Advances in Fan Coil Unit technology
and Controls
Presented By – Mick Holland
Technical Sales Manager, Ability projects
Established in 2001
No 1 UK supplier of FCU
New Factory in 2012
Supplying 16000 per annum
Independently tested
In house test facilities
Controls Specialist
Ongoing Development
Ability Product Range
EVOLUTION (Energy Efficient EC)

MATRIX (World Leading FCU)

EVO270

- Fan Deck, Std Pod or Smart Pod

MAT270 - Std or Smart Pod

EVO235

- Std Pod or Smart Pod

MAT235 - Std or Smart Pod

EVO190

- Std Pod or Smart Pod

MAT190 - Std or Smart Pod

EVO155

- Single Inlet Pod

MAT155 - Single Inlet Pod

EVOVERT

- Std Pod or Smart Pod

MATVERT - Std or Smart Pod

EVOLUTION range available as a FCU alone OR as a full package
including all valves and controls. MATRIX is a fully packaged unit.
Presentation Contents
• EC Motors
• Valves - PICC v ePIV
• Controls
• Matrix Range
EC Motors
EC/DC MOTOR
rotor
permanent
magnet
lamination
stack

Hall-effect
sensor

bearing
system
winding
commutation
electronics
Why the shift to EC/DC motor technology?
To use less energy.
Current building regulations require that that the specific fan power,
Watts per Litre per second, for a FCU does not exceed 0.6 W(L/S). Most
design specifications are looking for this to be 0.4 W(L/S) or less.
Energy costs have soared taking this further up the agenda.
To continue to give designers a choice.
AC motors are inefficient and use to much energy. Without the
introduction of energy efficient EC/DC technology designers would have
to look at using alternative systems.
What are the benefits of using EC/DC?
Use less energy

50% reduction compared to AC

Create Less Heat

Reduced heat pick up and, Therefore, overall
cooling requirement . Very useful in something that
provides cooling

Infinitely Variable

Fan speed is set via a 2 – 10 volt DC signal providing
a much greater level of control and flexibility.

Longer Life

Cooler running, sealed for life bearings and casings
make the EC/DC motor capable of lasting twice that
of it’s AC counterpart. 90,000 Hrs.

And Further Operational Benefits
EC Fan Deck
 Multiple scrolls onto a single motor
 Up to 3 scrolls on one single motor
 Single 1 piece fan deck
 Commonly know as a “Wobly”
 Power Factor of 0.35 to 0.5
 Only available with standard speed
control
EC Pod Fan - Std
 Single motor with single scroll
 Multiple units in a single FCU
 Fans can be removed individually
 Commonly know as a “ERM”
 Power Factor of 0.55 to 0.65
 2 – 10 Volt speed control
EC Pod Fan - Smart






Single motor with single scroll
Multiple units in a single FCU
Fans can be removed individually
Commonly know as a “ERM”
Power Factor of 0.55 to 0.65

 Pressure independent control
 Adjusts to different external pressure
 Air volume preset and remotely
adjustable
EC Pod Fan –
Single Inlet

 Single motor with single scroll
 Multiple units in a single FCU
 Fans can be removed individually
 Commonly know as a “Pan” unit
 Power Factor of 0.35 to 0.5
 2 – 10 Volt speed control
STANDARD FCU

5 Pa

10 Pa

15 Pa

Standard Pod or Fan Deck
Common Fan plenum
Single 0-10 volt signal/Voltage
Requires VCD’s
STANDARD FCU

5 Pa
15 Pa

10
15 Pa

15 Pa

Standard Pod or Fan Deck
Common Fan plenum
Single 0-10 volt signal/Voltage
Requires VCD’s
All ducts at same pressure
MATRIX CONCEPT

5 Pa

10 Pa

15 Pa

Smart Pod fan
Discharge Plenum per Fan
Multiple 0-10 volt signals
Does NOT Requires VCD’s
Ducts at lower pressures
VAV (Design Duty)

5 Pa

10 Pa

15 Pa

Design Duty
300 L/S (100%)
FAN = 60 Watts
SFP = 0.2 W(L/S)
W(M²) = 1
VAV (SetBack)

1 Pa

2 Pa

4 Pa

SetBack
150L/S (50%)
FAN = 15 Watts
SFP = 0.1 W(L/S)
W(M²) = 0.25
VAV (FanStop)

2 Pa

4 Pa

FanStop (Stage 1)
100L/S (33%)
FAN = 10 Watts
SFP = 0.1 W(L/S)
W(M²) = 0.125
VAV (FanStop)

2 Pa

FanStop (Stage 2)
50L/S (17%)
FAN = 5 Watts
SFP = 0.1 W(L/S)
W(M²) = 0.06
VAV (FanStop)

FCU Control Graph - Variable Air Volume
100 %

80 %

80 %

60 %

60 %

40 %

40 %

20 %

20 %

0%

0%
21.0 21.2 21.4 21.6 21.8 22.0 22.2 22.4 22.6 22.8 23.0 23.2 23.4 23.6 23.8 24.0
°C °C °C °C °C °C °C °C °C °C °C °C °C °C °C °C
RoomTemperature °C

Air Volume

120 %

100 %
Water Flow

120 %
VAV (FanStop)

50
40
30
20 r
15 Watts
60
5
FCU Control Graph - Variable Air Volume
100 %

80 %

80 %

60 %

60 %

40 %

40 %

20 %

20 %

0%

0%
21.0 21.2 21.4 21.6 21.8 22.0 22.2 22.4 22.6 22.8 23.0 23.2 23.4 23.6 23.8 24.0
°C °C °C °C °C °C °C °C °C °C °C °C °C °C °C °C
RoomTemperature °C

Air Volume

120 %

100 %
Water Flow

120 %
Commissioning The Airside
The Conventional Way
Matrix Way
1.
2.
3.
4.
5.
6.
7.
8.
9.

