                   R review of airborne disinfection
               X               V
                    A        n
                       research and techniques

  Presented by Peta de Jager

  for the architectural engineering   research   group
  CSIR Built Environment unit




  2011 SAFHE CEASA conference
  OR Tambo Conference Centre, Birchwood
Slide April
    71        2011
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref




                                                                    Introduction
                                                                    Mechanics of transmission
                                                                    Considerations
                                                                    Techniques
                                                                           Dilution
                                                                           Filtration
                                                                           UV 1: Zonal UVGI
                                                                           UV2: In-duct UVGI
                                                                           UV 3: Recirculation
                                                                           Photocatalytic Oxidation
                                                                           Plasmacluster Ions
                                                                           Advanced distribution
                  Riley Wells experimental TB ward, Baltimore
                  1958-62: Source Nardell 2010                      References

           Disinfect tr.v. To cleanse of disease carrying micro-organisms
                Disinfectant n. An agent that disinfects by destroying, neutralising, or

                                     A review of airborne
             inhibiting the growth of disease carrying organisms
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Airborne pathogens
            •
                 Bacteria
                   –
                       Measles
                   –
                       Tuberculosis
                   –
                       Varicella

            •
                 Bacterial spores
            •
                 Viruses
                   –
                       Influenza A
                   –
                       Picornavirus
                   –
                       Adenovirus
                                                                                     Riley Wells experimental TB
                                                                                     ward, Baltimore 1958-62:
                   –
                       Coronavirus (SARS)                                            Source Nardell 2010

                 Fungal spores
                                    A review of airborne
            •
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Mechanics of transmission

           Infectious particles <10 µm can penetrate the lungs
                 Evaporation can halve coughed particle size

                                                                                                        Tang and Settles
                                                                                                  Schlieren photography
                                                                        http://www.multimedia.kolobrzeg.pl/tag/th-image/




                                    A review of airborne
           experimental difficulties in working with bio aerosols
           include:
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Mechanics of transmission
           •
                For transmission to occur environmental factors must be conducive to pathogen
                survival
                 –
                      Temperature, relative humidity (RH)


           •
                Effect on relative humidity on pathogenic bacteria scarce
                 –
                      Some data on non-pathogenic surrogates
                        •   40 – 60% RH less favourable to non-pathogenic bacteria [Hatch, et al]
                        •   High RH less favourable for high-lipid viruses
                        •   High RH more favourable for viruses with no lipid [Assar , et al]




                                    A review of airborne
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Mechanics of transmission
            RH experiment influenza A with guinea pigs in a chamber [Lowen, et al]
                   –
                        Temperature 20˚



                                RH 20 %




                                     RH 35 %




                                     RH 65 %




                                    A review of airborne
                                     RH 80 %
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Considerations
           Is the technology


           •
                effective,
           •
                non-harmful,
           •
                useful,
                 –
                      cost effective
                 –
                      compatible with existing circumstance (for example ergonomics of retrofitting), and

           •
                user-friendly
                 –
                      should not undermine comfort conditions
                 –
                      easy to maintain
                 –



                 –
                                    A review of airborne
                      acceptable noise levels

                      energy efficient
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Techniques
           •
                Air dilution
           •
                Filtration
           •
                Ultraviolet germicidal irradiation (UVGI)
                 –
                      Zonal (upper air or lower room)
                 –
                      In-duct
                 –
                      Recirculation

           •
                Photocatalytic oxidation
           •
                Plasmacluster ions
           •
                Electrostatic precipitation
           •
                Ozone generators
           •
                                    A review of airborne
                Advanced air distribution techniques
                 –
                      Personalised ventilation
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Techniques: Plasmacluster ion, alpha electrolytic
           Plasmacluster ion technology.
           Claims to:
           •
                  neutralize 26 kinds of harmful airborne substances
           •
                  use negative (O2 -) and positive (H+) ions inactivate the pathogen by
                  binding on their surfaces, change the structure of the
                  proteins/polysaccharides by stealing an OH-radical, changing the
                  properties of the pathogen rendering it “impotent”
           Possible elevated levels of ozone



                                                 alpha electrolytic
                                                 water disinfectant system
                                       A review of airborne
               http://www.csnstores.com/Sharp          Source - http://www.engadget.com/
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          Techniques




                                     A review of airborne
      Source: http://www.scripps.edu/news/scientificreports/            Source: http://www.uvcomparison.com/uvscience.php
1835    Wheatstone invents mercury vapor arc lamp                     Hockberger 2002
1850     Stokes invents quartz arc lamp that produces 185 nm          Hockberger 2002
1842     Becquerel and Draper find 340-400nm light photoreactive Hockberger 2002
1877    Bactericidal effects of sunlight demonstrated                 Downs and Blunt
1889    UV light demonstrated to be erythemal                        Widmark
1892    UV component of sunlight identified as biocidal              Ward
1892    Geissler demonstrates arc lamps lethal to typhosus
                                                    B.                Hockberger 2002
1903     UV spectrum from 226 to 328nm found to be germicidal         Barnard and Morgan
1904    First quartz lamp for UV developed                           Lorch 1987
1906    UV used to disinfect drinking water                           van Recklinghausen 1914
1921   UV photoreactivity with TiO demonstrated
                                    2                                Renz
1925     UV photodegradation of materials demonstrated                Luckiesh and Taylor
1927    Erythemal action spectrum published                           Hausser and Vahle
1927    Bactericidal action scientifically quantified                 Bedford and Gates
1928    Virucidal action scientifically quantified                   Rivers and Gates
1929    Fungicidal action scientifically quantified                   Fulton and Coblentz
1932    UV germicidal peak at 253.7nm isolated                        Ehrismann and Noethling
1932    Erythemal action spectrum quantified                         Coblentz et al.
1936   Overhead UV system in hospitals                                Wells and Wells, Hart
1936    UV photoreactivation phenomena identified                    Prat
1937   Upper air UV to schools                                       Wells
1938    Fluorescent gas discharge UV lamp                             Whitby and Scheible 2004
1940   UV to airconditioning systems                                  Rentschler and Nagy
1942    UV air disinfection sizing guidelines                         Luckiesh and Holladay
1950     First catalogue sizing methods (General Electric)            Buttolph and Haynes
1954     UV reduce micro-organisms impingement on AHU                Harstad et al.
1954   UV is ineffective (faulty study)                              MRC
1957   UV is effective for TB                                        Riley


            A review of airborne
1959      Microbes on cooling equipment causes respiratory infection Anderson
1974    Microbial growth control systems                             Grun and Pitz
1985    Cooling coil UVGI (European Breweries)                       Philips
1997   UV LED's at 265nm                                              Guha and Bojarczuk
2003     In-duct UVGI demonstrated to reduce illness symptoms        Menzies et al .
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES: Upper Air UV1
          Riley-Middlebrook, 1976 - aerosolized BCG




                                          Exposure chamber, interior, Anderson air sampling
                                          equipment, aerosol generator
                                    A review of airborne                                     Riley 1976: Source Nardell 2010
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES: UV
          Riley-Middlebrook, 1976 - aerosolized BCG


                                                               •
                                                                    Room scale-study
                                                               •
                                                                    Single unshielded 17 W UV lamp
                                                               •
                                                                    Unventilated room
                                                               •
                                                                    Air mixing by radiator

                                                               Established current guideline of :
                                                               30 W fixture per 18,59m2 area.




