies.
4.2.2.3 Fire Zone No. 3- This should com-
prise areas having high hazard industrial build-
ings ( Sub-division G-3 ), storage buildings
( Group H ) and buildings for hazardous uses
( Group J ) or areas which are under develop-
ment for such occupancies.
4.3 Change in the Fire Zone Boundaries -
IS:1641-1988
or when it is intended to include other areas or
types of occupancies in any fire zone, it should be
done by following the same procedure as far
promulgating new rules.
4.4 Overlapping Fire Zones
4.4.1 When any building is so situated that it
extends to more than one fire zone, it should be
deemed to be in the fire zone in which the major
portion of the building or structure is situated.
4.4.2 When any building is SO situated that it
extends equally to more than one fire zone, it
should be deemed to be in the fire zone having
more hazardous occupancy buildings.
4.4 Temporary Buildings
4.51 Temporary buildings should be permitted
only in Fire Zones No. 1 and 2 as the case may
be, according to the purpose for which these are
to be used, by special permit from the authority
for a limited period and subject to such condi-
tions as may be imposed in the permit.
4.5.2 Such buildings should be completely
removed on the expiry of the period specified in
the permit.
4.6 Restrictions on Type of Construction for
New Buiidings ( see IS : 1642-1988* )
4.6.1 Buildings erected in Fire Zone No. 1
should conform to construction of Type 1, 2, 3
or 4.
4.6.2 Buildings erected in Fire Zone No. 2 should
conform to construction of Type 1, 2, or 3.
4.6.3 Buiidings erected in Fire Zone No. 3
should conform to construction of Type 1 or 2.
*Code of practice for fire safety of buildings. _ ^
When the boundaries of any fire zone are changed, (general ): ctetalls ut cons1ructron.
Bureau of Indian Standards
BIS is a statutory institution established under theBureau ofhdian StandardsAct, 1986 to promote harmonious
development of the activities of standardization, marking and quality certification of goods and attending to
connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without
‘the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the
‘standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to
copyright be addressed to the Director (Publications), BIS.
’ Review of Indian Standards
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or editron by referring to the latest issue
of ‘BIS Handbook’ and ‘Standards : Monthly Additions’.
Amendments Issued Since Publication
Amend No. Date of Issue Text Affected
Headquarters:
BUREAU OF INDIAN STANDARDS
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones : 323 01 31,323 94 02, 323 83 75
Telegrams: Manaksanstha
( Common to
all offices )
Regional Offices: Telephone
Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg 323 76 17
NEW DELHI 110002 323 3841
Eastern : l/14 C. I. T. Scheme VII M, V. I. P. Road, Maniktola
CALCUTTA 700054
Northern : SC0 335-336, Sector 34-A, CHANDIGARH 160022
I
337 84 99,337 85 61
337 86 26, 337 86 62
I
60 38 43
60 20 25
Southern : C. I. T. Campus, IV Cross Road, MADRAS 600113
I
235 02 16,235 04 42
235 15 19,235 23 15
Western : Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093
832 92 95,832 78 58
832 78 91,832 78 92
Branches : AHMADABAD. BANGALORE. BHOPAL. BHUBANESHWAR.
COIMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD.
JAIPUR. KANPUR. LUCKNOW. PATNA. THIRUVANANTHAPURAM
Printed at New India Printing Rosa, Khujr. India

Mais conteúdo relacionado

Destaque (13)

5121
51215121
5121
 
3558
35583558
3558
 
3559
35593559
3559
 
7500
75007500
7500
 
784
784784
784
 
9429
94299429
9429
 
2572
25722572
2572
 
785
785785
785
 
6509
65096509
6509
 
2911 1 3
2911 1 32911 1 3
2911 1 3
 
4998 1
4998 14998 1
4998 1
 
8th alg -l6.1--jan17
8th alg -l6.1--jan178th alg -l6.1--jan17
8th alg -l6.1--jan17
 
8th Alg - L7.1--Feb6
8th Alg - L7.1--Feb68th Alg - L7.1--Feb6
8th Alg - L7.1--Feb6
 

Semelhante a Fire Safety Standard for Building Classification

408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................SarveshMusale
 
Types of building cont.
Types of building cont.Types of building cont.
Types of building cont.danappadharwad
 
commentry on nbc part 4
commentry on nbc part 4commentry on nbc part 4
commentry on nbc part 4vakil jagdish
 