Check that the FCU installation is complete.
Turn on the fans in the FCU
Measure and Record the Airflow from each grille
Check proportional balance and adjust using dampers if required
Repeat steps 3 and 4 until balance is achieved
Measure and Calculate total air volume from Fan Coil Unit
Check Air volume is within CIBSE guidelines, -0 to +10%
Adjust air volume using transformer or altering control signal
Repeat steps 6 to 8 until scheduled Air Volume is achieved

TRIMMING
PICC Valves
Pressure Independent Characterised Control Valve?
Two part valve comprising
1. Pressure Regulator
• 30 to 350 kPa differential
pressure

2. Control Valve
• 2-way characterised control
valve
• Actuator
What are the benefits of using a PICC valve?
1. Self balancing system
2. Design water flow rate factory set

3. Remote setting of water flow rate
4. BMS knows the water flow rate
5 . No Double Regulating Valve
6. Air in system has little effect
PICC Valves Incorporated Into a Valve Set.
1. Flushing Bypass
2. Return Isolation Valve

3. Venturi Nozzle
4. Drain
5. Rotary PICC Valve
ABILITY PROJECTS

ePIV Valves
ePIV
Two part 15mm valve comprising
Hydraulic Balancing
Motorised Control

Pressure Independent Flow Control

Ultrasonic flow measurement
How does it work?
BMS

2-10v Flow Signal

Control Valve
• 2-Port control valve
• Intelligent Actuator

Two part 15mm valve comprising
• Individually calibrated flow
measurement device
• Continuous Flow Rate Feed
back via 2-10v signal
PICV vs ePIV
Mechanical pressure independent valves

Electronic pressure independent valves

Suffer from hysteresis

Do not suffer from hysteresis

Additional flow measurement devices required Flow measurement device built in
High minimum differential pressure
requirement (50 kPa)

Low minimum pressure differential
requirement (up to 15 kPa)

Control accuracy
+/- 10% at high flows high pressures
+/- 25% at low flows low pressures

Control Accuracy
+/- 10% standard
-0 / +10% Ability Delta Package

Considered low cost

Valveset with an ePIV valve same cost!
Valve Sets
Valve Sets
Valve Sets
New Features
Enhanced Flushing Mode
The flushing mode BV still opens the valves completely
But now it records the flushing velocity experienced, meaning if this differs
greatly day to day you can investigate the cause!
EPIV Details
Type

DN

V’nom [l/s]

open

15

0.35

0.004

open

20

0.65

0.007

open

25

1.15

open

32

1.80

open

40

2.50

0.025

open

50

4.80

0.048

Control
Characteristic
Control accuracy
Max. working pressure ps
Max. differential pressure pmax
Max. closing pressure ps
Medium temperature

V’max [l/s]

30 … 100% V’nom

V’min.controlabe [l/s]

0.012
0.018

modulating 0…10 V / MP-Bus
equal percentage / linear (switchable)
+/- 10% of V’actual value (25…100% V’nom)
1’600 kPa
340 kPa
690 kPa
-10 … +120°C (up to 50% Glycol)

*** May be subject to changes ***
ePIV Summary
•
•
•
•
•

Belimo 5 Year Guarantee
Continuous system health monitoring
Valve sets with bypasses and drains available
Soft Landing Friendly!
Low cost.

• Very easy to commissioning
• Consultants can witness commissioning
figures on all the FCUs
• Low pressure so energy savings at pump
Controls
The first ETL listed FCU controller and strategy!
Being on the Energy Technology List (ETL) means a business
can take advantage of the Enhanced Capital Allowance
Scheme (ECA).
The ECA scheme allows businesses to claim 100% first year
capital allowance on investments on ETL listed energy saving
equipment.
If a business spent £1000 the standard capital allowance
would be approx. £41.50. The ECA would be worth a £230
one off tax relief in the first year!
What is the specification for a modern controller?
1. Fully programmable
2. Native BACnet protocol

3. MS/TP or IP (Ethernet)
4. 4 analogue outputs
5 . 6 Triac Outputs
6. 11 Universal Inputs
7. Individually factory programmed
What Parameters are controlled or measured ?
1. Supply Air Volume (L/S)
2. Supply Air Temperature (° C)

3. Return Air Temperature (° C)
4. Water Flow Rate (kG/S)
5 . Water Supply Temperature (° C)
6. Water Return Temperature (° C)
7. Motor Power Consumption (VA)
How can we utilise these known Parameters ?
1. Supply Air Volume (L/S)
2. Supply Air Temperature (° C)

3. Return Air Temperature (° C)
4. Water Flow Rate (kG/S)
5 . Water Supply Temperature (° C)
6. Water Return Temperature (° C)
7. Motor Power Consumption (VA)
What can we calculate with these Parameters ?

Delivered kW

1. Supply Air Volume (L/S)
2. Supply Air Temperature (° C)

3. Return Air Temperature (° C)
4. Water Flow Rate (kG/S)
5 . Water Supply Temperature (° kW
Calculate delivered cooling or heating C)
6. Water Return Temperature (° C)
7. Motor Power Consumption (VA)

Supply Air Volume X Air Δ T X 1.22
What can we calculate with these Parameters ?

Delivered kW
Water Flow Rate

1. Supply Air Volume (L/S)
2. Supply Air Temperature (° C)

3. Return Air Temperature (° C)
4. Water Flow Rate (kG/S)

Calculate and Verify Water Supply Temperature (° C)
5 . Water Flow Rate
6. Water Return Temperature (° C)
7. Motor Power Consumption (VA)

Delivered kW / water ΔT / 4.186
What can we calculate with these Parameters ?

Delivered kW
1. Supply Air Volume (L/S)
Water Flow Rate 2. Supply Air Temperature (° C)
3. Return Air Temperature (° C)
Specific Fan Power 4. Water Flow Rate (kG/S)
Calculate the Specific Fan Power
5 . Water Supply Temperature (° C)
6. Water Return Temperature (° C)
7. Motor Power Consumption (VA)

SFP = (VA x 0.5) / Air Volume L/S
How can we use all of these?

Delivered kW
Water Flow Rate
Specific Fan Power

1. Supply Air Volume (L/S)
2. Supply Air Temperature (° C)

3. Return Air Temperature (° C)
4. Water Flow Rate (kG/S)
5 . Water Supply Temperature (° C)
6. Water Return Temperature (° C)
7. Motor Power Consumption (VA)
What is this the FCU Cubed board?
1. Daily Checks for Dirty Filter
2. Daily Checks For Fan Failure

3. Standby Sentinel
4. Basic Energy Monitoring
Heath Check - Dirty Filter

Heath Check - Fan Failure

The unit monitors the
power consumption
for a certain air
volume on its curve
after activation each
day.