                                      A review of airborne
            Riley 1976: Source Nardell 2010
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


     Determination of UV susceptibility of various
     airborne organisms Z value
     The Z-value represents the ratio of the inactivation rate normalized by UV irradiance:
                                        ln N0/Nuv

                   Z=       Dose (μWatt x sec x cm-2)                        [Kethley 1973]



      where N0 is the number of surviving microorganisms with no UVGI exposure,
     NUV is the number of surviving microorganisms following UV exposure, and
     D is the UVGI dose in μW·s/cm2.


     Z is the slope of the plot of the natural logarithm of colony count against UV dose:

     Theoretically, the higher the Z-value for a target microorganism, the greater the

                                    A review of airborne
     susceptibility tb at 50% humidity = quickly(23-42) Erdman strain be.
               M. to UVGI and the more 33 the microorganism will
                                       48 (44-55) 1 99RB
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


     Determination of UV effectiveness
      Effectiveness: A measure of the ability of an upper-room UVGI system to kill or
      inactivate microorganisms. This may be expressed as either eACH in decay
      experiments or the percentage of microorganisms killed or inactivated by UVGI in
      constant generation experiments. This latter measure of effectiveness may be
      expressed by the following equation:

                    EUV = 100 × (1 − CUV / C0),
                    where EUV represents the effectiveness of UVGI as a percentage,
                    CUV is the concentration of culturable micro organisms with UVGI exposure,
                    and
                    C0 is the concentration of culturable micro organisms without UVGI
                    exposure.




                                    A review of airborne
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref




      According to First et al [1999]:
      •
           When a volume equivalent to the volume of the room enters and is exhausted
      •
           1 ACH well-mixed air removes 63% of air contaminants
      •
           2 ACH well-mixed air removes 84% of air contaminants
      •
           Any air disinfection method that is 63% effective produces 1 Equivalent ACH


      This equivalence is not uncontested




                                    A review of airborne
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref




     In 1997, the Centers for Disease Control and Prevention (CDC), National Institute for
     Occupational Safety and Health (NIOSH) awarded a contract to the University of
     Colorado to evaluate UVGI to kill or inactivate airborne mycobacteria.
     •
          These included:
            –
                the irradiance level in the upper room that provides a UVGI dose over time that kills or
                inactivates an airborne surrogate of M.tb
            –
                how to best measure UVGI fluence levels
            –
                the effect of air mixing on UVGI performance
            –
                the relationship between mechanical ventilation and UVGI systems,
            –
                the effects of humidity and photoreactivation, and
            –
                the optimum placement of UVGI fixtures.




                                    A review of airborne
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES: comparative UVGI efficacy
                                       Riley (1976)            Miller (1999)         Ko (2000)
                                                                                                            Source Nardell 2010
                   Micro-organism              BCG              Mycobacterium               BCG
                                                                 parafortuitum
                 Particle size (μ m)           0.5 - 3             0.65 - 2.1            1.1 - 4.7

                     Suspending            0.2% BSA                 DW 10%                  FCS
                         medium
                 Temperature (°C)        n/a             n/a          15 - 35             4 - 26

                          RH (%)         25          20, 40           50 - 90             41- 69
                   Room size (m3)               61                      90                  46
                      Mechanical                No                     Yes                 Yes
                       ventilation
                             ACH          2           2-4         0             6     6-8            6
                       Mixing fan               Yes                    Yes                    No
                                             during
                                         aerosolisation
                   UV output (W)          17        46         99 (28)    99 (28)    36 (10)     59 (15)
                  UV output/ room        0.28      0.75          1.1        1.1       0.78         1.3
                              size

                           (W/m3)
                   UV fixture type       C1          C1&W      CN&C2 CN&C2   C2   C2&W
                  UV effectiveness       83          88, 89      98    95  52 ±19 64 ±10
                               (%)

                  UV effect (ACH)
                                       A review of airborne
                                          10         18-19,
                                                       33
                                                                          6-16, 19    9.8 ±
                                                                                       6.4
                                                                                                   11.7 ±
                                                                                                    7.1
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES
          Xu, et al 2002 – Boulder, Colorado




                                                                                               Source Department of Health and
                                                                                                     Human Services, et al 2009




                                    A review of airborne              Source Xu, et al 2003
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES
          Xu, Et al 2002 – UVGI full-scale efficacy studies
                                                          5 fixtures, totalling 216 W producing:
                                                                - avg. 42 μW/cm2 in the irradiated upper zone,
                                                                - 0.08 μW/cm2 at eye level

                                                                              250 C
                                                                              50% RH




             Spatial distribution of UV measured using actinometry in the upper-room zone with
             100% UVGI
                                    A review of airborne               Source Xu, et al 2003
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES
          Xu, Et al 2002 – Boulder, Colarado
      •
       Full scale room studies – 87 m2 test chamber
      •
       B. subtilis, M. parafortuitum, and M. bovis.
      •
       Two experiments:
                                                                   At 50% RH with all lamps:
             –
                 constant generation – effectiveness               culturable airborne bacteria reduced:
             –
                 inactivation rate – equivalent ACH
                                                                   •
                                                                     B. subtilis spores - 46% - 80%
                                                                   •
                                                                    M. parafortuitum - 83% - 98%
                                                                   •
                                                                     M. bovis BCG       - 96% - 97%

                                                                   Increasing the ventilation rate from 0 to 6 ACH
                                                                   decreased microbial inactivation for M.
                                                                   parafortuitum and B. sublilis spores

                                                                   Reducing lamp numbers decreased
                                    A review of airborne           effectiveness
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES
          Escombe et al 2009 – Hospital Nacional Dos de
          Mayo, Lima
                                                      Airborne transmission study facility with three
                                                      parallel ward air exposure chambers

                                                        TB/HIV
                                                        ward

                                                        Air injection vent


                                                        Upward-facing UVGI fixture
                                                        Simple mixing fan


                                    A review of airborne
                                          Air extraction                                     Source Escombe, et al 2009
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


             STUDIES
             Escombe et al 2009 – UVGI and Ionisation
         •
          535 days, 150 guinea pigs per enclosure, using a 2-d cycle.
         •
          UV-off days: Control and negative ioniser chambers (chamber 1 &2)
         •
          UV-on days: UV lights and mixing fans were turned on in the ward (chamber 3)
         •
            TB infection in guinea pigs was defined by monthly tuberculin skin tests
                   •
                            control group 35%
                   •
                          ionizers           14 %
                   •
                           UVGI        9.5 %
         Guinea pigs underwent autopsy to test for TB disease
         •


                   •
                            control group 8.5%
                                                                                   Ground plane             Power supply
                   •
                           ionizers          4.3 %
                   •
                           UVGI        3.6 %

                                                         Insulating spacers
                                            Needle tips discharge 25 000 V

                                    A review of airborne                                     Source Escombe, et al 2009
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