Hand book on building fire codes
Hand book on building fire codesHand book on building fire codes
Hand book on building fire codesabhijit9rane
 
Fire regulations for buildings
Fire regulations for buildingsFire regulations for buildings
Fire regulations for buildingsDeepak KUMAR
 
Statutory requirments on Health Safety Environment
Statutory requirments on Health Safety  EnvironmentStatutory requirments on Health Safety  Environment
Statutory requirments on Health Safety EnvironmentVikasMore37
 
Fire zone by national building code of india 2005
Fire zone by national building code of india 2005Fire zone by national building code of india 2005
Fire zone by national building code of india 2005Nayana 54321
 
E uv usexplosiveareas
E uv usexplosiveareasE uv usexplosiveareas
E uv usexplosiveareasIntertek CE
 
BIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdfBIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdfSunil Raiyani
 
HAC - Hazardous Area Classification
HAC - Hazardous Area ClassificationHAC - Hazardous Area Classification
HAC - Hazardous Area ClassificationHarkishan Prajapati
 
fire safety guide in nuclear powerplants.pptx
fire safety guide in nuclear powerplants.pptxfire safety guide in nuclear powerplants.pptx
fire safety guide in nuclear powerplants.pptxkiavash1
 
Fireprotection 170419080622
Fireprotection 170419080622Fireprotection 170419080622
Fireprotection 170419080622vishramsingh3
 
1212817147 rule vii bldg occupancy(anotated)
1212817147 rule vii bldg occupancy(anotated)1212817147 rule vii bldg occupancy(anotated)
1212817147 rule vii bldg occupancy(anotated)nealeekate11
 

Semelhante a Fire Safety Standard for Building Classification (20)

NBC FINAL.pptx
NBC FINAL.pptxNBC FINAL.pptx
NBC FINAL.pptx
 
408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................
 
Building construction(sujith)
Building construction(sujith)Building construction(sujith)
Building construction(sujith)
 
Types of building cont.
Types of building cont.Types of building cont.
Types of building cont.
 
commentry on nbc part 4
commentry on nbc part 4commentry on nbc part 4
commentry on nbc part 4
 
Hand book on building fire codes
Hand book on building fire codesHand book on building fire codes
Hand book on building fire codes
 
fire and safty re
fire and safty refire and safty re
fire and safty re
 
F05.pdf fire iitk
F05.pdf fire iitkF05.pdf fire iitk
F05.pdf fire iitk
 
Fire regulations for buildings
Fire regulations for buildingsFire regulations for buildings
Fire regulations for buildings
 
Ctc assignment
Ctc assignmentCtc assignment
Ctc assignment
 
Statutory requirments on Health Safety Environment
Statutory requirments on Health Safety  EnvironmentStatutory requirments on Health Safety  Environment
Statutory requirments on Health Safety Environment
 
Fire zone by national building code of india 2005
Fire zone by national building code of india 2005Fire zone by national building code of india 2005
Fire zone by national building code of india 2005
 
E uv usexplosiveareas
E uv usexplosiveareasE uv usexplosiveareas
E uv usexplosiveareas
 
BIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdfBIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdf
 
HAC - Hazardous Area Classification
HAC - Hazardous Area ClassificationHAC - Hazardous Area Classification
HAC - Hazardous Area Classification
 
module 1
module 1module 1
module 1
 
fire safety guide in nuclear powerplants.pptx
fire safety guide in nuclear powerplants.pptxfire safety guide in nuclear powerplants.pptx
fire safety guide in nuclear powerplants.pptx
 
Fire protection
Fire protectionFire protection
Fire protection
 
Fireprotection 170419080622
Fireprotection 170419080622Fireprotection 170419080622
Fireprotection 170419080622
 
1212817147 rule vii bldg occupancy(anotated)
1212817147 rule vii bldg occupancy(anotated)1212817147 rule vii bldg occupancy(anotated)
1212817147 rule vii bldg occupancy(anotated)
 

Mais de Boopathi Yoganathan (20)

28-5.21 Company Profile of Pyrmaid structural consultant.pptx
28-5.21 Company Profile of Pyrmaid structural consultant.pptx28-5.21 Company Profile of Pyrmaid structural consultant.pptx
28-5.21 Company Profile of Pyrmaid structural consultant.pptx
 