If a drop in power
consumption results
in an alarm

Standby Sentinel
When fans are not
required all non-essential
controls elements are
powered down
minimising consumption.

Basic Energy Monitoring
The controller monitors
the power consumption
of the unit and reports it
to an AV in watts
Control Strategy
Uses an energy saving Variable Air Volume
strategy.
With an increase in cooling demand the first
call is too raise the water flow rate.
At a given point the Airflow starts to increase
to provide more cooling.
If the supply air temperature from the FCU
approaches the minimum set value the air
volume will be raised to offset this.
All parameters are adjustable on a global or
individual basis.
100 %

Air

24 °C

Supply Temp

Typical With
6/12 Water

80 %

22 °C
20 °C

60 %

Air

18 °C

Supply Volume

16 °C

40 %

14 °C
20 %
12 °C
0%

Water

10 °C

Flow Rate

0%

25 %

50 %

Space Load kW

75 %

100%
100 %

Air

24 °C

Supply Temp

Typical With
14/17 Water

80 %

22 °C
20 °C

60 %

Air

18 °C

Supply Volume

16 °C

40 %

14 °C
20 %
12 °C
0%

Water

10 °C

Flow Rate

0%

25 %

50 %

Space Load kW

75 %

100%
Matrix ³
What Is
Matrix ³
Matrix ³
A Complete Terminal
Air Conditioning
Package
³
What is set in the controller in the Factory?
Controls Strategy

A Matrix controls strategy is fully loaded and
setup for the given project.

Address

Each Controller/FCU is addressed for use by the
BMS.

Airflows

Air Volumes for each duct/diffuser are
programmed. This includes setback air volumes for
VAV operation.

Water Flow Rate

Design water flow rates are programmed and set
utilizing the PICC characterization.

Setpoint

Room design Temperature set point is
programmed.
What checks are done at the end of the line?
Fans

All fans are enabled and checked that they
run from signal provided by the controller.

Actuators

Valve actuators are fully functioned through the
Delta Controller.

Temperature Sensors

A routine is run to normalize the temperature
readings from the four sensors to remove potential
measurement errors.

Triacs

All the Triac outputs are checked for function,
including those that are not connected.

Comms Check

Via a laptop, communication with the controller is
established to ensure it functions correctly.
Matrix ³ - Environmental Commissioning
Verifies kW cooling or heating output
remotely.
Accomplished by running a third of units in
cooling and the rest in heating.
Results are logged in a routine that runs
from a Laptop.
Results are corrected for differences
between test conditions and design.
FCU are selected to deliver cooling and
heating. Matrix gives you the Ability to site
verify this.
Matrix Engineering Tool
Supplied on a NetBook to every Matrix
project.
Commissioning Tool to check operation,
adjust operational parameters on a single or,
via BMS, multiple Fan Coils.
Can connect to the FCU via wireless network
if appropriate access points are installed.
This software has been developed over many
years and is tailored to the Matrix range of
Fan Coil Units.
What are the benefits of this system at install??
1.
2.
3.
4.
5.
6.

No volume control dampers to buy, install or air balance
No hydraulic commissioning stations to buy, install, water balance
or maintain – 2 per FCU
All individual air and water flow rates are factory loaded and stored
in each FCU controller
Matrix Engineering Tool does not need the BMS to be operative at
the time of FCU commissioning
Global water balance trimming feature as a single button press :
say, +%5 to all ChW coils on a floor
Matrix Engineering Tool includes the automatic generation of a
commissioning report including the source data used in the
calculation of flow rates
What are the client benefits?
1.
2.
3.
4.
5.
6.
7.

The most energy efficient and flexible FCU system available
Fault Finding becomes a non intrusive, remote activity
Remote verification of water flow rates
Remote verification of kW output
Remote changes to FCU kW, Airflow, Waterflow can be made at any
time
Dirty filter, Fan failure and other alarms come as standard
Fan energy usage can be monitored
Thank you for listening
This has been a CIBSE approved CPD seminar.

Mais conteúdo relacionado

Mais procurados

Sb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_enSb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_enYury Naumov
 
PRESENTATION AIRWELL VRF 2014 GB
PRESENTATION  AIRWELL VRF 2014 GBPRESENTATION  AIRWELL VRF 2014 GB
PRESENTATION AIRWELL VRF 2014 GBArjang Ahmadi
 
660 mw turbo governing & protection system
660 mw turbo  governing & protection system660 mw turbo  governing & protection system
660 mw turbo governing & protection systemAshvani Shukla
 
Perkin-Elmer 4400,4410,4450 Sputtering Deposition Systems
Perkin-Elmer 4400,4410,4450 Sputtering Deposition SystemsPerkin-Elmer 4400,4410,4450 Sputtering Deposition Systems
Perkin-Elmer 4400,4410,4450 Sputtering Deposition SystemsPeter Chen
 
Sb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_enSb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_enYury Naumov
 
Caleffi International NV - Brochure Solar
 Caleffi International NV - Brochure Solar Caleffi International NV - Brochure Solar
Caleffi International NV - Brochure SolarArchitectura
 
Nlc 0280-1250-co y-un50_00
Nlc 0280-1250-co y-un50_00Nlc 0280-1250-co y-un50_00
Nlc 0280-1250-co y-un50_00Oliverh Kalprit
 
Fc744 Hydraulics
Fc744 HydraulicsFc744 Hydraulics
Fc744 Hydraulicstheoryce
 
คู่มือการใช้งาน Danfoss รุ่น KPi
คู่มือการใช้งาน Danfoss รุ่น KPiคู่มือการใช้งาน Danfoss รุ่น KPi
คู่มือการใช้งาน Danfoss รุ่น KPiDNTMb Inc.
 