                   STUDIES
                   Escombe et al 2009 – UVGI and Ionisation


                          Control                            UV Lights                        Ionisers
                                                                                                                 Dust-related
                                                                                                                 outbreak
    TB Infected animals
    (% of exposed)




                                                                                             Source Escombe, et al 2009



                                    A review of airborne
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref

                                                                                                                                     

                                                                             UPPER AIR UVGI Summary Guidance DHHS                    


                                                                                                                                     
                                                                             Temperature              20 - 24 °C                     
                                                                             Ceiling supply air       room t °C - 3 °C               
                                                                             ACH                      <6                             
                                                                             RH                       30 - 60%                       


                                                                                                                                     
                                                                             min. ave. fluence        12 μW/cm2                      
                                                                             ave. UV fluence rate     30 - 50 μW/cm2                 
                                                                             Lamps                    Low-pressure mercury arc       


                                                                                                                    or               
                                                                                                      Medium-pressure (low ozone)    
                                                                             Irradiance               1.87 W/m2                      


                                                                                                                                     
                                                                            Power                     6 W/m3                         
                                                                           Mercury                    < 5mg                          


                                                                                                                                     
                                                                             Max lower room
                                                                             irradiance               0.2 μW/cm2 (conservative?)     
                                                                             CDC/NIOSH REL            6 mJ/cm2 per 8 hours           
                                                                             ACGIH TLV                6 mJ/cm2 per 8 hours           




                                    A review of airborne
                                                                                                                                     
                                                                             Ballast harmonic distortion < 10%                       
                                                                             Ceiling > 2.7m           unsheilded                     
                                                                             Ceiling 2.4 - 2.7m       sheilded                       
                                                                                                                                     
STUDIES
Escombe et al 2007 – Natural ventilation in Lima
OBJECTIVE : to investigate the rates, determinants, and effects of natural ventilation
in health care settings.

•
    5 ‘‘old-fashioned’’ design (built pre-1950) and 3 ‘‘modern’’ design (1970–1990)
    were studied = 70 naturally ventilated clinical rooms with infectious patients

•
    Compared to 12 post-2000 mechanically ventilated negative-pressure respiratory
    isolation rooms

      –
          CO2 tracer gas technique
      –
          368 experiments
      –
          Architectural and environmental
                variables were measured
      –
          Infection risk was estimated for
          TB exposure (Wells- Riley model)

                      A review of airborne                    Source: Google 2011 Malta
STUDIES
Escombe et al 2007                                                         Source Google 2011
Opening windows and doors provided median ventilation of 28 ACH:
    –
        >2 x mechanically ventilated negative-pressure rooms ventilated at 12 ACH
    –
        18 times that with windows and doors closed
•
    Facilities built more than 50 years ago, characterised by large windows and
    high ceilings, had greater ventilation than modern naturally ventilated rooms
    (40 versus 17 ACH)
•
    Even within the lowest quartile of wind speeds, natural ventilation exceeded
    mechanical
•
    Model predicted that following 24 h exposure to untreated TB patients:
    –
        39% of susceptible individuals in mechanically ventilated rooms
    –
        33% in modern
    –
        11% in pre-1950 naturally ventilated facilities with windows and doors open
 would become infectious
CONCLUSION: “Opening windows and doors maximises natural ventilation so that
the risk of airborne contagion is much lower than with … mechanical ventilation
systems.”
                   A review of airborne
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          STUDIES
          Zhao et al 2009 – Silver-doped Titanium Dioxide
      nano-Ag/TiO2 and UVA light irradiation can improve the efficiency of bacterial
      restraining in medical nursing institutions [Zhao et al]




                                    A review of airborne                                     Source: Google 2011 Ellis Island
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          References
          Bolashikov, Z.D. , Melikov, A.K., 2009. Methods for air cleaning and protection of building occupants from airborne pathogens.
          Building and Environment 44, 1378–1385. doi:10.1016/j.buildenv.2008.09.001.

          Digel, I., Temiz, Artmann, A., Nishikawa, K., Cook, M., Kurulgan, E.I. Artmann, G.M., 2005. Bactericidal effects of
          plasma-generated cluster ions. Medical Biological Engineering and Computing 43, 800-807.

          Department of Health and Human Services., Centers for Disease Control and Prevention., National Institute for Occupational
          Safety and Health., 2009. Environmental Control for Tuberculosis: Basic Upper-Room Ultraviolet Germicidal Irradiation Guidelines
          for Healthcare Settings.

          Escombe, R.A., Moore, D.J.A., Gilman, R.H., Navincopa, M., Ticona, E., Mitchell, B., Noakes, C,. Martı´nez, C., Sheen,P., Ramirez, R.,
          Quino, W., Gonzalez, A., Friedland, J.S., Evans, C.A., 2009. Natural Ventilation for the Prevention of Airborne Contagion. PLoS
          Medicine 6:3, 0-11. www.plosmedicine.org .

          Escombe, R.A., Oese, C.C., Gilman, R.H., Navincopa, M., Pan, W., Martı´nez, C., Chacaltana, J., Rodrı´guez, R., Moore, D.J.A.,
          Friedland, J.S., Evans, C.A., 2007. Upper-Room Ultraviolet Light and Negative Air Ionization to Prevent Tuberculosis Transmission
          PLoS Medicine 4:2, 309-317. www.plosmedicine.org .

          Kato, S., Sung,M., 2011. Using UVGI to counter contaminant dispersion. IFHE Digest 2011.
intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref


          References (continued)
          Kearns, A.M., Barrett, A., Marshall, C., Freeman, R., Magee, J.G., Bourke, S.J., Steward, M., 2000. Epidemiology and molecular
          typing of an outbreak of tuberculosis in a hostel for homeless men. Journal of Clinical Pathology 53, 122–124.

          Kowalski, W. 2010. Ultraviolet Germicidal Irradiation Handbook. Springer, New York. ISBN 978-3-642-01998-2.

          Nardell, E.A., 2010. Progress in the Application of Ultraviolet Germicidal Irradiation. American Society for Photobiology.
          Powerpoint accessed www.ghdonline .

          Riley, R.L., Knight, M., Middlebrook, G., 1976. Ultraviolet susceptibility of BCG and virulent tubercle bacilli. American Review of
          Respiratory Disease 113, 413–418.

          Xu, P., Peccia, J., Fabian, P., Martyny, J.W., Fennelly, K.P., Hernandez, M., Miller S.L., 2003. Efficacy of ultraviolet germicidal
          irradiation of upper-room air in inactivating airborne bacterial spores and mycobacteria in full-scale studies. Atmospheric
          Environment 37, 405–419.

