Ducted Distribution of Services
QUS 3206 / MDM NURUL AINI
Ducted Distribution of Services
• Service duct require careful planning and should be considered at
an early stage in the design of a building.
• Accommodation of the plant and the layout of services are the two
essential factors in design.
• It is usual to need some 7 – 10% of the total floor area for plant
spaces and ducts.
Ducted Distribution of Services
• The purpose :
• conceal the services and to facilitate
inspection, repair and alterations.
• Helps to reduce noise
• Protects the services from damage
Terminology
• Plant space – area required for the
accommodation of mechanical or electrical
equipment or control gear required for the
operation of services
• Storage space – area required for the
accommodation of storage containers required
for particular services
• Duct – space within a building specially
enclosed for the accommodation of services
and allowing facilities for working and
inspection.
Terminology
• Subway – a horizontal passage for the
conveyance of services underground or
below the bottom floor of the building which
allows walking headroom for access.
• Crawlway – passage for services similar to a
subway but where there is insufficient
headroom to stand upright.
• Trench – horizontal passage for services
below floor level where the access is by
removable covers in the floor.
Terminology
• Wells – vertical space used for the
accommodation of stairs or lifts or
to allow natural light or ventilation
• Casing – an enclosure formed over
pipes or cables running on the
surface of a wall or ceiling. Casing
are usually for decoration but can
also provide protection from
impact or corrosion.
Terminology
• Chase – a recess cut in a wall or
floor when building is over; it
accommodates pipes or cables and
is screed or plastered over
• Void – space may used for the
accommodation of services but
which is not primarily for this
purpose
Ducts for Small pipes or cables
• These may be formed in the floor or wall, or on
the surface of the wall.
• The size of ducts depends upon the outside
diameter of the pipe or cable and the number
of services installed.
• Normally the outside diameter not exceeding
64mm
• Casing & Chase
Terminology
• Sump – pit for seepage, leakage and draining
down of pipework that cannot be discharge by
gravity to the drain and must be collected and
pumped.
• Trunking – lightweight, usually sheet metal
enclosure for the passage of air or cables
Terminology
• Flue – builders’ work or metal passage to
convey the products of combustion to an
acceptable point for discharge to the
atmosphere
• Service core – zone extending vertically
through high rise building containing vertical
circulation, service ducts and other utility
and sanitary provisions.
Importantof unifiedsystemof services
distribution
• Most services can be run in common ducts except flammable
liquids and gases
• The pattern of distribution of services is considered as a whole in
relation to the building planning
• 3 different categories of services run having different requirements
for patterns of distribution:
• Wells and flues
• Pipes and ventilation trunkings
• Electrical cables
• Stair and lift wells run vertically through buildings. They do not
required linkage with services at each floor level but prevent an
obstacle to horizontal distribution of other services
Locationand approximatesizingof plant
spacesand ducts
• Different building functions will imposed different priorities on the
service
• Electrical cables do not normally imposed serious limitations on
planning however the length of cables may be a dominant factor
Locationandapproximatesizingofplantspacesand
ducts–Planningconsiderations
Air trunking
• large and essential to consider
them at the outset of any design
• They must be take into
consideration first before other
services due to the space
requirement
Waste and soil installation
• Are not as large as air trunking but
need to be design in the early stage
due to space requirement
Locationand ApproximateSizingof Plant Spaces
andDucts
Heating pipes
• May be larger than waste and soil pipes in
large buildings due to the insulation but