Whynter ARC-12SD Portable Air Conditioner
Whynter ARC-12SD Portable Air ConditionerWhynter ARC-12SD Portable Air Conditioner
Whynter ARC-12SD Portable Air ConditionerAirConFind
 
OBD2 Powertrain Code List (P0A00- P0A99)
OBD2 Powertrain Code List (P0A00- P0A99)OBD2 Powertrain Code List (P0A00- P0A99)
OBD2 Powertrain Code List (P0A00- P0A99)Tim Miller
 
Whynter ARC-110WD Portable Air Conditioner
Whynter ARC-110WD Portable Air ConditionerWhynter ARC-110WD Portable Air Conditioner
Whynter ARC-110WD Portable Air ConditionerAirConFind
 
Avp694 6 compressed
Avp694 6 compressedAvp694 6 compressed
Avp694 6 compressedjhonnyarpi
 
Yanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAI
Yanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAIYanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAI
Yanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAIAndrew Bowden Dubai
 
Siemens Zone Valve & Actuators
Siemens Zone Valve & ActuatorsSiemens Zone Valve & Actuators
Siemens Zone Valve & ActuatorsCONTROLS & SYSTEMS
 

Mais procurados (20)

Sb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_enSb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_en
 
LG VRF MULTI V
LG VRF MULTI VLG VRF MULTI V
LG VRF MULTI V
 
Hydrostatic Pressure Liquid Level Transmitter
Hydrostatic Pressure Liquid Level TransmitterHydrostatic Pressure Liquid Level Transmitter
Hydrostatic Pressure Liquid Level Transmitter
 
PRESENTATION AIRWELL VRF 2014 GB
PRESENTATION  AIRWELL VRF 2014 GBPRESENTATION  AIRWELL VRF 2014 GB
PRESENTATION AIRWELL VRF 2014 GB
 
660 mw turbo governing & protection system
660 mw turbo  governing & protection system660 mw turbo  governing & protection system
660 mw turbo governing & protection system
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
 
Perkin-Elmer 4400,4410,4450 Sputtering Deposition Systems
Perkin-Elmer 4400,4410,4450 Sputtering Deposition SystemsPerkin-Elmer 4400,4410,4450 Sputtering Deposition Systems
Perkin-Elmer 4400,4410,4450 Sputtering Deposition Systems
 
Sb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_enSb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_en
 
Caleffi International NV - Brochure Solar
 Caleffi International NV - Brochure Solar Caleffi International NV - Brochure Solar
Caleffi International NV - Brochure Solar
 
Nlc 0280-1250-co y-un50_00
Nlc 0280-1250-co y-un50_00Nlc 0280-1250-co y-un50_00
Nlc 0280-1250-co y-un50_00
 
Fc744 Hydraulics
Fc744 HydraulicsFc744 Hydraulics
Fc744 Hydraulics
 
คู่มือการใช้งาน Danfoss รุ่น KPi
คู่มือการใช้งาน Danfoss รุ่น KPiคู่มือการใช้งาน Danfoss รุ่น KPi
คู่มือการใช้งาน Danfoss รุ่น KPi
 
Whynter ARC-12SD Portable Air Conditioner
Whynter ARC-12SD Portable Air ConditionerWhynter ARC-12SD Portable Air Conditioner
Whynter ARC-12SD Portable Air Conditioner
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
 
Breathing Air Purifiers for Commercial and Industrial Use
Breathing Air Purifiers for Commercial and Industrial UseBreathing Air Purifiers for Commercial and Industrial Use
Breathing Air Purifiers for Commercial and Industrial Use
 
OBD2 Powertrain Code List (P0A00- P0A99)
OBD2 Powertrain Code List (P0A00- P0A99)OBD2 Powertrain Code List (P0A00- P0A99)
OBD2 Powertrain Code List (P0A00- P0A99)
 
Whynter ARC-110WD Portable Air Conditioner
Whynter ARC-110WD Portable Air ConditionerWhynter ARC-110WD Portable Air Conditioner
Whynter ARC-110WD Portable Air Conditioner
 
Avp694 6 compressed
Avp694 6 compressedAvp694 6 compressed
Avp694 6 compressed
 
Yanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAI
Yanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAIYanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAI
Yanmar 6 lpa-stp2datasheet ANDREW BOWDEN DUBAI
 
Siemens Zone Valve & Actuators
Siemens Zone Valve & ActuatorsSiemens Zone Valve & Actuators
Siemens Zone Valve & Actuators
 

Semelhante a Innovations - Ability 11.02.14

Ventilation
VentilationVentilation
VentilationDantherm
 
Catalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.comCatalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.comCTY TNHH HẠO PHƯƠNG
 
R501 ADVANCED TRANSFORMER MONITOR | Rugged Monitoring
R501 ADVANCED TRANSFORMER MONITOR | Rugged MonitoringR501 ADVANCED TRANSFORMER MONITOR | Rugged Monitoring
R501 ADVANCED TRANSFORMER MONITOR | Rugged Monitoringrugged_monitoring
 
High Efficiency Solutions EEV & Monitoring Systems
High Efficiency Solutions  EEV & Monitoring SystemsHigh Efficiency Solutions  EEV & Monitoring Systems
High Efficiency Solutions EEV & Monitoring SystemsCAREL Industries S.p.A
 
DB VRF CATALOG LATEST VERSION (1).pdf
DB VRF CATALOG LATEST VERSION (1).pdfDB VRF CATALOG LATEST VERSION (1).pdf
DB VRF CATALOG LATEST VERSION (1).pdfRubenElvisPizaMercha
 
Vfd 130221061349-phpapp02
Vfd 130221061349-phpapp02Vfd 130221061349-phpapp02
Vfd 130221061349-phpapp02Imtiaz Riaz
 
Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Marlon Torres
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Beeteco
 
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgFuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgDien Ha The
 
Varaible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire PumpsVaraible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire PumpsJames S Nasby
 
Electro-Hydraulic Linear Actuators for Industrial Valves
Electro-Hydraulic Linear Actuators for Industrial ValvesElectro-Hydraulic Linear Actuators for Industrial Valves
Electro-Hydraulic Linear Actuators for Industrial ValvesClassic Controls, Inc.
 