          Zhao, Y.K., Sung, W.P., Tsai, T.T., Wang, H.J., 2010. Application of Nanoscale Silver-Doped Titanium Dioxide as Photocatalyst for
          Indoor Airborne Bacteria Control: A Feasibility Study in Medical Nursing Institutions. Journal of Air and Waste Management
          Association 60:337–345. ISSN:1047-3289.
Architectural Engineering Research Group
           Dirk Conradie
           Faatiema Salie
           Geoff Abbott
           Jeremy Gibberd
           Lorato Motsatsi
           Nkhensani Baloyi
           Peta de Jager
           Sheldon Bole
           Thabang Molefi
           Tichoana Kumurai



           Sidney Parsons

Slide 31
Architectural Engineering research group

           Dirk Conradie
           Faatiema Salie
           Geoff Abbott
           Jeremy Gibberd
           Lorato Motsatsi
           Nkhensani Baloyi
           Peta de Jager
           Sheldon Bole
           Thabang Molefi



           In memory of Dr Sidney Parsons

Slide 32

Mais conteúdo relacionado

Semelhante a SAFHE/CEASA 2011 - Airborne disinfection methods

Günter Oberdorster_How to assess the risks of nanotechnology?
Günter Oberdorster_How to assess the risks of nanotechnology?Günter Oberdorster_How to assess the risks of nanotechnology?
Günter Oberdorster_How to assess the risks of nanotechnology?Ne3LS_Network
 
UV technology for disinfecting surfaces
UV technology for disinfecting surfacesUV technology for disinfecting surfaces
UV technology for disinfecting surfacesAnjum Hashmi MPH
 
Interventional radiology2
Interventional radiology2Interventional radiology2
Interventional radiology2IUOIR
 
Exposure assessment and controls at carbon black manufacturing sites in chian
Exposure assessment and controls at carbon black manufacturing sites in chianExposure assessment and controls at carbon black manufacturing sites in chian
Exposure assessment and controls at carbon black manufacturing sites in chianAbhinav Asthana
 
uvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdf
uvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdfuvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdf
uvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdfabhishekraja19
 
Positive effects of negative ions for sterilization in a clinical environment...
Positive effects of negative ions for sterilization in a clinical environment...Positive effects of negative ions for sterilization in a clinical environment...
Positive effects of negative ions for sterilization in a clinical environment...Indoor Air Sterilization Soma Medical IAQA
 
Midbrook Medical Products & Services Offerings
Midbrook Medical Products & Services OfferingsMidbrook Medical Products & Services Offerings
Midbrook Medical Products & Services OfferingsMidbrook
 
Occupational radiation safety in Radiotherapy, Timothy Peace S
Occupational radiation safety in Radiotherapy, Timothy Peace SOccupational radiation safety in Radiotherapy, Timothy Peace S
Occupational radiation safety in Radiotherapy, Timothy Peace Sohscmcvellore
 

Semelhante a SAFHE/CEASA 2011 - Airborne disinfection methods (11)

Günter Oberdorster_How to assess the risks of nanotechnology?
Günter Oberdorster_How to assess the risks of nanotechnology?Günter Oberdorster_How to assess the risks of nanotechnology?
Günter Oberdorster_How to assess the risks of nanotechnology?
 
Uvta
UvtaUvta
Uvta
 
UV technology for disinfecting surfaces
UV technology for disinfecting surfacesUV technology for disinfecting surfaces
UV technology for disinfecting surfaces
 
Micro Coriolis air sampler
Micro Coriolis air samplerMicro Coriolis air sampler
Micro Coriolis air sampler
 
Interventional radiology2
Interventional radiology2Interventional radiology2
Interventional radiology2
 
Exposure assessment and controls at carbon black manufacturing sites in chian
Exposure assessment and controls at carbon black manufacturing sites in chianExposure assessment and controls at carbon black manufacturing sites in chian
Exposure assessment and controls at carbon black manufacturing sites in chian
 
uvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdf
uvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdfuvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdf
uvtechnologyfordisinfectingsurfaces-130316232023-phpapp02 (1).pdf
 
Positive effects of negative ions for sterilization in a clinical environment...
Positive effects of negative ions for sterilization in a clinical environment...Positive effects of negative ions for sterilization in a clinical environment...
Positive effects of negative ions for sterilization in a clinical environment...
 
Saftey 1
Saftey 1Saftey 1
Saftey 1
 
Midbrook Medical Products & Services Offerings
Midbrook Medical Products & Services OfferingsMidbrook Medical Products & Services Offerings
Midbrook Medical Products & Services Offerings
 
Occupational radiation safety in Radiotherapy, Timothy Peace S
Occupational radiation safety in Radiotherapy, Timothy Peace SOccupational radiation safety in Radiotherapy, Timothy Peace S
Occupational radiation safety in Radiotherapy, Timothy Peace S
 

Mais de SA FHE

Order of Magnitude Estimator for Public Hospitals
Order of Magnitude Estimator for Public HospitalsOrder of Magnitude Estimator for Public Hospitals
Order of Magnitude Estimator for Public HospitalsSA FHE
 
Wi ebe 2014 call for nominations
Wi ebe 2014 call for nominationsWi ebe 2014 call for nominations
Wi ebe 2014 call for nominationsSA FHE
 
2014 07 31 iuss presentation ceasa
2014 07 31 iuss presentation ceasa2014 07 31 iuss presentation ceasa
2014 07 31 iuss presentation ceasaSA FHE
 
Phg cape town tour jul aug 2014
Phg cape town tour jul aug 2014Phg cape town tour jul aug 2014
Phg cape town tour jul aug 2014SA FHE
 
Phg provisional programme 9 jun 2014
Phg provisional programme   9 jun 2014Phg provisional programme   9 jun 2014
Phg provisional programme 9 jun 2014SA FHE
 
Safhe newsletter 2.1
Safhe newsletter 2.1Safhe newsletter 2.1
Safhe newsletter 2.1SA FHE
 
Presentation for safhe april 2014 handout
Presentation for safhe april 2014 handoutPresentation for safhe april 2014 handout
Presentation for safhe april 2014 handoutSA FHE
 
Uia 2014 durban uia phg competition brief c
Uia 2014 durban uia phg competition brief cUia 2014 durban uia phg competition brief c
Uia 2014 durban uia phg competition brief cSA FHE
 
Uia 2014 durban_uia_phg_competition_brief
Uia 2014 durban_uia_phg_competition_briefUia 2014 durban_uia_phg_competition_brief
Uia 2014 durban_uia_phg_competition_briefSA FHE
 
Overview of the Healthcare Technology Management Programme offered by the Uni...
Overview of the Healthcare Technology Management Programme offered by the Uni...Overview of the Healthcare Technology Management Programme offered by the Uni...
Overview of the Healthcare Technology Management Programme offered by the Uni...SA FHE
 
Sans healthcare watch
Sans healthcare watchSans healthcare watch
Sans healthcare watchSA FHE
 
SAFHE Newsletter 2 September 2013
SAFHE Newsletter 2 September 2013SAFHE Newsletter 2 September 2013
SAFHE Newsletter 2 September 2013SA FHE
 
Health facility design for infection control
Health facility design for infection controlHealth facility design for infection control
Health facility design for infection controlSA FHE
 
Am solar presentation hospital-engineers 2013
Am solar presentation   hospital-engineers 2013Am solar presentation   hospital-engineers 2013
Am solar presentation hospital-engineers 2013SA FHE
 
Engineers powerpoint presentation. june 2013
Engineers powerpoint presentation. june 2013Engineers powerpoint presentation. june 2013
Engineers powerpoint presentation. june 2013SA FHE
 
SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...
SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...
SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...SA FHE
 
SAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADE
SAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADESAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADE
SAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADESA FHE
 