generally they are smaller in size.
Water supply pipes
• Are very often smaller than heating supply
pipes and do not require heavy insulation.
• They are equal flexible in their detailed layout
and may be taken up and over or under
obstruction without any major problems.
Locationand ApproximateSizingof Plant
Spacesand Ducts
Electrical cables
• Very small in most buildings and they can
very easily be accommodate in
comparatively small trunking
• They are disposed within the thickness of a
floor screed
Approx.sizingof ducts:
Several factors to consider in deciding the size of ducts and recess:
• Number & size of pipes, cables & trunkings to be accommodated
• Any critical spacing or fixing position which must be followed for certain
pipe types
• Clearance required for placing the pipes in position, which must also allow
for ease of removal should it become necessary during maintenance
• Clearance to allow for position of fixings and to permit jointing
Approx.sizingof ducts:
Several factors to consider in deciding the size of ducts and recess (cont’d):
• Allowance for additional services which may be needed
• Space for access in the case of ducts
• Space of valve, dampers
• Space for expansion bands in long, straight horizontal or vertical ducts
• Space for branching and service junctions, and to carry these branches
past adjoining services
Vertical ducts & Undergroundducts
• Vertical ducts – dimensions are often
found varied due to lack of planning in the
design process
• Underground ducts – would conflict with
columns and foundations in construction
Vertical Duct
Underground ducts
Ceiling voids
• Space to accommodate services within the ceiling void but near the
points at which branches leave the primary vertical ducts to enter
secondary ceiling recesses, the trunking and pipes will be at their
maximum diameter and the necessity for crossing will be relatively
high
• Headroom on the various floors will be normally have been reduced
to the acceptable minimum
• Space available above suspended ceiling will also kept as low as
possible, in order to avoid increasing the overall height of the
building.
Service distribution above ceiling
Floorvoids
• Increasing use of electrical, telecommunications and computer
equipment in office has led to the use of suspended floors to
contain wiring and provide flexibility for additional and alterations.
Crossingservices& Spacearound trunking
Crossing services – where services cross it is
possible to have a great deal of wasted space
in ducts
Space around trunking – cable trays suspended
from ceilings should have minimum clearance
of 250mm at each side and similar distance
above each edge of the tray
Locationand ApproximateSizingof Plant
Spacesand Ducts
Ventilation trunking
• Ventilation trunking should have 250mm clearance of the
sides and at least 300mm clearance above the trunking
• The clearance above the trunking should be increase up to
500mm for 2m wide trunking
Firehazards
• Vertical ducts should have vents at the top so that smoke and
flame can be dissipated
• Ducts must be sealed where they pass through fire resisting
construction
• The walls and doors of the ducts must have adequate fire
resistance
• Pipes run through fire-resisting walls should have gaps tightly
packed with fire stopping material and depending on the
movement of pipe
Ductdetails
• All major underground ducts should provided with channels to carry
away seepage and leakage
• Vertical duct – simply a recess in corridor wall covered by ply facing
Duct details
• Some have to laid to fall – drainages
• Firmly support – heating/ or water pipe with pressure to avoid
movement
• Long and straight lengths pipes – adjustable level pipe clip
• Underground ducts – provide with channel to carry away
seepage or leakage
• Access to the services – maintenance
TUTORIAL
1.Choose any one (1) department/building/faculty in Inti IU
e.g. library. Provide photographic evidences to identify
various ducting system in Inti IU Building.
2. Explain the important of adopting unified system of
service distribution.
3. Explain the factors that must be considered in deciding
the size of the ducts and recesses.
Due Date : …………………………………
Task :