Interfacing delta v to motorized actuators addressing control applications
Interfacing delta v to motorized actuators addressing control applications Interfacing delta v to motorized actuators addressing control applications
Interfacing delta v to motorized actuators addressing control applications Emerson Exchange
 
An overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingAn overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingBill Spohn
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 

Semelhante a Innovations - Ability 11.02.14 (20)

Ventilation
VentilationVentilation
Ventilation
 
Catalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.comCatalog Frenic mini(NEW) -www.haophuong.com
Catalog Frenic mini(NEW) -www.haophuong.com
 
R501 ADVANCED TRANSFORMER MONITOR | Rugged Monitoring
R501 ADVANCED TRANSFORMER MONITOR | Rugged MonitoringR501 ADVANCED TRANSFORMER MONITOR | Rugged Monitoring
R501 ADVANCED TRANSFORMER MONITOR | Rugged Monitoring
 
High Efficiency Solutions EEV & Monitoring Systems
High Efficiency Solutions  EEV & Monitoring SystemsHigh Efficiency Solutions  EEV & Monitoring Systems
High Efficiency Solutions EEV & Monitoring Systems
 
DB VRF CATALOG LATEST VERSION (1).pdf
DB VRF CATALOG LATEST VERSION (1).pdfDB VRF CATALOG LATEST VERSION (1).pdf
DB VRF CATALOG LATEST VERSION (1).pdf
 
E lnt technical document
E lnt technical documentE lnt technical document
E lnt technical document
 
Vfd 130221061349-phpapp02
Vfd 130221061349-phpapp02Vfd 130221061349-phpapp02
Vfd 130221061349-phpapp02
 
Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)
 
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgFuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
 
lm555.pdf
lm555.pdflm555.pdf
lm555.pdf
 
Varaible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire PumpsVaraible Speed Drives for Motor Driven Fire Pumps
Varaible Speed Drives for Motor Driven Fire Pumps
 
Frenic hvac catalog
Frenic hvac catalogFrenic hvac catalog
Frenic hvac catalog
 
Smart act 1 English
Smart act 1 EnglishSmart act 1 English
Smart act 1 English
 
Electro-Hydraulic Linear Actuators for Industrial Valves
Electro-Hydraulic Linear Actuators for Industrial ValvesElectro-Hydraulic Linear Actuators for Industrial Valves
Electro-Hydraulic Linear Actuators for Industrial Valves
 
Interfacing delta v to motorized actuators addressing control applications
Interfacing delta v to motorized actuators addressing control applications Interfacing delta v to motorized actuators addressing control applications
Interfacing delta v to motorized actuators addressing control applications
 
An overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingAn overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testing
 
Automate
AutomateAutomate
Automate
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Urhe cf y-un50_00
Urhe cf y-un50_00Urhe cf y-un50_00
Urhe cf y-un50_00
 

Mais de Overbury

British Gypsum Innovation Seminar - Newman Street
British Gypsum Innovation Seminar - Newman StreetBritish Gypsum Innovation Seminar - Newman Street
British Gypsum Innovation Seminar - Newman StreetOverbury
 
Innovation centre
Innovation centreInnovation centre
Innovation centreOverbury
 
Innovation centre
Innovation centreInnovation centre
Innovation centreOverbury
 
Innovation centre
Innovation centreInnovation centre
Innovation centreOverbury
 
Innovation centre
Innovation centreInnovation centre
Innovation centreOverbury
 
Innovation centre
Innovation centreInnovation centre
Innovation centreOverbury
 
Innovations from SAS
Innovations from SASInnovations from SAS
Innovations from SASOverbury
 
Innovations - Mitshubishi Electric 07.02.14
Innovations - Mitshubishi Electric 07.02.14Innovations - Mitshubishi Electric 07.02.14
Innovations - Mitshubishi Electric 07.02.14Overbury
 
Style Partitions presentation 28.01.14
Style Partitions presentation 28.01.14Style Partitions presentation 28.01.14
Style Partitions presentation 28.01.14Overbury
 
Innovation in Air Conditioning
Innovation in Air ConditioningInnovation in Air Conditioning
Innovation in Air ConditioningOverbury
 
Innovation in Timber Veneer & Laminate Doors, Panels and Doorframes
Innovation in Timber Veneer & Laminate Doors, Panels and DoorframesInnovation in Timber Veneer & Laminate Doors, Panels and Doorframes
Innovation in Timber Veneer & Laminate Doors, Panels and DoorframesOverbury
 
Innovations in Office Partition Systems
Innovations in Office Partition SystemsInnovations in Office Partition Systems
Innovations in Office Partition SystemsOverbury
 
Innovation in Lighting
Innovation in LightingInnovation in Lighting
Innovation in LightingOverbury
 
Sustainability in Air Conditioning
Sustainability in Air ConditioningSustainability in Air Conditioning
Sustainability in Air ConditioningOverbury
 
Sustainability in Air Conditioning
Sustainability in Air ConditioningSustainability in Air Conditioning
Sustainability in Air ConditioningOverbury
 
Sustainability in Paint Products
Sustainability in Paint ProductsSustainability in Paint Products
Sustainability in Paint ProductsOverbury
 
Sustainability in Construction Products
Sustainability in Construction Products Sustainability in Construction Products
Sustainability in Construction Products Overbury
 
Sustainability in Flooring
Sustainability in FlooringSustainability in Flooring
Sustainability in FlooringOverbury
 
Sustainability in Ceilings
Sustainability in CeilingsSustainability in Ceilings
Sustainability in CeilingsOverbury
 
Sustainability in Ceilings
Sustainability in CeilingsSustainability in Ceilings
Sustainability in CeilingsOverbury
 

Mais de Overbury (20)

British Gypsum Innovation Seminar - Newman Street
British Gypsum Innovation Seminar - Newman StreetBritish Gypsum Innovation Seminar - Newman Street
British Gypsum Innovation Seminar - Newman Street
 
Innovation centre
Innovation centreInnovation centre
Innovation centre
 
Innovation centre
Innovation centreInnovation centre
Innovation centre
 
Innovation centre
Innovation centreInnovation centre
Innovation centre
 
Innovation centre
Innovation centreInnovation centre
Innovation centre
 
Innovation centre
Innovation centreInnovation centre
Innovation centre
 
Innovations from SAS
Innovations from SASInnovations from SAS
Innovations from SAS
 