Front page upto content new
Front page upto content newFront page upto content new
Front page upto content new
 
Book report new
Book report newBook report new
Book report new
 
Fem
FemFem
Fem
 
Exopy injection
Exopy injectionExopy injection
Exopy injection
 
Embedded
EmbeddedEmbedded
Embedded
 
Earthquakes seminar
Earthquakes seminarEarthquakes seminar
Earthquakes seminar
 
10334
1033410334
10334
 
10302
1030210302
10302
 
10297
1029710297
10297
 
9527 1
9527 19527 1
9527 1
 
9459
94599459
9459
 
9456
94569456
9456
 
9417
94179417
9417
 
7873
78737873
7873
 
7563
75637563
7563
 
7436 2
7436 27436 2
7436 2
 
7251
72517251
7251
 
7246
72467246
7246
 
7245
72457245
7245
 

Último

SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024Lorenzo Miniero
 
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdfHyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdfPrecisely
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.Curtis Poe
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningLars Bell
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek SchlawackFwdays
 
From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .Alan Dix
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 3652toLead Limited
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteDianaGray10
 
unit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxunit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxBkGupta21
 
SAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxSAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxNavinnSomaal
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024Stephanie Beckett
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionDilum Bandara
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 

Último (20)

SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024
 
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdfHyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
Hyperautomation and AI/ML: A Strategy for Digital Transformation Success.pdf
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
DSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine TuningDSPy a system for AI to Write Prompts and Do Fine Tuning
DSPy a system for AI to Write Prompts and Do Fine Tuning
 
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
"Subclassing and Composition – A Pythonic Tour of Trade-Offs", Hynek Schlawack
 
From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .
 
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data PrivacyTrustArc Webinar - How to Build Consumer Trust Through Data Privacy
TrustArc Webinar - How to Build Consumer Trust Through Data Privacy
 
Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365Ensuring Technical Readiness For Copilot in Microsoft 365
Ensuring Technical Readiness For Copilot in Microsoft 365
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test Suite
 
unit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptxunit 4 immunoblotting technique complete.pptx
unit 4 immunoblotting technique complete.pptx
 
SAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptxSAP Build Work Zone - Overview L2-L3.pptx
SAP Build Work Zone - Overview L2-L3.pptx
 
What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024What's New in Teams Calling, Meetings and Devices March 2024
What's New in Teams Calling, Meetings and Devices March 2024
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Advanced Computer Architecture – An Introduction
Advanced Computer Architecture – An IntroductionAdvanced Computer Architecture – An Introduction
Advanced Computer Architecture – An Introduction
 
DMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special EditionDMCC Future of Trade Web3 - Special Edition
DMCC Future of Trade Web3 - Special Edition
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 