Mais conteúdo relacionado

Mais procurados

BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2
BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2
BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2
MAHENDRAN Mahalingam
 

Mais procurados (20)

Climatic zones. warm and humid
Climatic zones. warm and humid Climatic zones. warm and humid
Climatic zones. warm and humid
 
Building services
Building servicesBuilding services
Building services
 
lic housing and morphogenesis housing
lic housing and morphogenesis housinglic housing and morphogenesis housing
lic housing and morphogenesis housing
 
Parking final
Parking finalParking final
Parking final
 
Amanora Future Towers, Hadapsar, Pune - Case Study
Amanora Future Towers, Hadapsar, Pune - Case StudyAmanora Future Towers, Hadapsar, Pune - Case Study
Amanora Future Towers, Hadapsar, Pune - Case Study
 
Architectural Case Study on Druk White Lotus School
Architectural Case Study on Druk White Lotus SchoolArchitectural Case Study on Druk White Lotus School
Architectural Case Study on Druk White Lotus School
 
"warm and humid" climate and their designs
"warm and humid" climate and their designs"warm and humid" climate and their designs
"warm and humid" climate and their designs
 
BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2
BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2
BASEMENT FIRE PROTECTION LAYOUT-SECTOR-2
 
Building Service Chapter 5
Building Service Chapter 5Building Service Chapter 5
Building Service Chapter 5
 
Mattuthavani bus terminal case study
Mattuthavani bus terminal  case studyMattuthavani bus terminal  case study
Mattuthavani bus terminal case study
 
building services -Lift's and escalators
building services -Lift's and escalatorsbuilding services -Lift's and escalators
building services -Lift's and escalators
 
Housing Data collection.pdf
Housing Data collection.pdfHousing Data collection.pdf
Housing Data collection.pdf
 
Mass Housing case study - Raheja Classique, Andheri
Mass Housing case study - Raheja Classique, AndheriMass Housing case study - Raheja Classique, Andheri
Mass Housing case study - Raheja Classique, Andheri
 
Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016
 
Vernacular architecture case study with examples
Vernacular architecture case study with examplesVernacular architecture case study with examples
Vernacular architecture case study with examples
 
Site analysis - Transit hub
Site analysis - Transit hubSite analysis - Transit hub
Site analysis - Transit hub
 
Case study- ATS Group housing
Case study- ATS Group housingCase study- ATS Group housing
Case study- ATS Group housing
 
Dhajji wall
Dhajji wallDhajji wall
Dhajji wall
 
Basements light and ventilation
Basements light and ventilationBasements light and ventilation
Basements light and ventilation
 
Building Service Project 2 Case Study Report
Building Service Project 2 Case Study ReportBuilding Service Project 2 Case Study Report
Building Service Project 2 Case Study Report
 

Semelhante a Ducted distribution of services

05_Overhead_or_Under_Floor_Installation.pptx
05_Overhead_or_Under_Floor_Installation.pptx05_Overhead_or_Under_Floor_Installation.pptx
05_Overhead_or_Under_Floor_Installation.pptx
JanixMagbanua1
 
Electrical services seminar
Electrical services seminarElectrical services seminar
Electrical services seminar
michaeljmack
 
Nu Flow Presentation Eric VA and YMCA
Nu Flow Presentation Eric VA and YMCANu Flow Presentation Eric VA and YMCA
Nu Flow Presentation Eric VA and YMCA
Eric Hopkins
 
Services report - plumbing, electrical and hvac
Services report - plumbing, electrical and hvacServices report - plumbing, electrical and hvac
Services report - plumbing, electrical and hvac
Yashna Garg
 
Chapter 2
Chapter 2Chapter 2
Chapter 2
Est
 

Semelhante a Ducted distribution of services (20)

BS-3-INTERNALS2.pptx
BS-3-INTERNALS2.pptxBS-3-INTERNALS2.pptx
BS-3-INTERNALS2.pptx
 
05_Overhead_or_Under_Floor_Installation.pptx
05_Overhead_or_Under_Floor_Installation.pptx05_Overhead_or_Under_Floor_Installation.pptx
05_Overhead_or_Under_Floor_Installation.pptx
 
Interceptors and manholes
Interceptors and manholesInterceptors and manholes
Interceptors and manholes
 
Supplier Hoist Cranes Jakarta | stahlindo
Supplier Hoist Cranes Jakarta | stahlindoSupplier Hoist Cranes Jakarta | stahlindo
Supplier Hoist Cranes Jakarta | stahlindo
 
Grid waffle slab
Grid waffle slabGrid waffle slab
Grid waffle slab
 
Electrical services seminar
Electrical services seminarElectrical services seminar
Electrical services seminar
 
High rise archive research
High rise archive researchHigh rise archive research
High rise archive research
 
Nu Flow Presentation Eric VA and YMCA
Nu Flow Presentation Eric VA and YMCANu Flow Presentation Eric VA and YMCA
Nu Flow Presentation Eric VA and YMCA
 
Services report - plumbing, electrical and hvac
Services report - plumbing, electrical and hvacServices report - plumbing, electrical and hvac
Services report - plumbing, electrical and hvac
 
Construction and testing of sewer line
Construction and testing of sewer lineConstruction and testing of sewer line
Construction and testing of sewer line
 