Innovations - Mitshubishi Electric 07.02.14
Innovations - Mitshubishi Electric 07.02.14Innovations - Mitshubishi Electric 07.02.14
Innovations - Mitshubishi Electric 07.02.14
 
Style Partitions presentation 28.01.14
Style Partitions presentation 28.01.14Style Partitions presentation 28.01.14
Style Partitions presentation 28.01.14
 
Innovation in Air Conditioning
Innovation in Air ConditioningInnovation in Air Conditioning
Innovation in Air Conditioning
 
Innovation in Timber Veneer & Laminate Doors, Panels and Doorframes
Innovation in Timber Veneer & Laminate Doors, Panels and DoorframesInnovation in Timber Veneer & Laminate Doors, Panels and Doorframes
Innovation in Timber Veneer & Laminate Doors, Panels and Doorframes
 
Innovations in Office Partition Systems
Innovations in Office Partition SystemsInnovations in Office Partition Systems
Innovations in Office Partition Systems
 
Innovation in Lighting
Innovation in LightingInnovation in Lighting
Innovation in Lighting
 
Sustainability in Air Conditioning
Sustainability in Air ConditioningSustainability in Air Conditioning
Sustainability in Air Conditioning
 
Sustainability in Air Conditioning
Sustainability in Air ConditioningSustainability in Air Conditioning
Sustainability in Air Conditioning
 
Sustainability in Paint Products
Sustainability in Paint ProductsSustainability in Paint Products
Sustainability in Paint Products
 
Sustainability in Construction Products
Sustainability in Construction Products Sustainability in Construction Products
Sustainability in Construction Products
 
Sustainability in Flooring
Sustainability in FlooringSustainability in Flooring
Sustainability in Flooring
 
Sustainability in Ceilings
Sustainability in CeilingsSustainability in Ceilings
Sustainability in Ceilings
 
Sustainability in Ceilings
Sustainability in CeilingsSustainability in Ceilings
Sustainability in Ceilings
 

Último

Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...Martijn de Jong
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonAnna Loughnan Colquhoun
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxKatpro Technologies
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityPrincipled Technologies
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonetsnaman860154
 
CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Servicegiselly40
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CVKhem
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxMalak Abu Hammad
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreternaman860154
 

Último (20)

Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptxFactors to Consider When Choosing Accounts Payable Services Providers.pptx
Factors to Consider When Choosing Accounts Payable Services Providers.pptx
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 
CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Service
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CV
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
The Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptxThe Codex of Business Writing Software for Real-World Solutions 2.pptx
The Codex of Business Writing Software for Real-World Solutions 2.pptx
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 