Fire Safety Standard for Building Classification

  • 1. IS:1641-1988 Indian Standard CODEOFPRACTICEFOR FIRESAFETYOFBUILDING(GENERAL): GENERALPRINCIPLESOFFIRE GRADING AND CLASSIFICATION ( First Revision) September 1988 Second Reprint JULY 1996 UDC 699.81 0 BIS 1988 BUREAU OF INDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG NEW DELHI 110002 Price Group 3 ( Reaffirmed 1998 )
  • 2. IS : 1641-1988 Indian Standard CODE OF PRACTICE FOR FIRE SAFETY OF BUILDING (GENERAL): GENERAL PRINCIPLES OF FIRE GRADING AND CLASSIFICATION ( First Revision) 0. FOREWORD 0.1 The Indian Standard ( First Revision ) was adopted by the Bureau of Indian Standards on 2 May 1988, after the draft finalized by the Fire Safety Sectional Committee had been approved by the Civil Engineering Division Council. 0.2 A series of Indian Standards covering fire, safety of buildings in general principles of fire grading details of construction, exit requirements and exposure hazards have been formulated. This Indian Standard covers general principles of fire grading and classification, which has been adopted in various Indian standards in respect to fire safety aspects. This standard was first issued in 1960. Based on considerable research done on field of fire protection in the past 25 years in advanced countries like USA, UK and Canada, the method of classification of building has been revised and covered in this revision. Further the calorific values and list of hazardous materials as existing have been deleted as the same are available in all standard text Books. NOTE- The information relating to calorific values and hazardous, materials in detail is covered in Hand- book on Fire Protection ( under preparation ). 0.3 For the purpose of deciding whether a parti- - cular requirements of this standard is complied with, the final value, observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance wilh IS : 2 - 1960*. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard. *Rulesfor rounding off numerical values ( revised ). 1. SCOPE 1.1 This code covers the general principles of fire grading of buildings and classification. 2. FIRE LOAD 2.1 Classification - Fire load is the amount of heat in kilocalories which is liberated per square metre of floor area of a compartment by the combustion of the contents of the building and any combustible parts of the building itself. This amount of heat is used as the basis for classifica- tion of occupancies. 2.2 The fire load is determined by multiplying the weight of all combustible materials by their calorific values and dividing the figure by the floor area under consideration. 2.3 Different materials having the same weight and same calorific value may present different hazards on account of their other properties, such as ease of ignition, speed of burning, and liberation of heat and fumes. Thus, some ‘inateirals are more readily ignited than others, 1 again, some burn more rapidly than others, some materials when heated on fire liberate dangerous fumes, and some may readily cause ignition of other materials. 2.4 The content of a building are rarely distri- buted uniformly over the whole floor area. ,From the fire protection point, it would be undesirable to have all combustible material concentrated on a fraction of the floor area, as the average taken over the whole area would not give a true representation of the actual conditions, and the resulting effects on the structure immediately surrounding would be out of all proportion to these expected on the basis of average fire load. 3. CLASSIFICATION OF BUILDING BASED ON OCMJPANCY 3.1 General Classifhation -All buildings should be classified, according to the use or the character of occupancy in one of the following groups : Group A Residential
  • 3. XS:1641-1988 Group B Educational Group C Institutional Group D Assembly Group E Business Group F Mercantile Group G Industrial Group H Storage Group J Hazardous 3.1.1 Minor occupancy incidental to operations in another type of occupancy should be consi- dered as part of the main occupancy and should be classified under the relevant group for the main occupancy. Examples of buildings in each group are given in 3.1.1.1 to 3.1.1.9. 3.1.1.1 Group A residential buildings - These should include any building in which sleeping accommodation is provided for normal residential purposes, with or without cooking or dining or both facilities, except any building classified under Group C. Buildings and structures under Group A shou!d be further subdivided as follows: a) Subdivision A-l lodging for rooming houses - These should include any build- ing or group of buildings under the same management, in which separate sleeping accommodation for total of not more than 15 persons, on transient or permanent basis, with or without dining facilities, but without cooking facilities for individuals, is provided. A lodging or rooming house should be classified as a dwelling in Subdivision A-2, if no room in any of its private dwelling units is rented to more than three persons. b) Subdivision A-2 one- or two-family private dwelling - These should include any private dwelling which is occupied by members of a single family and has a total sleeping accommodation for not more than 20 persons. If rooms in a private dwelling are rented to outsiders, these should be For accommo- dating not more than three persons per room. If sleeping accommodation for more than 20 persons is provided in any one resi- dential building, it shall be classiiied as a building in Subdivision A-3 or A-4 as the case may be. Subdivision A 3 dormitories - These should include