B.Service Report
B.Service ReportB.Service Report
B.Service Report
 
Floors, roofs, shoring and underpinning.pptx
Floors, roofs, shoring and underpinning.pptxFloors, roofs, shoring and underpinning.pptx
Floors, roofs, shoring and underpinning.pptx
 
Chapter 2
Chapter 2Chapter 2
Chapter 2
 
Volumetric Construction.pdf
Volumetric  Construction.pdfVolumetric  Construction.pdf
Volumetric Construction.pdf
 
Trenchless Technology
Trenchless TechnologyTrenchless Technology
Trenchless Technology
 
MODERN CONSTRUCTION TECHNOLOGIES IN ENGINEERING PERSPECTIVE
MODERN CONSTRUCTION TECHNOLOGIES IN ENGINEERING PERSPECTIVEMODERN CONSTRUCTION TECHNOLOGIES IN ENGINEERING PERSPECTIVE
MODERN CONSTRUCTION TECHNOLOGIES IN ENGINEERING PERSPECTIVE
 
Duct Design & Air distribution
Duct Design & Air distributionDuct Design & Air distribution
Duct Design & Air distribution
 
newCHris Resume
newCHris ResumenewCHris Resume
newCHris Resume
 
Pre Engineered buildings
Pre Engineered buildingsPre Engineered buildings
Pre Engineered buildings
 
Form-woks-additional.pptx
Form-woks-additional.pptxForm-woks-additional.pptx
Form-woks-additional.pptx
 

Mais de Noorule Inie Osman

Mais de Noorule Inie Osman (7)

Topik 4 lighting
Topik 4 lightingTopik 4 lighting
Topik 4 lighting
 
Topik 8 kilat
Topik 8 kilatTopik 8 kilat
Topik 8 kilat
 
Air conditioning system
Air conditioning systemAir conditioning system
Air conditioning system
 
Ventilation system
Ventilation systemVentilation system
Ventilation system
 
Fire fighting active system
Fire fighting active systemFire fighting active system
Fire fighting active system
 
Fire fighting passive system
Fire fighting passive systemFire fighting passive system
Fire fighting passive system
 
Introduction to building services part 2
Introduction to building services part 2Introduction to building services part 2
Introduction to building services part 2
 

Último

Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
Nauman Safdar
 
Structuring and Writing DRL Mckinsey (1).pdf
Structuring and Writing DRL Mckinsey (1).pdfStructuring and Writing DRL Mckinsey (1).pdf
Structuring and Writing DRL Mckinsey (1).pdf
laloo_007
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
daisycvs
 

Último (20)

Mckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for ViewingMckinsey foundation level Handbook for Viewing
Mckinsey foundation level Handbook for Viewing
 
PHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation FinalPHX May 2024 Corporate Presentation Final
PHX May 2024 Corporate Presentation Final
 
Falcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business PotentialFalcon Invoice Discounting: Unlock Your Business Potential
Falcon Invoice Discounting: Unlock Your Business Potential
 
BeMetals Investor Presentation_May 3, 2024.pdf
BeMetals Investor Presentation_May 3, 2024.pdfBeMetals Investor Presentation_May 3, 2024.pdf
BeMetals Investor Presentation_May 3, 2024.pdf
 
Arti Languages Pre Seed Teaser Deck 2024.pdf
Arti Languages Pre Seed Teaser Deck 2024.pdfArti Languages Pre Seed Teaser Deck 2024.pdf
Arti Languages Pre Seed Teaser Deck 2024.pdf
 
New 2024 Cannabis Edibles Investor Pitch Deck Template
New 2024 Cannabis Edibles Investor Pitch Deck TemplateNew 2024 Cannabis Edibles Investor Pitch Deck Template
New 2024 Cannabis Edibles Investor Pitch Deck Template
 
Structuring and Writing DRL Mckinsey (1).pdf
Structuring and Writing DRL Mckinsey (1).pdfStructuring and Writing DRL Mckinsey (1).pdf
Structuring and Writing DRL Mckinsey (1).pdf
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All TimeCall 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
Call 7737669865 Vadodara Call Girls Service at your Door Step Available All Time
 