Innovations - Ability 11.02.14

  • 1.
  • 2. Advances in Fan Coil Unit technology and Controls Presented By – Mick Holland Technical Sales Manager, Ability projects
  • 3. Established in 2001 No 1 UK supplier of FCU New Factory in 2012 Supplying 16000 per annum Independently tested In house test facilities Controls Specialist Ongoing Development
  • 4. Ability Product Range EVOLUTION (Energy Efficient EC) MATRIX (World Leading FCU) EVO270 - Fan Deck, Std Pod or Smart Pod MAT270 - Std or Smart Pod EVO235 - Std Pod or Smart Pod MAT235 - Std or Smart Pod EVO190 - Std Pod or Smart Pod MAT190 - Std or Smart Pod EVO155 - Single Inlet Pod MAT155 - Single Inlet Pod EVOVERT - Std Pod or Smart Pod MATVERT - Std or Smart Pod EVOLUTION range available as a FCU alone OR as a full package including all valves and controls. MATRIX is a fully packaged unit.
  • 5. Presentation Contents • EC Motors • Valves - PICC v ePIV • Controls • Matrix Range
  • 8. Why the shift to EC/DC motor technology? To use less energy. Current building regulations require that that the specific fan power, Watts per Litre per second, for a FCU does not exceed 0.6 W(L/S). Most design specifications are looking for this to be 0.4 W(L/S) or less. Energy costs have soared taking this further up the agenda. To continue to give designers a choice. AC motors are inefficient and use to much energy. Without the introduction of energy efficient EC/DC technology designers would have to look at using alternative systems.
  • 9. What are the benefits of using EC/DC? Use less energy 50% reduction compared to AC Create Less Heat Reduced heat pick up and, Therefore, overall cooling requirement . Very useful in something that provides cooling Infinitely Variable Fan speed is set via a 2 – 10 volt DC signal providing a much greater level of control and flexibility. Longer Life Cooler running, sealed for life bearings and casings make the EC/DC motor capable of lasting twice that of it’s AC counterpart. 90,000 Hrs. And Further Operational Benefits
  • 10. EC Fan Deck  Multiple scrolls onto a single motor  Up to 3 scrolls on one single motor  Single 1 piece fan deck  Commonly know as a “Wobly”  Power Factor of 0.35 to 0.5  Only available with standard speed control
  • 11. EC Pod Fan - Std  Single motor with single scroll  Multiple units in a single FCU  Fans can be removed individually  Commonly know as a “ERM”  Power Factor of 0.55 to 0.65  2 – 10 Volt speed control
  • 12. EC Pod Fan - Smart      Single motor with single scroll Multiple units in a single FCU Fans can be removed individually Commonly know as a “ERM” Power Factor of 0.55 to 0.65  Pressure independent control  Adjusts to different external pressure  Air volume preset and remotely adjustable
  • 13. EC Pod Fan – Single Inlet  Single motor with single scroll  Multiple units in a single FCU  Fans can be removed individually  Commonly know as a “Pan” unit  Power Factor of 0.35 to 0.5  2 – 10 Volt speed control
  • 14. STANDARD FCU 5 Pa 10 Pa 15 Pa Standard Pod or Fan Deck Common Fan plenum Single 0-10 volt signal/Voltage Requires VCD’s
  • 15. STANDARD FCU 5 Pa 15 Pa 10 15 Pa 15 Pa Standard Pod or Fan Deck Common Fan plenum Single 0-10 volt signal/Voltage Requires VCD’s All ducts at same pressure
  • 16. MATRIX CONCEPT 5 Pa 10 Pa 15 Pa Smart Pod fan Discharge Plenum per Fan Multiple 0-10 volt signals Does NOT Requires VCD’s Ducts at lower pressures
  • 17. VAV (Design Duty) 5 Pa 10 Pa 15 Pa Design Duty 300 L/S (100%) FAN = 60 Watts SFP = 0.2 W(L/S) W(M²) = 1
  • 18. VAV (SetBack) 1 Pa 2 Pa 4 Pa SetBack 150L/S (50%) FAN = 15 Watts SFP = 0.1 W(L/S) W(M²) = 0.25
  • 19. VAV (FanStop) 2 Pa 4 Pa FanStop (Stage 1) 100L/S (33%) FAN = 10 Watts SFP = 0.1 W(L/S) W(M²) = 0.125
  • 20. VAV (FanStop) 2 Pa FanStop (Stage 2) 50L/S (17%) FAN = 5 Watts SFP = 0.1 W(L/S) W(M²) = 0.06
  • 21. VAV (FanStop) FCU Control Graph - Variable Air Volume 100 % 80 % 80 % 60 % 60 % 40 % 40 % 20 % 20 % 0% 0% 21.0 21.2 21.4 21.6 21.8 22.0 22.2 22.4 22.6 22.8 23.0 23.2 23.4 23.6 23.8 24.0 °C °C °C °C °C °C °C °C °C °C °C °C °C °C °C °C RoomTemperature °C Air Volume 120 % 100 % Water Flow 120 %
  • 22. VAV (FanStop) 50 40 30 20 r 15 Watts 60 5 FCU Control Graph - Variable Air Volume 100 % 80 % 80 % 60 % 60 % 40 % 40 % 20 % 20 % 0% 0% 21.0 21.2 21.4 21.6 21.8 22.0 22.2 22.4 22.6 22.8 23.0 23.2 23.4 23.6 23.8 24.0 °C °C °C °C °C °C °C °C °C °C °C °C °C °C °C °C RoomTemperature °C Air Volume 120 % 100 % Water Flow 120 %
  • 23. Commissioning The Airside The Conventional Way Matrix Way 1. 2. 3. 4. 5. 6. 7. 8. 9. Check that the FCU installation is complete. Turn on the fans in the FCU Measure and Record the Airflow from each grille Check proportional balance and adjust using dampers if required Repeat steps 3 and 4 until balance is achieved Measure and Calculate total air volume from Fan Coil Unit Check Air volume is within CIBSE guidelines, -0 to +10% Adjust air volume using transformer or altering control signal Repeat steps 6 to 8 until scheduled Air Volume is achieved TRIMMING
  • 25.
  • 26. Pressure Independent Characterised Control Valve? Two part valve comprising 1. Pressure Regulator • 30 to 350 kPa differential pressure 2. Control Valve • 2-way characterised control valve • Actuator
  • 27. What are the benefits of using a PICC valve? 1. Self balancing system 2. Design water flow rate factory set 3. Remote setting of water flow rate 4. BMS knows the water flow rate 5 . No Double Regulating Valve 6. Air in system has little effect
  • 28. PICC Valves Incorporated Into a Valve Set. 1. Flushing Bypass 2. Return Isolation Valve 3. Venturi Nozzle 4. Drain 5. Rotary PICC Valve
  • 30. ePIV Two part 15mm valve comprising Hydraulic Balancing Motorised Control Pressure Independent Flow Control Ultrasonic flow measurement
  • 31. How does it work? BMS 2-10v Flow Signal Control Valve • 2-Port control valve • Intelligent Actuator Two part 15mm valve comprising • Individually calibrated flow measurement device • Continuous Flow Rate Feed back via 2-10v signal
  • 32. PICV vs ePIV Mechanical pressure independent valves Electronic pressure independent valves Suffer from hysteresis Do not suffer from hysteresis Additional flow measurement devices required Flow measurement device built in High minimum differential pressure requirement (50 kPa) Low minimum pressure differential requirement (up to 15 kPa) Control accuracy +/- 10% at high flows high pressures +/- 25% at low flows low pressures Control Accuracy +/- 10% standard -0 / +10% Ability Delta Package Considered low cost Valveset with an ePIV valve same cost!
  • 36. New Features Enhanced Flushing Mode The flushing mode BV still opens the valves completely But now it records the flushing velocity experienced, meaning if this differs greatly day to day you can investigate the cause!
  • 37. EPIV Details Type DN V’nom [l/s] open 15 0.35 0.004 open 20 0.65 0.007 open 25 1.15 open 32 1.80 open 40 2.50 0.025 open 50 4.80 0.048 Control Characteristic Control accuracy Max. working pressure ps Max. differential pressure pmax Max. closing pressure ps Medium temperature V’max [l/s] 30 … 100% V’nom V’min.controlabe [l/s] 0.012 0.018 modulating 0…10 V / MP-Bus equal percentage / linear (switchable) +/- 10% of V’actual value (25…100% V’nom) 1’600 kPa 340 kPa 690 kPa -10 … +120°C (up to 50% Glycol) *** May be subject to changes ***