any building in which group sleeping accommodation is provided, with or without dining facilities, -for persons 4 4 who are not members of the same family, in one room or a series of closely associ- ated rooms under joint occupancy and single management, for example, school and college dormitories, students’ and their hostels, and military barracks. Subdivision A-4 apartment houses ( j?ats ) - These should include any building or structure in which living quarters are provided for three or more families, living independently of each other and with independent cooking facilities, for example, apartment houses, mansions and chawls. Subdivision A-5 hotels - These should include any building or group of buildings under single management, in which sleep- ing accommodation with or without dining facilities, is provided for hire to more than 15 persons who are primarily transient, for example, hotels, inns, clubs and motels. 3.1.1.2Group B educational buildings - These should include any buildings used for school, college or day-care purposes involving assembly for instruction, education or recreation and which is not covered by Group D. 3.1.1.3 Group C institutional buildings - These should include any building or part thereof, which is used for purposes, such as medical or other treatment or care of persons suffering from physical or mental illness, disease or infirmity; care of infants, convalescents or aged persons and for penal or correctional detention in which the Iiberty of the inmates is restricted. Insti- tutional buildings ordinarily provide sleeping accommodation for the occupants. Buildings and structures under Group C should be further subdivided as follows: a) b) cl Subdivision C-I hospitals and sanatoria - This subdivision include any buildmg or a group of buildings under single manage- ment, which is used for housing persons suffering from physical limitations because of health or age, for example, hospitals, infirmaries, sanatoria and nursing homes. Subdivision C-2 custodial institutions - This subdivision should include any build- ing or a group of buildings under single management, which is used for the custody and care of persons, such as children con- valescents and the aged, for example, homes for the aged and infirm, convales- cent homes and orphanages. Subdivision C-3 penal and mental insti- tutions - This subdivision should include any building or a group of buildings under single management, which is used for hous- ing persons under restraint, or who are 2.
  • 4. detained for penal or corrective purposes, in which the Iiberty of the inmates is restricted, for example, jails, prisons, mental hospitals, mental sanatoria and reformatories. 3.1.1.4 GPOUPD, assembly buildings - These should include any building or part of a building, where groups of people congregate or -gather for amusement, recreation, social, reli- gious, patriotic, civil, travel and similar purposes, for example, theatres, motion picture houses, assembly halls, auditoria, exhibition halls, museums, skating rinks, gymnasiums, restaurants, places of worship, dance halls, club rooms, passenger stations and terminals of air, surface .and marine public transportation services, recre- ation piers and stadia, etc. Buildings under Group D should be further subdivided as follows: a) b) 4 4 Subdivision D-I - This subdivision should include any building primarily meant for theatrical or operatic performance and exhibitions, and which has a raised stage, proscenium curtain, fixed or portable scenery or scenery loft, lights, motion picture booth, mechanical appliances or other theatrical accessories and equipment, and which is provided with fixed seats for over 1 000 persons. Subdivision D-2 - This subdivision should include any building primarily meant for use as described for Subdivision D-1, but with fixed seats for less than 1 000 persons. Subdivision D-3 - This subdivision should include any building, its lobbies, rooms and other spaces connected thereto, pri- marily intended for assembly of people, but which has no theatrical stage or theat- rical and/or cinematographic accessories, and has accommodation for more than 300 persons, for example, dance halls, night clubs, halls for incidental picture shows, dramatic, theatrical or educational present- ation, lectures or other simiiar purposes, having no theatrical stage except a raised platform and used without permanent seating arrangement; art galleries, museums, lecture halls, libraries, passenger terminals; and buildings used for educa- tional purposes for less than 8 hours per week. Subdivision D-4 - This subdivision should include any building primarily intended for use as described in Subdivision D-3; but with accommodation for less than 300 persons. Subdivision D-5 - This subdivision should include any building meant for outdoor assembiy of people not covered by Sub- 8s : 1641- 1988 divisions D-l to D-4, for example, grand- stands, stadia, amusement park structures, reviewing stands and circus tents. 3.1.1.5 Group E business buildings - These should include any building or part of a building which is used for transaction of business ( other than that covered by Group F and parts of buildings covered by 3.1.1 ) for keeping of accounts and records and similar purposes, professional establishments, service facilities, etc. City halls, town halls, court houses and libraries should be classified in this group so far as the principal function of these is transaction of public business and keeping of books and records. Business buildings should be further sub- classified as follows: a) Subdivision E-I - Offices, banks, pro- fessional establishments, like offices of architects, engineers, doctors, lawyers, etc. b) Subdivision E-2 - Laboratories, research establishments and test houses. c) Subdivision E-3 - Computer installations. 