SAFHE/CEASA 2011 - Clarity Amid Confusion
SAFHE/CEASA 2011 - Clarity Amid ConfusionSAFHE/CEASA 2011 - Clarity Amid Confusion
SAFHE/CEASA 2011 - Clarity Amid ConfusionSA FHE
 
SAFHE/CEASA2011 - Hospital Design in Southern Africa
SAFHE/CEASA2011 - Hospital Design in Southern AfricaSAFHE/CEASA2011 - Hospital Design in Southern Africa
SAFHE/CEASA2011 - Hospital Design in Southern AfricaSA FHE
 

Mais de SA FHE (19)

Order of Magnitude Estimator for Public Hospitals
Order of Magnitude Estimator for Public HospitalsOrder of Magnitude Estimator for Public Hospitals
Order of Magnitude Estimator for Public Hospitals
 
Wi ebe 2014 call for nominations
Wi ebe 2014 call for nominationsWi ebe 2014 call for nominations
Wi ebe 2014 call for nominations
 
2014 07 31 iuss presentation ceasa
2014 07 31 iuss presentation ceasa2014 07 31 iuss presentation ceasa
2014 07 31 iuss presentation ceasa
 
Phg cape town tour jul aug 2014
Phg cape town tour jul aug 2014Phg cape town tour jul aug 2014
Phg cape town tour jul aug 2014
 
Phg provisional programme 9 jun 2014
Phg provisional programme   9 jun 2014Phg provisional programme   9 jun 2014
Phg provisional programme 9 jun 2014
 
Safhe newsletter 2.1
Safhe newsletter 2.1Safhe newsletter 2.1
Safhe newsletter 2.1
 
Presentation for safhe april 2014 handout
Presentation for safhe april 2014 handoutPresentation for safhe april 2014 handout
Presentation for safhe april 2014 handout
 
Uia 2014 durban uia phg competition brief c
Uia 2014 durban uia phg competition brief cUia 2014 durban uia phg competition brief c
Uia 2014 durban uia phg competition brief c
 
Uia 2014 durban_uia_phg_competition_brief
Uia 2014 durban_uia_phg_competition_briefUia 2014 durban_uia_phg_competition_brief
Uia 2014 durban_uia_phg_competition_brief
 
Overview of the Healthcare Technology Management Programme offered by the Uni...
Overview of the Healthcare Technology Management Programme offered by the Uni...Overview of the Healthcare Technology Management Programme offered by the Uni...
Overview of the Healthcare Technology Management Programme offered by the Uni...
 
Sans healthcare watch
Sans healthcare watchSans healthcare watch
Sans healthcare watch
 
SAFHE Newsletter 2 September 2013
SAFHE Newsletter 2 September 2013SAFHE Newsletter 2 September 2013
SAFHE Newsletter 2 September 2013
 
Health facility design for infection control
Health facility design for infection controlHealth facility design for infection control
Health facility design for infection control
 
Am solar presentation hospital-engineers 2013
Am solar presentation   hospital-engineers 2013Am solar presentation   hospital-engineers 2013
Am solar presentation hospital-engineers 2013
 
Engineers powerpoint presentation. june 2013
Engineers powerpoint presentation. june 2013Engineers powerpoint presentation. june 2013
Engineers powerpoint presentation. june 2013
 
SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...
SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...
SAFHE/CEASA 2011 - Open Building for Healthcare Facilities: Lessons from the ...
 
SAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADE
SAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADESAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADE
SAFHE/CEASA 2011 - DR. A.G. JEETOO HOSPITAL UPGRADE
 
SAFHE/CEASA 2011 - Clarity Amid Confusion
SAFHE/CEASA 2011 - Clarity Amid ConfusionSAFHE/CEASA 2011 - Clarity Amid Confusion
SAFHE/CEASA 2011 - Clarity Amid Confusion
 
SAFHE/CEASA2011 - Hospital Design in Southern Africa
SAFHE/CEASA2011 - Hospital Design in Southern AfricaSAFHE/CEASA2011 - Hospital Design in Southern Africa
SAFHE/CEASA2011 - Hospital Design in Southern Africa
 

Último

Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...
Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...
Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...GENUINE ESCORT AGENCY
 
Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...
Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...
Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...Dipal Arora
 
Top Rated Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...
Top Rated  Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...Top Rated  Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...
Top Rated Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...chandars293
 
Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...
Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...
Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...parulsinha
 
Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...
Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...
Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...parulsinha
 
Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426
Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426
Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426jennyeacort
 
Call Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service AvailableCall Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service AvailableDipal Arora
 
(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...
(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...
(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...parulsinha
 
Top Rated Bangalore Call Girls Majestic ⟟ 9332606886 ⟟ Call Me For Genuine S...
Top Rated Bangalore Call Girls Majestic ⟟  9332606886 ⟟ Call Me For Genuine S...Top Rated Bangalore Call Girls Majestic ⟟  9332606886 ⟟ Call Me For Genuine S...
Top Rated Bangalore Call Girls Majestic ⟟ 9332606886 ⟟ Call Me For Genuine S...narwatsonia7
 
Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟ 9332606886 ⟟ Call Me For G...
Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟  9332606886 ⟟ Call Me For G...Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟  9332606886 ⟟ Call Me For G...
Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟ 9332606886 ⟟ Call Me For G...narwatsonia7
 
Call Girls Shimla Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Shimla Just Call 8617370543 Top Class Call Girl Service AvailableCall Girls Shimla Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Shimla Just Call 8617370543 Top Class Call Girl Service AvailableDipal Arora
 
Top Rated Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...
Top Rated  Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...Top Rated  Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...
Top Rated Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...chandars293
 
Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...
Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...
Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...hotbabesbook
 
Call Girls Kurnool Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Kurnool Just Call 8250077686 Top Class Call Girl Service AvailableCall Girls Kurnool Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Kurnool Just Call 8250077686 Top Class Call Girl Service AvailableDipal Arora
 
The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...
The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...
The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...chandars293
 
VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...
VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...
VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...jageshsingh5554
 
Call Girls Raipur Just Call 9630942363 Top Class Call Girl Service Available
Call Girls Raipur Just Call 9630942363 Top Class Call Girl Service AvailableCall Girls Raipur Just Call 9630942363 Top Class Call Girl Service Available
Call Girls Raipur Just Call 9630942363 Top Class Call Girl Service AvailableGENUINE ESCORT AGENCY
 
Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...
Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...
Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...chetankumar9855
 
Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...
Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...
Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...vidya singh
 

Último (20)

Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...
Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...
Pondicherry Call Girls Book Now 9630942363 Top Class Pondicherry Escort Servi...
 
Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...
Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...
Call Girls Visakhapatnam Just Call 8250077686 Top Class Call Girl Service Ava...
 
Top Rated Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...
Top Rated  Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...Top Rated  Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...
Top Rated Hyderabad Call Girls Erragadda ⟟ 9332606886 ⟟ Call Me For Genuine ...
 
Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...
Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...
Call Girls Service Jaipur {8445551418} ❤️VVIP BHAWNA Call Girl in Jaipur Raja...
 
Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...
Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...
Independent Call Girls In Jaipur { 8445551418 } ✔ ANIKA MEHTA ✔ Get High Prof...
 
Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426
Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426
Call Girls in Delhi Triveni Complex Escort Service(🔝))/WhatsApp 97111⇛47426
 
Call Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service AvailableCall Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Rishikesh Just Call 8250077686 Top Class Call Girl Service Available
 
(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...
(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...
(Low Rate RASHMI ) Rate Of Call Girls Jaipur ❣ 8445551418 ❣ Elite Models & Ce...
 
Top Rated Bangalore Call Girls Majestic ⟟ 9332606886 ⟟ Call Me For Genuine S...
Top Rated Bangalore Call Girls Majestic ⟟  9332606886 ⟟ Call Me For Genuine S...Top Rated Bangalore Call Girls Majestic ⟟  9332606886 ⟟ Call Me For Genuine S...
Top Rated Bangalore Call Girls Majestic ⟟ 9332606886 ⟟ Call Me For Genuine S...
 
Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟ 9332606886 ⟟ Call Me For G...
Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟  9332606886 ⟟ Call Me For G...Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟  9332606886 ⟟ Call Me For G...
Top Rated Bangalore Call Girls Ramamurthy Nagar ⟟ 9332606886 ⟟ Call Me For G...
 
Call Girls Shimla Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Shimla Just Call 8617370543 Top Class Call Girl Service AvailableCall Girls Shimla Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Shimla Just Call 8617370543 Top Class Call Girl Service Available
 
Top Rated Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...
Top Rated  Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...Top Rated  Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...
Top Rated Hyderabad Call Girls Chintal ⟟ 9332606886 ⟟ Call Me For Genuine Se...
 
Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...
Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...
Night 7k to 12k Chennai City Center Call Girls 👉👉 7427069034⭐⭐ 100% Genuine E...
 
Call Girls Kurnool Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Kurnool Just Call 8250077686 Top Class Call Girl Service AvailableCall Girls Kurnool Just Call 8250077686 Top Class Call Girl Service Available
Call Girls Kurnool Just Call 8250077686 Top Class Call Girl Service Available
 
The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...
The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...
The Most Attractive Hyderabad Call Girls Kothapet 𖠋 9332606886 𖠋 Will You Mis...
 
VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...
VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...
VIP Service Call Girls Sindhi Colony 📳 7877925207 For 18+ VIP Call Girl At Th...
 
Call Girls Raipur Just Call 9630942363 Top Class Call Girl Service Available
Call Girls Raipur Just Call 9630942363 Top Class Call Girl Service AvailableCall Girls Raipur Just Call 9630942363 Top Class Call Girl Service Available
Call Girls Raipur Just Call 9630942363 Top Class Call Girl Service Available
 
Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...
Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...
Call Girl In Pune 👉 Just CALL ME: 9352988975 💋 Call Out Call Both With High p...
 
🌹Attapur⬅️ Vip Call Girls Hyderabad 📱9352852248 Book Well Trand Call Girls In...
🌹Attapur⬅️ Vip Call Girls Hyderabad 📱9352852248 Book Well Trand Call Girls In...🌹Attapur⬅️ Vip Call Girls Hyderabad 📱9352852248 Book Well Trand Call Girls In...
🌹Attapur⬅️ Vip Call Girls Hyderabad 📱9352852248 Book Well Trand Call Girls In...
 
Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...
Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...
Manyata Tech Park ( Call Girls ) Bangalore ✔ 6297143586 ✔ Hot Model With Sexy...
 

