Typical flow rates for various types of outlets and fixtures with non-simultaneous use factors
1. Typical flow rates for various types of outlets / fixtures Non simultaneous use
Flow rate K
Liters/min. Factor
1 12 1 1
2 6 2 1
3 3 3 0.7
4 6 4 0.6
5 30 5 0.5
6 15 6 - 8 0.42
7 10 9 - 13 0.32
8 6 14 - 18 0.26
9 90 19 - 25 0.22
10 6 26 - 36 0.18
11 30 37 - 45 0.16
12 12 46 - 55 0.14
13 6
14 40
Note
To calculate the approximate minimum water required in L/min. determine the flow rate for all fixtures in the building
then correct the non simultaneous use by multiplying by the appropriate K factor for the total number of fixtures in the
building.