3.1.1.6 Group F mercantile buildings - These should include any building or part of a building, which is used as shops, stores, market, for display and sale of merchandise, either whole- sale or retail. Mercantile buildings should be further sub- classified as follows : a) Subdivision F-l - Shops, stores, markets with rrea up to 500 ma. b) Subdivkion F-2 - Underground shopping centres, departmental stores with area more than 500 m2. Storage and service facilities incidental to the sale of merchandise and located in the same building should be included under this group. 3.1.1.7 Group G industrial buildings - These should include any building or part of a building or structure, in which products or materials of all kinds and properties are fabti- cated, assembled, manufactured or processed, for example, assembly plants, laboratories,’ dry cleaning plants, power plants, pumping stations, smoke houses, laundries, gas plants, refineries, dairies and mills. The hazard of occupancy, for the purpose of the Code should be the relative danger of the start and spread of fire, the danger sf smoke or gases generated, the danger of explosion or other occurrence potentially endangering the lives and safety of the occupants of the buildings. Hazard of occupancy should be determined by the authority on the basis of the character of the contents and the processes or operations 3
  • 5. Is;.!.1641 - 1988 conducted in. the building, provided, however, that the combustibility .of the building, the flame spread rating of the interior finish or other features of the building or structure are such as to involve a greater than the occupancy hazard, the greater degree of hazard should govern the classification. Where different degrees of hazard of occu- pancy exist in different parts of a building, the most hazardous of those should govern the classification for the purpose of this code, except in as far as hazardous areas are segregated or protected as specified in the code. Buildings under Group G shall be further sub-divided as follows: a) b) 4 Subdivision G-I - This subdivision should include any building in which the contents are of such low combustibility and the industrial processes or operations con- ducted therein are of such a nature that there are no possibilities for any self- propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source. Subdivision G-2 - This subdivision should include any building in which the contents or industrial processes of operations con- ducted therein are liable to give rise to a fire which will burn with extreme rapidity and give off a considerable volume of smoke, but from which neither toxic fumes nor explosions are to be feared in the event of a fire. Subdivision G-3 - This subdivision should include any building in which the contents or industrial processes or operations con- ducted therein are liable to give :ise to a fire which will burn with extreme rapi- dity or from which poisonous fumes are explosions are to be feared in the event of a fire. 3.1.1.8 Group H storage buildings - These should include any building or part of a building. used primarily for the storage or sheltering ( including servicing, processing or repairs incidental to storage ) of goods wares or merchandise ( except ) those that. involve highly combustible or explosive products or materials ), vehicles or animals, for example, warehouses, cold storage, freight depots, transit sheds, store- houses, truck and marine terminals garages, hangars ( other than aircraft repair hangars ) grain elevators, barns and stables. Storage properties are characterized by t,he presence of relatively small number of persons in proportion to the area. Any new use which increases the number of occupants to a figure comparable with other classes of occupancy should change the classification of the building to that of. the new use, example, hangars used for assembly purposes, warehouses used for office purposes, garage buildings used or manu- facturing. 3.1.1.9 Group J hazardms hri1di:lg.r- These should include any building or part of a building which is used for the storage, handling,. manufacture or processing of highly combustible or explosive materials or products are liable to burn with extreme rapidity and/or which may produce poisonous fumes or explosions for storage, handling, manufacturing or processing which involve highly corrosive, toxic or noxious alkalis, acids or other liquids or chemicals producing flame, fumes and explosive poisonous.. irritant or corrosive gases; and for the storag., handling or processing of any material corrosive gases; and for the storage, handling or processing of any material producing explosive mixtures of dust which result in the division of matter into line particles subject to spontaneous ignition. Examples of buildings in this class are those buildings which are used for: a) Storage, under pressure of more than 0’1 N/mm2 and in quantities exceeding 70 m3 .of acetylene, hydrogen, illuminating and natural gases, ammonia, chlorine, phosgene, sulphur dioxide, carbon dioxide, methyloxide and all gases subject to explosion, fume or toxic hazard, cryogenic gases, etc; b) d) Storage and handling of hazardous and highly flammable liquids, rocket propel- lants, etc; Storage and handling of hazardous and highly flammable or explosive materials, other than liquids; and Manufacture of artificial flowers, synthetic leather, ammunition, explosives and fire- works. 3.2 Any building not covered by the above should be classified in the group which most nearly resembles its existing or proposed use. 3.3 Where change in the occupancy of any build- ing places it in a different group or in a different subdivision of the same group, such building should be made to comply with the requirements of the code the new group or its subdivision. 3.4 Where the new occupancy of any building is less hazardous, based on life and fire risk than its existing occupancy, it should not be, necessary to conform to the requirements of the code for the new group or Its subdivision. 4. FIRE ZONES 4.1 Demarcatioq - The city or area should,. for the purpose of the code,, be demarcated into, distinct zones, based on fire hazard inherent in 4