SAFHE/CEASA 2011 - Airborne disinfection methods

  • 1. a : R review of airborne disinfection X V A n research and techniques Presented by Peta de Jager for the architectural engineering research group CSIR Built Environment unit 2011 SAFHE CEASA conference OR Tambo Conference Centre, Birchwood Slide April 71 2011
  • 2. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Introduction Mechanics of transmission Considerations Techniques Dilution Filtration UV 1: Zonal UVGI UV2: In-duct UVGI UV 3: Recirculation Photocatalytic Oxidation Plasmacluster Ions Advanced distribution Riley Wells experimental TB ward, Baltimore 1958-62: Source Nardell 2010 References Disinfect tr.v. To cleanse of disease carrying micro-organisms Disinfectant n. An agent that disinfects by destroying, neutralising, or A review of airborne inhibiting the growth of disease carrying organisms
  • 3. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Airborne pathogens • Bacteria – Measles – Tuberculosis – Varicella • Bacterial spores • Viruses – Influenza A – Picornavirus – Adenovirus Riley Wells experimental TB ward, Baltimore 1958-62: – Coronavirus (SARS) Source Nardell 2010 Fungal spores A review of airborne •
  • 4. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Mechanics of transmission Infectious particles <10 µm can penetrate the lungs Evaporation can halve coughed particle size Tang and Settles Schlieren photography http://www.multimedia.kolobrzeg.pl/tag/th-image/ A review of airborne experimental difficulties in working with bio aerosols include:
  • 5. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Mechanics of transmission • For transmission to occur environmental factors must be conducive to pathogen survival – Temperature, relative humidity (RH) • Effect on relative humidity on pathogenic bacteria scarce – Some data on non-pathogenic surrogates • 40 – 60% RH less favourable to non-pathogenic bacteria [Hatch, et al] • High RH less favourable for high-lipid viruses • High RH more favourable for viruses with no lipid [Assar , et al] A review of airborne
  • 6. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Mechanics of transmission RH experiment influenza A with guinea pigs in a chamber [Lowen, et al] – Temperature 20˚ RH 20 % RH 35 % RH 65 % A review of airborne RH 80 %
  • 7. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Considerations Is the technology • effective, • non-harmful, • useful, – cost effective – compatible with existing circumstance (for example ergonomics of retrofitting), and • user-friendly – should not undermine comfort conditions – easy to maintain – – A review of airborne acceptable noise levels energy efficient
  • 8. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Techniques • Air dilution • Filtration • Ultraviolet germicidal irradiation (UVGI) – Zonal (upper air or lower room) – In-duct – Recirculation • Photocatalytic oxidation • Plasmacluster ions • Electrostatic precipitation • Ozone generators • A review of airborne Advanced air distribution techniques – Personalised ventilation
  • 9. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Techniques: Plasmacluster ion, alpha electrolytic Plasmacluster ion technology. Claims to: • neutralize 26 kinds of harmful airborne substances • use negative (O2 -) and positive (H+) ions inactivate the pathogen by binding on their surfaces, change the structure of the proteins/polysaccharides by stealing an OH-radical, changing the properties of the pathogen rendering it “impotent” Possible elevated levels of ozone alpha electrolytic water disinfectant system A review of airborne http://www.csnstores.com/Sharp Source - http://www.engadget.com/
  • 10. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Techniques A review of airborne Source: http://www.scripps.edu/news/scientificreports/ Source: http://www.uvcomparison.com/uvscience.php
  • 11. 1835 Wheatstone invents mercury vapor arc lamp Hockberger 2002 1850 Stokes invents quartz arc lamp that produces 185 nm Hockberger 2002 1842 Becquerel and Draper find 340-400nm light photoreactive Hockberger 2002 1877 Bactericidal effects of sunlight demonstrated Downs and Blunt 1889 UV light demonstrated to be erythemal Widmark 1892 UV component of sunlight identified as biocidal Ward 1892 Geissler demonstrates arc lamps lethal to typhosus B. Hockberger 2002 1903 UV spectrum from 226 to 328nm found to be germicidal Barnard and Morgan 1904 First quartz lamp for UV developed Lorch 1987 1906 UV used to disinfect drinking water van Recklinghausen 1914 1921 UV photoreactivity with TiO demonstrated 2 Renz 1925 UV photodegradation of materials demonstrated Luckiesh and Taylor 1927 Erythemal action spectrum published Hausser and Vahle 1927 Bactericidal action scientifically quantified Bedford and Gates 1928 Virucidal action scientifically quantified Rivers and Gates 1929 Fungicidal action scientifically quantified Fulton and Coblentz 1932 UV germicidal peak at 253.7nm isolated Ehrismann and Noethling 1932 Erythemal action spectrum quantified Coblentz et al. 1936 Overhead UV system in hospitals Wells and Wells, Hart 1936 UV photoreactivation phenomena identified Prat 1937 Upper air UV to schools Wells 1938 Fluorescent gas discharge UV lamp Whitby and Scheible 2004 1940 UV to airconditioning systems Rentschler and Nagy 1942 UV air disinfection sizing guidelines Luckiesh and Holladay 1950 First catalogue sizing methods (General Electric) Buttolph and Haynes 1954 UV reduce micro-organisms impingement on AHU Harstad et al. 1954 UV is ineffective (faulty study) MRC 1957 UV is effective for TB Riley A review of airborne 1959 Microbes on cooling equipment causes respiratory infection Anderson 1974 Microbial growth control systems Grun and Pitz 1985 Cooling coil UVGI (European Breweries) Philips 1997 UV LED's at 265nm Guha and Bojarczuk 2003 In-duct UVGI demonstrated to reduce illness symptoms Menzies et al .
  • 12. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES: Upper Air UV1 Riley-Middlebrook, 1976 - aerosolized BCG Exposure chamber, interior, Anderson air sampling equipment, aerosol generator A review of airborne Riley 1976: Source Nardell 2010
  • 13. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES: UV Riley-Middlebrook, 1976 - aerosolized BCG • Room scale-study • Single unshielded 17 W UV lamp • Unventilated room • Air mixing by radiator Established current guideline of : 30 W fixture per 18,59m2 area. A review of airborne Riley 1976: Source Nardell 2010
  • 14. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Determination of UV susceptibility of various airborne organisms Z value The Z-value represents the ratio of the inactivation rate normalized by UV irradiance: ln N0/Nuv Z= Dose (μWatt x sec x cm-2) [Kethley 1973] where N0 is the number of surviving microorganisms with no UVGI exposure, NUV is the number of surviving microorganisms following UV exposure, and D is the UVGI dose in μW·s/cm2. Z is the slope of the plot of the natural logarithm of colony count against UV dose: Theoretically, the higher the Z-value for a target microorganism, the greater the A review of airborne susceptibility tb at 50% humidity = quickly(23-42) Erdman strain be. M. to UVGI and the more 33 the microorganism will 48 (44-55) 1 99RB
  • 15. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref Determination of UV effectiveness Effectiveness: A measure of the ability of an upper-room UVGI system to kill or inactivate microorganisms. This may be expressed as either eACH in decay experiments or the percentage of microorganisms killed or inactivated by UVGI in constant generation experiments. This latter measure of effectiveness may be expressed by the following equation: EUV = 100 × (1 − CUV / C0), where EUV represents the effectiveness of UVGI as a percentage, CUV is the concentration of culturable micro organisms with UVGI exposure, and C0 is the concentration of culturable micro organisms without UVGI exposure. A review of airborne
  • 16. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref According to First et al [1999]: • When a volume equivalent to the volume of the room enters and is exhausted • 1 ACH well-mixed air removes 63% of air contaminants • 2 ACH well-mixed air removes 84% of air contaminants • Any air disinfection method that is 63% effective produces 1 Equivalent ACH This equivalence is not uncontested A review of airborne
  • 17. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref In 1997, the Centers for Disease Control and Prevention (CDC), National Institute for Occupational Safety and Health (NIOSH) awarded a contract to the University of Colorado to evaluate UVGI to kill or inactivate airborne mycobacteria. • These included: – the irradiance level in the upper room that provides a UVGI dose over time that kills or inactivates an airborne surrogate of M.tb – how to best measure UVGI fluence levels – the effect of air mixing on UVGI performance – the relationship between mechanical ventilation and UVGI systems, – the effects of humidity and photoreactivation, and – the optimum placement of UVGI fixtures. A review of airborne