Falcon Invoice Discounting: Aviate Your Cash Flow Challenges
Falcon Invoice Discounting: Aviate Your Cash Flow ChallengesFalcon Invoice Discounting: Aviate Your Cash Flow Challenges
Falcon Invoice Discounting: Aviate Your Cash Flow Challenges
 
HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
 
Pre Engineered Building Manufacturers Hyderabad.pptx
Pre Engineered  Building Manufacturers Hyderabad.pptxPre Engineered  Building Manufacturers Hyderabad.pptx
Pre Engineered Building Manufacturers Hyderabad.pptx
 
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAIGetting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Lucknow Housewife Escorts by Sexy Bhabhi Service 8250092165
Lucknow Housewife Escorts  by Sexy Bhabhi Service 8250092165Lucknow Housewife Escorts  by Sexy Bhabhi Service 8250092165
Lucknow Housewife Escorts by Sexy Bhabhi Service 8250092165
 
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdfTVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
TVB_The Vietnam Believer Newsletter_May 6th, 2024_ENVol. 006.pdf
 
Cannabis Legalization World Map: 2024 Updated
Cannabis Legalization World Map: 2024 UpdatedCannabis Legalization World Map: 2024 Updated
Cannabis Legalization World Map: 2024 Updated
 
Putting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptxPutting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptx
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 