  • 6. the buildings and structures according to occu- pancy ( see 3 ), which should be called the ‘Fire Zones’. ,4.2 Number and Designation of Fire Zones 4.2.1 The number of fire zones in a city or area under the jurisdiction of the authority ,depends upon the existing layout, types of build- ing construction classification of existing buiidings based on occupancy ( see 2 ) and the expected future development of the city or area. In large cities on areas, three fire zones may be necessary, while in smaller ones, one or two may be adequate. 4.2.2 The fire zones should be made use of in land use development plan and should be desig- nated as follows: 4.2.2.1 Fire Zone No. 1 - This should com- prise areas having residential ( Group A ), educational ( Group B ), institutional ( Group C 1, assembly ( Group D ), small business ( Sub- division E-l ) and retail mercantile ( Group F > buildings, or areas which are under development for such occupancies. 4.2.2.2 Fire Zone No. 2 - This should com- prise business ( Subdivisions E-2 and E-3 ) and industrial buildings ( Subdivisions G-l and G-2 ) except high hazard industrial buildings ( Subdivision G-3 ) or areas which are under development for such occupancies. 4.2.2.3 Fire Zone No. 3- This should com- prise areas having high hazard industrial build- ings ( Sub-division G-3 ), storage buildings ( Group H ) and buildings for hazardous uses ( Group J ) or areas which are under develop- ment for such occupancies. 4.3 Change in the Fire Zone Boundaries - IS:1641-1988 or when it is intended to include other areas or types of occupancies in any fire zone, it should be done by following the same procedure as far promulgating new rules. 4.4 Overlapping Fire Zones 4.4.1 When any building is so situated that it extends to more than one fire zone, it should be deemed to be in the fire zone in which the major portion of the building or structure is situated. 4.4.2 When any building is SO situated that it extends equally to more than one fire zone, it should be deemed to be in the fire zone having more hazardous occupancy buildings. 4.4 Temporary Buildings 4.51 Temporary buildings should be permitted only in Fire Zones No. 1 and 2 as the case may be, according to the purpose for which these are to be used, by special permit from the authority for a limited period and subject to such condi- tions as may be imposed in the permit. 4.5.2 Such buildings should be completely removed on the expiry of the period specified in the permit. 4.6 Restrictions on Type of Construction for New Buiidings ( see IS : 1642-1988* ) 4.6.1 Buildings erected in Fire Zone No. 1 should conform to construction of Type 1, 2, 3 or 4. 4.6.2 Buildings erected in Fire Zone No. 2 should conform to construction of Type 1, 2, or 3. 4.6.3 Buiidings erected in Fire Zone No. 3 should conform to construction of Type 1 or 2. *Code of practice for fire safety of buildings. _ ^ When the boundaries of any fire zone are changed, (general ): ctetalls ut cons1ructron.
  • 7. Bureau of Indian Standards BIS is a statutory institution established under theBureau ofhdian StandardsAct, 1986 to promote harmonious development of the activities of standardization, marking and quality certification of goods and attending to connected matters in the country. Copyright BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without ‘the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the ‘standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to copyright be addressed to the Director (Publications), BIS. ’ Review of Indian Standards Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards should ascertain that they are in possession of the latest amendments or editron by referring to the latest issue of ‘BIS Handbook’ and ‘Standards : Monthly Additions’. Amendments Issued Since Publication Amend No. Date of Issue Text Affected Headquarters: BUREAU OF INDIAN STANDARDS Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002 Telephones : 323 01 31,323 94 02, 323 83 75 Telegrams: Manaksanstha ( Common to all offices ) Regional Offices: Telephone Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg 323 76 17 NEW DELHI 110002 323 3841 Eastern : l/14 C. I. T. Scheme VII M, V. I. P. Road, Maniktola CALCUTTA 700054 Northern : SC0 335-336, Sector 34-A, CHANDIGARH 160022 I 337 84 99,337 85 61 337 86 26, 337 86 62 I 60 38 43 60 20 25 Southern : C. I. T. Campus, IV Cross Road, MADRAS 600113 I 235 02 16,235 04 42 235 15 19,235 23 15 Western : Manakalaya, E9 MIDC, Marol, Andheri (East) MUMBAI 400093 832 92 95,832 78 58 832 78 91,832 78 92 Branches : AHMADABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE. FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. LUCKNOW. PATNA. THIRUVANANTHAPURAM Printed at New India Printing Rosa, Khujr. India