  • 18. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES: comparative UVGI efficacy Riley (1976) Miller (1999) Ko (2000) Source Nardell 2010 Micro-organism BCG Mycobacterium BCG parafortuitum Particle size (μ m) 0.5 - 3 0.65 - 2.1 1.1 - 4.7 Suspending 0.2% BSA DW 10% FCS medium Temperature (°C) n/a n/a 15 - 35 4 - 26 RH (%) 25 20, 40 50 - 90 41- 69 Room size (m3) 61 90 46 Mechanical No Yes Yes ventilation ACH 2 2-4 0 6 6-8 6 Mixing fan Yes Yes No during aerosolisation UV output (W) 17 46 99 (28) 99 (28) 36 (10) 59 (15) UV output/ room 0.28 0.75 1.1 1.1 0.78 1.3 size (W/m3) UV fixture type C1 C1&W CN&C2 CN&C2 C2 C2&W UV effectiveness 83 88, 89 98 95 52 ±19 64 ±10 (%) UV effect (ACH) A review of airborne 10 18-19, 33 6-16, 19 9.8 ± 6.4 11.7 ± 7.1
  • 19. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Xu, et al 2002 – Boulder, Colorado Source Department of Health and Human Services, et al 2009 A review of airborne Source Xu, et al 2003
  • 20. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Xu, Et al 2002 – UVGI full-scale efficacy studies 5 fixtures, totalling 216 W producing: - avg. 42 μW/cm2 in the irradiated upper zone, - 0.08 μW/cm2 at eye level 250 C 50% RH Spatial distribution of UV measured using actinometry in the upper-room zone with 100% UVGI A review of airborne Source Xu, et al 2003
  • 21. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Xu, Et al 2002 – Boulder, Colarado • Full scale room studies – 87 m2 test chamber • B. subtilis, M. parafortuitum, and M. bovis. • Two experiments: At 50% RH with all lamps: – constant generation – effectiveness culturable airborne bacteria reduced: – inactivation rate – equivalent ACH • B. subtilis spores - 46% - 80% • M. parafortuitum - 83% - 98% • M. bovis BCG - 96% - 97% Increasing the ventilation rate from 0 to 6 ACH decreased microbial inactivation for M. parafortuitum and B. sublilis spores Reducing lamp numbers decreased A review of airborne effectiveness
  • 22. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Escombe et al 2009 – Hospital Nacional Dos de Mayo, Lima Airborne transmission study facility with three parallel ward air exposure chambers TB/HIV ward Air injection vent Upward-facing UVGI fixture Simple mixing fan A review of airborne Air extraction Source Escombe, et al 2009
  • 23. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Escombe et al 2009 – UVGI and Ionisation • 535 days, 150 guinea pigs per enclosure, using a 2-d cycle. • UV-off days: Control and negative ioniser chambers (chamber 1 &2) • UV-on days: UV lights and mixing fans were turned on in the ward (chamber 3) • TB infection in guinea pigs was defined by monthly tuberculin skin tests • control group 35% • ionizers 14 % • UVGI 9.5 % Guinea pigs underwent autopsy to test for TB disease • • control group 8.5% Ground plane Power supply • ionizers 4.3 % • UVGI 3.6 % Insulating spacers Needle tips discharge 25 000 V A review of airborne Source Escombe, et al 2009
  • 24. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Escombe et al 2009 – UVGI and Ionisation Control UV Lights Ionisers Dust-related outbreak TB Infected animals (% of exposed) Source Escombe, et al 2009 A review of airborne
  • 25. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref             UPPER AIR UVGI Summary Guidance DHHS         Temperature   20 - 24 °C     Ceiling supply air   room t °C - 3 °C     ACH   <6     RH   30 - 60%         min. ave. fluence   12 μW/cm2   ave. UV fluence rate 30 - 50 μW/cm2   Lamps   Low-pressure mercury arc     or       Medium-pressure (low ozone)   Irradiance   1.87 W/m2       Power   6 W/m3     Mercury   < 5mg       Max lower room   irradiance   0.2 μW/cm2 (conservative?)     CDC/NIOSH REL   6 mJ/cm2 per 8 hours     ACGIH TLV   6 mJ/cm2 per 8 hours   A review of airborne       Ballast harmonic distortion < 10%     Ceiling > 2.7m   unsheilded     Ceiling 2.4 - 2.7m   sheilded            
  • 26. STUDIES Escombe et al 2007 – Natural ventilation in Lima OBJECTIVE : to investigate the rates, determinants, and effects of natural ventilation in health care settings. • 5 ‘‘old-fashioned’’ design (built pre-1950) and 3 ‘‘modern’’ design (1970–1990) were studied = 70 naturally ventilated clinical rooms with infectious patients • Compared to 12 post-2000 mechanically ventilated negative-pressure respiratory isolation rooms – CO2 tracer gas technique – 368 experiments – Architectural and environmental variables were measured – Infection risk was estimated for TB exposure (Wells- Riley model) A review of airborne Source: Google 2011 Malta
  • 27. STUDIES Escombe et al 2007 Source Google 2011 Opening windows and doors provided median ventilation of 28 ACH: – >2 x mechanically ventilated negative-pressure rooms ventilated at 12 ACH – 18 times that with windows and doors closed • Facilities built more than 50 years ago, characterised by large windows and high ceilings, had greater ventilation than modern naturally ventilated rooms (40 versus 17 ACH) • Even within the lowest quartile of wind speeds, natural ventilation exceeded mechanical • Model predicted that following 24 h exposure to untreated TB patients: – 39% of susceptible individuals in mechanically ventilated rooms – 33% in modern – 11% in pre-1950 naturally ventilated facilities with windows and doors open would become infectious CONCLUSION: “Opening windows and doors maximises natural ventilation so that the risk of airborne contagion is much lower than with … mechanical ventilation systems.” A review of airborne
  • 28. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref STUDIES Zhao et al 2009 – Silver-doped Titanium Dioxide nano-Ag/TiO2 and UVA light irradiation can improve the efficiency of bacterial restraining in medical nursing institutions [Zhao et al] A review of airborne Source: Google 2011 Ellis Island
  • 29. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref References Bolashikov, Z.D. , Melikov, A.K., 2009. Methods for air cleaning and protection of building occupants from airborne pathogens. Building and Environment 44, 1378–1385. doi:10.1016/j.buildenv.2008.09.001. Digel, I., Temiz, Artmann, A., Nishikawa, K., Cook, M., Kurulgan, E.I. Artmann, G.M., 2005. Bactericidal effects of plasma-generated cluster ions. Medical Biological Engineering and Computing 43, 800-807. Department of Health and Human Services., Centers for Disease Control and Prevention., National Institute for Occupational Safety and Health., 2009. Environmental Control for Tuberculosis: Basic Upper-Room Ultraviolet Germicidal Irradiation Guidelines for Healthcare Settings. Escombe, R.A., Moore, D.J.A., Gilman, R.H., Navincopa, M., Ticona, E., Mitchell, B., Noakes, C,. Martı´nez, C., Sheen,P., Ramirez, R., Quino, W., Gonzalez, A., Friedland, J.S., Evans, C.A., 2009. Natural Ventilation for the Prevention of Airborne Contagion. PLoS Medicine 6:3, 0-11. www.plosmedicine.org . Escombe, R.A., Oese, C.C., Gilman, R.H., Navincopa, M., Pan, W., Martı´nez, C., Chacaltana, J., Rodrı´guez, R., Moore, D.J.A., Friedland, J.S., Evans, C.A., 2007. Upper-Room Ultraviolet Light and Negative Air Ionization to Prevent Tuberculosis Transmission PLoS Medicine 4:2, 309-317. www.plosmedicine.org . Kato, S., Sung,M., 2011. Using UVGI to counter contaminant dispersion. IFHE Digest 2011.
  • 30. intro I transmission I considerations I techniques I dilution I filtration I UV 123 I PCO I ionisation I advanced distribution I ref References (continued) Kearns, A.M., Barrett, A., Marshall, C., Freeman, R., Magee, J.G., Bourke, S.J., Steward, M., 2000. Epidemiology and molecular typing of an outbreak of tuberculosis in a hostel for homeless men. Journal of Clinical Pathology 53, 122–124. Kowalski, W. 2010. Ultraviolet Germicidal Irradiation Handbook. Springer, New York. ISBN 978-3-642-01998-2. Nardell, E.A., 2010. Progress in the Application of Ultraviolet Germicidal Irradiation. American Society for Photobiology. Powerpoint accessed www.ghdonline . Riley, R.L., Knight, M., Middlebrook, G., 1976. Ultraviolet susceptibility of BCG and virulent tubercle bacilli. American Review of Respiratory Disease 113, 413–418. Xu, P., Peccia, J., Fabian, P., Martyny, J.W., Fennelly, K.P., Hernandez, M., Miller S.L., 2003. Efficacy of ultraviolet germicidal irradiation of upper-room air in inactivating airborne bacterial spores and mycobacteria in full-scale studies. Atmospheric Environment 37, 405–419. Zhao, Y.K., Sung, W.P., Tsai, T.T., Wang, H.J., 2010. Application of Nanoscale Silver-Doped Titanium Dioxide as Photocatalyst for Indoor Airborne Bacteria Control: A Feasibility Study in Medical Nursing Institutions. Journal of Air and Waste Management Association 60:337–345. ISSN:1047-3289.
  • 31. Architectural Engineering Research Group Dirk Conradie Faatiema Salie Geoff Abbott Jeremy Gibberd Lorato Motsatsi Nkhensani Baloyi Peta de Jager Sheldon Bole Thabang Molefi Tichoana Kumurai Sidney Parsons Slide 31
  • 32. Architectural Engineering research group Dirk Conradie Faatiema Salie Geoff Abbott Jeremy Gibberd Lorato Motsatsi Nkhensani Baloyi Peta de Jager Sheldon Bole Thabang Molefi In memory of Dr Sidney Parsons Slide 32