Ducted distribution of services

  • 1. Ducted Distribution of Services QUS 3206 / MDM NURUL AINI
  • 2. Ducted Distribution of Services • Service duct require careful planning and should be considered at an early stage in the design of a building. • Accommodation of the plant and the layout of services are the two essential factors in design. • It is usual to need some 7 – 10% of the total floor area for plant spaces and ducts.
  • 3. Ducted Distribution of Services • The purpose : • conceal the services and to facilitate inspection, repair and alterations. • Helps to reduce noise • Protects the services from damage
  • 4. Terminology • Plant space – area required for the accommodation of mechanical or electrical equipment or control gear required for the operation of services • Storage space – area required for the accommodation of storage containers required for particular services • Duct – space within a building specially enclosed for the accommodation of services and allowing facilities for working and inspection.
  • 5. Terminology • Subway – a horizontal passage for the conveyance of services underground or below the bottom floor of the building which allows walking headroom for access. • Crawlway – passage for services similar to a subway but where there is insufficient headroom to stand upright. • Trench – horizontal passage for services below floor level where the access is by removable covers in the floor.
  • 6. Terminology • Wells – vertical space used for the accommodation of stairs or lifts or to allow natural light or ventilation • Casing – an enclosure formed over pipes or cables running on the surface of a wall or ceiling. Casing are usually for decoration but can also provide protection from impact or corrosion.
  • 7. Terminology • Chase – a recess cut in a wall or floor when building is over; it accommodates pipes or cables and is screed or plastered over • Void – space may used for the accommodation of services but which is not primarily for this purpose
  • 8. Ducts for Small pipes or cables • These may be formed in the floor or wall, or on the surface of the wall. • The size of ducts depends upon the outside diameter of the pipe or cable and the number of services installed. • Normally the outside diameter not exceeding 64mm
  • 9. • Casing & Chase
  • 10. Terminology • Sump – pit for seepage, leakage and draining down of pipework that cannot be discharge by gravity to the drain and must be collected and pumped. • Trunking – lightweight, usually sheet metal enclosure for the passage of air or cables
  • 11. Terminology • Flue – builders’ work or metal passage to convey the products of combustion to an acceptable point for discharge to the atmosphere • Service core – zone extending vertically through high rise building containing vertical circulation, service ducts and other utility and sanitary provisions.
  • 12. Importantof unifiedsystemof services distribution • Most services can be run in common ducts except flammable liquids and gases • The pattern of distribution of services is considered as a whole in relation to the building planning • 3 different categories of services run having different requirements for patterns of distribution: • Wells and flues • Pipes and ventilation trunkings • Electrical cables • Stair and lift wells run vertically through buildings. They do not required linkage with services at each floor level but prevent an obstacle to horizontal distribution of other services
  • 13. Locationand approximatesizingof plant spacesand ducts • Different building functions will imposed different priorities on the service • Electrical cables do not normally imposed serious limitations on planning however the length of cables may be a dominant factor
  • 14. Locationandapproximatesizingofplantspacesand ducts–Planningconsiderations Air trunking • large and essential to consider them at the outset of any design • They must be take into consideration first before other services due to the space requirement Waste and soil installation • Are not as large as air trunking but need to be design in the early stage due to space requirement
  • 15. Locationand ApproximateSizingof Plant Spaces andDucts Heating pipes • May be larger than waste and soil pipes in large buildings due to the insulation but generally they are smaller in size. Water supply pipes • Are very often smaller than heating supply pipes and do not require heavy insulation. • They are equal flexible in their detailed layout and may be taken up and over or under obstruction without any major problems.
  • 16. Locationand ApproximateSizingof Plant Spacesand Ducts Electrical cables • Very small in most buildings and they can very easily be accommodate in comparatively small trunking • They are disposed within the thickness of a floor screed
  • 17. Approx.sizingof ducts: Several factors to consider in deciding the size of ducts and recess: • Number & size of pipes, cables & trunkings to be accommodated • Any critical spacing or fixing position which must be followed for certain pipe types • Clearance required for placing the pipes in position, which must also allow for ease of removal should it become necessary during maintenance • Clearance to allow for position of fixings and to permit jointing
  • 18. Approx.sizingof ducts: Several factors to consider in deciding the size of ducts and recess (cont’d): • Allowance for additional services which may be needed • Space for access in the case of ducts • Space of valve, dampers • Space for expansion bands in long, straight horizontal or vertical ducts • Space for branching and service junctions, and to carry these branches past adjoining services
  • 19. Vertical ducts & Undergroundducts • Vertical ducts – dimensions are often found varied due to lack of planning in the design process • Underground ducts – would conflict with columns and foundations in construction
  • 22. Ceiling voids • Space to accommodate services within the ceiling void but near the points at which branches leave the primary vertical ducts to enter secondary ceiling recesses, the trunking and pipes will be at their maximum diameter and the necessity for crossing will be relatively high • Headroom on the various floors will be normally have been reduced to the acceptable minimum • Space available above suspended ceiling will also kept as low as possible, in order to avoid increasing the overall height of the building.
  • 24. Floorvoids • Increasing use of electrical, telecommunications and computer equipment in office has led to the use of suspended floors to contain wiring and provide flexibility for additional and alterations.
  • 25. Crossingservices& Spacearound trunking Crossing services – where services cross it is possible to have a great deal of wasted space in ducts Space around trunking – cable trays suspended from ceilings should have minimum clearance of 250mm at each side and similar distance above each edge of the tray
  • 26. Locationand ApproximateSizingof Plant Spacesand Ducts Ventilation trunking • Ventilation trunking should have 250mm clearance of the sides and at least 300mm clearance above the trunking • The clearance above the trunking should be increase up to 500mm for 2m wide trunking
  • 27. Firehazards • Vertical ducts should have vents at the top so that smoke and flame can be dissipated • Ducts must be sealed where they pass through fire resisting construction • The walls and doors of the ducts must have adequate fire resistance • Pipes run through fire-resisting walls should have gaps tightly packed with fire stopping material and depending on the movement of pipe
  • 28. Ductdetails • All major underground ducts should provided with channels to carry away seepage and leakage • Vertical duct – simply a recess in corridor wall covered by ply facing
  • 29. Duct details • Some have to laid to fall – drainages • Firmly support – heating/ or water pipe with pressure to avoid movement • Long and straight lengths pipes – adjustable level pipe clip • Underground ducts – provide with channel to carry away seepage or leakage • Access to the services – maintenance
  • 30. TUTORIAL 1.Choose any one (1) department/building/faculty in Inti IU e.g. library. Provide photographic evidences to identify various ducting system in Inti IU Building. 2. Explain the important of adopting unified system of service distribution. 3. Explain the factors that must be considered in deciding the size of the ducts and recesses. Due Date : ………………………………… Task :