  • 38. ePIV Summary • • • • • Belimo 5 Year Guarantee Continuous system health monitoring Valve sets with bypasses and drains available Soft Landing Friendly! Low cost. • Very easy to commissioning • Consultants can witness commissioning figures on all the FCUs • Low pressure so energy savings at pump
  • 40.
  • 41. The first ETL listed FCU controller and strategy! Being on the Energy Technology List (ETL) means a business can take advantage of the Enhanced Capital Allowance Scheme (ECA). The ECA scheme allows businesses to claim 100% first year capital allowance on investments on ETL listed energy saving equipment. If a business spent £1000 the standard capital allowance would be approx. £41.50. The ECA would be worth a £230 one off tax relief in the first year!
  • 42. What is the specification for a modern controller? 1. Fully programmable 2. Native BACnet protocol 3. MS/TP or IP (Ethernet) 4. 4 analogue outputs 5 . 6 Triac Outputs 6. 11 Universal Inputs 7. Individually factory programmed
  • 43. What Parameters are controlled or measured ? 1. Supply Air Volume (L/S) 2. Supply Air Temperature (° C) 3. Return Air Temperature (° C) 4. Water Flow Rate (kG/S) 5 . Water Supply Temperature (° C) 6. Water Return Temperature (° C) 7. Motor Power Consumption (VA)
  • 44. How can we utilise these known Parameters ? 1. Supply Air Volume (L/S) 2. Supply Air Temperature (° C) 3. Return Air Temperature (° C) 4. Water Flow Rate (kG/S) 5 . Water Supply Temperature (° C) 6. Water Return Temperature (° C) 7. Motor Power Consumption (VA)
  • 45. What can we calculate with these Parameters ? Delivered kW 1. Supply Air Volume (L/S) 2. Supply Air Temperature (° C) 3. Return Air Temperature (° C) 4. Water Flow Rate (kG/S) 5 . Water Supply Temperature (° kW Calculate delivered cooling or heating C) 6. Water Return Temperature (° C) 7. Motor Power Consumption (VA) Supply Air Volume X Air Δ T X 1.22
  • 46. What can we calculate with these Parameters ? Delivered kW Water Flow Rate 1. Supply Air Volume (L/S) 2. Supply Air Temperature (° C) 3. Return Air Temperature (° C) 4. Water Flow Rate (kG/S) Calculate and Verify Water Supply Temperature (° C) 5 . Water Flow Rate 6. Water Return Temperature (° C) 7. Motor Power Consumption (VA) Delivered kW / water ΔT / 4.186
  • 47. What can we calculate with these Parameters ? Delivered kW 1. Supply Air Volume (L/S) Water Flow Rate 2. Supply Air Temperature (° C) 3. Return Air Temperature (° C) Specific Fan Power 4. Water Flow Rate (kG/S) Calculate the Specific Fan Power 5 . Water Supply Temperature (° C) 6. Water Return Temperature (° C) 7. Motor Power Consumption (VA) SFP = (VA x 0.5) / Air Volume L/S
  • 48. How can we use all of these? Delivered kW Water Flow Rate Specific Fan Power 1. Supply Air Volume (L/S) 2. Supply Air Temperature (° C) 3. Return Air Temperature (° C) 4. Water Flow Rate (kG/S) 5 . Water Supply Temperature (° C) 6. Water Return Temperature (° C) 7. Motor Power Consumption (VA)
  • 49. What is this the FCU Cubed board? 1. Daily Checks for Dirty Filter 2. Daily Checks For Fan Failure 3. Standby Sentinel 4. Basic Energy Monitoring Heath Check - Dirty Filter Heath Check - Fan Failure The unit monitors the power consumption for a certain air volume on its curve after activation each day. If a drop in power consumption results in an alarm Standby Sentinel When fans are not required all non-essential controls elements are powered down minimising consumption. Basic Energy Monitoring The controller monitors the power consumption of the unit and reports it to an AV in watts
  • 50. Control Strategy Uses an energy saving Variable Air Volume strategy. With an increase in cooling demand the first call is too raise the water flow rate. At a given point the Airflow starts to increase to provide more cooling. If the supply air temperature from the FCU approaches the minimum set value the air volume will be raised to offset this. All parameters are adjustable on a global or individual basis.
  • 51. 100 % Air 24 °C Supply Temp Typical With 6/12 Water 80 % 22 °C 20 °C 60 % Air 18 °C Supply Volume 16 °C 40 % 14 °C 20 % 12 °C 0% Water 10 °C Flow Rate 0% 25 % 50 % Space Load kW 75 % 100%
  • 52. 100 % Air 24 °C Supply Temp Typical With 14/17 Water 80 % 22 °C 20 °C 60 % Air 18 °C Supply Volume 16 °C 40 % 14 °C 20 % 12 °C 0% Water 10 °C Flow Rate 0% 25 % 50 % Space Load kW 75 % 100%
  • 55. Matrix ³ A Complete Terminal Air Conditioning Package
  • 56. ³
  • 57. What is set in the controller in the Factory? Controls Strategy A Matrix controls strategy is fully loaded and setup for the given project. Address Each Controller/FCU is addressed for use by the BMS. Airflows Air Volumes for each duct/diffuser are programmed. This includes setback air volumes for VAV operation. Water Flow Rate Design water flow rates are programmed and set utilizing the PICC characterization. Setpoint Room design Temperature set point is programmed.
  • 58. What checks are done at the end of the line? Fans All fans are enabled and checked that they run from signal provided by the controller. Actuators Valve actuators are fully functioned through the Delta Controller. Temperature Sensors A routine is run to normalize the temperature readings from the four sensors to remove potential measurement errors. Triacs All the Triac outputs are checked for function, including those that are not connected. Comms Check Via a laptop, communication with the controller is established to ensure it functions correctly.
  • 59. Matrix ³ - Environmental Commissioning Verifies kW cooling or heating output remotely. Accomplished by running a third of units in cooling and the rest in heating. Results are logged in a routine that runs from a Laptop. Results are corrected for differences between test conditions and design. FCU are selected to deliver cooling and heating. Matrix gives you the Ability to site verify this.
  • 60. Matrix Engineering Tool Supplied on a NetBook to every Matrix project. Commissioning Tool to check operation, adjust operational parameters on a single or, via BMS, multiple Fan Coils. Can connect to the FCU via wireless network if appropriate access points are installed. This software has been developed over many years and is tailored to the Matrix range of Fan Coil Units.
  • 61. What are the benefits of this system at install?? 1. 2. 3. 4. 5. 6. No volume control dampers to buy, install or air balance No hydraulic commissioning stations to buy, install, water balance or maintain – 2 per FCU All individual air and water flow rates are factory loaded and stored in each FCU controller Matrix Engineering Tool does not need the BMS to be operative at the time of FCU commissioning Global water balance trimming feature as a single button press : say, +%5 to all ChW coils on a floor Matrix Engineering Tool includes the automatic generation of a commissioning report including the source data used in the calculation of flow rates
  • 62. What are the client benefits? 1. 2. 3. 4. 5. 6. 7. The most energy efficient and flexible FCU system available Fault Finding becomes a non intrusive, remote activity Remote verification of water flow rates Remote verification of kW output Remote changes to FCU kW, Airflow, Waterflow can be made at any time Dirty filter, Fan failure and other alarms come as standard Fan energy usage can be monitored